What is the Duty Cycle/Operating Sequence of Circuit Breaker specified on the


Name Plate
Posted by Pranali N | Mar 2, 2019 | Circuit Breaker, SF6CB, VCB | 0  |     

https://electricalfundaz.com/duty-cycle-circuit-breaker/ 1/8
8/26/2019 Duty Cycle of Circuit Breaker / Operating Sequence of Circuit Breaker

We keep wondering what the heck this sequence on the name plate of the Circuit Brekaer. Lets nd it out now.

What is the Duty Cycle/ Operating Sequence of CB?


It is the Mechanical Duty requirement to be full lled by the  Operating Mechanism of the Breaker and speci ed on the Name
Plate of the Breaker by the Manafucturer.

https://electricalfundaz.com/duty-cycle-circuit-breaker/ 2/8
8/26/2019 Duty Cycle of Circuit Breaker / Operating Sequence of Circuit Breaker

What is its Significance ?


It is mainly used during Circuit Breaker Auto Reclosing.

How is it specified ?
It speci ed as: O-t-CO-t’-CO and generally given as  O-0.3 SEC-CO-3 MIN-CO, where O is CB Tripping, t is the Dead Time,
CO is Reclose with immediate Tripping (AR Unsucessful)  and t’ is the Reclaim Time and then the cycle continous, if its a
Multishot AR or the Fault reccours.

Sequence of Operation:
1. When there is a fault, the concerned relay operates, which inturn operates the Master Trip Relay (86).
2. CB Trip initiates and at the same time Auto Reclose Initiates.

https://electricalfundaz.com/duty-cycle-circuit-breaker/ 3/8
8/26/2019 Duty Cycle of Circuit Breaker / Operating Sequence of Circuit Breaker

3. CB Trips in about 30ms, which is indicated by “O” in the Duty Cycle.


4. Then CB will remain open for some time (0.3 sec) to complete the Arc Quenching which is called as Dead Time and is
indicated by “0.3Sec” in the Duty Cycle.
5. After 0.3 sec, if AR is in Service, a Reclose will be attempted, and if the fault persists, CB Trips immediately  ( AR
Unsucessful ) which is indicated by “CO” in the duty cycle.
6. If its a Single Shot Auto-reclose, the Breaker will go into Auto Reclose Lockout, that means , the AutoReclose Relay will not
give any futher Reclose Command to the Breaker.
7. After CO, there is a Reclaim Time of 3 Minutes, in which the CB gets ready for Closing, which includes Cb Spring Charging
Time, indicated by “3 Min” in the Duty Cycle.
8. After the Reclaim Time has completed, Second Reclose will be attempted in following two cases:
       Case i) If its a Multishot AR, the breaker will close again, and if the fault is cleared it will remain close, but if the fault is still 
                       there then the breaker will open immediately, and now breaker will remain open until it is closed manually.
     Case ii) Auto-reclose was sucessful (Fault Cleared & Breaker had closed), but after the Reclaim Time, the Fault Reoccured. 
                     In this Case, the Duty Cycle will continue. 

Please do watch this video on our Youtube Channel (Its in Hindi Language though).

Duty Cycle of Circuit Breaker - Circuit Breaker Speci cation Series in Hindi

https://electricalfundaz.com/duty-cycle-circuit-breaker/ 4/8
8/26/2019 Duty Cycle of Circuit Breaker / Operating Sequence of Circuit Breaker

Thank You so Much. See you in some other Post.

Subscribe to get more post like these !!


Just enter your Email Adress and hit the Subscribe Button !!!!!!

EMAIL SUBSCRIBE!

SHARE:           RATE:

 PREVIOUS NEXT 
https://electricalfundaz.com/duty-cycle-circuit-breaker/ 5/8
8/26/2019 Duty Cycle of Circuit Breaker / Operating Sequence of Circuit Breaker

Circuit Breaker Testing with Standard Test Results Master Trip Relay (86) Concept in Power System Explained in
Detail

RELATED POSTS

Tripping Circuit of Circuit Breaker Circuit Breaker What is Local


33 KV Outdoor GO Antipumping Device Testing with Breaker Backup or
VCB 16.06.18 Standard Test Breaker Failure
14.01.19
Results Relay for Protection
27.01.19
of Local end
Breaker
26.12.18

Leave a reply
Your email address will not be published. Required fields are marked *

COMMENT

https://electricalfundaz.com/duty-cycle-circuit-breaker/ 6/8
8/26/2019 Duty Cycle of Circuit Breaker / Operating Sequence of Circuit Breaker

NAME * EMAIL * WEBSITE

POST COMMENT

https://electricalfundaz.com/duty-cycle-circuit-breaker/ 7/8
8/26/2019 Duty Cycle of Circuit Breaker / Operating Sequence of Circuit Breaker

© 2019 Electrical Fundaz 

https://electricalfundaz.com/duty-cycle-circuit-breaker/ 8/8

S-ar putea să vă placă și