Sunteți pe pagina 1din 9

This article has been accepted for publication in a future issue of this journal, but has not been

fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TIA.2018.2864106, IEEE
Transactions on Industry Applications
1

Grounding the AC Microgrid


J. Mohammadi, Student Member, IEEE, F. Badrkhani Ajaei, Member, IEEE, and G. Stevens

The grounding strategies of AC microgrids and those of the


Abstract— Grounding strategy of an AC microgrid affects its traditional AC distribution systems are affected by similar
line-to-ground fault response, personnel/equipment safety, service constraints and concerns, and thus have significant
continuity, insulation requirements, and protection criteria. commonalities. However, there are differences due to the
Therefore, a comprehensive knowledge of the available grounding
strategies and their effects is essential for design and operation of
unique characteristics of the microgrid, such as the possibility
the microgrid components and especially its protection. In this of islanded operation and the higher reliability expectations.
paper, characteristics of different AC distribution system The existing literature does not provide a comprehensive
grounding devices and grounding configurations are investigated. comparison between different AC microgrid grounding
Subsequently, AC microgrid grounding requirements and issues strategies, i.e., grounding configurations and grounding
are identified based on the unique characteristics and constraints devices. There are a few useful references in this area, each
of microgrids. The results of the aforementioned investigations are
used to identify the best grounding strategies, i.e., grounding
focusing on a specific aspect of grounding strategies while
configurations, transformer connection types, and grounding ignoring other relevant technical and non-technical concerns.
devices, for the AC microgrid. The study results indicate that the Advantages and disadvantages of multi-grounded microgrid
four-wire multi-grounded configuration is the most suitable choice configuration are briefly mentioned in [7] where the rest of
for the majority of microgrids, especially in North America. The possible grounding configurations are not discussed. Transient
Yg/Δ and Yg/Yg transformers are identified as the most response of a uni-grounded Low-Voltage (LV) AC microgrid
appropriate choices for DER interface to the four-wire multi-
grounded microgrid. Besides, low-reactance and low-resistance
using different grounding impedances is studied in [8], [9]. In
grounding devices are recommended for the DER interface [10], [11], transient response of the ungrounded microgrid
transformers. configuration under Line-to-Ground (LG) fault is investigated.
The studies reported in [12], [13] highlight the effects of AC
microgrid grounding strategies only on fault current magnitude
Index Terms— AC Microgrid, grounding strategies, ground and touch potential. The impacts of different AC microgrid
faults, AC system protection, overvoltages. grounding strategies on stray currents and personnel/equipment
safety are investigated in [14]. None of these studies provides
comprehensive information to enable appropriate grounding
I. INTRODUCTION system design for the AC microgrid. Considering the

A LTERNATING Current (AC) microgrids offer significant


advantages such as improving power quality, reliability,
and efficiency, while facilitating grid integration of Distributed
shortcomings of the existing literature, this paper:
● introduces different AC distribution system grounding
strategies, i.e., grounding configurations and grounding
Energy Resources (DER) including Distributed Generation devices, that can be utilized in AC microgrids;
(DG) units and Energy Storage Systems (ESS) [1], [2]. Similar ● investigates and reports technical characteristics and effects
to the traditional AC distribution systems, the grounding of each grounding strategy, including their impacts on LG
strategy of an AC microgrid drastically affects (i) its fault- fault current magnitude, transient over-voltages, required
induced overcurrent and overvoltage stress and thereby its surge arrester type, maintenance cost, possibility of
protection system design and coordination, (ii) safety of continuous operation under LG faults, personnel safety, and
personnel and equipment, (iii) reliability of energy supply, (iv) required protective relay types;
harmonics, and (v) maintenance costs [3]-[6]. In this context, ● discusses the grounding issues and requirements of the AC
the term grounding strategy refers to the choice of system microgrid, which affect the choice of the appropriate
configuration and the grounding devices. The former grounding strategies;
determines whether the system has multi-grounded, uni- ● investigates the impacts of different DER transformer
grounded, or ungrounded configuration. The latter determines connection types, grounding configurations, and grounding
the type of the grounding device impedance that leads to an impedances in the AC microgrid;
ungrounded, resonant grounded, resistive grounded, reactance ● provides a comprehensive review of the advantages and
grounded, or solidly grounded system [3]-[6]. disadvantages of the aforementioned grounding strategies,
and makes application recommendations.

This work was supported in part by Mitacs Inc. and the Green Municipal (e-mail: jmohamm7@uwo.ca; fajaei@uwo.ca), and G. Stevens is with S2E
Fund granted to S2e Technologies Inc. and London Hydro partnership. Technologies Inc., St. Jacobs, Ontario, Canada, N0B 2N0 (e-mail:
J. Mohammadi and F. Badrkhani Ajaei are with the Department of Electrical gstevens@s2etech.com).
and Computer Engineering, Western University, London, Canada, N6A 3K7

0093-9994 (c) 2018 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TIA.2018.2864106, IEEE
Transactions on Industry Applications
2

II. GROUNDING AC DISTRIBUTION SYSTEMS


In this section, different grounding devices and grounding
configurations used in AC distribution systems are introduced
and compared with each other. The information provided in this
section constitute the base for AC microgrid grounding
recommendations made in Section III. Fig. 1. Grounding devices used in (a) ungrounded, (b) solidly grounded, (c)
resistance grounded, (d) reactance grounded, and (e) resonant grounded, and (f)
A. Grounding Devices zigzag transformer-grounded systems.
Grounded AC distribution systems generally involves
connecting the neutral to the ground through a grounding 2) Solidly grounded system
device. Source transformers and generators with Y-connected In a solidly grounded system, the neutral is grounded without
windings provide a readily available neutral connection in an intentionally inserted impedance [3]-[6], [16]-[18], [28].
three-phase AC systems. In absence of Y-connected windings, Therefore, the ILG/I3ϕ ratio is at least 60 percent, and the
a neutral point can be obtained using a grounding transformer, transient overvoltage caused by LG faults is less than 1.5 p.u.
e.g., zigzag and Y-Δ type transformers [3]-[6]. [3], [4]. In this system, the neutrals of surge arresters are
Different types of impedances can be used as the grounding grounded [3], [19], [20]. Instantaneous or time-delay ground
device that connects the system neutral to the ground. The overcurrent (OC) relays are used to quickly detect LG faults [3],
choice of the grounding device, Figs. 1(a)-(e) [3]-[6], results in [6], [16].
the five main categories of ungrounded (infinite impedance), The applications of the solidly grounded system are as
solidly grounded (zero impedance), resistance grounded, follows [3], [6], [17], [18], [23], [29]:
reactance grounded, and resonant grounded systems. For all of ● LV distribution systems (600 V and below) where single-
these cases, the effectiveness of grounding is determined by the phase loads must be supplied, outages due to LG faults are
LG fault current ratio, that is, the ratio of the LG fault current acceptable, or solid grounding is needed to detect LG faults.
magnitude to the three-phase fault current magnitude ILG/I3ϕ. A
● Medium-Voltage (MV) or High-Voltage (HV) systems with
larger ratio indicates a more effective grounding [3], [4].
Basic Insulation Level (BIL) below LL voltage level.
Different AC system grounding devices are introduced in this
part and their advantages, disadvantages, system impacts, and ● MV or HV applications where the need for selective LG
applications are briefly described and compared with each fault detection justifies increased risk of arc flash.
other. A more detailed treatment of this subject including a ● Utility systems supplying service to commercial and
comprehensive review of the advantages and disadvantages of industrial customers.
each grounding device is provided in [15].
3) Resistance grounded system
1) Ungrounded system The neutral of a resistance grounded system is grounded by
Conductors of an ungrounded system are not intentionally
a resistor. This system can be high- or low-resistance grounded,
connected to the ground. However, any ungrounded system is
which are distinguished by the LG fault current ratio [3]-[6],
in fact capacitance grounded due to the presence of stray
[16]-[18], [30]-[35]. The large neutral resistor used in a high-
capacitances. LG fault current magnitude in such a system is
resistance grounded system is selected to achieve a LG fault
equal to the total stray capacitance charging current [3]-[6],
current ratio below one percent, typically 10 A [3], [4], [16]-
[16]-[18]. Hence, the LG fault current ratio is usually below one
[18], [31]-[35]. In this system, the un-faulted phase voltages can
percent.
reach the LL voltage level and the transient LG overvoltage
LG faults in ungrounded systems cause overvoltages on the
magnitude can reach 2.73 p.u. [3], [4], [16]-[18], [31]-[35].
un-faulted phases, which can reach the Line-to-Line (LL)
Ungrounded neutral type surge arresters are used in the high-
voltage level. Under transient conditions, the overvoltages can
resistance grounded system [3], [19], [20]. Due to the limited
exceed 3 p.u. [3], [4]. Ungrounded neutral type surge arresters
fault current levels in high-resistance grounded systems, where
are used in ungrounded systems to limit the overvoltages [3],
service continuity is a priority, LG fault protection usually
[19], [20]. The National Electrical Code (NEC) [21] and the
initiates an alarm instead of immediately tripping circuit
Canadian Electrical Code (CEC) [22] require the LG faults in
breakers [3], [23], [31]-[35]. The alarm can be initiated by a
ungrounded systems to be detected by a neutral overvoltage
neutral overvoltage relay (59N) [3], [16], [31]-[35]. The
relay (59N) or LG detection lights connected to a broken ΔY
applications of high-resistance grounding are as follows [3],
voltage transformer [16].
[31]-[35]:
Ungrounded systems provide the possibility of operation
under LG faults without need for immediate service ● LV systems without single phase loads.
interruption for fault clearance [23]. Ungrounded systems also ● Systems below 600 V where service continuity is a priority.
result in the least investment in absence of single-phase loads
● MV systems up to 5 kV where service continuity is a priority
[5], [6], [24]-[27]. However, application of ungrounded systems
and capacitive charging current is less than 5.5A.
is not recommended due to the excessive transient overvoltages
[3], [17], [18]. ● Retrofits of ungrounded systems in order to reduce transient
LG overvoltages.

0093-9994 (c) 2018 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TIA.2018.2864106, IEEE
Transactions on Industry Applications
3

A low-resistance grounded system limits the LG fault current


ratio to less than 25 percent, typically with a magnitude in the
range of 100 A to 1000 A [3], [4], [17], [18]. Transient LG
overvoltage in a low-resistance grounded system is below 2.5
p.u. [4], and ungrounded neutral type surge arresters are used to
limit overvoltages [3], [19], [20]. A time-delay ground OC relay
is used to promptly detect and clear LG faults [3], [6], [16]. The
applications of low-resistance grounding are [3], [17], [18]:
● 2.4 kV to 15 kV MV systems feeding only three-wire loads,
where occasional outages due to LG faults are acceptable,
and the grounding resistor prevents equipment damage by
limiting LG fault current. Fig. 2. Grounding configurations in AC distribution systems: (a) four-wire
● Providing sufficient fault current to enable selective multi grounded, (b) four-wire uni-grounded, (c) three-wire uni-grounded, (d)
three-wire ungrounded (served from a Y transformer), (e) three-wire
protection in industrial distribution systems above 5kV. ungrounded (served from a Δ transformer).
● Mining systems supplying portable equipment.
4) Reactance grounded system The characteristics, protection schemes, and applications of
In a reactance grounded system, a reactor is used as the different grounding strategies are summarized and compared in
grounding device to limit the LG fault current magnitude. This Table I, [3]-[6], [16]-[37], where R and X are the system
system can be high- or low-reactance grounded [3]-[6], [16]- resistance and reactance, respectively, and subscripts 0 and 1
[18], [30]. In the low-reactance grounded system, the LG fault represent zero and positive sequence parameters, respectively.
current ratio is between 25 percent and 100 percent, to prevent A comprehensive description of the information provided in
excessive transient overvoltages [3], [4], [17], [18]. Hence, the Table I can be found in [15].
transient overvoltage under LG faults is below 2.3 p.u. [3], [4].
Application of low-reactance grounding results in lower cost B. Grounding Configurations
and power loss as compared to low-resistance grounding, if the Another aspect of the grounding strategy is choosing the
desired fault current level is in the range of thousand amperes appropriate locations and numbers of grounding devices, which
[3]. However, due to the large LG fault current, a low-reactance hereafter will be referred to as the grounding system
grounded system requires fast fault clearing using instantaneous configuration. The distribution system can be four-wire multi-
or time-delay ground OC relays [3], [16]. Grounded neutral grounded, four-wire uni-grounded, three-wire uni-grounded, or
type surge arresters are used in this system if the LG fault three-wire ungrounded, as shown in Fig. 2 [5], [6], [10], [24].
current ratio is 60% or larger [3], [19], [20]. The applications of This part introduces and compares these configurations.
low-reactance grounding are as follows [3], [6], [30], [36]: 1) Four-wire multi-grounded configuration
● Systems below 600V or above 15 kV. In a four-wire multi-grounded system, the neutral conductor
of the primary feeder is grounded at multiple locations [5], [6],
● Generator grounding in industrial and commercial systems.
[24]-[27], [30] and often interconnected with the neutral
● North American utilities. conductor of the secondary distribution system [25], [27]. This
In high-reactance grounded systems, the LG fault current grounding configuration is commonly used in the MV
ratio is between 5 percent and 25 percent [3], [4]. Ungrounded distribution systems of North America [6], [11], [24]-[26], [30],
neutral surge arresters are used in these systems [3]. High- [38] due to its safety and economic advantages. Multi-grounded
reactance grounded systems are not popular due to excessive systems must be used at voltages above 600V and not be used
transient LG overvoltages (2.73 p.u.) [3], [4]. in commercial or industrial facilities, to prevent circulating
5) Resonant grounded system ground currents [6], [21].
In a resonant grounded system, the grounding device, i.e., This configuration has lower cost when the loads are mostly
reactor, is specially designed to resonate with the system stray single phase [6], [24], [27] and requires lower arrester ratings
capacitance so that the LG fault current is small and in-phase and BIL [27]. Under a single LG fault, this grounding
with the LG voltage [3], [4], [18], [37]. The transient LG configuration limits the voltage rise on un-faulted phases to
overvoltage magnitude can reach 2.73 p.u. [3], [4]. Ungrounded about 1.25 p.u. to 1.35 p.u. [24] and provides sufficiently large
neutral type surge arresters are used in such systems [3], [19], current for fault detection and location [27]. However,
[20]. The applications of resonant grounding are [3], [4], [18]: protection against high-impedance LG faults in four-wire multi-
● MV industrial and commercial systems that are isolated grounded systems is difficult. Residual ground OC relays are
from the utility system by transformers and do not involve not sufficiently sensitive to detect high-impedance LG fault
frequent circuit reconfiguration, e.g., MV generators. currents, because their pickup current settings must be above
● Relatively common in European distribution systems. the maximum expected load imbalances [5].
● Not popular in North America. Applied in a few instances
for generator grounding in New England.

0093-9994 (c) 2018 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TIA.2018.2864106, IEEE
Transactions on Industry Applications
4

TABLE I
COMPARISON OF DIFFERENT GROUNDING DEVICES
Neutral High-
Resonant High-Reactance Low-Resistance Low-Reactance Solidly
Grounding Ungrounded Resistance
Grounded Grounded Grounded Grounded Grounded
Device Grounded
R0 X0 X0 X0 X0
Ratio of > 100 > 10 0< < 10 3≤ ≤ 10 0≤ ≤1
Symmetrical X1 X1 X1 X1 X1
N/A N/A
component R0 R0 R0 R0 R0
parameters ≤1 <2 ≥2 0≤ ≤1 0≤ ≤ 0.1
X0 X0 X0 X1 X1

LG fault current I LG I LG I LG I LG I LG I LG I LG
< 1% < 1% < 1% 5% ≤ ≤ 25% ≤ 25% 25% ≤ ≤ 100% > 95%
ratio I 3φ I 3φ I 3φ I3φ I 3φ I 3φ I 3φ

Magnitude of
expected third Negligible,
None Negligible Appreciable Appreciable Appreciable Appreciable
harmonics Small
current

Required BIL VLL VLL VLL VLL VLN VLN VLN


Transient LG
VLG > 3 VLG ≤ 2.73 VLG ≤ 2.73 VLG ≤ 2.73 VLG ≤ 2.5 VLG ≤ 2.3 VLG ≤ 1.5
voltage
Grounded neutral type
Ungrounded Ungrounded Ungrounded Ungrounded Ungrounded Grounded
Surge Arresters if LG fault current is
neutral type neutral type neutral type neutral type neutral type neutral type
60% or greater
Maintenance
High Low Low Reasonable Reasonable Reasonable Reasonable
Costs
Service
Possible, not
Continuity under Ideal Ideal Not Possible Not Possible Not Possible Not Possible
recommended
LG Fault
Personnel Safety Poor Excellent Excellent Reasonable Reasonable Reasonable Poor
Equipment
Low Low Low Low High High High
Thermal Stress
Interference with
Communication Average Low Low Low High High High
Lines
Instantaneous
Time-delay
LG Fault Overvoltage Overvoltage Instantaneous or time- or time-delay
N/A N/A ground OC relay
Protection relay (59N). relay (59N). delay ground OC relay. ground OC
(51G).
relay.
Relay
Difficult Excellent Excellent Good Good Good Good
Coordination
Protection
Average Average Average Good Good Good Good
Sensitivity
Systems below
600V and
Not MV systems of Systems below 600V 600V or over
MV generators. below, where Not used due to
recommended 2.4kV to 15kV, or over 15kV. 15kV.
Applications Rarely used in service excessive
due to transient with only Commonly used in Commonly
North America. continuity is a overvoltages.
overvoltages. three-wire loads. North America. used in North
priority.
America.

2) Four-wire uni-grounded configuration America, four-wired uni-grounded systems are used sparingly
In a four-wire uni-grounded distribution system, the primary [27]. Uni-grounded systems have been recommended to be used
neutral conductor is connected to the neutral point of the source at low voltages, 600V and below [6], [21].
transformer and to ground, only in one location [5], [6], [24]- This configuration enables application of sensitive ground
[27]. In this configuration, single-phase distribution fault protection which is not adversely affected by unbalanced
transformers are usually connected between phase and neutral loads [5], [6], [27]. However, the four-wire uni-grounded
conductors and surge arrester are connected between phase and configuration causes higher voltage swells [27] and higher LG
ground. An arrester or a spark gap may also be connected fault-induced overvoltages as compared with the multi-
between the neutral conductor and ground [5]. In North grounded system [24].

0093-9994 (c) 2018 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TIA.2018.2864106, IEEE
Transactions on Industry Applications
5

3) Three-wire uni-grounded configuration


There is no neutral conductor in a three-wire uni-grounded
system, but the system is grounded through a substation
transformer neutral [5], [6], [24]-[27]. Single-phase distribution
transformers are connected between phases. Surge arresters are
generally connected phase to ground, and the surge-arrester
Fig. 3. Microgrid overvoltage due to back-feed under a LG fault.
rating is higher than that of the multi-grounded configuration
since the overvoltages under LG faults are higher [5], [6], [24].
This configuration is usually used in the industrial power
systems that mainly consist of three-phase motors rather than
loads connected to neutral [6], [29]. Three-wire uni-grounded
MV distribution systems are popular in Europe [26], [27]. Uni-
grounded systems have been recommended to be used at low
voltages, 600V and below [6], [21]. Three-wire uni-grounded
systems can use more sensitive ground relay settings since load Fig. 4. Utility grid contribution to the LV-side LG fault current.
imbalances do not cause residual current [5], [6], [24].
4) Three-wire ungrounded configuration
Three-wire ungrounded systems have no intentional
grounding to earth. However, as explained in Section II-A, stray
capacitances provide a path for small currents flowing between
the phase conductors and ground [24]. Three-wire ungrounded
systems are seldom used in North American distribution Fig. 5. DER contribution to the MV-side LG fault current.
systems [24]. For personnel and equipment safety, this
configuration is currently not recommended for modern
distribution systems [6]. A single LG fault does not result in 2) Utility grid contribution to LV-side LG fault current
When a LG fault occurs at the LV-side of a DER interface
disruptive fault currents in this configuration. However, LG
transformer, the fault current magnitude depends on the
faults are difficult if not impossible to locate, due to the small
interface transformer connection type. If the transformer allows
fault current [27].
flow of zero-sequence current from the MV-side to the LV-side,
Fig. 4, the LG fault current magnitude can be as high as 15 to
III. AC MICROGRID GROUNDING
25 times the transformer rated current until the microgrid
The grounding strategies described in Section II are becomes islanded. Otherwise, this value is considerably lower
essentially applicable to AC microgrids as well. However, the and mainly depends on the grounding of the DERs [39].
unique characteristics of AC microgrids lead to additional Therefore, the DER transformer grounding impedance should
criteria that affect the choice of applicable grounding strategies. be carefully selected to prevent possible damage to the DER
In this section, AC microgrid grounding issues and transformers.
requirements are discussed, impacts of different DER 3) DER contribution to the MV-side LG fault current
transformer connection types, grounding configurations, and The large fault current magnitude under three-phase, LL and
grounding impedances are investigated, and the most solid LG faults in the grid-connected microgrid enables
appropriate AC microgrid grounding strategies are selective operation of properly coordinated OC protective
recommended. devices [40]. However, this does not apply to high-impedance
A. AC Microgrid Grounding Issues and Requirements LG faults. Utility grid protective relays may become
desensitized to high-impedance LG faults, due to fault current
This part highlights specific phenomena that require special
contributions of DER interface transformers, as shown in Fig. 5
attention due to their impacts on grounding requirements of the
[11], [24], [40]. Using large impedances to ground interface
AC microgrid.
transformers usually reduces this adverse effect, but leads to
1) Back-feed
When a microgrid is islanded due to an internal LG fault, the higher overvoltages under back-feed conditions. Therefore, in
faulted portion of the microgrid remains energized by the DERs choosing the grounding impedance, a tradeoff exists between
while losing the grounding support from the utility grid, as limiting LG fault-induced overvoltages and maintaining
shown in Fig. 3. Under the aforementioned scenario, which is protection sensitivities of utility grid relays [11], [40].
referred to as back-feed, the system would be mainly grounded Another issue associated with LG fault current contribution
by the DERs and their transformers. As a result, the fault of DERs is sympathetic tripping of feeder protective relays.
response of the system under back-feed conditions highly Breakers of un-faulted feeders may unnecessarily trip under LG
depends on the microgrid grounding strategy [24], [39]. If the faults on parallel feeders served from the same substation bus.
DERs and the associated transformers do not effectively ground In order to prevent sympathetic tripping, directional overcurrent
the MV-side, LG fault-induced overvoltages on the un-faulted relays can be used [11], [26].
phases can reach the LL voltage level [11], [40].

0093-9994 (c) 2018 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TIA.2018.2864106, IEEE
Transactions on Industry Applications
6

B. DER Transformer Connection Types TABLE II


ZERO-SEQUENCE EQUIVALENT CIRCUITS OF DIFFERENT TRANSFORMER
The interface transformer connection type determines how WINDING CONNECTION TYPES.
each DER interacts with the MV-side of the microgrid and the Transformer winding connection type Zero-sequence equivalent circuit
utility grid, especially under LG faults [40]. As emphasized in
the previous part, this interaction impacts protection of the
microgrid as well as the overvoltage and overcurrent stresses
caused by internal LG faults. Hence, AC microgrid grounding
systems should be designed based on the winding connection
types of the utilized DER interface transformers [39]. There is
no connection type that is optimal for all systems [11], [40].
Therefore, the commonly used DER transformer connection
types [24] are compared here in terms of their impacts on the
AC microgrid grounding system.
A Yg/Yg (MV/LV) interface transformer is not a ground
current source by itself. The MV-side grounding in the islanded
mode would depend on the grounding of the source behind the
transformer [24], [39]. This can be explained by the zero-
sequence equivalent circuit shown in Table II [41]. If all sources
behind the Yg/Yg interface transformers are ungrounded or A disadvantage of the Yg/Δ transformer is zero-sequence
high-impedance grounded, LG fault-induced overvoltages at current circulation in the Δ-connected windings under LG faults
the MV-side of the microgrid may approach the LL voltage or unbalanced loads, which may cause transformer heating [3],
level [11], [39]. Solid grounding of the sources would increase [11], [40]. This problem can be resolved using a grounding
the current contributions of the DERs to the LG faults in the impedance at the MV-side neutral connection, to limit the zero-
utility grid, which would affect coordination of the utility grid sequence current. The ground impedance should be sufficiently
ground fault protection systems [11], [39], [40]. Solidly large to limit the Δ-side circulating current and sufficiently low
grounded Yg/Yg interface transformers also necessitate to provide effective grounding to the MV-side [11], [40]
coordination of MV-side ground OC relays with LV-side relays particularly under islanded operation mode of the microgrid.
[11]. A compromise between the aforementioned overvoltage The Yg/Δ transformer also contributes to LG fault current in the
and overcurrent issues can be made by using appropriate neutral utility grid, and thus may adversely affect coordination of the
grounding impedance. This type of transformer is mainly used utility LG fault protection systems [11], [26], [40].
as distribution transformer in solidly grounded utility The most common connection types of DER interface
distribution systems [3]. transformers in multi-grounded and uni-grounded microgrids
Δ/Δ, Y/Δ, and Δ/Yg (MV/LV) interface transformers neither are Yg/Δ and Yg/Yg [7]-[9]. The reason is that, with
are ground current sources at the MV-side nor provide a path appropriate grounding impedances, these transformers enable
for the zero-sequence current contribution by DERs [39], [40], ground OC protection of the islanded microgrid and prevent LG
as shown in Table II. DERs interfaced to the microgrid by these fault-induced overvoltages under back-feed conditions.
types of transformers do not contribute to the fault current under
C. Microgrid Grounding Configurations
LG faults in the utility grid, and thus do not adversely affect
coordination of the utility ground fault protection systems. This part investigates applicability of different grounding
However, the major concern is the LG fault-induced configurations to microgrids, considering the information
overvoltages under back-feed conditions, as explained in part provided in Section II.
III-A [11], [40]. Grounding transformer(s) may be needed at the 1) Three-wire ungrounded microgrid
MV-side to provide an effective ground current source and limit Three-wire ungrounded systems do not suffer from
overvoltages [39]. Some utilities prefer blocking LG fault disruptive LG fault currents and are designed to tolerate LG
current contribution from large DERs at the cost of having to fault-induced overvoltages [24]. Therefore, these systems may
tolerate larger temporary overvoltages [40]. cause less frequent service interruption due to faults. In other
A Yg/Δ interface transformer is a ground current source at words, removing the LG fault may be postponed until the next
the Y-side and enables effective grounding of the MV system scheduled maintenance. This may seem to be a significant
even in the islanded mode [39]. It blocks the zero-sequence advantage in microgrid applications where reliability of the
current contribution from the MV-side to faults at the LV-side. power supplied to loads is a priority. However, as mentioned in
Hence, the MV-side relays do not react to ground faults on the Section II-B, aside from the overvoltage issues, locating LG
LV-sides of the interface transformers [11], [40]. As a result, faults in ungrounded system is extremely difficult. Voltage-
the MV-side ground relays may use lower pickup currents and based protection strategies used in ungrounded systems are
achieve faster operation since they do not need to be non-selective [28]. This issue may lead to excessively long
coordinated with the ground relays at the LV-side [39]. service restoration delays after LG faults in the three-wire
ungrounded microgrid. Another serious issue is the possibility
of undetected LG faults evolving to LL faults.

0093-9994 (c) 2018 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TIA.2018.2864106, IEEE
Transactions on Industry Applications
7

Considering the aforementioned issues, application of three- D. Microgrid Grounding Devices


wired ungrounded microgrids is not recommended. A rare The grounding strategy of the microgrid impacts fault
exception is when the host utility grid has three-wire response and protection coordination of the host utility systems,
ungrounded configuration and the microgrid has to comply with and thus cannot be determined independent of the utility system
the utility grounding strategy. grounding strategy. In the grid-connected mode, the DERs in
2) Three-wire uni-grounded microgrid the microgrid are seen by the utility grid as regular distributed
A three-wire uni-grounded microgrid does not contain any generation systems. Therefore, in case of an ungrounded utility
grounding device itself and is connected to a three-wire uni- system, to maintain compatibility and prevent desensitization
grounded utility system [8], [9]. Due to the grounding support of the utility ground fault protection systems, the DERs should
from the grid, the grid-connected uni-grounded microgrid does behave as ungrounded sources, e.g., interfaced by ∆/Yg or ∆/∆
not necessarily suffer from the fault location and overvoltage transformer. In case the utility system is grounded, the DERs in
issues associated with the ungrounded configuration. However, the microgrid should be grounded as well, to prevent
this is not the case when the microgrid becomes ungrounded destructive overvoltages under back-feed conditions. If the
after islanding. A possible solution is to restore the uni- utility system is impedance grounded, solid grounding of the
grounded nature of the islanded microgrid by automatically DERs would still cause protection desensitization issues.
grounding it at a single location immediately after islanding Based on the information provided in parts III-C, the
detection. This solution does not fully resolve the problem since grounding configuration suitable for the majority of microgrids
the islanded microgrid would be exposed to excessive is four-wire multi-grounded, especially in North America. As
overvoltages before the islanding is detected and the grounding mentioned in part III-B, the most common connection types of
device is switched in. Considering the aforementioned technical DER interface transformers in four-wire multi-grounded
issues, application of three-wire uni-grounded microgrid is not systems are Yg/Δ and Yg/Yg. For each specific microgrid
recommended. project, the grounding impedances of the DER interface
3) Four-wire uni-grounded microgrid transformers should be chosen taking into account the
Unlike the three-wire uni-grounded scenario, a four-wire uni- information provided in Table I. However, low-reactance and
grounded microgrid does not become ungrounded in the low-resistance grounding are generally more advantageous
islanded mode. The neutral conductor continues to provide considering criteria such as LG fault current magnitude, LG
grounding support to the microgrid after islanding [8], [9]. fault-induced overvoltage level, and personnel safety.
Hence, depending on the utilized grounding impedance, the
islanded four-wire uni-grounded microgrid does not necessarily IV. CONCLUSIONS
suffer from fault detection issues or excessive overvoltages.
In this paper, different grounding strategies, i.e., grounding
However, the microgrid may experience neutral voltage rise
configurations and grounding devices, of the traditional AC
and large voltage imbalance if the neutral is not solidly
distribution systems are investigated and their advantages and
grounded or if the feeder is long, e.g., rural microgrids.
disadvantages are compared. Subsequently, grounding
4) Four-wire multi-grounded microgrid
The four-wire multi-grounded AC microgrid offers many requirements and issues of AC microgrids are discussed. Based
advantages including (i) improved voltage transients, (ii) on the identified grounding requirements, the appropriate
optimized size of overvoltage protective devices, (iii) lower grounding strategies for microgrid applications are identified
zero-sequence impedance compared to the uni-grounded case, and reported. The microgrid grounding recommendations made
(iv) improved safety and (v) the possibility of providing power in this paper mainly focus on the grounding configurations of
to single-phase loads. the AC microgrid, the DER interface transformer connection
Multi-grounded AC microgrids suffer from ground potential type, and the grounding device.
rise, large LG fault currents, and ground fault protection This study indicates that the grounding strategy of an AC
coordination issues. LG faults in such systems must be detected, microgrid, regardless of its grid-connection mode, must ensure
located, and isolated as quick as possible, in order to minimize proper operation of relays, insulation integrity, and personnel
damages and voltage dip [7]. However, some of these issues can safety. This should be achieved by (i) effective grounding of the
be resolved by using appropriate grounding impedances and MV-side of the islanded microgrid with Δ/Y connected DER
more sophisticated protection strategies. The remaining interface transformers, (ii) effective grounding of the LV-side
unresolved issues are not as serious as those of the other of the islanded microgrid with Yg/Yg connected DER interface
configurations. Therefore, based on the stare-of-the-art transformers, (iii) utilizing compatible grounding strategies in
technologies, the four-wire multi-grounded configuration is the microgrid and the utility feeder.
currently the most suitable case for the majority of microgrid The study results also indicate that for the majority of
applications. Of course, each of the other configurations may microgrid applications, the most suitable grounding strategy
be chosen for specific cases that impose different requirements involves four-wire multi-grounded configuration, Yg/Δ and
in terms of microgrid protection, reliability, insulation Yg/Yg type of DER interface transformers, and low-reactance
coordination, power quality, and cost. or low-resistance grounding devices.

0093-9994 (c) 2018 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TIA.2018.2864106, IEEE
Transactions on Industry Applications
8

REFERENCES [20] Guide for the application of metal-oxide surge arresters for alternating-
current systems, IEEE STD C62.22-2009 (Revision of IEEE STD C62.22-
[1] K. T. Tan, P. L. So, Y. C. Chu, and M. Z. Q. Chen,“Coordinated control 1997), pp.1-142, Jul. 2009.
and energy management of distributed generation inverters in a
microgrid”, IEEE Trans. Power Delivery, vol. 28, no. 2, pp. 704–713, [21] NFPA 70, National Electrical Code 2002, National Fire Protection
Apr. 2013. Association, 2002, Quincy, Massachusetts.
[22] Canadian Electrical Code Part I #C22.1-02 rule 10-106(2).
[2] J. Rocabert, A. Luna, F. Blaabjerg and P. Rodríguez, "Control of power
converters in AC microgrids," IEEE Trans. Power Electronics, vol. 27, [23] J. D. McDonald, B. Wojszczyk, B. Flynn, and I. Voloh, “Distribution
no. 11, pp. 4734-4749, Nov. 2012. systems, substations, and integration of distributed generation”, Electrical
Transmission Systems and Smart Grids, pp. 7-68. Nov. 2012.
[3] Recommended practice for grounding of industrial and commercial
power systems, IEEE STD 142-2007 (Revision of IEEE STD 142-1991), [24] Application Guide for IEEE STD 1547(TM), IEEE standard for
pp.1-225, Nov. 2007. interconnecting distributed resources with electric power systems, IEEE
STD 1547.2-2008, pp.1-217, Apr. 2009.
[4] Guide for the application of neutral grounding electrical utility systems-
part I: introduction, IEEE STD C62.92.1-2016 (Revision of IEEE STD [25] E. S. Thomas, R. A. Barber, J. B. Dagenhart and A. L. Clapp,
C62.92.1-2000), pp.1-38, 2017. "Distribution system grounding fundamentals," Rural Electric Power
Conference, 2004, 2004, pp. A2-1-16.
[5] Guide for the application of neutral grounding electrical utility systems-
part IV: distribution, IEEE STD C62.92.4-2014 (Revision of IEEE STD [26] A. Dexters, T. Loix, J. Driesen, and R. Belmans, “A comparison of
C62.92.4-1991), pp.1-44, Jan. 19 2015. grounding techniques for distributed generators implemented in four-wire
distribution grids, UPS systems and microgrids,” 19th International
[6] J. P. Nelson, "The grounding of power systems above 600 volts: a
Conference on Electricity Distribution, Vienna, 21-24 May 2007.
practical view point," IEEE Industry Applications Society 50th Annual
Petroleum and Chemical Industry Conference, 2003. Record of [27] J. Burke and M. Marshall, "Distribution system neutral grounding," 2001
Conference Papers, 2003, pp. 13-22. IEEE/PES Transmission and Distribution Conference and Exposition.
[7] K. Y. Lien, D. M. Bui, S. L. Chen, W. X. Zhao, Y. R. Chang, Y. D. Lee, Developing New Perspectives (Cat. No.01CH37294), Atlanta, GA, 2001,
pp. 166-170 vol.1.
and J. L. Jiang, "A novel fault protection system using communication-
assisted digital relays for AC microgrids having a multiple grounding [28] S. Teimourzadeh, F. Aminifar, M. Davarpanah and J. M. Guerrero,
system," Elsevier, Elec. Power Energy Sys. vol. 78, pp. 600–625, 2016. "Macroprotections for Microgrids: Toward a new protection paradigm
subsequent to distributed energy resource integration," IEEE Ind. Electr.
[8] D. M. Bui, S. L. Chen, K. Y. Lien, Y. R. Chang, Y. D. Lee, and J. L. Jiang,
Magazine, vol. 10, no. 3, pp. 6-18, Sept. 2016.
"Investigation on transient behaviors of a uni-grounded low voltage AC
microgrid and evaluation on its available fault protection methods: [29] Recommended practice for protection and coordination of industrial and
Review and proposals," Elsevier, Renewable and Sustainable Energy commercial power systems, IEEE STD 242-2001 (Revision of IEEE STD
Reviews. vol. 75, pp. 1417–1452, 2017. 242-1986). pp. 1-710, Dec. 17 2001.
[9] D. M. Bui, S. L. Chen, K. Y. Lien and J. L. Jiang, "A generalized fault [30] M. Vaziri and D. R. Smith, "Grounding of primary system for LV
protection structure for uni-grounded low-voltage AC microgrids," 2015 networks," IEEE Trans. Power Delivery, vol. 31, no. 2, pp. 419-427, Apr.
IEEE Innovative Smart Grid Technologies - Asia (ISGT ASIA), Bangkok, 2016.
2015, pp. 1-6. [31] D. Paul, "High-resistance grounded power system," IEEE Trans. Ind.
[10] D. M. Bui, and S. L. Chen, "Fault protection solutions appropriately Appl., vol. 51, no. 6, pp. 5261-5269, Nov.-Dec. 2015.
proposed for ungrounded low voltage AC microgrids: Review and [32] D. Paul, "High-resistance grounded power-system equivalent circuit
proposals," Elsevier, Renewable and Sustainable Energy Reviews. vol. 75, damage at the line–ground fault location—part I," IEEE Trans. Ind. Appl.,
pp. 1156–1174, 2017. vol. 50, no. 6, pp. 4179-4187, Nov.-Dec. 2014.
[11] C. J. Mozina, "Impact of green power distributed generation," IEEE Ind. [33] D. Paul and P. E. Sutherland, "High-resistance grounded power-system
Appl. Magazine, vol. 16, no. 4, pp. 55-62, July-Aug. 2010. equivalent circuit damage at the line–ground fault location—Part II,"
[12] R. Kamel, A. Chaouachi, and K. Nagasaka, "Design and testing of three IEEE Trans. Ind. Appl., vol. 50, no. 6, pp. 4188-4196, Nov.-Dec. 2014.
earthing systems for micro-grid protection during the islanding mode," [34] A. Bapat, R. Hanna and S. Panetta, "Advanced concepts in high resistance
Smart Grid Renew Energy, vol. 1, no. 3, pp. 132-142, 2010. grounding," 2012 Petroleum and Chemical Industry Conference (PCIC),
[13] R. Kamel, A. Chaouachi, and K. Nagasaka, "Comparison the Chicago, IL, 2012, pp. 1-9.
performances of three earthing systems for micro-grid protection during [35] J. C. Das, "Selective high resistance grounding system for a cogeneration
the grid connected mode," Smart Grid Renew Energy, vol. 2, no. 3, pp. facility," IEEE Trans. Ind. Appl., vol. 51, no. 6, pp. 5270-5280, Nov.-Dec.
206-215, 2011. 2015.
[14] B. Li, Y. Li and T. Ma, "Research on earthing schemes in LV [36] Guide for generator ground protection, IEEE STD C37.101- 2006
microgrids," 2011 International Conference on Advanced Power System (Revision of IEEE STD C37.101-1993/Incorporates IEEE STD C37.101-
Automation and Protection, Beijing, 2011, pp. 1003-1007. 2006/Cor1:2007), pp.1-70, Nov. 15, 2007.
[15] J. Mohammadi, F. B. Ajaei and G. Stevens, "AC microgrid grounding [37] H. R. Tomlinson, and F. B. Hunt, “Operation of a ground fault neutralizer
strategies," 2018 IEEE/IAS 54th Industrial and Commercial Power on a regulated distribution system,” AIEE Transactions, vol. 68, no. 2, pp.
Systems Technical Conference (I&CPS), Niagara Falls, ON, Canada, 1321–1328, 1949.
2018, pp. 1-7. [38] J. R. Acharya, Y. Wang and W. Xu, "Temporary overvoltage and GPR
[16] J. Roberts and J. H. Aituve, “Review of ground fault protection methods characteristics of distribution feeders with multi-grounded neutral," IEEE
for grounded, ungrounded, and compensated distribution systems,” SEL, Trans. Power Delivery, vol. 25, no. 2, pp. 1036-1044, Apr. 2010.
2001. 2001 Proceedings. 27th Annual Western Protective Relay [39] S. Chowdhury, S. P. Chowdhury and P. Crossley “Microgrids and active
Conference. distribution networks” The Institution of Engineering and Technology,
[17] P. Pillai, et al., "Grounding and ground fault protection of multiple 2009.
generator installations on medium-voltage industrial and commercial [40] T. K. Abdel-Galil, A. E. B. Abu-Elanien, E. F. El-Saadany, A. Girgis, Y.
power systems-part 2: grounding methods," IEEE Trans. Ind. Appl., vol. A. -R. I. Mohamed, M. M. A. Salama, H. H. M. Zeineldin, "Protection
40, no. 1, pp. 17-23, 2004. coordination planning with distributed generation," NRCAN, Varennes,
[18] D. Paul and S. I. Venugopalan, "Low-resistance grounding method for QC., Technical Report CETC 2007-149/2007-09-14, Jun. 2007.
medium voltage power systems," Conference Record of the 1991 IEEE [41] J.J. Grainger, and W.D. Stevenson, “Power system analysis”, McGraw-
Industry Applications Society Annual Meeting, Dearborn, MI, USA, 1991, Hill, New York, 1994, ISBN: 0071133380.
pp. 1571-1578, vol. 2.
[19] Standard for metal-oxide surge arresters for AC power circuits (>1 kV),
IEEE STD C62.11-2012 (Revision of IEEE STD C62.11-2005), pp.1-121,
Dec. 2012.

0093-9994 (c) 2018 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TIA.2018.2864106, IEEE
Transactions on Industry Applications
9

Jafar Mohammadi received the B.Sc. degree in Gary Stevens received the B.Sc. degree in chemistry
electrical engineering from The University of in 1980, and the M.Sc. degree in inorganic chemistry
Mazandaran, Iran, in 2009 and the M.Sc. degree in in 1984, both from Texas Tech University, Lubbock,
electrical engineering from The University of TX.
Tehran, Tehran, Iran, in 2012. Gary has over 30 years of experience in process
Currently, he is working toward the Ph.D. degree development and advanced manufacturing of Solar
at the Department of Electrical and Computer and Semiconductor technologies. In 1984, he joined
Engineering, University of Western Ontario, Texas Instruments in Dallas, where he was involved
Canada. His research interests include Protection and in projects related to high-reliability power
Control of Power systems especially Microgrids and transistors, microcircuits, and molten silicon refining.
Renewable Energy Systems. In 1997, he joined Matrix Solar Technologies in Texas (an ATS Automation
holding company), and led several projects related to silicon wafer cutting and
Firouz Badrkhani Ajaei (S’12-M'15) received the photovoltaic module manufacturing. In 2001, he joined the Spheral Solar Power
B.Sc. degree in electrical engineering from Tehran division of ATS Automation, Cambridge ON, Canada, to manage the IP
Polytechnic University, Iran, in 2006, the M.Sc. portfolio and lead R&D efforts for new processes and product enhancements.
degree in electrical engineering from The University Currently, he is a Chief Scientist at s2e technologies Inc., St Jacobs, ON,
of Tehran, Iran in 2009, and the Ph.D. degree in Canada, where he continues to lead R&D projects focused on promoting and
electrical engineering from The University of implementing sustainable technologies worldwide. He holds eight US Patents
Toronto, Canada, in 2015. with numerous international filings.
Currently, he is an Assistant Professor with the
Department of Electrical and Computer Engineering,
University of Western Ontario, Canada. His research
interests include Protection and Control of Power Systems with focus on
Renewable Energy Systems, Microgrids, and HVDC-AC Grids.

0093-9994 (c) 2018 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.

S-ar putea să vă placă și