Model: PEFY-P15NMHU-E

Job Name:

Drawing Reference: Schedule No.

External Finish . . . . . . . . . . . . . . . . . Galvanized steel plate

Dimensions
Inches . . . . . . . . . . . . . 14-31/32 h x 29-17/32 w x 35-7/16 d
mm . . . . . . . . . . . . . . . . . . . . . . . . . . 380 h x 750 w x 900 d

Net Weight . . . . . . . . . . . . . . . . . . . . . . . . . . . 98 lb / 44 kg

Coil Type . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Cross fin


(aluminum plate fin and copper tube)
GENERAL FEATURES Fan
• R410A or R22 refrigerant-compatible Type x Quantity . . . . . . . . . . . . . . . . . . . . . . Sirocco fan x 1
• Ducted fan coil supports multiple configurations for Airflow Rate (Low - High) . . . . . . . . . . . . . . . 353-494 CFM
flexible installation External Static Pressure
@ 208V . . . . . . . . . . . . . . . . 0.20 (default) - 0.64 in. WG
• High external static pressure capabilities
@ 230V . . . . . . . . . . . . 0.40-0.60 (default) - 0.80 in. WG
• Multiple sizes up to 96,000 Btu/h Motor
• Quiet operation: 25-54 dB(A) Type . . . . . . . . . . . . . . . . .Single phase induction motor
Output . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 0.130 kW
SPECIFICATIONS
Air Filter . . . . . . . . . . . . . . . Filter must be procured locally
Capacity*
Cooling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .15,000 Btu/h Refrigerant Pipe Dimensions
Heating . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .17,000 Btu/h R410A or R22
Liquid. . . . . . . . . . . . . . . . . . . . . . . . 1/4" / 6.35 mm flare
Gas . . . . . . . . . . . . . . . . . . . . . . . . . 1/2" / 12.7 mm flare
Power
Power Source . . . . . . . . . . . . . . . .208-230V, 1 phase, 60Hz
Power Consumption
Drainpipe Dimension . . . . . . . . . . . O.D.1-1/4" / 32 mm
Cooling . . . . . . . . . . . . . . . . . . . . . . . . 0.188 / 0.207 kW
Heating . . . . . . . . . . . . . . . . . . . . . . . . 0.188 / 0.207 kW
Sound Level (Low - High)
@ 208V . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25-32 dB(A)
Current
@ 230V . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34-39 dB(A)
Cooling . . . . . . . . . . . . . . . . . . . . . . . . . . . . 0.96-1.06 A
Heating . . . . . . . . . . . . . . . . . . . . . . . . . . . . 0.96-1.06 A
Minimum Circuit Ampacity (MCA) (208/230) . . 1.20 / 1.33 A Options
Maximum Overcurrent Protection (MOCP). . . . . . . . . . . 15A ❏ Drain pump kit. . . . . . . . . . . . . . . . . . . . . PAC-KE04DM-F
❏ Condensate pump . . . . . . . . . . . . . . . . . . . . .SI1730-230
❏ Long-life filter . . . . . . . . . . . . . . . . . . . . . . PAC-KE86LAF
❏ Filter box . . . . . . . . . . . . . . . . . . . . . . . . . PAC-KE63TB-F

* Cooling / Heating capacity indicated the maximum value at operation under the
following conditions:
Cooling: Indoor 80°F (27°C) DB / 67°F (19°C) WB, Outdoor 95°F (35°C) DB
Heating: Indoor 70°F (21°C) DB, Outdoor 47°F (8°C) DB / 43°F (6°C) WB

** Ventilation air: providing sufficient ventilation air is an important part of every


building design. ASHRAE Standard 62 provides the minimum ventilation air
requirements. Also check local codes.

Notes:
Model: PEFY-P15NMHU-E

50(1-31/32)X(J-1)=K
B(Suspension bolt pitch)
50(1-31/32)X(G-1)=H

E
D

A
Air inlet Air outlet

50 (1-31/32)
50(1-31/32)

(1-31/32)
80 50
15(19/32)

(3-5/32)
F

10(13/32)
(2-25/32)

(1-5/8)
41
70

23(29/32)
((2-3/8)

((2-31/32)
60

75
340(13-13/32) 383(15-3/32) 250(9-27/32)

Suspension bolt hole 814(32-1/16)(Suspension bolt pitch) 60(2-3/8)


Model:P15~30 (Note3)
4-14X30(9/16X1-3/16) Slot 904(35-19/32)

900(35-7/16)
24(31/32) 847(33-3/8) 29(1-5/32)
10(13/32) 15(19/32)

Drain hole
Control box (option)

50 (1-31/32)
(3-1/16)

(1-31/32X4=7-7/8)
(1-31/32)X5=(9-27/32)

250(9-27/32)
328(12-15/16)
50X4=200
77
50(1-31/32)

380(14-31/32)
340(13-13/32)
50X5=250

(5-1/8)

25(1)
130
5/8)
41
(1-

Terminal bed
45(1-25/32)

163 (6-13/32)
17(11/16)

94(3-23/32)
30(1-3/16)

(Power source) (3-5/8)


92 200(7-7/8)
Terminal box 343(13-17/32)
Terminal bed 387(15-1/4)
Keep duct-work length 850mm(33-15/32 in.) or more. (Transmission)
Drain hole

m(in.)
Model A B C D E F G H J K L <Flare> <Flare>
PEFY-P15NMHU-E
800 754 6 80 600 550 50 11 500 10 450 780
PEFY-P18NMHU-E (31-1/2) (29-11/16) (26-25/32) (23-5/8) (21-21/32) (1-31/32) (19-11/16) (17-23/32) (30-23/32) Drain hose
32mm(1-1/4inch)
PEFY-P24NMHU-E <flexible joint>
PEFY-P27 ·30NMHU-E 1050 1004 930 850 800 25 17 800 15 700 1030 (accessory)
(41-11/32) (39-17/32) (36-5/8) (33-1/2) (31-1/2) (1) (31-1/2) (27-9/16) (40-9/16)
1250 1204 1130 1050 1000 25 21 1000 19 900 1230
PEFY-P36 ·48·54NMHU-E
(49-7/32) (47-13/32) (44-1/2) (41-11/32) (39-3/8) (1) (39-3/8) (35-7/16) (48-7/16)

Note 1.Use M10 screw for the suspension bolt (field supply). Required space for
2.Keep the service space for the maintenance from the bottom 300(11-13/16) or less service and 625
(24
-5
when the heat exchanger is cleaned. maintenance. 6) /8)
3.This chart indicates for PEFY-P36 ·48·54NMHU-E models, which have two fans. -9/1
(27 7/8)
PEFY-P15 ·18·24·27·30NMHU-E models have one fan. 700 9/32~7- ~200
(3-1 100 (5-2 150
4.Make sure to install the air filter(field supply) on the air intake side. 5/16 ~2
~7-7 00 2) L
�n case field supplied air filter is used, attach it where the filter /8) -31/3 Note 2
50(1
(17- 450
550(21-21/32) Max

service is easily done. 50


23/3 (1-
2) 450-23/32) 31/32)
5.On Model :18,36,48 and 54, use flare nut packed with the (17
Access door
i ndoor unit, when connecting the o utdoor unit for R22. 3

20(13/16) or more

When installing the drain water lifting-up mechanism (option)


20(13/16)

Access door Ceiling surface


or more

Carefully make the access door at the appointed position for service maintenance.

Mitsubishi Electric Air Conditioning & Refrigeration Systems Works acquired ISO
9001 certification under Series 9000 of the International Standard Organization (ISO)
based on a review of quality warranties for the production of refrigeration and air
conditioning equipment.

ISO Authorization System


The ISO 9000 series is a plant authorization system relating to quality warranties as
stipulated by the ISO. ISO 9001 certifies quality warranties based on the "design,
Certificate Number FM33568 development, production, installation and auxiliary services" for products built at
an authorized plant.

HVAC Advanced Products Division


Mitsubishi Electric Air Conditioning & Refrigeration Systems Works acquired environmental
management system standard ISO 14001 certification.
Mitsubishi Electric & Electronics USA, Inc.
The ISO 14000 series is a set of standards applying to environmental protection set by the
International Standard Organization (ISO). 3400 Lawrenceville Suwanee Rd.
Certificate Number EC97J1227 Suwanee, GA 30024
Tele: 678-376-2900 • Fax: 800-889-9904
C SD - PEFY-P15NMHU-E - 1 - 200607 © MITSUBISHI ELECTRIC / HVAC 2006 Toll Free: 800-433-4822 (#4)
www.mehvac.com
Model: PEFY-P18NMHU-E
Job Name:

Drawing Reference: Schedule No.

External Finish . . . . . . . . . . . . . . . . . Galvanized steel plate

Dimensions
Inches . . . . . . . . . . . . . 14-31/32 h x 29-17/32 w x 35-7/16 d
mm . . . . . . . . . . . . . . . . . . . . . . . . . . 380 h x 750 w x 900 d

Net Weight . . . . . . . . . . . . . . . . . . . . . . . . . . 100 lb / 45 kg


Coil Type . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Cross fin
(aluminum plate fin and copper tube)

GENERAL FEATURES Fan


Type x Quantity . . . . . . . . . . . . . . . . . . . . . . Sirocco fan x 1
• R410A or R22 refrigerant-compatible Airflow Rate (Low - High) . . . . . . . . . . . . . . . 353-494 CFM
• Ducted fan coil supports multiple configurations for External Static Pressure
flexible installation @ 208V . . . . . . . . . . . . . . . . 0.20 (default) - 0.64 in. WG
• High external static pressure capabilities @ 230V . . . . . . . . . . . . 0.40-0.60 (default) - 0.80 in. WG
• Multiple sizes up to 96,000 Btu/h Motor
Type . . . . . . . . . . . . . . . . .Single phase induction motor
• Quiet operation: 25-54 dB(A)
Output . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 0.130 kW

SPECIFICATIONS Air Filter . . . . . . . . . . . . . . . Filter must be procured locally

Capacity* Refrigerant Pipe Dimensions


Cooling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .18,000 Btu/h R410A
Heating . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .20,000 Btu/h Liquid. . . . . . . . . . . . . . . . . . . . . . . . 1/4" / 6.35 mm flare
Gas . . . . . . . . . . . . . . . . . . . . . . . . . 1/2" / 12.7 mm flare
Power R22
Power Source . . . . . . . . . . . . . . . .208-230V, 1 phase, 60Hz Liquid. . . . . . . . . . . . . . . . . . . . . . . . 3/8" / 9.52 mm flare
Power Consumption Gas . . . . . . . . . . . . . . . . . . . . . . . . 5/8" / 15.88 mm flare
Cooling . . . . . . . . . . . . . . . . . . . . . . . . 0.188 / 0.207 kW
Heating . . . . . . . . . . . . . . . . . . . . . . . . 0.188 / 0.207 kW Drainpipe Dimension . . . . . . . . . . . O.D.1-1/4" / 32 mm
Current
Cooling . . . . . . . . . . . . . . . . . . . . . . . . . . . . 0.96-1.06 A Sound Level (Low - High)
Heating . . . . . . . . . . . . . . . . . . . . . . . . . . . . 0.96-1.06 A @ 208V . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25-32 dB(A)
Minimum Circuit Ampacity (MCA) (208/230) . . 1.20 / 1.33 A @ 230V . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34-39 dB(A)
Maximum Overcurrent Protection (MOCP). . . . . . . . . . . 15A
Options
❏ Drain pump kit. . . . . . . . . . . . . . . . . . . . . PAC-KE04DM-F
❏ Condensate pump . . . . . . . . . . . . . . . . . . . . .SI1730-230
❏ Long-life filter . . . . . . . . . . . . . . . . . . . . . . PAC-KE86LAF
❏ Filter box . . . . . . . . . . . . . . . . . . . . . . . . . PAC-KE63TB-F
* Cooling / Heating capacity indicated the maximum value at operation under the
following conditions:
Cooling: Indoor 80°F (27°C) DB / 67°F (19°C) WB, Outdoor 95°F (35°C) DB
Heating: Indoor 70°F (21°C) DB, Outdoor 47°F (8°C) DB / 43°F (6°C) WB

** Ventilation air: providing sufficient ventilation air is an important part of every


building design. ASHRAE Standard 62 provides the minimum ventilation air
requirements. Also check local codes.

Notes:
Model: PEFY-P18NMHU-E

50(1-31/32)X(J-1)=K
B(Suspension bolt pitch)
50(1-31/32)X(G-1)=H

E
D

A
Air inlet Air outlet

50 (1-31/32)
50(1-31/32)

(1-31/32)
80 50
15(19/32)

(3-5/32)
F

10(13/32)
(2-25/32)

(1-5/8)
41
70

23(29/32)
((2-3/8)

((2-31/32)
60

75
340(13-13/32) 383(15-3/32) 250(9-27/32)

Suspension bolt hole 814(32-1/16)(Suspension bolt pitch) 60(2-3/8)


Model:P15~30 (Note3)
4-14X30(9/16X1-3/16) Slot 904(35-19/32)

900(35-7/16)
24(31/32) 847(33-3/8) 29(1-5/32)
10(13/32) 15(19/32)

Drain hole
Control box (option)

50 (1-31/32)
(3-1/16)

(1-31/32X4=7-7/8)
(1-31/32)X5=(9-27/32)

250(9-27/32)
328(12-15/16)
50X4=200
77
50(1-31/32)

380(14-31/32)
340(13-13/32)
50X5=250

(5-1/8)

25(1)
130
5/8)
41
(1-

Terminal bed
45(1-25/32)

163 (6-13/32)
17(11/16)

94(3-23/32)
30(1-3/16)

(Power source) (3-5/8)


92 200(7-7/8)
Terminal box 343(13-17/32)
Terminal bed 387(15-1/4)
Keep duct-work length 850mm(33-15/32 in.) or more. (Transmission)
Drain hole

m(in.)
Model A B C D E F G H J K L <Flare> <Flare>
PEFY-P15NMHU-E
800 754 6 80 600 550 50 11 500 10 450 780
PEFY-P18NMHU-E (31-1/2) (29-11/16) (26-25/32) (23-5/8) (21-21/32) (1-31/32) (19-11/16) (17-23/32) (30-23/32) Drain hose
32mm(1-1/4inch)
PEFY-P24NMHU-E <flexible joint>
PEFY-P27 ·30NMHU-E 1050 1004 930 850 800 25 17 800 15 700 1030 (accessory)
(41-11/32) (39-17/32) (36-5/8) (33-1/2) (31-1/2) (1) (31-1/2) (27-9/16) (40-9/16)
1250 1204 1130 1050 1000 25 21 1000 19 900 1230
PEFY-P36 ·48·54NMHU-E
(49-7/32) (47-13/32) (44-1/2) (41-11/32) (39-3/8) (1) (39-3/8) (35-7/16) (48-7/16)

Note 1.Use M10 screw for the suspension bolt (field supply). Required space for
2.Keep the service space for the maintenance from the bottom 300(11-13/16) or less service and 625
(24
-5
when the heat exchanger is cleaned. maintenance. 6) /8)
3.This chart indicates for PEFY-P36 ·48·54NMHU-E models, which have two fans. -9/1
(27 7/8)
PEFY-P15 ·18·24·27·30NMHU-E models have one fan. 700 9/32~7- ~200
(3-1 100 (5-2 150
4.Make sure to install the air filter(field supply) on the air intake side. 5/16 ~2
~7-7 00 2) L
�n case field supplied air filter is used, attach it where the filter /8) -31/3 Note 2
50(1
(17- 450
550(21-21/32) Max

service is easily done. 50


23/3 (1-
2) 450-23/32) 31/32)
5.On Model :18,36,48 and 54, use flare nut packed with the (17
Access door
i ndoor unit, when connecting the o utdoor unit for R22. 3

20(13/16) or more

When installing the drain water lifting-up mechanism (option)


20(13/16)

Access door Ceiling surface


or more

Carefully make the access door at the appointed position for service maintenance.

Mitsubishi Electric Air Conditioning & Refrigeration Systems Works acquired ISO
9001 certification under Series 9000 of the International Standard Organization (ISO)
based on a review of quality warranties for the production of refrigeration and air
conditioning equipment.

ISO Authorization System


The ISO 9000 series is a plant authorization system relating to quality warranties as
stipulated by the ISO. ISO 9001 certifies quality warranties based on the "design,
Certificate Number FM33568 development, production, installation and auxiliary services" for products built at
an authorized plant.

HVAC Advanced Products Division


Mitsubishi Electric Air Conditioning & Refrigeration Systems Works acquired environmental
management system standard ISO 14001 certification.
Mitsubishi Electric & Electronics USA, Inc.
The ISO 14000 series is a set of standards applying to environmental protection set by the
International Standard Organization (ISO). 3400 Lawrenceville Suwanee Rd.
Certificate Number EC97J1227 Suwanee, GA 30024
Tele: 678-376-2900 • Fax: 800-889-9904
C SD - PEFY-P18NMHU-E - 1 - 200607 © MITSUBISHI ELECTRIC / HVAC 2006 Toll Free: 800-433-4822 (#4)
www.mehvac.com
Model: PEFY-P24NMHU-E
Job Name:

Drawing Reference: Schedule No.

External Finish . . . . . . . . . . . . . . . . . Galvanized steel plate

Dimensions
Inches . . . . . . . . . . . . . 14-31/32 h x 29-17/32 w x 35-7/16 d
mm . . . . . . . . . . . . . . . . . . . . . . . . . . 380 h x 750 w x 900 d

Net Weight . . . . . . . . . . . . . . . . . . . . . . . . . . 100 lb / 45 kg

Coil Type . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Cross fin


(aluminum plate fin and copper tube)
GENERAL FEATURES Fan
• R410A or R22 refrigerant-compatible Type x Quantity . . . . . . . . . . . . . . . . . . . . . . Sirocco fan x 1
• Ducted fan coil supports multiple configurations for Airflow Rate (Low - High) . . . . . . . . . . . . . . . 477-671 CFM
flexible installation External Static Pressure
@ 208V . . . . . . . . . . . . . . . . 0.20 (default) - 0.64 in. WG
• High external static pressure capabilities
@ 230V . . . . . . . . . . . . 0.40-0.60 (default) - 0.80 in. WG
• Multiple sizes up to 96,000 Btu/h Motor
• Quiet operation: 25-54 dB(A) Type . . . . . . . . . . . . . . . . .Single phase induction motor
Output . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 0.180 kW
SPECIFICATIONS
Air Filter . . . . . . . . . . . . . . . Filter must be procured locally
Capacity*
Cooling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .24,000 Btu/h Refrigerant Pipe Dimensions
Heating . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .27,000 Btu/h R410A or R22
Liquid. . . . . . . . . . . . . . . . . . . . . . . . 3/8" / 9.52 mm flare
Gas . . . . . . . . . . . . . . . . . . . . . . . . 5/8" / 15.88 mm flare
Power
Power Source . . . . . . . . . . . . . . . .208-230V, 1 phase, 60Hz
Power Consumption
Drainpipe Dimension . . . . . . . . . . . O.D.1-1/4" / 32 mm
Cooling . . . . . . . . . . . . . . . . . . . . . . . . 0.245 / 0.270 kW
Heating . . . . . . . . . . . . . . . . . . . . . . . . 0.245 / 0.270 kW
Sound Level (Low - High)
@ 208V . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29-36 dB(A)
Current
@ 230V . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36-41 dB(A)
Cooling . . . . . . . . . . . . . . . . . . . . . . . . . . . 1.25 / 1.38 A
Heating . . . . . . . . . . . . . . . . . . . . . . . . . . . 1.25 / 1.38 A
Minimum Circuit Ampacity (MCA) (208/230) . 1.57 / 1.73 A Options
Maximum Overcurrent Protection (MOCP). . . . . . . . . . . 15A ❏ Drain pump kit. . . . . . . . . . . . . . . . . . . . . PAC-KE04DM-F
❏ Condensate pump . . . . . . . . . . . . . . . . . . . . .SI1730-230
❏ Long-life filter . . . . . . . . . . . . . . . . . . . . . . PAC-KE86LAF
❏ Filter box . . . . . . . . . . . . . . . . . . . . . . . . . PAC-KE63TB-F

* Cooling / Heating capacity indicated the maximum value at operation under the
following conditions:
Cooling: Indoor 80°F (27°C) DB / 67°F (19°C) WB, Outdoor 95°F (35°C) DB
Heating: Indoor 70°F (21°C) DB, Outdoor 47°F (8°C) DB / 43°F (6°C) WB

** Ventilation air: providing sufficient ventilation air is an important part of every


building design. ASHRAE Standard 62 provides the minimum ventilation air
requirements. Also check local codes.

Notes:
Model: PEFY-P24NMHU-E

50(1-31/32)X(J-1)=K
B(Suspension bolt pitch)
50(1-31/32)X(G-1)=H

E
D

A
Air inlet Air outlet

50 (1-31/32)
50(1-31/32)

(1-31/32)
80 50
15(19/32)

(3-5/32)
F

10(13/32)
(2-25/32)

(1-5/8)
41
70

23(29/32)
((2-3/8)

((2-31/32)
60

75
340(13-13/32) 383(15-3/32) 250(9-27/32)

Suspension bolt hole 814(32-1/16)(Suspension bolt pitch) 60(2-3/8)


Model:P15~30 (Note3)
4-14X30(9/16X1-3/16) Slot 904(35-19/32)

900(35-7/16)
24(31/32) 847(33-3/8) 29(1-5/32)
10(13/32) 15(19/32)

Drain hole
Control box (option)

50 (1-31/32)
(3-1/16)

(1-31/32X4=7-7/8)
(1-31/32)X5=(9-27/32)

250(9-27/32)
328(12-15/16)
50X4=200
77
50(1-31/32)

380(14-31/32)
340(13-13/32)
50X5=250

(5-1/8)

25(1)
130
5/8)
41
(1-

Terminal bed
45(1-25/32)

163 (6-13/32)
17(11/16)

94(3-23/32)
30(1-3/16)

(Power source) (3-5/8)


92 200(7-7/8)
Terminal box 343(13-17/32)
Terminal bed 387(15-1/4)
Keep duct-work length 850mm(33-15/32 in.) or more. (Transmission)
Drain hole

m(in.)
Model A B C D E F G H J K L <Flare> <Flare>
PEFY-P15NMHU-E
800 754 6 80 600 550 50 11 500 10 450 780
PEFY-P18NMHU-E (31-1/2) (29-11/16) (26-25/32) (23-5/8) (21-21/32) (1-31/32) (19-11/16) (17-23/32) (30-23/32) Drain hose
32mm(1-1/4inch)
PEFY-P24NMHU-E <flexible joint>
PEFY-P27 ·30NMHU-E 1050 1004 930 850 800 25 17 800 15 700 1030 (accessory)
(41-11/32) (39-17/32) (36-5/8) (33-1/2) (31-1/2) (1) (31-1/2) (27-9/16) (40-9/16)
1250 1204 1130 1050 1000 25 21 1000 19 900 1230
PEFY-P36 ·48·54NMHU-E
(49-7/32) (47-13/32) (44-1/2) (41-11/32) (39-3/8) (1) (39-3/8) (35-7/16) (48-7/16)

Note 1.Use M10 screw for the suspension bolt (field supply). Required space for
2.Keep the service space for the maintenance from the bottom 300(11-13/16) or less service and 625
(24
-5
when the heat exchanger is cleaned. maintenance. 6) /8)
3.This chart indicates for PEFY-P36 ·48·54NMHU-E models, which have two fans. -9/1
(27 7/8)
PEFY-P15 ·18·24·27·30NMHU-E models have one fan. 700 9/32~7- ~200
(3-1 100 (5-2 150
4.Make sure to install the air filter(field supply) on the air intake side. 5/16 ~2
~7-7 00 2) L
�n case field supplied air filter is used, attach it where the filter /8) -31/3 Note 2
50(1
(17- 450
550(21-21/32) Max

service is easily done. 50


23/3 (1-
2) 450-23/32) 31/32)
5.On Model :18,36,48 and 54, use flare nut packed with the (17
Access door
i ndoor unit, when connecting the o utdoor unit for R22. 3

20(13/16) or more

When installing the drain water lifting-up mechanism (option)


20(13/16)

Access door Ceiling surface


or more

Carefully make the access door at the appointed position for service maintenance.

Mitsubishi Electric Air Conditioning & Refrigeration Systems Works acquired ISO
9001 certification under Series 9000 of the International Standard Organization (ISO)
based on a review of quality warranties for the production of refrigeration and air
conditioning equipment.

ISO Authorization System


The ISO 9000 series is a plant authorization system relating to quality warranties as
stipulated by the ISO. ISO 9001 certifies quality warranties based on the "design,
Certificate Number FM33568 development, production, installation and auxiliary services" for products built at
an authorized plant.

HVAC Advanced Products Division


Mitsubishi Electric Air Conditioning & Refrigeration Systems Works acquired environmental
management system standard ISO 14001 certification.
Mitsubishi Electric & Electronics USA, Inc.
The ISO 14000 series is a set of standards applying to environmental protection set by the
International Standard Organization (ISO). 3400 Lawrenceville Suwanee Rd.
Certificate Number EC97J1227 Suwanee, GA 30024
Tele: 678-376-2900 • Fax: 800-889-9904
C SD - PEFY-P24NMHU-E - 1 - 200607 © MITSUBISHI ELECTRIC / HVAC 2006 Toll Free: 800-433-4822 (#4)
www.mehvac.com
Model: PEFY-P27NMHU-E
Job Name:

Drawing Reference: Schedule No.

External Finish . . . . . . . . . . . . . . . . . Galvanized steel plate

Dimensions
Inches . . . . . . . . . . . . . . . 14-31/32 h x 39-3/8 w x 35-7/16 d
mm . . . . . . . . . . . . . . . . . . . . . . . . . 380 h x 1000 w x 900 d

Net Weight . . . . . . . . . . . . . . . . . . . . . . . . . . 111 lb / 50 kg

Coil Type . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Cross fin


(aluminum plate fin and copper tube)
GENERAL FEATURES Fan
• R410A or R22 refrigerant-compatible Type x Quantity . . . . . . . . . . . . . . . . . . . . . . Sirocco fan x 1
• Ducted fan coil supports multiple configurations for Airflow Rate (Low - High) . . . . . . . . . . . . . . . 547-777 CFM
flexible installation External Static Pressure
@ 208V . . . . . . . . . . . . . . . . 0.20 (default) - 0.64 in. WG
• High external static pressure capabilities
@ 230V . . . . . . . . . . . . 0.40-0.60 (default) - 0.80 in. WG
• Multiple sizes up to 96,000 Btu/h Motor
• Quiet operation: 25-54 dB(A) Type . . . . . . . . . . . . . . . . .Single phase induction motor
Output . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 0.220 kW
SPECIFICATIONS
Air Filter . . . . . . . . . . . . . . . Filter must be procured locally
Capacity*
Cooling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .27,000 Btu/h Refrigerant Pipe Dimensions
Heating . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .30,000 Btu/h R410A or R22
Liquid. . . . . . . . . . . . . . . . . . . . . . . . 3/8" / 9.52 mm flare
Gas . . . . . . . . . . . . . . . . . . . . . . . . 5/8" / 15.88 mm flare
Power
Power Source . . . . . . . . . . . . . . . .208-230V, 1 phase, 60Hz
Power Consumption
Drainpipe Dimension . . . . . . . . . . . O.D.1-1/4" / 32 mm
Cooling . . . . . . . . . . . . . . . . . . . . . . . . 0.270 / 0.297 kW
Heating . . . . . . . . . . . . . . . . . . . . . . . . 0.270 / 0.297 kW
Sound Level (Low - High)
@ 208V . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30-38 dB(A)
Current
@ 230V . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35-41 dB(A)
Cooling . . . . . . . . . . . . . . . . . . . . . . . . . . . 1.37 / 1.51 A
Heating . . . . . . . . . . . . . . . . . . . . . . . . . . . 1.37 / 1.51 A
Minimum Circuit Ampacity (MCA) (208/230) . 1.72 / 1.89 A Options
Maximum Overcurrent Protection (MOCP). . . . . . . . . . . 15A ❏ Drain pump kit. . . . . . . . . . . . . . . . . . . . . PAC-KE04DM-F
❏ Condensate pump . . . . . . . . . . . . . . . . . . . . .SI1730-230
❏ Long-life filter . . . . . . . . . . . . . . . . . . . . . . PAC-KE86LAF
❏ Filter box . . . . . . . . . . . . . . . . . . . . . . . . . PAC-KE63TB-F

* Cooling / Heating capacity indicated the maximum value at operation under the
following conditions:
Cooling: Indoor 80°F (27°C) DB / 67°F (19°C) WB, Outdoor 95°F (35°C) DB
Heating: Indoor 70°F (21°C) DB, Outdoor 47°F (8°C) DB / 43°F (6°C) WB

** Ventilation air: providing sufficient ventilation air is an important part of every


building design. ASHRAE Standard 62 provides the minimum ventilation air
requirements. Also check local codes.

Notes:
Model: PEFY-P27NMHU-E

50(1-31/32)X(J-1)=K
B(Suspension bolt pitch)
50(1-31/32)X(G-1)=H

E
D

A
Air inlet Air outlet

50 (1-31/32)
50(1-31/32)

(1-31/32)
80 50
15(19/32)

(3-5/32)
F

10(13/32)
(2-25/32)

(1-5/8)
41
70

23(29/32)
((2-3/8)

((2-31/32)
60

75
340(13-13/32) 383(15-3/32) 250(9-27/32)

Suspension bolt hole 814(32-1/16)(Suspension bolt pitch) 60(2-3/8)


Model:P15~30 (Note3)
4-14X30(9/16X1-3/16) Slot 904(35-19/32)

900(35-7/16)
24(31/32) 847(33-3/8) 29(1-5/32)
10(13/32) 15(19/32)

Drain hole
Control box (option)

50 (1-31/32)
(3-1/16)

(1-31/32X4=7-7/8)
(1-31/32)X5=(9-27/32)

250(9-27/32)
328(12-15/16)
50X4=200
77
50(1-31/32)

380(14-31/32)
340(13-13/32)
50X5=250

(5-1/8)

25(1)
130
5/8)
41
(1-

Terminal bed
45(1-25/32)

163 (6-13/32)
17(11/16)

94(3-23/32)
30(1-3/16)

(Power source) (3-5/8)


92 200(7-7/8)
Terminal box 343(13-17/32)
Terminal bed 387(15-1/4)
Keep duct-work length 850mm(33-15/32 in.) or more. (Transmission)
Drain hole

m(in.)
Model A B C D E F G H J K L <Flare> <Flare>
PEFY-P15NMHU-E
800 754 6 80 600 550 50 11 500 10 450 780
PEFY-P18NMHU-E (31-1/2) (29-11/16) (26-25/32) (23-5/8) (21-21/32) (1-31/32) (19-11/16) (17-23/32) (30-23/32) Drain hose
32mm(1-1/4inch)
PEFY-P24NMHU-E <flexible joint>
PEFY-P27 ·30NMHU-E 1050 1004 930 850 800 25 17 800 15 700 1030 (accessory)
(41-11/32) (39-17/32) (36-5/8) (33-1/2) (31-1/2) (1) (31-1/2) (27-9/16) (40-9/16)
1250 1204 1130 1050 1000 25 21 1000 19 900 1230
PEFY-P36 ·48·54NMHU-E
(49-7/32) (47-13/32) (44-1/2) (41-11/32) (39-3/8) (1) (39-3/8) (35-7/16) (48-7/16)

Note 1.Use M10 screw for the suspension bolt (field supply). Required space for
2.Keep the service space for the maintenance from the bottom 300(11-13/16) or less service and 625
(24
-5
when the heat exchanger is cleaned. maintenance. 6) /8)
3.This chart indicates for PEFY-P36 ·48·54NMHU-E models, which have two fans. -9/1
(27 7/8)
PEFY-P15 ·18·24·27·30NMHU-E models have one fan. 700 9/32~7- ~200
(3-1 100 (5-2 150
4.Make sure to install the air filter(field supply) on the air intake side. 5/16 ~2
~7-7 00 2) L
�n case field supplied air filter is used, attach it where the filter /8) -31/3 Note 2
50(1
(17- 450
550(21-21/32) Max

service is easily done. 50


23/3 (1-
2) 450-23/32) 31/32)
5.On Model :18,36,48 and 54, use flare nut packed with the (17
Access door
i ndoor unit, when connecting the o utdoor unit for R22. 3

20(13/16) or more

When installing the drain water lifting-up mechanism (option)


20(13/16)

Access door Ceiling surface


or more

Carefully make the access door at the appointed position for service maintenance.

Mitsubishi Electric Air Conditioning & Refrigeration Systems Works acquired ISO
9001 certification under Series 9000 of the International Standard Organization (ISO)
based on a review of quality warranties for the production of refrigeration and air
conditioning equipment.

ISO Authorization System


The ISO 9000 series is a plant authorization system relating to quality warranties as
stipulated by the ISO. ISO 9001 certifies quality warranties based on the "design,
Certificate Number FM33568 development, production, installation and auxiliary services" for products built at
an authorized plant.

HVAC Advanced Products Division


Mitsubishi Electric Air Conditioning & Refrigeration Systems Works acquired environmental
management system standard ISO 14001 certification.
Mitsubishi Electric & Electronics USA, Inc.
The ISO 14000 series is a set of standards applying to environmental protection set by the
International Standard Organization (ISO). 3400 Lawrenceville Suwanee Rd.
Certificate Number EC97J1227 Suwanee, GA 30024
Tele: 678-376-2900 • Fax: 800-889-9904
C SD - PEFY-P27NMHU-E - 1 - 200607 © MITSUBISHI ELECTRIC / HVAC 2006 Toll Free: 800-433-4822 (#4)
www.mehvac.com
Model: PEFY-P30NMHU-E
Job Name:

Drawing Reference: Schedule No.

External Finish . . . . . . . . . . . . . . . . . Galvanized steel plate

Dimensions
Inches . . . . . . . . . . . . . . . 14-31/32 h x 39-3/8 w x 35-7/16 d
mm . . . . . . . . . . . . . . . . . . . . . . . . . 380 h x 1000 w x 900 d

Net Weight . . . . . . . . . . . . . . . . . . . . . . . . . . 111 lb / 50 kg

Coil Type . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Cross fin


(aluminum plate fin and copper tube)
GENERAL FEATURES Fan
• R410A or R22 refrigerant-compatible Type x Quantity . . . . . . . . . . . . . . . . . . . . . . Sirocco fan x 1
• Ducted fan coil supports multiple configurations for Airflow Rate (Low - High) . . . . . . . . . . . . . . . 636-883 CFM
flexible installation External Static Pressure
@ 208V . . . . . . . . . . . . . . . . 0.20 (default) - 0.64 in. WG
• High external static pressure capabilities
@ 230V . . . . . . . . . . . . 0.40-0.60 (default) - 0.80 in. WG
• Multiple sizes up to 96,000 Btu/h Motor
• Quiet operation: 25-54 dB(A) Type . . . . . . . . . . . . . . . . .Single phase induction motor
Output . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 0.230 kW
SPECIFICATIONS
Air Filter . . . . . . . . . . . . . . . Filter must be procured locally
Capacity*
Cooling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .30,000 Btu/h Refrigerant Pipe Dimensions
Heating . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .34,000 Btu/h R410A or R22
Liquid. . . . . . . . . . . . . . . . . . . . . . . . 3/8" / 9.52 mm flare
Gas . . . . . . . . . . . . . . . . . . . . . . . . 5/8" / 15.88 mm flare
Power
Power Source . . . . . . . . . . . . . . . .208-230V, 1 phase, 60Hz
Power Consumption
Drainpipe Dimension . . . . . . . . . . . O.D.1-1/4" / 32 mm
Cooling . . . . . . . . . . . . . . . . . . . . . . . . 0.326 / 0.360 kW
Heating . . . . . . . . . . . . . . . . . . . . . . . . 0.326 / 0.360 kW
Sound Level (Low - High)
@ 208V . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33-40 dB(A)
Current
@ 230V . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38-43 dB(A)
Cooling . . . . . . . . . . . . . . . . . . . . . . . . . . . 1.66 / 1.83 A
Heating . . . . . . . . . . . . . . . . . . . . . . . . . . . 1.66 / 1.83 A
Minimum Circuit Ampacity (MCA) (208/230) . 2.08 / 2.29 A Options
Maximum Overcurrent Protection (MOCP). . . . . . . . . . . 15A ❏ Drain pump kit. . . . . . . . . . . . . . . . . . . . . PAC-KE04DM-F
❏ Condensate pump . . . . . . . . . . . . . . . . . . . . .SI1730-230
❏ Long-life filter . . . . . . . . . . . . . . . . . . . . . . PAC-KE88LAF
❏ Filter box . . . . . . . . . . . . . . . . . . . . . . . . . PAC-KE80TB-F

* Cooling / Heating capacity indicated the maximum value at operation under the
following conditions:
Cooling: Indoor 80°F (27°C) DB / 67°F (19°C) WB, Outdoor 95°F (35°C) DB
Heating: Indoor 70°F (21°C) DB, Outdoor 47°F (8°C) DB / 43°F (6°C) WB

** Ventilation air: providing sufficient ventilation air is an important part of every


building design. ASHRAE Standard 62 provides the minimum ventilation air
requirements. Also check local codes.

Notes:
Model: PEFY-P30NMHU-E

50(1-31/32)X(J-1)=K
B(Suspension bolt pitch)
50(1-31/32)X(G-1)=H

E
D

A
Air inlet Air outlet

50 (1-31/32)
50(1-31/32)

(1-31/32)
80 50
15(19/32)

(3-5/32)
F

10(13/32)
(2-25/32)

(1-5/8)
41
70

23(29/32)
((2-3/8)

((2-31/32)
60

75
340(13-13/32) 383(15-3/32) 250(9-27/32)

Suspension bolt hole 814(32-1/16)(Suspension bolt pitch) 60(2-3/8)


Model:P15~30 (Note3)
4-14X30(9/16X1-3/16) Slot 904(35-19/32)

900(35-7/16)
24(31/32) 847(33-3/8) 29(1-5/32)
10(13/32) 15(19/32)

Drain hole
Control box (option)

50 (1-31/32)
(3-1/16)

(1-31/32X4=7-7/8)
(1-31/32)X5=(9-27/32)

250(9-27/32)
328(12-15/16)
50X4=200
77
50(1-31/32)

380(14-31/32)
340(13-13/32)
50X5=250

(5-1/8)

25(1)
130
5/8)
41
(1-

Terminal bed
45(1-25/32)

163 (6-13/32)
17(11/16)

94(3-23/32)
30(1-3/16)

(Power source) (3-5/8)


92 200(7-7/8)
Terminal box 343(13-17/32)
Terminal bed 387(15-1/4)
Keep duct-work length 850mm(33-15/32 in.) or more. (Transmission)
Drain hole

m(in.)
Model A B C D E F G H J K L <Flare> <Flare>
PEFY-P15NMHU-E
800 754 6 80 600 550 50 11 500 10 450 780
PEFY-P18NMHU-E (31-1/2) (29-11/16) (26-25/32) (23-5/8) (21-21/32) (1-31/32) (19-11/16) (17-23/32) (30-23/32) Drain hose
32mm(1-1/4inch)
PEFY-P24NMHU-E <flexible joint>
PEFY-P27 ·30NMHU-E 1050 1004 930 850 800 25 17 800 15 700 1030 (accessory)
(41-11/32) (39-17/32) (36-5/8) (33-1/2) (31-1/2) (1) (31-1/2) (27-9/16) (40-9/16)
1250 1204 1130 1050 1000 25 21 1000 19 900 1230
PEFY-P36 ·48·54NMHU-E
(49-7/32) (47-13/32) (44-1/2) (41-11/32) (39-3/8) (1) (39-3/8) (35-7/16) (48-7/16)

Note 1.Use M10 screw for the suspension bolt (field supply). Required space for
2.Keep the service space for the maintenance from the bottom 300(11-13/16) or less service and 625
(24
-5
when the heat exchanger is cleaned. maintenance. 6) /8)
3.This chart indicates for PEFY-P36 ·48·54NMHU-E models, which have two fans. -9/1
(27 7/8)
PEFY-P15 ·18·24·27·30NMHU-E models have one fan. 700 9/32~7- ~200
(3-1 100 (5-2 150
4.Make sure to install the air filter(field supply) on the air intake side. 5/16 ~2
~7-7 00 2) L
�n case field supplied air filter is used, attach it where the filter /8) -31/3 Note 2
50(1
(17- 450
550(21-21/32) Max

service is easily done. 50


23/3 (1-
2) 450-23/32) 31/32)
5.On Model :18,36,48 and 54, use flare nut packed with the (17
Access door
i ndoor unit, when connecting the o utdoor unit for R22. 3

20(13/16) or more

When installing the drain water lifting-up mechanism (option)


20(13/16)

Access door Ceiling surface


or more

Carefully make the access door at the appointed position for service maintenance.

Mitsubishi Electric Air Conditioning & Refrigeration Systems Works acquired ISO
9001 certification under Series 9000 of the International Standard Organization (ISO)
based on a review of quality warranties for the production of refrigeration and air
conditioning equipment.

ISO Authorization System


The ISO 9000 series is a plant authorization system relating to quality warranties as
stipulated by the ISO. ISO 9001 certifies quality warranties based on the "design,
Certificate Number FM33568 development, production, installation and auxiliary services" for products built at
an authorized plant.

HVAC Advanced Products Division


Mitsubishi Electric Air Conditioning & Refrigeration Systems Works acquired environmental
management system standard ISO 14001 certification.
Mitsubishi Electric & Electronics USA, Inc.
The ISO 14000 series is a set of standards applying to environmental protection set by the
International Standard Organization (ISO). 3400 Lawrenceville Suwanee Rd.
Certificate Number EC97J1227 Suwanee, GA 30024
Tele: 678-376-2900 • Fax: 800-889-9904
C SD - PEFY-P30NMHU-E - 1 - 200607 © MITSUBISHI ELECTRIC / HVAC 2006 Toll Free: 800-433-4822 (#4)
www.mehvac.com
Model: PEFY-P36NMHU-E
Job Name:

Drawing Reference: Schedule No.

External Finish . . . . . . . . . . . . . . . . . Galvanized steel plate

Dimensions
Inches . . . . . . . . . . . . . . . 14-31/32 h x 47-1/4 w x 35-7/16 d
mm . . . . . . . . . . . . . . . . . . . . . . . . . 380 h x 1200 w x 900 d

Net Weight . . . . . . . . . . . . . . . . . . . . . . . . . . 155 lb / 70 kg


Coil Type . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Cross fin
(aluminum plate fin and copper tube)

GENERAL FEATURES Fan


Type x Quantity . . . . . . . . . . . . . . . . . . . . . . Sirocco fan x 2
• R410A or R22 refrigerant-compatible Airflow Rate (Low - High) . . . . . . . . . . . . . . . 936-1342 CFM
• Ducted fan coil supports multiple configurations for External Static Pressure
flexible installation @ 208V . . . . . . . . . . . . . . . . 0.20 (default) - 0.64 in. WG
• High external static pressure capabilities @ 230V . . . . . . . . . . . . 0.40-0.60 (default) - 0.80 in. WG
• Multiple sizes up to 96,000 Btu/h Motor
Type . . . . . . . . . . . . . . . . .Single phase induction motor
• Quiet operation: 25-54 dB(A)
Output . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 0.400 kW

SPECIFICATIONS Air Filter . . . . . . . . . . . . . . . Filter must be procured locally

Capacity* Refrigerant Pipe Dimensions


Cooling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .36,000 Btu/h R410A
Heating . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .40,000 Btu/h Liquid. . . . . . . . . . . . . . . . . . . . . . . . 3/8" / 9.52 mm flare
Gas . . . . . . . . . . . . . . . . . . . . . . . . 5/8" / 15.88 mm flare
Power R22
Power Source . . . . . . . . . . . . . . . .208-230V, 1 phase, 60Hz Liquid. . . . . . . . . . . . . . . . . . . . . . . . 3/8" / 9.52 mm flare
Power Consumption Gas . . . . . . . . . . . . . . . . . . . . . . . . 3/4" / 19.05 mm flare
Cooling . . . . . . . . . . . . . . . . . . . . . . . . 0.683 / 0.754 kW
Heating . . . . . . . . . . . . . . . . . . . . . . . . 0.683 / 0.754 kW Drainpipe Dimension . . . . . . . . . . . O.D.1-1/4" / 32 mm
Current
Cooling . . . . . . . . . . . . . . . . . . . . . . . . . . . 3.38 / 3.73 A Sound Level (Low - High)
Heating . . . . . . . . . . . . . . . . . . . . . . . . . . . 3.38 / 3.73 A @ 208V . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31-41 dB(A)
Minimum Circuit Ampacity (MCA) (208/230) . 4.23 / 4.67 A @ 230V . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38-44 dB(A)
Maximum Overcurrent Protection (MOCP). . . . . . . . . . . 15A
Options
❏ Drain pump kit. . . . . . . . . . . . . . . . . . . . . PAC-KE04DM-F
❏ Condensate pump . . . . . . . . . . . . . . . . . . . . .SI1730-230
❏ Long-life filter . . . . . . . . . . . . . . . . . . . . . . PAC-KE89LAF
❏ Filter box . . . . . . . . . . . . . . . . . . . . . . . . PAC-KE140TB-F
* Cooling / Heating capacity indicated the maximum value at operation under the
following conditions:
Cooling: Indoor 80°F (27°C) DB / 67°F (19°C) WB, Outdoor 95°F (35°C) DB
Heating: Indoor 70°F (21°C) DB, Outdoor 47°F (8°C) DB / 43°F (6°C) WB

** Ventilation air: providing sufficient ventilation air is an important part of every


building design. ASHRAE Standard 62 provides the minimum ventilation air
requirements. Also check local codes.

Notes:
Model: PEFY-P36NMHU-E

50(1-31/32)X(J-1)=K
B(Suspension bolt pitch)
50(1-31/32)X(G-1)=H

E
D

A
Air inlet Air outlet

50 (1-31/32)
50(1-31/32)

(1-31/32)
80 50
15(19/32)

(3-5/32)
F

10(13/32)
(2-25/32)

(1-5/8)
41
70

23(29/32)
((2-3/8)

((2-31/32)
60

75
340(13-13/32) 383(15-3/32) 250(9-27/32)

Suspension bolt hole 814(32-1/16)(Suspension bolt pitch) 60(2-3/8)


Model:P15~30 (Note3)
4-14X30(9/16X1-3/16) Slot 904(35-19/32)

900(35-7/16)
24(31/32) 847(33-3/8) 29(1-5/32)
10(13/32) 15(19/32)

Drain hole
Control box (option)

50 (1-31/32)
(3-1/16)

(1-31/32X4=7-7/8)
(1-31/32)X5=(9-27/32)

250(9-27/32)
328(12-15/16)
50X4=200
77
50(1-31/32)

380(14-31/32)
340(13-13/32)
50X5=250

(5-1/8)

25(1)
130
5/8)
41
(1-

Terminal bed
45(1-25/32)

163 (6-13/32)
17(11/16)

94(3-23/32)
30(1-3/16)

(Power source) (3-5/8)


92 200(7-7/8)
Terminal box 343(13-17/32)
Terminal bed 387(15-1/4)
Keep duct-work length 850mm(33-15/32 in.) or more. (Transmission)
Drain hole

m(in.)
Model A B C D E F G H J K L <Flare> <Flare>
PEFY-P15NMHU-E
800 754 6 80 600 550 50 11 500 10 450 780
PEFY-P18NMHU-E (31-1/2) (29-11/16) (26-25/32) (23-5/8) (21-21/32) (1-31/32) (19-11/16) (17-23/32) (30-23/32) Drain hose
32mm(1-1/4inch)
PEFY-P24NMHU-E <flexible joint>
PEFY-P27 ·30NMHU-E 1050 1004 930 850 800 25 17 800 15 700 1030 (accessory)
(41-11/32) (39-17/32) (36-5/8) (33-1/2) (31-1/2) (1) (31-1/2) (27-9/16) (40-9/16)
1250 1204 1130 1050 1000 25 21 1000 19 900 1230
PEFY-P36 ·48·54NMHU-E
(49-7/32) (47-13/32) (44-1/2) (41-11/32) (39-3/8) (1) (39-3/8) (35-7/16) (48-7/16)

Note 1.Use M10 screw for the suspension bolt (field supply). Required space for
2.Keep the service space for the maintenance from the bottom 300(11-13/16) or less service and 625
(24
-5
when the heat exchanger is cleaned. maintenance. 6) /8)
3.This chart indicates for PEFY-P36 ·48·54NMHU-E models, which have two fans. -9/1
(27 7/8)
PEFY-P15 ·18·24·27·30NMHU-E models have one fan. 700 9/32~7- ~200
(3-1 100 (5-2 150
4.Make sure to install the air filter(field supply) on the air intake side. 5/16 ~2
~7-7 00 2) L
�n case field supplied air filter is used, attach it where the filter /8) -31/3 Note 2
50(1
(17- 450
550(21-21/32) Max

service is easily done. 50


23/3 (1-
2) 450-23/32) 31/32)
5.On Model :18,36,48 and 54, use flare nut packed with the (17
Access door
i ndoor unit, when connecting the o utdoor unit for R22. 3

20(13/16) or more

When installing the drain water lifting-up mechanism (option)


20(13/16)

Access door Ceiling surface


or more

Carefully make the access door at the appointed position for service maintenance.

Mitsubishi Electric Air Conditioning & Refrigeration Systems Works acquired ISO
9001 certification under Series 9000 of the International Standard Organization (ISO)
based on a review of quality warranties for the production of refrigeration and air
conditioning equipment.

ISO Authorization System


The ISO 9000 series is a plant authorization system relating to quality warranties as
stipulated by the ISO. ISO 9001 certifies quality warranties based on the "design,
Certificate Number FM33568 development, production, installation and auxiliary services" for products built at
an authorized plant.

HVAC Advanced Products Division


Mitsubishi Electric Air Conditioning & Refrigeration Systems Works acquired environmental
management system standard ISO 14001 certification.
Mitsubishi Electric & Electronics USA, Inc.
The ISO 14000 series is a set of standards applying to environmental protection set by the
International Standard Organization (ISO). 3400 Lawrenceville Suwanee Rd.
Certificate Number EC97J1227 Suwanee, GA 30024
Tele: 678-376-2900 • Fax: 800-889-9904
C SD - PEFY-P36NMHU-E - 1 - 200607 © MITSUBISHI ELECTRIC / HVAC 2006 Toll Free: 800-433-4822 (#4)
www.mehvac.com
Model: PEFY-P48NMHU-E
Job Name:

Drawing Reference: Schedule No.

External Finish . . . . . . . . . . . . . . . . . Galvanized steel plate

Dimensions
Inches . . . . . . . . . . . . . . . 14-31/32 h x 47-1/4 w x 35-7/16 d
mm . . . . . . . . . . . . . . . . . . . . . . . . . 380 h x 1200 w x 900 d

Net Weight . . . . . . . . . . . . . . . . . . . . . . . . . . 155 lb / 70 kg


Coil Type . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Cross fin
(aluminum plate fin and copper tube)

GENERAL FEATURES Fan


Type x Quantity . . . . . . . . . . . . . . . . . . . . . . Sirocco fan x 2
• R410A or R22 refrigerant-compatible Airflow Rate (Low - High) . . . . . . . . . . . . . . . 936-1342 CFM
• Ducted fan coil supports multiple configurations for External Static Pressure
flexible installation @ 208V . . . . . . . . . . . . . . . . 0.20 (default) - 0.64 in. WG
• High external static pressure capabilities @ 230V . . . . . . . . . . . . 0.40-0.60 (default) - 0.80 in. WG
• Multiple sizes up to 96,000 Btu/h Motor
Type . . . . . . . . . . . . . . . . .Single phase induction motor
• Quiet operation: 25-54 dB(A)
Output . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 0.400 kW

SPECIFICATIONS Air Filter . . . . . . . . . . . . . . . Filter must be procured locally

Capacity* Refrigerant Pipe Dimensions


Cooling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .48,000 Btu/h R410A
Heating . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .54,000 Btu/h Liquid. . . . . . . . . . . . . . . . . . . . . . . . 3/8" / 9.52 mm flare
Gas . . . . . . . . . . . . . . . . . . . . . . . . 5/8" / 15.88 mm flare
Power R22
Power Source . . . . . . . . . . . . . . . .208-230V, 1 phase, 60Hz Liquid. . . . . . . . . . . . . . . . . . . . . . . . 3/8" / 9.52 mm flare
Power Consumption Gas . . . . . . . . . . . . . . . . . . . . . . . . 3/4" / 19.05 mm flare
Cooling . . . . . . . . . . . . . . . . . . . . . . . . 0.683 / 0.754 kW
Heating . . . . . . . . . . . . . . . . . . . . . . . . 0.683 / 0.754 kW Drainpipe Dimension . . . . . . . . . . . O.D.1-1/4" / 32 mm
Current
Cooling . . . . . . . . . . . . . . . . . . . . . . . . . . . 3.38 / 3.73 A Sound Level (Low - High)
Heating . . . . . . . . . . . . . . . . . . . . . . . . . . . 3.38 / 3.73 A @ 208V . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31-41 dB(A)
Minimum Circuit Ampacity (MCA) (208/230) . 4.23 / 4.67 A @ 230V . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38-44 dB(A)
Maximum Overcurrent Protection (MOCP). . . . . . . . . . . 15A
Options
❏ Drain pump kit. . . . . . . . . . . . . . . . . . . . . PAC-KE04DM-F
❏ Condensate pump . . . . . . . . . . . . . . . . . . . . .SI1730-230
❏ Long-life filter . . . . . . . . . . . . . . . . . . . . . . PAC-KE89LAF
❏ Filter box . . . . . . . . . . . . . . . . . . . . . . . . PAC-KE140TB-F
* Cooling / Heating capacity indicated the maximum value at operation under the
following conditions:
Cooling: Indoor 80°F (27°C) DB / 67°F (19°C) WB, Outdoor 95°F (35°C) DB
Heating: Indoor 70°F (21°C) DB, Outdoor 47°F (8°C) DB / 43°F (6°C) WB

** Ventilation air: providing sufficient ventilation air is an important part of every


building design. ASHRAE Standard 62 provides the minimum ventilation air
requirements. Also check local codes.

Notes:
Model: PEFY-P48NMHU-E

50(1-31/32)X(J-1)=K
B(Suspension bolt pitch)
50(1-31/32)X(G-1)=H

E
D

A
Air inlet Air outlet

50 (1-31/32)
50(1-31/32)

(1-31/32)
80 50
15(19/32)

(3-5/32)
F

10(13/32)
(2-25/32)

(1-5/8)
41
70

23(29/32)
((2-3/8)

((2-31/32)
60

75
340(13-13/32) 383(15-3/32) 250(9-27/32)

Suspension bolt hole 814(32-1/16)(Suspension bolt pitch) 60(2-3/8)


Model:P15~30 (Note3)
4-14X30(9/16X1-3/16) Slot 904(35-19/32)

900(35-7/16)
24(31/32) 847(33-3/8) 29(1-5/32)
10(13/32) 15(19/32)

Drain hole
Control box (option)

50 (1-31/32)
(3-1/16)

(1-31/32X4=7-7/8)
(1-31/32)X5=(9-27/32)

250(9-27/32)
328(12-15/16)
50X4=200
77
50(1-31/32)

380(14-31/32)
340(13-13/32)
50X5=250

(5-1/8)

25(1)
130
5/8)
41
(1-

Terminal bed
45(1-25/32)

163 (6-13/32)
17(11/16)

94(3-23/32)
30(1-3/16)

(Power source) (3-5/8)


92 200(7-7/8)
Terminal box 343(13-17/32)
Terminal bed 387(15-1/4)
Keep duct-work length 850mm(33-15/32 in.) or more. (Transmission)
Drain hole

m(in.)
Model A B C D E F G H J K L <Flare> <Flare>
PEFY-P15NMHU-E
800 754 6 80 600 550 50 11 500 10 450 780
PEFY-P18NMHU-E (31-1/2) (29-11/16) (26-25/32) (23-5/8) (21-21/32) (1-31/32) (19-11/16) (17-23/32) (30-23/32) Drain hose
32mm(1-1/4inch)
PEFY-P24NMHU-E <flexible joint>
PEFY-P27 ·30NMHU-E 1050 1004 930 850 800 25 17 800 15 700 1030 (accessory)
(41-11/32) (39-17/32) (36-5/8) (33-1/2) (31-1/2) (1) (31-1/2) (27-9/16) (40-9/16)
1250 1204 1130 1050 1000 25 21 1000 19 900 1230
PEFY-P36 ·48·54NMHU-E
(49-7/32) (47-13/32) (44-1/2) (41-11/32) (39-3/8) (1) (39-3/8) (35-7/16) (48-7/16)

Note 1.Use M10 screw for the suspension bolt (field supply). Required space for
2.Keep the service space for the maintenance from the bottom 300(11-13/16) or less service and 625
(24
-5
when the heat exchanger is cleaned. maintenance. 6) /8)
3.This chart indicates for PEFY-P36 ·48·54NMHU-E models, which have two fans. -9/1
(27 7/8)
PEFY-P15 ·18·24·27·30NMHU-E models have one fan. 700 9/32~7- ~200
(3-1 100 (5-2 150
4.Make sure to install the air filter(field supply) on the air intake side. 5/16 ~2
~7-7 00 2) L
�n case field supplied air filter is used, attach it where the filter /8) -31/3 Note 2
50(1
(17- 450
550(21-21/32) Max

service is easily done. 50


23/3 (1-
2) 450-23/32) 31/32)
5.On Model :18,36,48 and 54, use flare nut packed with the (17
Access door
i ndoor unit, when connecting the o utdoor unit for R22. 3

20(13/16) or more

When installing the drain water lifting-up mechanism (option)


20(13/16)

Access door Ceiling surface


or more

Carefully make the access door at the appointed position for service maintenance.

Mitsubishi Electric Air Conditioning & Refrigeration Systems Works acquired ISO
9001 certification under Series 9000 of the International Standard Organization (ISO)
based on a review of quality warranties for the production of refrigeration and air
conditioning equipment.

ISO Authorization System


The ISO 9000 series is a plant authorization system relating to quality warranties as
stipulated by the ISO. ISO 9001 certifies quality warranties based on the "design,
Certificate Number FM33568 development, production, installation and auxiliary services" for products built at
an authorized plant.

HVAC Advanced Products Division


Mitsubishi Electric Air Conditioning & Refrigeration Systems Works acquired environmental
management system standard ISO 14001 certification.
Mitsubishi Electric & Electronics USA, Inc.
The ISO 14000 series is a set of standards applying to environmental protection set by the
International Standard Organization (ISO). 3400 Lawrenceville Suwanee Rd.
Certificate Number EC97J1227 Suwanee, GA 30024
Tele: 678-376-2900 • Fax: 800-889-9904
C SD - PEFY-P48NMHU-E - 1 - 200607 © MITSUBISHI ELECTRIC / HVAC 2006 Toll Free: 800-433-4822 (#4)
www.mehvac.com
Model: PEFY-P54NMHU-E
Job Name:

Drawing Reference: Schedule No.

External Finish . . . . . . . . . . . . . . . . . Galvanized steel plate

Dimensions
Inches . . . . . . . . . . . . . . . 14-31/32 h x 47-1/4 w x 35-7/16 d
mm . . . . . . . . . . . . . . . . . . . . . . . . . 380 h x 1200 w x 900 d

Net Weight . . . . . . . . . . . . . . . . . . . . . . . . . . 155 lb / 70 kg

Coil Type . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Cross fin


(aluminum plate fin and copper tube)
GENERAL FEATURES Fan
• R410A or R22 refrigerant-compatible Type x Quantity . . . . . . . . . . . . . . . . . . . . . . Sirocco fan x 2
• Ducted fan coil supports multiple configurations for Airflow Rate . . . . . . . . . . . . . . . . . . . . . . . . 484 - 1412 CFM
flexible installation External Static Pressure
@ 208V . . . . . . . . . . . . . . . . 0.20 (default) - 0.64 in. WG
• High external static pressure capabilities
@ 230V . . . . . . . . . . . . 0.40-0.60 (default) - 0.80 in. WG
• Multiple sizes up to 96,000 Btu/h Motor
• Quiet operation: 25-54 dB(A) Type . . . . . . . . . . . . . . . . .Single phase induction motor
Output . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 0.400 kW
SPECIFICATIONS
Air Filter . . . . . . . . . . . . . . . Filter must be procured locally
Capacity*
Cooling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .54,000 Btu/h Refrigerant Pipe Dimensions
Heating . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .60,000 Btu/h R410A
Liquid. . . . . . . . . . . . . . . . . . . . . . . . 3/8" / 9.52 mm flare
Gas . . . . . . . . . . . . . . . . . . . . . . . . 5/8" / 15.88 mm flare
Power
Power Source . . . . . . . . . . . . . . . .208-230V, 1 phase, 60Hz
R22
Power Consumption
Liquid. . . . . . . . . . . . . . . . . . . . . . . . 3/8" / 9.52 mm flare
Cooling . . . . . . . . . . . . . . . . . . . . . . . . 0.645 / 0.767 kW
Gas . . . . . . . . . . . . . . . . . . . . . . . . 3/4" / 19.05 mm flare
Heating . . . . . . . . . . . . . . . . . . . . . . . . 0.645 / 0.767 kW
Current
Cooling . . . . . . . . . . . . . . . . . . . . . . . . . . . 3.43 / 3.78 A
Drainpipe Dimension . . . . . . . . . . . O.D.1-1/4" / 32 mm
Heating . . . . . . . . . . . . . . . . . . . . . . . . . . . 3.43 / 3.78 A
Minimum Circuit Ampacity (MCA) (208/230) . 4.24 / 4.73 A
Sound Level (Low - High)
@ 208V . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31-41 dB(A)
Maximum Overcurrent Protection (MOCP). . . . . . . . . . . 15A
@ 230V . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38-44 dB(A)

Options
❏ Drain pump kit. . . . . . . . . . . . . . . . . . . . . PAC-KE04DM-F
❏ Condensate pump . . . . . . . . . . . . . . . . . . . . .SI1730-230
❏ Long-life filter . . . . . . . . . . . . . . . . . . . . . . PAC-KE89LAF
❏ Filter box . . . . . . . . . . . . . . . . . . . . . . . . PAC-KE140TB-F
* Cooling / Heating capacity indicated the maximum value at operation under the
following conditions:
Cooling: Indoor 80°F (27°C) DB / 67°F (19°C) WB, Outdoor 95°F (35°C) DB
Heating: Indoor 70°F (21°C) DB, Outdoor 47°F (8°C) DB / 43°F (6°C) WB

** Ventilation air: providing sufficient ventilation air is an important part of every


building design. ASHRAE Standard 62 provides the minimum ventilation air
requirements. Also check local codes.

Notes:
Model: PEFY-P54NMHU-E

50(1-31/32)X(J-1)=K
B(Suspension bolt pitch)
50(1-31/32)X(G-1)=H

E
D

A
Air inlet Air outlet

50 (1-31/32)
50(1-31/32)

(1-31/32)
80 50
15(19/32)

(3-5/32)
F

10(13/32)
(2-25/32)

(1-5/8)
41
70

23(29/32)
((2-3/8)

((2-31/32)
60

75
340(13-13/32) 383(15-3/32) 250(9-27/32)

Suspension bolt hole 814(32-1/16)(Suspension bolt pitch) 60(2-3/8)


Model:P15~30 (Note3)
4-14X30(9/16X1-3/16) Slot 904(35-19/32)

900(35-7/16)
24(31/32) 847(33-3/8) 29(1-5/32)
10(13/32) 15(19/32)

Drain hole
Control box (option)

50 (1-31/32)
(3-1/16)

(1-31/32X4=7-7/8)
(1-31/32)X5=(9-27/32)

250(9-27/32)
328(12-15/16)
50X4=200
77
50(1-31/32)

380(14-31/32)
340(13-13/32)
50X5=250

(5-1/8)

25(1)
130
5/8)
41
(1-

Terminal bed
45(1-25/32)

163 (6-13/32)
17(11/16)

94(3-23/32)
30(1-3/16)

(Power source) (3-5/8)


92 200(7-7/8)
Terminal box 343(13-17/32)
Terminal bed 387(15-1/4)
Keep duct-work length 850mm(33-15/32 in.) or more. (Transmission)
Drain hole

m(in.)
Model A B C D E F G H J K L <Flare> <Flare>
PEFY-P15NMHU-E
800 754 6 80 600 550 50 11 500 10 450 780
PEFY-P18NMHU-E (31-1/2) (29-11/16) (26-25/32) (23-5/8) (21-21/32) (1-31/32) (19-11/16) (17-23/32) (30-23/32) Drain hose
32mm(1-1/4inch)
PEFY-P24NMHU-E <flexible joint>
PEFY-P27 ·30NMHU-E 1050 1004 930 850 800 25 17 800 15 700 1030 (accessory)
(41-11/32) (39-17/32) (36-5/8) (33-1/2) (31-1/2) (1) (31-1/2) (27-9/16) (40-9/16)
1250 1204 1130 1050 1000 25 21 1000 19 900 1230
PEFY-P36 ·48·54NMHU-E
(49-7/32) (47-13/32) (44-1/2) (41-11/32) (39-3/8) (1) (39-3/8) (35-7/16) (48-7/16)

Note 1.Use M10 screw for the suspension bolt (field supply). Required space for
2.Keep the service space for the maintenance from the bottom 300(11-13/16) or less service and 625
(24
-5
when the heat exchanger is cleaned. maintenance. 6) /8)
3.This chart indicates for PEFY-P36 ·48·54NMHU-E models, which have two fans. -9/1
(27 7/8)
PEFY-P15 ·18·24·27·30NMHU-E models have one fan. 700 9/32~7- ~200
(3-1 100 (5-2 150
4.Make sure to install the air filter(field supply) on the air intake side. 5/16 ~2
~7-7 00 2) L
�n case field supplied air filter is used, attach it where the filter /8) -31/3 Note 2
50(1
(17- 450
550(21-21/32) Max

service is easily done. 50


23/3 (1-
2) 450-23/32) 31/32)
5.On Model :18,36,48 and 54, use flare nut packed with the (17
Access door
i ndoor unit, when connecting the o utdoor unit for R22. 3

20(13/16) or more

When installing the drain water lifting-up mechanism (option)


20(13/16)

Access door Ceiling surface


or more

Carefully make the access door at the appointed position for service maintenance.

Mitsubishi Electric Air Conditioning & Refrigeration Systems Works acquired ISO
9001 certification under Series 9000 of the International Standard Organization (ISO)
based on a review of quality warranties for the production of refrigeration and air
conditioning equipment.

ISO Authorization System


The ISO 9000 series is a plant authorization system relating to quality warranties as
stipulated by the ISO. ISO 9001 certifies quality warranties based on the "design,
Certificate Number FM33568 development, production, installation and auxiliary services" for products built at
an authorized plant.

HVAC Advanced Products Division


Mitsubishi Electric Air Conditioning & Refrigeration Systems Works acquired environmental
management system standard ISO 14001 certification.
Mitsubishi Electric & Electronics USA, Inc.
The ISO 14000 series is a set of standards applying to environmental protection set by the
International Standard Organization (ISO). 3400 Lawrenceville Suwanee Rd.
Certificate Number EC97J1227 Suwanee, GA 30024
Tele: 678-376-2900 • Fax: 800-889-9904
C SD - PEFY-P54NMHU-E - 1 - 200607 © MITSUBISHI ELECTRIC / HVAC 2006 Toll Free: 800-433-4822 (#4)
www.mehvac.com
Model: PEFY-P72NMHU-E
Job Name:

Drawing Reference: Schedule No.

External Finish . . . . . . . . . . . . . . . . . Galvanized steel plate

Dimensions
Inches . . . . . . . . . . . . . . . 18-17/32 h x 49-7/32 w x 44-1/8 d
mm . . . . . . . . . . . . . . . . . . . . . . . . 470 h x 1250 w x 1120 d

Net Weight . . . . . . . . . . . . . . . . . . . . . . . . . 221 lb / 100 kg

Coil Type . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Cross fin


(aluminum plate fin and copper tube)
GENERAL FEATURES Fan
• R410A or R22 refrigerant-compatible Type x Quantity . . . . . . . . . . . . . . . . . . . . . . Sirocco fan x 2
• Ducted fan coil supports multiple configurations for Airflow Rate . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2048 CFM
flexible installation External Static Pressure
@ 208V . . . . . . . . . . . . . . . . 0.28 - 0.64 (default) in. WG
• High external static pressure capabilities
@ 230V . . . . . . . . . . . . . . . . 0.40 - 0.80 (default) in. WG
• Multiple sizes up to 96,000 Btu/h Motor
• Quiet operation: 25-54 dB(A) Type . . . . . . . . . . . . . . . . . Three phase induction motor
Output . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 0.650 kW
SPECIFICATIONS
Air Filter . . . . . . . . . . . . . . . Filter must be procured locally
Capacity*
Cooling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .72,000 Btu/h Refrigerant Pipe Dimensions
Heating . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .80,000 Btu/h R410A
Liquid. . . . . . . . . . . . . . . . . . . . . . 3/8" / 9.52 mm brazed
Gas . . . . . . . . . . . . . . . . . . . . . . 3/4" / 19.05 mm brazed
Power
Power Source . . . . . . . . . . . . . . . .208-230V, 3 phase, 60Hz
R22
Power Consumption
Liquid. . . . . . . . . . . . . . . . . . . . . . 1/2" / 12.7 mm brazed
Cooling . . . . . . . . . . . . . . . . . . . . . . . . 1.352 / 1.495 kW
Gas . . . . . . . . . . . . . . . . . . . . . . . . . 1" / 25.4 mm brazed
Heating . . . . . . . . . . . . . . . . . . . . . . . . 1.352 / 1.495 kW
Current
Cooling . . . . . . . . . . . . . . . . . . . . . . . . . . . 4.48 / 4.94 A
Drainpipe Dimension . . . . . . . . . . . O.D.1-1/4" / 32 mm
Heating . . . . . . . . . . . . . . . . . . . . . . . . . . . 4.48 / 4.94 A
Minimum Circuit Ampacity (MCA) (208/230) . . 5.60 /6.18 A
Sound Level
@ 208V . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45 dB(A)
Maximum Overcurrent Protection (MOCP). . . . . . . . . . . 15A
@ 230V . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47 dB(A)

Options
❏ Drain pump kit. . . . . . . . . . . . . . . . . . . . . PAC-KE04DM-F
❏ Condensate pump . . . . . . . . . . . . . . . . . . . . .SI1730-230
❏ Long-life filter . . . . . . . . . . . . . . . . . . . . . . PAC-KE85LAF
❏ Filter box . . . . . . . . . . . . . . . . . . . . . . . . PAC-KE250TB-F
* Cooling / Heating capacity indicated the maximum value at operation under the
following conditions:
Cooling: Indoor 80°F (27°C) DB / 67°F (19°C) WB, Outdoor 95°F (35°C) DB
Heating: Indoor 70°F (21°C) DB, Outdoor 47°F (8°C) DB / 43°F (6°C) WB

** Ventilation air: providing sufficient ventilation air is an important part of every


building design. ASHRAE Standard 62 provides the minimum ventilation air
requirements. Also check local codes.

Notes:
Model: PEFY-P72NMHU-E

50X21=1050(1-31/32X21=41-11/32)

50X20=1000(1-31/32X20=39-3/8)
1326(52-7/32)(Suspension bolt pitch)

1100(43-5/16)
110(43-5/16)

1250(49-7/32)

1372(54-1/32)
Air inlet Air outlet

50(1-31/32)
50(1-31/32)

(1-31/32)
100 50
(4-1/32) (1)
102 25

10 (13/32) 15(19/32)

(3-15/16)

23(29/32)
((3-3/32)
78
)
420(16-9/16) 340(13-13/32)
1034(40-23/32)(Suspension bolt pitch) 60(2-3/8)
Suspension bolt hole
4-14X30(9/16X3/16) Slot 1124(44-9/32)

1120(44-1/8)
24(31/32) 1067(42-1/32) 29(1-5/32)
10(13/32) 15(19/32)
Drain hole
(option)
Control box Note 1. Use M10 screw for the suspension bolt (field supply).
2. Keep the service space for the maintenance from the bottom
when the heat exchanger is cleaned.

20 (1-31/32X6=11-13/16)
3. Make sure to install the air filter (field supply)
on the air intake side.
(1-31/32X7=13-25/32)

340(13-13/32)
�n case field supplied air filter is used�attach it where

470(18-17/32)
50X6=300
(1-3/4)
420(16-9/16)

327(12-7/8)
the filter service is easily done.
50X7=350

44
4. �n this model�use pipe packed with the i ndoor unit�
50 (1-31/32)

when connecting the outdoor unit for R22.


(6-15/32)

(13/16)

(4-5/32)
164

105
35(1-13/32)

(1-3/16)

222(8-3/4)
20(13/16)

41(1-5/8)
30

Terminal bed (3-3/4)


95 249(9-13/16)
(Power source)
Terminal bed 422(16-5/8)
Drain hole 489(19-9/32)
Keep duct-work length 850mm(33-15/32 in.) or more.
(Transmission)
Required space for service
and maintenance. 730
(28
<Brazing> - 3/4
)
)
-1/2 )
mm(in.) (31 7/8
Model <Brazing> <Brazing> 800 29/32~7- ~200
(7-7 ( 5- 150
/8~1 200~ /32 )
PEFY-P72NMHU-E Drain hose 32mm 1-13 300 ( 53-5 Note2
/16) 2) 50
(1-1/4inch) (1 -31/3 13
<flexible joint > (17 450 50
-2 50
PEFY-P96NMHU-E (accessory) 3/3 (1
-31
2)
450-23/32) / 32)
(17
Access door
300(11-13/16) or less

20(13/16) or more
550(21-21/32) Max

When installing the drain water lifting-up mechanism (option).


3
20(13/16) or more

Access door Ceiling surface


Carefully make the access door at the appointed position for service maintenance.

Mitsubishi Electric Air Conditioning & Refrigeration Systems Works acquired ISO
9001 certification under Series 9000 of the International Standard Organization (ISO)
based on a review of quality warranties for the production of refrigeration and air
conditioning equipment.

ISO Authorization System


The ISO 9000 series is a plant authorization system relating to quality warranties as
stipulated by the ISO. ISO 9001 certifies quality warranties based on the "design,
Certificate Number FM33568 development, production, installation and auxiliary services" for products built at
an authorized plant.

HVAC Advanced Products Division


Mitsubishi Electric Air Conditioning & Refrigeration Systems Works acquired environmental
management system standard ISO 14001 certification.
Mitsubishi Electric & Electronics USA, Inc.
The ISO 14000 series is a set of standards applying to environmental protection set by the
International Standard Organization (ISO). 3400 Lawrenceville Suwanee Rd.
Certificate Number EC97J1227 Suwanee, GA 30024
Tele: 678-376-2900 • Fax: 800-889-9904
C SD - PEFY-P72NMHU-E - 1 - 200607 © MITSUBISHI ELECTRIC / HVAC 2006 Toll Free: 800-433-4822 (#4)
www.mehvac.com
Model: PEFY-P96NMHU-E
Job Name:

Drawing Reference: Schedule No.

External Finish . . . . . . . . . . . . . . . . . Galvanized steel plate

Dimensions
Inches . . . . . . . . . . . . . . . 18-17/32 h x 49-7/32 w x 44-1/8 d
mm . . . . . . . . . . . . . . . . . . . . . . . . 470 h x 1250 w x 1120 d

Net Weight . . . . . . . . . . . . . . . . . . . . . . . . . 221 lb / 100 kg


Coil Type . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Cross fin
(aluminum plate fin and copper tube)

GENERAL FEATURES Fan


Type x Quantity . . . . . . . . . . . . . . . . . . . . . . Sirocco fan x 2
• R410A or R22 refrigerant-compatible Airflow Rate . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2541 CFM
• Ducted fan coil supports multiple configurations for External Static Pressure
flexible installation @ 208V . . . . . . . . . . . . . . . . 0.28 - 0.64 (default) in. WG
• High external static pressure capabilities @ 230V . . . . . . . . . . . . . . . . 0.40 - 0.80 (default) in. WG
• Multiple sizes up to 96,000 Btu/h Motor
Type . . . . . . . . . . . . . . . . . Three phase induction motor
• Quiet operation: 25-54 dB(A)
Output . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 0.850 kW

SPECIFICATIONS Air Filter . . . . . . . . . . . . . . . Filter must be procured locally

Capacity* Refrigerant Pipe Dimensions


Cooling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .96,000 Btu/h R410A
Heating . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .108,000 Btu/h Liquid. . . . . . . . . . . . . . . . . . . . . . 3/8" / 9.52 mm brazed
Gas . . . . . . . . . . . . . . . . . . . . . . . 7/8" / 22.2 mm brazed
Power R22
Power Source . . . . . . . . . . . . . . . .208-230V, 3 phase, 60Hz Liquid. . . . . . . . . . . . . . . . . . . . . . 1/2" / 12.7 mm brazed
Power Consumption Gas . . . . . . . . . . . . . . . . . . . . .1-1/8" / 28.58 mm brazed
Cooling . . . . . . . . . . . . . . . . . . . . . . . . 1.690 / 1.870 kW
Heating . . . . . . . . . . . . . . . . . . . . . . . . 1.690 / 1.870 kW Drainpipe Dimension . . . . . . . . . . . O.D.1-1/4" / 32 mm
Current
Cooling . . . . . . . . . . . . . . . . . . . . . . . . . . . 5.69 / 6.28 A Sound Level
Heating . . . . . . . . . . . . . . . . . . . . . . . . . . . 5.69 / 6.28 A @ 208V . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52 dB(A)
Minimum Circuit Ampacity (MCA) (208/230) . 7.12 / 7.85 A @ 230V . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54 dB(A)
Maximum Overcurrent Protection (MOCP). . . . . . . . . . . 15A
Options
❏ Drain pump kit. . . . . . . . . . . . . . . . . . . . . PAC-KE04DM-F
❏ Condensate pump . . . . . . . . . . . . . . . . . . . . .SI1730-230
❏ Long-life filter . . . . . . . . . . . . . . . . . . . . . . PAC-KE85LAF
❏ Filter box . . . . . . . . . . . . . . . . . . . . . . . . PAC-KE250TB-F
* Cooling / Heating capacity indicated the maximum value at operation under the
following conditions:
Cooling: Indoor 80°F (27°C) DB / 67°F (19°C) WB, Outdoor 95°F (35°C) DB
Heating: Indoor 70°F (21°C) DB, Outdoor 47°F (8°C) DB / 43°F (6°C) WB

** Ventilation air: providing sufficient ventilation air is an important part of every


building design. ASHRAE Standard 62 provides the minimum ventilation air
requirements. Also check local codes.

Notes:
Model: PEFY-P96NMHU-E

50X21=1050(1-31/32X21=41-11/32)

50X20=1000(1-31/32X20=39-3/8)
1326(52-7/32)(Suspension bolt pitch)

1100(43-5/16)
110(43-5/16)

1250(49-7/32)

1372(54-1/32)
Air inlet Air outlet

50(1-31/32)
50(1-31/32)

(1-31/32)
100 50
(4-1/32) (1)
102 25

10 (13/32) 15(19/32)

(3-15/16)

23(29/32)
((3-3/32)
78
)
420(16-9/16) 340(13-13/32)
1034(40-23/32)(Suspension bolt pitch) 60(2-3/8)
Suspension bolt hole
4-14X30(9/16X3/16) Slot 1124(44-9/32)

1120(44-1/8)
24(31/32) 1067(42-1/32) 29(1-5/32)
10(13/32) 15(19/32)
Drain hole
(option)
Control box Note 1. Use M10 screw for the suspension bolt (field supply).
2. Keep the service space for the maintenance from the bottom
when the heat exchanger is cleaned.

20 (1-31/32X6=11-13/16)
3. Make sure to install the air filter (field supply)
on the air intake side.
(1-31/32X7=13-25/32)

340(13-13/32)
�n case field supplied air filter is used�attach it where

470(18-17/32)
50X6=300
(1-3/4)
420(16-9/16)

327(12-7/8)
the filter service is easily done.
50X7=350

44
4. �n this model�use pipe packed with the i ndoor unit�
50 (1-31/32)

when connecting the outdoor unit for R22.


(6-15/32)

(13/16)

(4-5/32)
164

105
35(1-13/32)

(1-3/16)

222(8-3/4)
20(13/16)

41(1-5/8)
30

Terminal bed (3-3/4)


95 249(9-13/16)
(Power source)
Terminal bed 422(16-5/8)
Drain hole 489(19-9/32)
Keep duct-work length 850mm(33-15/32 in.) or more.
(Transmission)
Required space for service
and maintenance. 730
(28
<Brazing> - 3/4
)
)
-1/2 )
mm(in.) (31 7/8
Model <Brazing> <Brazing> 800 29/32~7- ~200
(7-7 ( 5- 150
/8~1 200~ /32 )
PEFY-P72NMHU-E Drain hose 32mm 1-13 300 ( 53-5 Note2
/16) 2) 50
(1-1/4inch) (1 -31/3 13
<flexible joint > (17 450 50
-2 50
PEFY-P96NMHU-E (accessory) 3/3 (1
-31
2)
450-23/32) / 32)
(17
Access door
300(11-13/16) or less

20(13/16) or more
550(21-21/32) Max

When installing the drain water lifting-up mechanism (option).


3
20(13/16) or more

Access door Ceiling surface


Carefully make the access door at the appointed position for service maintenance.

Mitsubishi Electric Air Conditioning & Refrigeration Systems Works acquired ISO
9001 certification under Series 9000 of the International Standard Organization (ISO)
based on a review of quality warranties for the production of refrigeration and air
conditioning equipment.

ISO Authorization System


The ISO 9000 series is a plant authorization system relating to quality warranties as
stipulated by the ISO. ISO 9001 certifies quality warranties based on the "design,
Certificate Number FM33568 development, production, installation and auxiliary services" for products built at
an authorized plant.

HVAC Advanced Products Division


Mitsubishi Electric Air Conditioning & Refrigeration Systems Works acquired environmental
management system standard ISO 14001 certification.
Mitsubishi Electric & Electronics USA, Inc.
The ISO 14000 series is a set of standards applying to environmental protection set by the
International Standard Organization (ISO). 3400 Lawrenceville Suwanee Rd.
Certificate Number EC97J1227 Suwanee, GA 30024
Tele: 678-376-2900 • Fax: 800-889-9904
C SD - PEFY-P96NMHU-E - 1 - 200607 © MITSUBISHI ELECTRIC / HVAC 2006 Toll Free: 800-433-4822 (#4)
www.mehvac.com