Sunteți pe pagina 1din 1

Procedure 02.18.60.

06
Qatargas Operating Company Effective 01/12/2014
Issue Date 23/11/2014
Limited Valid Until 30/11/2017
Revision 03

10.26 PAINTING SYSTEM PL - 01

GRP, HDPE & PVC external surfaces which require UV protection


ONSHORE
Typical Applications: External surfaces of GRP, HOPE & PVC Tanks & Piping

Surface Preparation: Remove old paint, dirt, dust, chemicals, salts, grease & other
contaminants from surfaces using hand tools combined with degreaser &/or solvent cleaning,
followed by fresh water pressure washing.
On-line facilities: Abrade with silicone free emery paper to clean & achieve desired roughness for
better adhesion of paints.
Refer detailed procedures as indicated in appendices & related Industry standard.

Recommended Painting System

COATS GENERIC NAME OFT EXISTING COATING SYSTEM

PRIMER Polyamide Adduct Cured Epoxy 125 ~m QG 1 23 (maintenance)

MID COAT ------ ----- QG 2; QG 3&4 Not Painted

TOP COAT Acrylic polyurethane 50 ~m LR Not Painted

TOTAL MINIMUM OFT 175 ~m CSP Not Painted

Approved Paint Products: For Spot repairs, Renovation, Refurbishment & New Construction

COATS HEMPEL INTERNATIONAL JOTUN SIGMA

PRIMER Hemadur 45550 Interseal 1052 Penguard HB Sigmacover 280

MID COAT ----- ----- ----- ------


TOPCOAT Hempathane 5521 0 lnterthane 990SG Hardtop XP Sigmacap PU Finish

Prepared By:
Protective Coating Procedure Corrosion Engineering- Integrity Division
Page 41 Issued By:
Engineering & Ventures