What is the controller gain of a temperature What is the controller output be for a

with 50% PB if its input range is 200C to proportional plus derivative controller a)
700C and its output is 4mA to 20mA initially and b) 2 seconds after the error
begins to change from zero at the rate of 2%
Ans: 0.64mA/C
per second? Assume the controller has Kp=4
Is an arrangement of parts within some and TD=0.4s
boundary which work together to provide some Ans: 3.2%, 19.2% respectively
form of output from specified inputs
The systems measuring element is
Ans: Systems

For comparator to be OFF, V2==2 VOLTS OR


VIN>>VS1

Ans: Tachogenerator
Ans: False
Refers to the behavior the time the input value
A device that performs an action on one of the changes and the time that the value given by the
input variables of a process according to a signal system settles down to steady-state value
received from the controller Ans: Dynamic Characteristics
Ans: Actuator The systems set point is indicated by
It is used for taking measurements to give the
user a numeric value of the variable being
measured

Ans: Measurement System

Which of the following is not the tuning of a


PID Controller?

Ans: None of the Choices

Which of the following is not a displacement Ans: Potentiometer


Sensor?

Ans: Capacitors

Is its ability to give the same output when


used to measure a constant input over a
period of time

Ans: Stability
Is used to describe the degree of freedom of a
measurement system from random errors

Ans: Precision

What are the required measurement systems


and functional elements that could be used to
form the production of an electrical signal when
a package on a conveyor belt has reach a
particular position?

Ans: Weight-Operated Electrical Switch


Ans: Increase, no effects
Which of the following is not a dynamic
Is the element to which the value indicated by characteristic of an element?
a measurement system or element might be
wrong? Ans: None of the Choices

Ans: Accuracy If in a proportional-plus-integral controller is


away from the set point for a long period, the
Is the limits between which the input can vary? controllers output will be
Ans: Range Ans: O or 100 percent, depending on action
selected
The failure rate for a pressure measurement
system used in the factory X is found to be A proportional controller will have an offset
1.0 per year while the system used by factory difference between set point and control point:
Y is 3.0 per year. Which factory has the most
reliable pressure measurement? Ans: At all times

Ans: Factory X What are the required measurement systems


and functional elements that could be used to
Calibration of a voltmeter gave the following form the air temperature for an electrical meter
data. Determine the maximum hysteresis intended to indicate when temperature drops
error as a percentage of the full scale range below freezing point?

Ans: Thermistor, potential divider


circuit, voltmeter

The level in a tank shown below is to be


controlled with PID controller the following
specifications are given
Ans: 5% Ans: 2.5, 7.0, 9.9 Volts

Is the difference between the result of a The term PLC stands for
measurement and the true value of the
quantity being measured Ans: Programmable logic controller

Ans: Error
What are the required measurement systems A platinum resistance coil is to be used as a
and functional elements that could be used to temperature sensor and has a resistance at 00c
form the production of an electrical signal when of 100 ohms. Its forms one arm of a
a driverless vehicle designed for operation in a wheatstone bridge with bridge being balanced
factory to move/transport materials between at this temperature and each of the arms is 100
machines on a given direct route? ohms. If the temperature coefficient of the
platinum is 0.0039K-1, what will be the output
Ans: Painted Stripes on floor and optical sensor; voltage of the bridge per degree change in
optical encoder to monitor rotation of wheel
temperature if the supply is 6 Volts
Temperature is to be measured in the range of Ans: 0.39 ohms, 0.010Volts
2500C to 4500C. The sensor is a resistance that
varies linearly from 280 ohms to 1060 ohms for Tuning PID design using Ziegler Nichols
this temperature range. Power dissipated in the method has the advantage of
sensor should be kept below 5mW. Given below
Ans: results in good tuning
is its analog signal conditioning circuit that
provides a voltage varying linearly from -5 to The Correction element of the system is
5V. Sensor must be kept below 2mW

Ans: True

Indicates how much the output of an


instrument system changes when the quantity
being measured changes by a given amount

Ans: Sensitivity

Given figures a) and b) The hardwired relay Ans: motor


logic circuit and PLC ladder diagram shown
below. Which following is true? Which of the following is not a dynamic
characteristic of an element?
Ans: B
Ans: none of the choices
A temperature control system inputs the
controlled variable as a range from 0 to 4V. It is used for taking measurements to give the
The output is a heater requiring 0 to 8v. A PID user a numerical value of the variable being
controller is to be used with Kp=2.4%, Ki=0.9% measured
and KD = 27%. The period of the fasted
expected change is 4 seconds. The integrator Ans: Instrumentation and Measurement System
Gain Gi is For PD Controller which of the following is the
Ans: 1.8/s output?

A derivative controller has a derivative constant


of 0.3 second. What will be the controller
output when the error changes from 1.5% per
seconds?

0.45%
Ans: none
For Kp parameter, the overshoot tends to

Ans: increases

Which sensor load cell is most appropriate for


measurement of the level of a corrosive acid in
a circular vessel of diameter 1 meter that will
give an electrical output in mV? The acid level
can vary from 0 to 3 meters and the minimum
change in level is 0.1m. The empty vessel has a
weight of 50kg. The acid has a density of 1050
kg/m3.

Ans: 3 load cells, each range between 0 to 5kN


with resolution of 0.3kN

Temperature is to be measured in the range of


2500C to 4500C. The sensor is a resistance that
varies linearly from 280 ohms to 1060 ohms for
this temperature range. Power dissipated in the
sensor should be kept below 5mW. Given below
is its analog signal conditioning circuit that
provides a voltage varying linearly from -5 to
5V. The maximum power dissipation in the
sensor Is

Ans: 2.17mW