Documente Academic
Documente Profesional
Documente Cultură
For continual product development, LG Electronics U.S.A., Inc., reserves the right to change specifications
without notice.
For additional technical materials including submittals, engineering data books, and catalogs visit www.lg-vrf.com.
Table of Contents
Purpose .............................................................................................................................................4
Heat Recovery ...................................................................................................................................5
Why LG VRF? .....................................................................................................................................7
Installation .................................................................................................................................................... 7
LG VRF Benefits ............................................................................................................................................ 7
Efficient Design ............................................................................................................................................. 7
Zoned Comfort Control & Dehumidification ............................................................................................... 8
Sustainability ................................................................................................................................................ 8
Quiet Operation ........................................................................................................................................... 8
Controls ........................................................................................................................................... 10
Why Is VRF a good application for a K-12 School? ............................................................................. 12
Is VRF too complicated? ................................................................................................................... 14
Is a VRF system more expensive than other conventional systems? ................................................... 14
What about Outside Air?.................................................................................................................. 16
What about the Gym HVAC? ............................................................................................................ 17
What about ASHRAE Standards 15, 34, 55, 62.1 and VRF? ................................................................. 20
How does VRF compare to Water Source Heat Pump (WSHP) Systems for K-12?................................ 24
VRF vs. WSHP Systems: .................................................................................................................... 28
What about using Ground Source Heat Pump (GHP) Systems for K-12 Schools? ................................. 30
Beware of Marketed EER .................................................................................................................. 37
VRF vs. GHP Systems: ....................................................................................................................... 39
Use LG Multi V Water IV Instead of WSHP/GHP ................................................................................ 41
LG Hydro Kit..................................................................................................................................... 49
What about the use of Air Cooled Chilled Water Systems for K-12 Schools? ....................................... 52
Operating Cost Examples: ................................................................................................................ 54
Purpose
The purpose of this document is to provide engineers, designers and decision makers with information
on how to apply LG Variable Refrigerant Flow (VRF) systems in their designs for the HVAC systems in
kindergarten through 12th grade (K-12) schools, the benefits of VRF that make it well suited for K-12
school HVAC designs and how VRF stacks up against other conventional school HVAC systems such as
Water Source Heat Pumps (WSHPs), Ground Heat Pump (GHP) Systems, and Air Cooled Chilled Water
Systems (CHW).
As shown below, R410A refrigerant, the heat transfer medium used in LG VRF systems, can contain the
greatest energy per pound compared to air and water, which is the transfer medium for conventional
HVAC systems. Also, when comparing molecular characteristics, one molecule of R410A refrigerant is
smaller than air and water. This capacity to transfer more energy at a smaller size is the reason LG VRF
systems are so energy efficient while using limited physical space and thereby have the lowest life cycle
cost compared to other HVAC systems. This makes VRF a good choice for schools construction where a
district has limited funds and requires zoned control.
Also, what makes an advantage of LG VRF systems for use in K-12 schools is the heat recovery option.
Heat recovery uses rejected heat from class rooms in cooling mode to heat classrooms that need
heating. This makes for an efficient application. Water Source Heat Pump Systems (WSHP) do this as
well, but they require the routing of bigger water pipes throughout the school and WSHP systems
require pumps to circulate the water. VRF systems do not require additional pumps to circulate the
refrigerant.
The LG Multi V IV system combines the best features of heat recovery VRF systems. Condensate drains
are not required for Multi V Heat Recovery units. Heat recovery units that can serve 2, 3, or 4 zones are
strategically placed in series or in parallel to maximize piping reach while minimizing material and labor
costs. Piping, fittings, branches, headers, hangers, insulation, joints, nitrogen, and labor hours can be
greatly reduced resulting in significantly lower installed costs.
Heat Recovery
It can be seen that the LG heat recovery layout offers many advantages over other manufactures due to
the following highlights noted below:
Why LG VRF?
The benefits are numerous: modern style,
mirror units for interior designers, less
piping for installers and energy efficiency
for owners. LG is among the industry
leaders in low sound levels, so units are
quiet and can be installed where sound is
an issue. LG manufactured inverter scroll
compressors optimize system energy
efficiency and are certified using AHRI
Standard 1230. Other benefits include the
following:
Installation
LG VRF system components are modular, small and lightweight compared to conventional HVAC
system components. They are typically installed without the use of a crane, saving substantially on
installation cost. The unit modularity supports building a system over time to serve floors as a building
is occupied. The low weight can reduce the need for structural reinforcement to support more massive
equipment. The compressor units are typically installed outdoors and do not need a machine room or
mechanical penthouse reducing noise within the occupied space.
LG VRF Benefits
Your project can realize significant benefits by using LG's VRF Technology. Efficiency and modern
modular design are just the beginning. The modular design of VRF results in superior energy savings
giving occupants the choice to air condition or heat only the zones in use. A VRF system provides
exceptional dehumidification and temperature control by rapidly adapting to changing loads as seen in
a school environment.
Efficient Design
Without using large distribution ducts, the LG Multi V system removes losses that are unavoidable in
other systems. In addition, the use of optimized scroll or rotary compressors, specially designed heat
exchangers, and inverter technology, the Multi V system minimizes energy consumption to levels
previously unattainable by non-VRF systems. The modular design offers comfort on demand allowing
the choice to use the system only in the zones where it is needed further promoting reduced energy
consumption.
Sustainability
The architectural and engineering community is adopting a balanced design approach that considers
energy and water consumption, repetitive maintenance costs, the impact of development on the
environment, and the building’s initial cost as equally important factors in developing high
performance, sustainable buildings that will increase building value. LG’s Multi V VRF systems help
achieves points for sustainability programs.
The USGBC has developed holistic design standards for constructing new and retrofitting existing
buildings known as LEED® - Leadership in Energy and Environmental Design. The Multi V variable
refrigerant flow air conditioning systems are engineered for sustainable green buildings and provide
opportunities for designers to claim numerous LEED® prerequisites and points.
Quiet Operation
With LG VRF, Students can work
without distraction. With indoor
units that can operate at sound
levels as low as 23dB (A) and
outdoor units that operate as
low as 50dB (A) and lower with
night quiet operation, LG Multi V
creates a comfortable
environment so quiet it’s almost
undetectable. For additional
sound level control, a night quiet
mode can be set to limit fan speed during off peak hours.
“The importance of quality room acoustics in schools has been recognized by Educators and School
Architects as evidenced by the new standard, ANSI S12.60, "Standard for Classroom Acoustics." This
standard was recently created to provide acoustical criteria for those involved in school building
design.”
“Designing to reduce noise generated by the HVAC system is also critical for creating a quiet space.
The more quiet the space, the better the students hear and understand.”
http://www.kineticsnoise.com/schools/index.html
Controls
Controls are an integral part of LG VRF systems. LG VRF systems incorporate sophisticated controls and
automation; control of the complex refrigerant system requires this. The many control points of the
refrigerant system are monitored resulting in easy trouble-shooting, and automatic diagnostics of the
refrigerant system. Control of the internal refrigerant management has been optimized for the
system’s overall efficiency, longevity, and comfort to the space. Detailed system diagnostics of
internal refrigerant management can be viewed through LG’s Mobile LGMV software.
LG’s controls allow users to control and monitor the system for individual zone comfort. Utilizing LG’s
individual zone remote controllers, occupants can control their individual zone, central controllers
allow building managers to control the entire VRF system, and BACnetTM and LonWorksTM gateways
allow the Energy Management System to integrate the VRF system with other systems within the
building.
Comfort
LG indoor units can be sized to serve small spaces with independent temperature control, such as
individual private offices or classrooms. With capability to provide heating or cooling and modulation
of the compressor, a narrow temperature range can be maintained. Anecdotal information, and results
of one informal field study, indicates that attention needs to be paid to ensure that controls are
working to maintain stable temperature control without alternating heating and cooling.
Commissioning of zone temperature control is recommended.
LG Air Conditioning Systems Page 10
© LG Electronics U.S.A., Inc. 2016
VRF and K-12 Schools
Space Requirements
Transferring heat through refrigerant piping requires a lot less space than ductwork. This makes LG
VRF systems well suited to retrofits, particularly historic buildings that may not have any ductwork or
cooling. However, if outside air requirements are not met by natural ventilation already, then
ductwork of sufficient size to provide code-required ventilation will need to be added. In new buildings,
the low space requirement can result in reduced floor-to-floor height, providing initial cost savings.
Maintenance
Regular maintenance of LG VRF systems consists of changing filters and cleaning coils for the fan coil
units. This level of maintenance is not substantially different than for other zonal systems, such as
conventional water-source fan coils and split systems. Maintenance of the compressor unit is minimal,
and there will be significant maintenance savings for this part of the system compared to chilled water
and hot water plant equipment.
LG Inverter Scroll
There are several ways to modulate the cooling capacity in compressor air conditioning and heating
systems. The most common in air conditioning are the following: on-off cycling, hot gas bypass, use or
not of liquid injection, manifold configurations of multiple compressors, mechanical modulation (also
called digital) and inverter technology.
• On-off cycling: results in switching off the fixed-speed compressor under light load conditions
and could lead to short cycling and the reduction in compressor lifetime. Efficiency of the unit is
reduced by pressure cycling and transient losses. The turndown capacity is 100% or 0%.
• Hot gas pass: involves injecting a quantity of gas from discharge to the suction side. The
compressor will keep operating at the same speed but thanks to the bypass, the refrigerant
mass flow circulating with the system is reduced and thus the cooling capacity. This naturally
causes the compressor to run uselessly during the periods where the bypass is operating. The
turndown capacity varies between 0 and 100%.[1]
• Manifold configurations: several compressors can be installed in the system to provide the peak
cooling capacity. Each compressor can run or not in order to stage the cooling capacity of the
unit. The turndown capacity is either 0/33/66 or 100% for a trio configuration and either 0/50 or
100% for a tandem.[2]
• Mechanically modulated compressor: this internal mechanical capacity modulation is based on
periodic compression process with a control valve, the 2 scroll set move apart stopping the
compression for a given time period. This method varies refrigerant flow by changing the
average time of compression, but not the actual speed of the motor. Despite an excellent
turndown ratio – from 10 to 100% of the cooling capacity, mechanically modulated scrolls have
high energy consumption as the motor continuously runs.
• Inverter compressor: uses an external variable frequency drive - to control the speed of the
compressor. The refrigerant flow rate is changed by the change in the speed of compressor. The
LG Air Conditioning Systems Page 11
© LG Electronics U.S.A., Inc. 2016
VRF and K-12 Schools
turndown ratio depends on the system configuration and manufacturer. It modulates from 15 or
25% up to 100% at full capacity with a single inverter from 12 to 100% with a hybrid tandem.
A new high side shell innovation offers a more compact size for the same capacity output with greater
reliability in cold climates. Multi V IV is AHRI 1230 Certification performance certified. This ensures that
you are getting verified ratings.
1. http://www.pipelineandgasjournal.com/bypass-method-recip-compressor-capacity-control
http://www.ishrae.in/journals/2000apr/article02.html
2. http://info.aia.org/aiarchitect/thisweek09/0410/0410p_vrf.cfm
Compact Design
VRF offers more indoor zones, less outdoor space. When space or
access is at a premium, this equates to significant cost advantages
for the owner on large projects.
Owners can reach extra zones further off the same VRF units. This
eliminates the need to invest in extra systems and saves on installation.
Energy Modeling
LG has provided and updated library curves, modeling guides, white papers, and sample files for
customers who use building energy simulation programs such as: eQUEST®, Energy Pro, Trane Trace™
700, EnergyPlus, Carrier Hourly Analysis Program (HAP), and others.
The layout of a school breaks down the building’s total capacity into zones or classrooms typically
between 1-1/2 to 3 tons (excluding OA), which is just the right capacity for a VRF system. Each of these
classrooms or zones must be able to operate with a widely varying load (as people come and go) and
even as an individual zone when the full building may not be occupied.
That’s not possible with a traditional air cooled chiller system because the central plant has to turn on
the chiller or boiler, and pumps to turn the air conditioning or heating on. With a water cooled chiller, a
cooling tower and associated pumps must also be energized. With a WSHP system, pumps and a cooling
tower or boiler must be energized to provide air conditioning or heating. So with a conventional air and
water cooled chiller and WSHP system, the central plant must run when cooling or heating is needed in
any portion of the building. If only one person is working after hours, the central plant for the whole
school must run to provide cooling or heating.
The second major driving force is energy and water consumption. While air cooled chillers and electric
heating systems are reasonably first-cost effective, they are not energy friendly. In the last five years as
LEED and other “green” building programs have become the norm, we have seen many school districts
change their design strategy to reach higher efficiency goals. A VRF system provides an avenue for
school districts to improve energy efficiency without driving construction costs higher and without a
substantial water consumption increase.
The “sophistication” of any HVAC system is in the controls system. This is nothing new for K-12
operations people, who already work with third-party building automation system (BAS) controls
providers to program and manage controls for other ‘conventional” systems. The primary difference
between a third-party controls system and an LG VRF system is the controls are an integral part of the
VRF system. The internal refrigerant management has been optimized for the system’s overall efficiency,
longevity, and comfort to the space. The individual zone remote controllers, central controllers, and
gateways all communicate across the VRF system requiring minimum setup or configuration.
The installation cost of VRF is actually less than chilled water and WSHP systems when used in the
correct application. Because of the high number of separate classrooms or zones, K-12 schools offer an
excellent opportunity for VRF applications. In a K-12 school application, each classroom would have one
or more separate indoor VRF units providing heating and cooling for the classroom. This allows
individual classroom HVAC control. Heat Recovery VRF is also recommended to allow simultaneous
operation of heating and cooling. Simultaneous heating and cooling means that the HVAC system in one
classroom may provide cooling, while another classroom may be in the heating mode. The heat rejected
from the classroom in cooling mode is used to heat the classroom in heating mode. This makes for a
very efficient HVAC system.
This mode of operation where each classroom has a fan coil unit can also be found on chilled water
systems. The difference between VRF and Fan Coil Chilled Water (FCCW) systems is that chilled water
systems do not have the ability to do simultaneous heating and cooling unless they have a 4 pipe
arrangement where there is a cooling supply and return pipe and a heating supply and return pipe. Also
FCCW systems do not use rejected heat from one zone to heat another zone, and thus are not as energy
efficient as VRF systems when simultaneously heating and cooling and may not comply with state and
local energy codes.
WSHP systems can provide simultaneous heating and cooling, but instead of refrigerant, they use water
as the medium to transfer the energy. A pound of R410a refrigerant in liquid phase can hold more
energy than a pound of water
LG Air Conditioning Systems Page 14
© LG Electronics U.S.A., Inc. 2016
VRF and K-12 Schools
Also FCCW systems require the installation of either an air or water cooled chiller, a cooling tower if the
chiller is water cooled, chilled water pumps, cooling tower pumps if water cooled chiller, boilers and
boiler pumps, all associated balancing and gate valves, pressure and temperature valves, strainers, flow
switches, and service ports, and fan coils for each classroom and all the associated control valves,
pressure/temperature ports, ball valves, Y strainer and air vents for the fan coils.
The above is an example of how the installation of a VRF system compares in cost to similar size
Geo Thermal Heat Pump (GHP) system. It can be seen that the VRF system is 38% less than a
comparable GHP system.
The best system for this strategy is a DOAS that provides a neutral temperature supply air at 72-75
degrees F, at a humidity ratio of between 40-45 grains of moisture/lb. of dry air. At this low humidity
ratio, the ventilation air being delivered to a classroom will dehumidify the ventilation air load and can
provide additional drying effect to the humidity sources already in the classroom such as the students
and teachers and any other source of moisture. This strategy reduces the condensate in the VRF indoor
units and greatly reduces long-term maintenance required for the condensate piping because most of
the latent load is taken care of by the DOAS unit. This also increases the efficiency of the VRF system
because the remaining cooing load is almost all sensible where the VRF system is most efficient in
removing.
The below Decoupled Dedicated Outdoor Air System is the preferred way of introducing ventilation air
into the school class rooms. The outside ventilation air is introduced into the class rooms separately
from the main heating and cooling system. This method prevents problems associated with trying to mix
outside air with return air directly at the heating and cooling unit serving the class room. (Typically
associated with VAV (variable air volume) systems)
DOAS
In a K-12 school, the Dedicated Outdoor Air System (DOAS) optimizes energy savings and performance.
The DOAS provides numerous benefits including:
• Airflow rate variable from 400 to 2000 CFM
• Air handler controller senses high outdoor air humidity and provides dehumidification mode
• Reheat coil allows heating of dehumidified air to room neutral temperatures
• Flexible design allows matching of outdoor unit to meet local outdoor air design conditions
• Web access to air handler controller
• Air handler controller connects to laptop computer without special software
• Varying outdoor air temperatures can be conditioned using energy efficient LG VRF technology
• Available in two models - with electric preheat coil or without electric preheat coil
The unit is provided with an integrated microprocessor-based controller. Remote duct discharge air
temperature sensor, outdoor air temperature sensor, and outdoor air humidity sensor for field
mounting in the ductwork are shipped loose inside the control cabinet. The field supplied
communication cable between the air handler and outdoor units is to be a minimum of 18 AWG, 4-
conductor, stranded, and shielded cable (RS-485), terminated via screw terminal on the control boards.
The microprocessor control will operate the air handler using one of the five operating modes:
• Cooling
• Heating
• Dehumidification
• Ventilation
• Defrost
Cooling mode is activated when the outdoor air temperature sensor detects temperature increase
above the outside air cooling enable set-point. Outdoor unit compressors modulate to meet the cooling
demand by the main coil and maintain discharge air temperature set point. Heating mode is activated
when the outdoor air temperature sensor detects temperature decrease below the outside air heating.
Another option available to HVAC engineers/designers is the option of using LG’s AHU kit to interface
with another manufacturer’s AHU that may be used for the Gym. The benefit of using The LG AHU kit is
the use of LG’s VRF condensing unit.
The LG AHU kit can be configured for return air or supply air temperature control. Some of the criteria
for using the AHU kit include the following:
For Gymnasium
For Gymnasium
ASHRAE 15-2013 and ASHRAE 34-2013: Designing for Refrigerant Safety with Multi V
The Standards address the safety and classification of the refrigerant chemical. All LG Multi V systems
use R-410A refrigerant. ASHRAE Standard 34-2007 classifies this refrigerant in Safety Group “A1” and a
rated as “neither” in the toxicity category titled “highly toxic or toxic under code classification.1” These
are the safest ratings given in the Standard to any refrigerant and are the same ratings are given to
refrigerants R-22, R-134A, and R-407C.
Of primary concern is the displacement of all oxygen in a room that could lead to occupant asphyxiation
in the event of a catastrophic release of the entire system refrigerant charge. The Standard states R-
410A has a Refrigerant Concentration Limit (RCL) of 0.026 lbs./ft3. The RCL indicates the allowable
volume (by weight) of refrigerant per cubic foot of room volume to avoid escape-impairing effects such
as oxygen deprivation, flammability, and cardiac sensitization among others.
The Standard is written to cover a worst case scenario and assumes the complete system charge is
dumped into a confined space over a short period of time. If a refrigerant leak occurs, the actual
concentration level in the confined space is dependent upon the quantity of refrigerant in the
equipment and the volume of air available for dispersion and dilution. The calculated concentration
level in each room cannot exceed the RCL (or 50% of the RCL for institutional buildings such as asylums,
nursing homes, hospitals and spaces containing locked cells.)
Note 1: This designation does not indicate that R-410A is non-toxic, with high enough concentrations all
refrigerants can be hazardous.
ASHRAE 15-2013 and ASHRAE 34-2013 Designing for Refrigerant Safety with LG Multi V (continued)
The total estimated charge of the refrigeration system is calculated using LG’s LATS refrigerant piping
design software. Secondly, the designer must determine which zone or room has the smallest cubic
volume served by the system. Calculate the volume of air in each area or room using the following
guidelines to determine the dimensions of each zone or room.
Non-connecting Spaces: Defined as “where a refrigerating system or a part thereof is located in one or
more enclosed occupied spaces that do not connect through permanent openings or HVAC ducts.
Where different stories and floor levels connect through an open atrium or mezzanine arrangement, the
volume to be used in calculating the refrigerant quantity limit shall be determined by multiplying the
floor area of the lowest space by 8.2 ft.”
Ventilated Spaces: Defined as “where a refrigerating system or a part thereof is located within an air
handler, an air distribution duct system, or an occupied space served by a mechanical ventilation system,
the entire air distribution system shall be analyzed to determine the smallest volume area.”
Closures: “Closures in the air distribution system shall be considered. If one or more spaces of several
arranged in parallel can be closed off from the source of the refrigerant leak, the volume(s) shall not be
used in the calculation.”
Closure exceptions include smoke and fire dampers or combinations thereof that close only in an
emergency not associated with a refrigerant leak and dampers where airflow is never reduced below 10%
of its maximum with the fan running.
Plenums: “The space above a suspended ceiling shall not be included in calculating the refrigerant
quantity limit in the system unless such space is part of the air supply or return system.”
Supply and Return Ducts: “The volume of the supply and return ducts and plenums shall be included
when calculating the refrigerant quantity limit in the system.”
Concentration Calculations
The Standard calculates the concentration as follows: After the zone dimensions are known, calculate
the volume of air in the smallest zone and divide by 1000 (Eq 1.) Finally, divide the refrigerant charge in
lbs. by the resultant of Eq 1. If the resultant is higher than the allowed RCL as documented in Standard
15-2013, increase the cubic volume of the smallest zone or modify the piping system design.
The resultant must be less than 0.026 lbs./ft3. When applying any standard or regulation in practice, the
designer must use some engineering judgment in determining which rooms or areas are connected,
non-connected, or ventilated. Use of transfer ducts between rooms, undercut doors, ventilation grilles
in doors, using the area above the ceiling as part of the return or supply air path are all methods that
can be used to increase the dilution volume of the smallest areas of the building.
The environmental factors addressed are temperature, thermal radiation, humidity and air speed; the
personal factors are those of activity and clothing.”
In the past emphasis was put on building structures airtight with little or no control provided to the
occupants. Since the green building movement began and the LEED building rating system gained
momentum, individual adjustment of comfort parameters such as thermostats and air flow are being
considered upfront as part of the overall mechanical system design. To satisfy the minimum
requirement for a LEED point credit for thermal comfort, 50% of the occupants must be provided
individual control of selected comfort parameters. Another LEED point is available for Thermal Comfort-
Design (IEQ credit 7.1) if the HVAC system design complies with Section 6.1.1 of Standard 55-2004.
A water source heat pump system operates much like a traditional air source heat pump system except
that it extracts and dissipates heat by way of water instead of air.
Traditional air source heat pumps get their heat from the air outside, as even relatively cold air actually
contains a substantial amount of heat.
Water source heat pumps work on basically the same principle as air source heat pumps, but they
extract heat from a body of water rather than the air. A boiler is used to add heat to the water loop to
make the water source heat pumps more effective and efficient because in heating mode as the water
loop temperature decreases so does the water source unit’s efficiency.
In the summer, water source heat pumps dissipate heat to water. They do this by cycling water through
a system of pipes that are routed through a cooling tower. A cooling tower extracts waste heat to the
atmosphere though the cooling of a water stream to a lower temperature. The type of heat rejection in
a cooling tower is termed "evaporative" in that it allows a small portion of the water being cooled to
evaporate into a moving air stream to provide significant cooling to the rest of that water stream. The
heat from the water stream transferred to the air stream raises the air's temperature and its relative
humidity to 100%, and this air is discharged to the atmosphere.
In an open circuit cooling tower the water to be cooled is distributed over a fill pack whilst air is blown
or drawn through the packing. A small quantity of the water evaporates and this causes the remainder
of the water to be cooled. The cooled water falls into the sump of the tower and the heat extracted
from the water is carried out in the leaving air stream.
Evaporative condensers or closed circuit evaporative cooling towers have a heat exchanger or coil within
the tower instead of a fill pack. Water is distributed over the heat exchange coil and heat is extracted
from the refrigerant or primary fluid circulating through the coil by the same evaporative process.The
above WSHP system uses a closed circuit cooling tower.
Closed circuit cooling towers are preferred for WSHP systems because they completely isolate process
cooling fluid from the atmosphere. A closed loop system protects the quality of the process fluid,
reduces system maintenance, and provides operational flexibility at a slightly higher initial cost.
Of course, you do also need to have access to an appropriate body of water to have a water source heat
pump system installed. The impact of water usage is something that should be understood as per the
below:
“It is important to note that the volume of ground water in storage is decreasing in many areas of the
United States in response to withdrawals. If these water-level declines are sustained over time, the
effect is often described as ground-water depletion. Among the consequences of ground-water-level
declines are increased pumping costs, deterioration of water quality, reduction of water in streams
and lakes, and land subsidence. Such negative effects, while variable, happen to some degree with
any ground-water use.” http://water.usgs.gov/watercensus/AdHocComm/Background/Ground-
WaterAvailabilityintheUnitedStates.pdf
With the decline of ground water storage volume, the cost of water will continue to rise. When
evaluating any water use HVAC system, this rise in cost should be taken in account.
Cooling Tower
Boiler
Outside
Ventilation
Air Fire Dampers
Return Typical
Typical
Supply Duct
Typical
Water Piping
Typical
Outside
Ventilation
Return Duct Air
Typical Supply
Typical
Vertical WSHP
Typical
Mechanical
Room
Typical
To DOAS To DOAS
Unit Water Piping Unit
to other
Wings
Fire Seal
Typical
HRUs and
Class Room Class Room
Refrigerant
Piping Located
above Egress
Fire Damper
Typical
Refrigerant
Piping
Typical
To DOAS To DOAS
Unit Unit
The above piping diagram is a Ground Source Heat Pump (GHP) System in the cooling and heating mode. Ground source
heat pumps work on basically the same principle as water source heat pumps, but in cooling mode, they reject heat to
the ground through water circulating in pipes inserted into the ground rather than from water to the ambient air.
In heating mode, heat is removed from the ground through the same piping used for cooling. A boiler may be used to
add heat to the water loop to make the water source heat pumps more effective and efficient because in heating mode
as the water loop temperature decreases so does the water source unit’s efficiency.
This method of heat rejection is more efficient than a water source heat pump system using a cooling tower because the
ground has more constant temperatures. With GHP systems though, there are many other obstacles to consider as
noted below:
Ground
Temperatures
are Before
Adding Load
(Btu/hr)
11/26/2014 http://www.builditsolar.com/Projects/Cooling/EarthTemperatures.htm
The above map shows how the ground temperatures varying from one area to others. It is
interesting to note that the temperatures are not constant but rather are averages. Comfort
heating and cooling is not determined using average temperatures but worst case. So care
should be exercised when using the map to determine the ground temperatures that can be used
to calculate the heating and cooling load.
04/30/2015 http://igs.indiana.edu/Geothermal/HeatPumps.cfm
The above graph shows how the ground temperatures varying in depth. The most constant temperatures
are those that have the greatest depth in the ground. For this reason, deep boreholes are the
recommended method of ground heat pump loop construction. Deep boreholes have to be drilled into the
ground and because of that they are also the most expensive.
Thermal Conductivity (K) of the ground used to determine the number of wells:
• Thermal Conductivity(K)
• Btu/hr = K (Area) Temp Difference / Thickness
• Different Soil types at different depths
There are different soil types at different levels in the ground and each different soil type has different
Thermal Conductivity (K) values. The K value determines how many wells are needed to reject and absorb
heat for a given load.
HDPE
Topsoil
Pipe
Static Water Level
Upper Confining Trench
Bed
Borehole Wall
Un-grouted
Borehole
Confined Aquifer
Local Governments are restricting use
of open wells because of potential to
contaminate ground water
HDPE
Pipe
HDPE U Bend
The above is an example of a closed loop grout sealed well. A well of 200 – 800’ deep is drilled and HDPE pipe
is routed down into the well. The HDPE piping is connected to other wells to make network of wells that are
used to reject and absorb heat for a GHP system.
The above is a diagram of how the ground K value is determined. A known amount of water at a known
temperature is pumped down through the pipe in the well and the returning water temperature is used to
determine the K value.
http://www.ahrinet.org/App_Content/ahri/files/standards%20pdfs/AHRI%20standards%20pdfs/AHRI%20Sta
ndard%20330-1998.pdf
Multi V Water IV, a Variable Refrigerant Flow (VRF) system, is among the industry’s best air-conditioning
units with great advantage on vertical rise and piping lengths. Choosing an LG Multi V Water IV VRF
system provides the system designer an edge to engineer a system with individual control and design
flexibility with advanced controls. Multi V Water IV is available in two configurations, heat pump and
heat recovery.
Multi V Water IV heat pumps are two-pipe systems available in nominal capacities of 6.0 to 48.0 tons.
These are best suited for applications with zones that require heating or cooling, such as residential and
small office buildings.
Multi V Water IV heat recovery is a three pipe system that provides simultaneous heating and cooling
operation from the same water source unit. Both Multi V Water IV heat pump and heat recovery
systems allow the designer to accommodate up to 64 thermal zones, each controlled from a separate
controller.
Multi V Water IV water source units are available in 208–230 Volt, 60 Hz, 3 Phase and 460 Volt, 60 Hz, 3
Phase.
Refrigerant Pipe
Refrigerant Pipe
Water Pipe
Classrooms
Boiler
Refrigerant Pipe
Water Pipe
Closed Circuit
Cooling Tower
Refrigerant Pipe
Refrigerant Pipe
Server Room
Water Pipe
Boiler
Boiler
Service Valve
Service Valve
Modulating Control Valve Power (24V)
Valve and Control
50 Mesh Flow
Strainer Switch PWFCKN000
Shutoff
Valve Flex
Connector
Control Wiring
99°F
Refrigerant Pipe
Control
Room 1 Room 2 Room 3 Wiring
Pumping Operation
Signal
Mechanical Room
68°F Bypass
59°F Valve
Temperature
Sensor
Strainer
(50
Mesh)
LG Hydro Kit
The LG Hydro Kit is an efficient way to recover waste heat from VRF air conditioning systems. The Hydro
Kit receives heat from the Multi V VRF systems’ waste heat to provide hot water for use where it is
needed in areas such as kitchens, bathrooms, radiators, and floor heating.
The LG Hydro kit provides hot water with less energy consumption than a boiler. Gas Boiler systems
require exhaust to the outside. No exhaust or exhaust piping is required with the Hydro Kit. The LG
Hydro Kit is compact and easy to install, and can connect to multiple heat pumps in a system for
additional savings.
The Hydro Kit may be used in conjunction with 3-phase Multi V Heat Pump and Heat Recovery outdoor
and water source units. The Hydro Kit system uses a refrigerant to water heat exchanger to produce
chilled or heated water. Hydro Kit can be used to preheat domestic water stored in an indirect storage
tank, snow melt, in-floor or other radiant heating systems. Alternately, the K2
Hydro kit can supply chilled or heated water for use with 2-pipe fan coils and the K3 Hydro kit can
produce hot water up to 176°F.
K3
K2
ARNH963K2A2 ARNH763K3B2
Refrigerant
cooling/heating
Hot-water tank Indoor unit
Water
cooling/heating
R
HR Unit
Multi V High Temp.
Heat Recovery Hydro kit
Medium Temp.
Water
Hydro kit
cooling/heating Heating
Rejected heat
from IDU
Indoor unit
HR Unit
Rejected heat
from IDU
Multi V WATER
Medium temp Hydro Kit
Heat exchanger
LG VRF offers the benefit of lower first cost and maintenance, and high efficiency as compared to air and
water cooled chillers. With LG VRF, operation is very simple, as simple as operating a split air
conditioning system and hence no separate manpower is required for operating the system.
LG VRF is a better option for providing air conditioning to K-12 schools where the complexity of the
system can be kept to a minimum and energy efficiency is maximized.
The energy efficiency of air-cooled chillers is rated in terms of Energy Efficiency Ratio (EER). EER is a
dimensional measure of efficiency. It is the ratio of the rate of cooling to electrical power consumption
by the evaporator and the condenser fans.
EER (Btu/Wh) = Qevap (Btu/hr.) / (Wcomp + W condfans) (W) @ ARI Std 590-92 conditions
The performance of a typical air cooled chiller is shown below. As predicted by a Carnot analysis,
efficiency improves when the temperature of air entering the condenser declines or the leaving water
temperature increases.
Using the data in the preceding table, the following relation gives chiller EER as a function of leaving
water temperature of 45 °F and when the condenser air temperature is 95 F. The resultant EER is 9.7.
This EER value does not include pump losses. The additional pump losses are calculated as below using
TACO pump Selection Software:
LG Air Conditioning Systems Page 53
© LG Electronics U.S.A., Inc. 2016
VRF and K-12 Schools
• 1,500 VRF Cooling Run Hours per year (Reduced Cooling Run Hours due to VRF compressor)
• VRF Outdoor Unit Power Input KW from LG Performance Data for Multi V IV @ 75 db/63 wb Indoor
Temperature, 95 db Outdoor Temperature (4 x 22 Ton @ 100% Combination Ratio) = (4 X 14.3) =
57.16 KW for Outdoor Unit
• VRF Indoor Unit Power Input KW from LG Performance Data for (Total 54) – (2 per 27 classrooms)
ARNU183TQC2 Ceiling Cassette @ 80 db/67 wb Indoor Temperature, 95 db Outdoor Temperature (54
x 30 watts) = 1.62KW for Total Indoor Units
Solution:
• Total Power Input (Watts) for VRF = (57,160 Outdoor Unit + 1,620 Indoor Unit) = 58,780 Total Watts
• Annual Energy Cost (Cooling) = 1,500 X 58.8 X 0.10 = $ 8,820 Annual Cost of Cooling (VRF)
• 4 X (ARUB264 – 22 Ton Outdoor Unit) = 4 X (275.9 Mbh Heating) = 1,103.6 Mbh Heating
• 600 VRF Heating Run Hours per year (Reduced Heating Run Hours due to VRF compressor)
• VRF Outdoor Unit Power Input KW from LG Performance Data for Multi V IV @ 70:F db Indoor
Temperature, 10:F db Outdoor Temperature (4 x 22 Ton @ 100% Combination Ratio) = (4 X 26.94) =
107.8 KW for Outdoor Unit (Heating)
• VRF Indoor Unit Power Input KW from LG Performance Data for (Total 54) – (2 per 27 classrooms)
ARNU183TQC2 Ceiling Cassette @ 70:F db Indoor Temperature, 10:F db Outdoor Temperature (54 x
30 watts) = 1.62KW for Total Indoor Units
Solution:
• Total Power Input (Watts) for VRF = (107,760 + 1,620) = 109,380 Total Watts
• Annual Energy Cost (Heating)= 600 X 109.4 X $ 0.10 = $ 6,564 Annual Cost of Heating (VRF)
Solution:
• Annual Energy Cost (Cooling)= Annual Run Hours X KW X $/KWh
• (27) Roof Top Units (RTU) – One per each classroom, (27) X 1.2 Therms = 32.4 Therms
Solution:
• Annual Energy Cost (Electric)= Run Hours X kW X $/kWh = 600 X (25.3) X $0.10 = $1,518
• Annual Energy Cost (Natural Gas) = 600 Hours X 32.4 Therms X 0.55= $10,692
• (27) Fan Coil Units (FCU) – One per each classroom, ½ H.P. Per each from performance data
Solution:
• Total Power Input (Watts) for Chiller/FCUs = (82,300 + 5,086 + 20,732) = 108,118 Watts = 108.1 KW
• (27) Fan Coil Units (FCU) – One per each classroom, ½ H.P. Fan Per each from performance data
• Pump(Boiler) Power(Watts) = (Volts X Amperage X √3) X 0.84 = (460 X 1.4 X √3) X 0.84 = 937 Watts
• Total Power input (Watts) = (20,732 + 2,276 + 937) = 23,945 Watts = 23.9 KW
Solution:
• Annual Energy Cost (Electric)= Run Hours X KW X $/KWh = 800 X (23.9) X $0.10 = $1,912
• Annual Energy Cost (Natural Gas) = 800 Hours X 13.88 Therms X 0.55= $6,107
• (27) WSHPs @ 1.899 KW/Each (from performance data), Total 51.3 (Kilowatts) WSHPs
• Cooling Tower has (1) 10 HP Fan Motor and (1) 2 HP Pump Motor
• System Total (Watts) (WSHPs + Pump(System) + Cooling Tower) = (51,300 + 5,086 + 11,645) = 68,031
Watts
Solution:
• System EER = Btu/hr./Watts (WSHPs + Pump(System) + Cooling Tower)
• 68 KW X 2000 run hours = 136,000 KWh x $ 0.10 = $ 13,600 (Annual Cooling cost with WSHP)
• Total Mbh Boiler Load = 70% of (27 X 41Mbh) = 775 Mbh Total Boiler Load
• High Efficiency Natural Gas Boiler used for heating loop water = 89% Efficient
• Use 1000 MBH Boiler with Net Capacity = 1,000 MBH X .89 = 890 MBH
• 800 WSHP Unit Annual Heating Full Load Run Hours/400 Run Hours for the Boiler
• Pump(Boiler) Power(Watts) = (Volts X Amperage X √3) X 0.84 = (460 X 1.4 X √3) X 0.84 = 937 Watts
• Total (Watts) (WSHPs + Pump(System) + Pump(Boiler)) = (64,260 + 7,362 + 937) = 72,559 Watts
Solution:
• Annual Energy Cost (Electric)= Run Hours X KW X $/KWh = 800 X (72.6) X $0.10 = $5,808
• Annual Energy Cost (Natural Gas) = 400 Hours X 10.0 Therms X 0.55= $2,200
Solution:
• System EER = Btu/hr./Watts (GHPs + Pump)
• 60.19 KW X 2000 run hours = 120,380 KWh x $ 0.10 = $ 12,038 (Annual Cooling cost with GHP)
• (29) GHPs @ 38.2 Mbh/Each, 1,103.6 Mbh Total, 8.4 GPM/Each, 260.4 GPM Total @ 100’ Head
Pressure, 30% Glycol Fluid, Performance based on 50:F Entering Water Temperature EWT
• Power Out GHPs (kW) = P(BTU/hr) / 3,412 = 1,103,600 Btu/hr. / 3,412 = 299 kW
Solution:
• System COP = Watts (Output)/Watts (WSHPs + Pump)
• 78.0 KW X 800 run hours = 62,400 KWh x $ 0.10 = $ 6,616 (Annual Heating cost with GHP)
$Cooling $Heating
VRF $8,820 $6,564