Sunteți pe pagina 1din 37

American National Standard SJI 200 - 2015

STANDARD SPECIFICATION
FOR CJ-SERIES COMPOSITE STEEL JOISTS

CJ-Series Adopted by the Steel Joist Institute May 10, 2006


Revised to May 18, 2010, Effective December 31, 2010
Revised to November 9, 2015; Effective August 1, 2016

SECTION 1.
SCOPE AND DEFINITIONS
1.1 SCOPE

The Standard Specification for CJ-Series Composite Steel Joists, hereafter referred to as the Specification, covers the
design, manufacture, application, and erection stability and handling of CJ-Series Composite Steel Joists in buildings or
other structures, where other structures are defined as those structures designed, manufactured, and erected in a manner
similar to buildings. CJ-Series joists shall be designed using Load and Resistance Factor Design (LRFD) in accordance
with this Specification.

1.2 OTHER REGULATIONS

CJ-Series joists shall be erected in accordance with the Occupational Safety and Health Administration (OSHA), 29 CFR
Part 1926, Safety Standards for Steel Erection, Subpart R – Steel Erection. The erection of CJ-Series joists shall be in
accordance with the requirements of Section 1926.757, Open Web Steel Joists.

1.3 APPLICATION

This Specification includes Section 1 through Section 8. The user notes shall not be part of the Specification.

User Note: User notes are intended to provide practical guidance in the use and application of this
Specification.

1.4 DEFINITIONS

The following terms shall, for the purposes of this Specification, have the meanings shown in this Section. Where terms
are not defined in this Section, those terms shall have their ordinary accepted meanings in the context in which it applies.

CJ-Series shall be open web, parallel chord, load-carrying steel members utilizing hot-rolled or cold-formed steel,
including cold-formed steel whose yield strength has been attained by cold working. Shear connection between the top
chord and overlying concrete slab allows the steel joist and slab to act together as an integral unit after the concrete has
adequately cured.

The CJ-Series joist standard designation is determined by its nominal depth in inches (mm), the letters “CJ”, followed by
the total uniform composite load, uniform composite live load, and finally the uniform composite dead load. Composite
Steel Joists shall be designed in accordance with this Specification to support the loads defined by the specifying
professional.

User Note: CJ-Series joists are suitable for the direct support of one-way floors and roof slabs or decks.
CJ-Series joists have parallel chords and are standardized in depths from 10 inches (254 mm) through 96
inches (2438 mm), for spans through 120 feet (36.58 m).

Page 1 of 37
American National Standard SJI 200 - 2015

Two standard types of CJ-Series joists are designed and manufactured. These types are underslung (top
chord bearing) or square-ended (bottom chord bearing).

The CJ-Series joists have bearing depths that range from 2½ inches (64 mm) to 7 ½ inches (191 mm).

1.5 STRUCTURAL DESIGN DRAWINGS AND SPECIFICATIONS

The structural design drawings and specifications shall meet the requirements in the Code of Standard Practice for
Composite Steel Joists, except for deviations specifically identified in the design drawings and/or specifications.

SECTION 2.
REFERENCED
SPECIFICATIONS, CODES
AND STANDARDS

2.1 REFERENCES

The standards listed below shall be considered part of the requirements of this Specification. Where conflicts occur
between this Specification and a referenced standard, the provisions of this Specification shall take precedence unless
otherwise so stated. This section lists the standards that are referenced in this Specification. The standards are listed in
alphabetical order by name of the standards developer organization, with the specific standard designation, title and date
of each referenced standard below.

ACI International (ACI), Farmington Hills, MI


ACI 318-14, Building Code Requirements for Structural Concrete and Commentary
ACI 318M-14, Metric Building Code Requirements for Structural Concrete and Commentary

American Institute of Steel Construction, Inc. (AISC), Chicago, IL


ANSI/AISC 360-10 Specification for Structural Steel Buildings

American Iron and Steel Institute (AISI), Washington, DC


ANSI/AISI S100-2012 North American Specification for the Design of Cold-Formed Steel Structural Members

American Society of Civil Engineers (ASCE), Reston, VA


SEI/ASCE 7-10 Minimum Design Loads for Buildings and Other Structures

Page 2 of 37
American National Standard SJI 200 - 2015
American Society of Testing and Materials, ASTM International (ASTM), West Conshohocken, PA
ASTM A6/A6M-14, Standard Specification for General Requirements for Rolled Structural Steel Bars, Plates, Shapes,
and Sheet Piling
ASTM A36/A36M-14, Standard Specification for Carbon Structural Steel
ASTM A242/242M-13, Standard Specification for High-Strength Low-Alloy Structural Steel
ASTM A307-14, Standard Specification for Carbon Steel Bolts and Studs, 60 000 PSI Tensile Strength
ASTM A325-14 Standard Specification for Structural Bolts, Steel, Heat Treated, 120/105 ksi Minimum Tensile
Strength
ASTM A325M-14 Standard Specification for Structural Bolts, Steel, Heat Treated 830 MPa Minimum Tensile Strength
(Metric)

ASTM A370-14, Standard Test Methods and Definitions for Mechanical Testing of Steel Products
ASTM A500/A500M-13, Standard Specification for Cold-Formed Welded and Seamless Carbon Steel Structural
Tubing in Rounds and Shapes
ASTM A501/A501M-14 Standard Specification for Hot-Formed Welded and Seamless Carbon Steel Structural Tubing
ASTM A529/A529M-14, Standard Specification for High-Strength Carbon-Manganese Steel of Structural Quality
ASTM A572/A572M-15, Standard Specification for High-Strength Low-Alloy Columbium-Vanadium Structural Steel
ASTM A588/A588M-15, Standard Specification for High-Strength Low-Alloy Structural Steel, up to 50 ksi [345 MPa]
Minimum Yield Point, with Atmospheric Corrosion Resistance
ASTM A606/A606M-09a, Standard Specification for Steel, Sheet and Strip, High-Strength, Low-Alloy, Hot-Rolled and
Cold-Rolled, with Improved Atmospheric Corrosion Resistance
ASTM A992/A992M-11 (2015), Standard Specification for Structural Steel Shapes
ASTM A1008/A1008M-15, Standard Specification for Steel, Sheet, Cold-Rolled, Carbon, Structural, High-Strength
Low-Alloy and High-Strength Low-Alloy with Improved Formability, Solution Hardened, and Bake Hardenable
ASTM A1011/A1011M-14, Standard Specification for Steel, Sheet and Strip, Hot-Rolled, Carbon, Structural, High-
Strength Low-Alloy, High-Strength Low-Alloy with Improved Formability, and Ultra-High Strength
ASTM A1065/A1065M-15 Standard Specification for Cold-Formed Electric-Fusion (ARC) Welded High-Strength Low
Alloy Structural Tubing in Shapes with 50 ksi (345 MPA) Minimum Yield Point
ASTM A1085-13 Standard Specification for Cold-Formed Welded Carbon Steel Hollow Structural Sections (HSS)

American Welding Society (AWS), Miami, FL


AWS A5.1/A5.1M-2012, Specification for Carbon Steel Electrodes for Shielded Metal Arc Welding
AWS A5.5/A5.5M:2006, Specification for Low-Alloy Steel Electrodes for Shielded Metal Arc Welding
AWS A5.17/A5.17M-97:R2007, Specification for Carbon Steel Electrodes and Fluxes for Submerged Arc Welding
AWS A5.18/A5.18M:2005, Specification for Carbon Steel Electrodes and Rods for Gas Shielded Arc Welding
AWS A5.20/A5.20M:2005, Specification for Carbon Steel Electrodes for Flux Cored Arc Welding
AWS A5.23/A5.23M:2011, Specification for Low-Alloy Steel Electrodes and Fluxes for Submerged Arc Welding
AWS A5.28/A5.28M:2005, Specification for Low-Alloy Steel Electrodes and Rods for Gas Shielded Arc Welding
AWS A5.29/A5.29M:2010, Specification for Low Alloy Steel Electrodes for Flux Cored Arc Welding
AWS D1.1/D1.1M:2015, Structural Welding Code - Steel
AWS D1.3/D1.3M:2008, Structural Welding Code Sheet Steel

Page 3 of 37
American National Standard SJI 200 - 2015

Steel Deck Institute (SDI), Glenshaw, PA


ANSI/SDI C-2011, Standard for Composite Steel Floor Deck - Slabs
ANSI/SDI NC-2010, Standard for Non-Composite Steel Floor Deck

Steel Joist Institute (SJI), Florence, SC


ANSI/SJI 100-2015, Standard Specification for K-Series, LH-Series, and DLH-Series Open Web Steel Joists and for Joist
Girders

User Note: The following references provide additional practical guidance in the use and application of
this Specification:
Code of Federal Regulations (CFR), Occupational Safety and Health Administration (OSHA), 29 CFR Part 1926, Safety
Standards for Steel Erection; Subpart R – Steel Erection; January 18, 2001, Washington, D.C
Steel Joist Institute (SJI), Florence, SC
ANSI/SJI-CJ COSP-2015, Code of Standard Practice for Composite Steel Joists
Technical Digest No. 3 (2007), Structural Design of Steel Joist Roofs to Resist Ponding Loads
Technical Digest No. 5 (2014), Vibration of Steel Joist-Concrete Slab Floors
Technical Digest No. 6 (2010), Structural Design of Steel Joist Roofs to Resist Uplift Loads
Technical Digest No. 8 (2008), Welding of Open Web Steel Joists and Joist Girders
Technical Digest No. 9 (2008), Handling and Erection of Steel Joists and Joist Girders
Technical Digest No. 10 (2003), Design of Fire Resistive Assemblies with Steel Joists
Technical Digest No. 11 (2007), Design of Lateral Load Resisting Frames Using Steel Joists and Joist Girders
Technical Digest No. 13 (2016), Design of Composite Steel Joists

The Society for Protective Coatings (SSPC), Pittsburgh, PA


SSPC 08-02 Steel Structures Painting Manual – Volume 2 – Systems and Specifications, 2011 Edition
SSPC Paint 15 Steel Joist Shop Primer/Metal Building Primer (Includes 2004 Revisions) 05/01/1999

Alsamsam, Iyad (1988), An Experimental Investigation Into the Behavior of Composite Open Web Steel Joists, Master’s
Thesis, Department of Civil and Mineral Engineering Institute of Technology, University of Minnesota, MN.
ASCE Task Committee on Design Criteria for Composite Structures in Steel and Concrete (1996), Proposed Specification
and Commentary for Composite Joists and Composite Trusses, ASCE Journal of Structural Engineering, Vol. 122, No. 4,
April.
Atkinson, A.H., and Cran, J.A. (1972), The Design and Economics of Composite Open-Web Steel Joists, Canadian
Structural Engineering Conference.
Avci, Onur and Easterling, Sam (2003), Strength of Welded Weak Position Shear Studs, Report No. CE/VPI-ST03/08,
Department of Civil and Environmental Engineering, Virginia Polytechnic Institute and State University, Blacksburg, VA.
Azmi, M.H. (1972), Composite Open-Web Trusses with Metal Cellular Floor, A Master of Engineering Thesis, McMaster
University, Hamilton, Ontario, April.
Band, B.S. and Murray, T.M. (1999), Floor Vibrations: Ultra-Long Span Joist Floors, Proceedings of the 1999 Structures
Congress, American Society of Civil Engineers, New Orleans, Louisiana, April 18-21.
Boice, Michael and Murray, T.M. (2002), Report of Floor Vibration Testing, University of Tennessee Medical Center,
Knoxville, TN, Report CE/VPI–ST02/10, Department of Civil and Environmental Engineering, Virginia Polytechnic Institute
and State University, Blacksburg, VA.

Page 4 of 37
American National Standard SJI 200 - 2015
Brattland, A., and Kennedy, D.J. Laurie (1992), Flexural Tests of Two Full-Scale Composite Trusses, Canadian Journal of
Civil Engineering, Volume 19, Number 2, April, pp. 279-295.
CISC (1984), Chien, E.Y.L., and Ritchie, J.K., Design and Construction of Composite Floor Systems, Chapter 5 –
“Composite Open Web Steel Joists and Trusses”, Canadian Institute of Steel Construction, Willowdale, Ontario.
CISC ICCA (2012), Handbook of Steel Construction, includes S16-09 “Design of Steel Structures”, Section 16 - “Open–
web steel joists”, Tenth Edition, Canadian Institute of Steel Construction, Willowdale, Ontario.

Corrin, Michael (1993), Stanley D. Lindsey & Associates, Ltd, 312 Elm Street- Innovation Pays Off, The Military Engineer,
No. 554, January - February.
Cran, J.A. (1972), Design and Testing Composite Open Web Steel Joists, Technical Bulletin 11, Stelco, January.
Curry, Jamison Hyde (1988), Full Scale Tests on Two Long-Span Composite Open-Web Steel Joists, Master’s Thesis,
Department of Civil and Mineral Engineering Institute of Technology, University of Minnesota, MN.
Easterling, W.S., Gibbings, D.R. and Murray, T.M. (1993) Strength of Shear Studs in Steel Deck on Composite Beams
and Joists, AISC Engineering Journal, Second Quarter, pp 44-55.
Easterling, W. Samuel (1999) Composite Joist Behavior and Design Requirements, ASCE Structures Congress, New
Orleans, LA, April 18-21.
Easterling, W. Samuel, Samuelson, David and Murray, Thomas M. (2000), Behavior and Design of Longspan Composite
Joists, Fourth ASCE Composite Construction in Steel and Concrete Conference, Banff, Alberta, Canada, May 28-June 2.
Federal Register, Department of Labor, Occupational Safety and Health Administration (2001), 29 CFR Part 1926 Safety
Standards for Steel Erection; Final Rule, §1926.757 Open Web Steel Joists - January 18, 2001, Washington, D.C.
Gibbings, D. R. and Easterling, W.S. (1991), Strength of Composite Long Span Joists, Report CE/VPI–ST91/02,
Department of Civil and Environmental Engineering, Virginia Polytechnic Institute and State University, Blacksburg, VA.
Gibbings, D. R. and Easterling, W.S. (1991), Strength of Composite Long Span Joists- Addendum, Report CE/VPI–
ST91/02 (Addendum), Department of Civil and Environmental Engineering, Virginia Polytechnic Institute and State
University, Blacksburg, VA.
Lembeck, Jr., H.G. (1965), Composite Design of Open Web Steel Joists, M.Sc. Thesis, Washington University, St. Louis,
MO.
Leon, R.T. and Curry, J., (1987), Behavior of Long Span Composite Joists, ASCE Structures Congress Proceedings.,
Florida, August, pp. 390-403.
Lyons, John; Easterling, Sam; and Murray, Tom (1994), Strength of Welded Shear Studs, Vols. I and II, Report No.
CE/VPI-ST94/07, Department of Civil and Environmental Engineering, Virginia Polytechnic Institute and State University,
Blacksburg, VA
Nguyen, S.; Gibbings, D. R.; Easterling, W.S.; and Murray, T. M. (1992), Elastic –Plastic Finite Element Modeling of Long
Span Composite Joists with Incomplete Interaction, Department of Civil and Environmental Engineering, Virginia
Polytechnic Institute and State University, Blacksburg, VA.
Nguyen, S.; Gibbings, D. R.; Easterling, W.S.; and Murray, T. M. (1992), Further Studies of Composite Long–Span Joists,
Report No. CE/VPI-ST92/05, Department of Civil and Environmental Engineering, Virginia Polytechnic Institute and State
University, Blacksburg, VA.
Patras, Wayne and Azizinimini, Atrod (1991), Open Web Composite Joist Systems Utilizing Ultra-High Strength Concrete,
Masters Thesis, College of Engineering and Technology, University of Nebraska – Lincoln, NE.
Robinson, H. and Fahmy, E.H. (1978), The Design of Partially Connected Composite Open-Web Joists, Canadian Journal
of Civil Engineering, Volume 5, pp. 611-614.
Roddenberry, Michelle; Easterling, Sam; and Murray, Tom (2000), Strength Prediction Method for Shear Studs and
Resistance Factor for Composite Beams, Volume No. II , Department of Civil and Environmental Engineering, Virginia
Polytechnic Institute and State University, Blacksburg, VA.

Page 5 of 37
American National Standard SJI 200 - 2015
Roddenberry, Michelle; Easterling, Sam; and Murray, Tom (2002), Behavior and Strength of Welded Stud Shear
Connectors, CE/VPI-ST02/04, Department of Civil and Environmental Engineering, Virginia Polytechnic Institute and State
University, Blacksburg, VA.
Roddenberry, Michelle; Easterling, Sam; and Murray, Tom (2002), Behavior and Strength of Welded Stud Shear
Connectors-Data Report, CE/VPI-ST02/05, Department of Civil and Environmental Engineering, Virginia Polytechnic
Institute and State University, Blacksburg, VA.
Samuelson, David (1999) Composite Joist Case Histories, ASCE Structures Congress, New Orleans, LA, April 18-21.
Samuelson, David (2003) Composite Joist Advantage, Modern Steel Construction Magazine, September.
Samuelson, David (2002) Composite Steel Joists, AISC Engineering Journal, Vol. 39, No. 3, Third Quarter.
Samuelson, David (2004) SJI Updates – Expanded Load Tables for Noncomposite Joists/Joist Girders and Development
of New Composite Joist Series, North American Steel Construction Conference, Long Beach, CA, March 24-27.
Sublett, Charles and Easterling, Sam (1992), Strength of Welded Headed Studs in Ribbed Metal Deck on Composite
Joists, CE/VPI-ST92/03, Department of Civil and Environmental Engineering, Virginia Polytechnic Institute and State
University, Blacksburg, VA.
Tide, R.H.R. and Galambos, T.V. (1970), Composite Open-Web Steel Joists, AISC Engineering Journal, January, Vol. 7,
No. 1.
Van Malssen, S.H. (1984), The Effects of Arc Strikes on Steel Used in Nuclear Construction, Welding Journal, American
Welding Society, Miami, FL, July 1984.
Viest, Ivan; Colaco, Joseph; Furlong, Richard; Griffis, Lawrence; Leon, Roberto; and Wyllie Jr., Loring A. (1997), Section
3.8 – Composite Joists and Trusses, Composite Construction Design for Buildings, Co-published by American Society of
Civil Engineers, and McGraw Hill.

SECTION 3.
MATERIALS
3.1 STEEL CHORD AND WEB MEMBERS

The steel used in the manufacture of CJ-Series joists shall conform to one of the following ASTM specifications:
Carbon Structural Steel, ASTM A36/A36M
High-Strength Low-Alloy Structural Steel, ASTM A242/A242M
Cold-Formed Welded and Seamless Carbon Steel Structural Tubing in Rounds and Shapes, ASTM A500/A500M
High-Strength Carbon-Manganese Steel of Structural Quality, ASTM A529/A529M
High-Strength Low-Alloy Columbium-Vanadium Structural Steel, ASTM A572/A572M
High-Strength Low-Alloy Structural Steel up to 50 ksi [345 MPa] Minimum Yield Point with Atmospheric Corrosion
Resistance, ASTM A588/A588M
Steel, Sheet and Strip, High-Strength, Low-Alloy, Hot-Rolled and Cold-Rolled, with Improved Atmospheric
Corrosion Resistance, ASTM A606/A606M
Structural Steel Shapes, ASTM A992/A992M
Steel, Sheet, Cold-Rolled, Carbon, Structural, High-Strength Low-Alloy, High-Strength Low-Alloy with Improved
Formability, Solution Hardened, and Bake Hardenable, ASTM A1008/A1008M
Steel, Sheet and Strip, Hot-Rolled, Carbon, Structural, High-Strength Low-Alloy, High-Strength Low-Alloy with
Improved Formability, and Ultra High Strength, ASTM A1011/A1011M
Page 6 of 37
American National Standard SJI 200 - 2015

EXCEPTION: Steel used in the manufacture of CJ-Series joists shall be permitted to be of suitable quality
ordered or produced to other than the listed ASTM specifications, provided that such material in the state used for
final assembly and manufacture is weldable and is proven by tests performed by the producer or manufacturer to
have properties, in accordance with Section 3.2.

3.2 MECHANICAL PROPERTIES

3.2.1 Minimum Yield Strength: Steel used for CJ-Series joists shall have a minimum yield strength determined in
accordance with one of the procedures specified in this section, which is equal to the yield strength assumed in the
design.

User Note: The term "Yield Strength" as used herein designates the yield level of a material as
determined by the applicable method outlined in paragraph 13.1 “Yield Point”, and in paragraph 13.2
“Yield Strength”, of ASTM A370, Standard Test Methods and Definitions for Mechanical Testing of Steel
Products, or as specified in Section 3.2.3.

Evidence that the steel furnished meets or exceeds the design yield strength shall, if requested, be provided in the form of
an affidavit or by witnessed or certified test reports.

For material used without consideration of increase in yield strength resulting from cold forming, the specimens shall be
taken from as-rolled material. In the case of such material, the mechanical properties of which conform to the
requirements of one of the listed ASTM specifications in Section 3.1, the test specimens and procedures shall conform to
those of the applicable ASTM specification and to ASTM A370.

3.2.2 Other Materials: For materials where the mechanical properties do not conform to the requirements of one of the
ASTM specifications listed in Section 3.1, these materials shall conform to the following requirements:
a) The specimens shall comply with ASTM A370.
b) The specimens shall exhibit a yield strength equal to or exceeding the design yield strength.
c) The specimens shall have an elongation of not less than 20 percent in 2 inches (51 mm) for sheet strip, or 18
percent in 8 inches (203 mm) for plates, shapes and bars with adjustments for thickness for plates, shapes and
bars as prescribed in either ASTM A36/A36M, A242/A242M, A500/A500M, A529/A529M, A572/A572M,
A588/A588M, or A992/A992M, whichever ASTM specification is applicable, on the basis of design yield strength.
d) The number of tests for (a), (b), and (c) above shall be as prescribed in ASTM A6/A6M for plates, shapes, and
bars; and ASTM A606/A606M, A1008/A1008M and A1011/A1011M for sheet and strip.

3.2.3 As-Formed Strength: If as-formed strength is utilized for cold-formed steel members, the test reports shall show
the results performed on full section specimens in accordance with the provisions of AISI S100. The test reports shall also
indicate compliance with the following additional requirements:
a) The yield strength calculated from the test data shall equal or exceed the design yield strength.
b) Where tension tests are made for acceptance and control purposes, the tensile strength shall be at least 8
percent greater than the yield strength of the section.
c) Where compression tests are used for acceptance and control purposes, the specimen shall withstand a gross
shortening of 2 percent of its original length without cracking. The length of the specimen shall be not greater
than 20 times the least radius of gyration.
d) If any test specimen fails to pass the requirements of subparagraphs (a), (b), or (c) above, as applicable, two
retests shall be made of specimens from the same lot. Failure of one of the retest specimens to meet such
requirements shall be the cause for rejection of the lot represented by the specimens.

3.3 WELDING ELECTRODES

Page 7 of 37
American National Standard SJI 200 - 2015

3.3.1 Welding Electrodes: The welding electrodes used for arc welding shall be in accordance with the following:
a) For connected members both having a specified minimum yield strength greater than 36 ksi (250 MPa), one of
the following electrodes shall be used:
AWS A5.1: E70XX
AWS A5.5: E70XX-X
AWS A5.17: F7XX–EXXX, F7XX–ECXXX flux electrode combination
AWS A5.18: ER70S-X, E70C-XC, E70C-XM
AWS A5.20: E7XT-X, E7XT-XM
AWS A5.23: F7XX–EXXX-XX, F7XX–ECXXX-XX
AWS A5.28: ER70S-XXX, E70C-XXX
AWS A5.29: E7XTX-X, E7XTX-XM

b) For connected members both having a specified minimum yield strength of 36 ksi (250 MPa) or one having a
specified minimum yield strength of 36 ksi (250 MPa), and the other having a specified minimum yield strength
greater than 36 ksi (250 MPa), one of the following electrodes shall be used:
AWS A5.1: E60XX
AWS A5.17: F6XX-EXXX, F6XX-ECXXX flux electrode combination
AWS A5.20: E6XT-X, E6XT-XM
AWS A5.29: E6XTX-X, E6XTX-XM

or any of those listed in Section 3.3.1(a).

3.3.2 Other Welding Methods: Other welding methods, providing equivalent strength as demonstrated by tests, shall be
permitted to be used.

3.4 PAINT

CJ-Series joists shall be provided unpainted to facilitate installation of welded shear studs, unless otherwise specified.

When specified, the standard shop paint shall be considered an impermanent and provisional coating and shall conform
to one of the following:
a) The Society for Protective Coatings, SSPC Paint Specification No. 15.
b) Or, shall be a shop paint which meets the minimum performance requirements of SSPC Paint Specification No.
15.

User Note: The standard shop paint is intended to protect the steel for only a short period of exposure in
ordinary atmospheric conditions. It is usually considered preferable to leave CJ-Series joists unpainted
due to concerns that paint may potentially hinder the installation of welded shear studs to the joist top
chord.

SECTION 4.
DESIGN
103.1
METHOD
AND MANUFACTURE
4.1 METHOD

CJ-Series joist design shall be based on achieving the nominal flexural strength of the composite member and is
designed as a one-way, composite joist system that meets the following criteria:

Page 8 of 37
American National Standard SJI 200 - 2015
a) Members are simply-supported and are not considered part of a designated lateral force resisting system, such as
a braced frame or moment frame.
b) Horizontal shear connection is achieved using welded steel stud anchors, except as provided in Section 8..

CJ-Series joists shall be designed in accordance with this Specification as simply-supported trusses supporting a floor or
roof deck so constructed as to brace the top chord of the steel joists against lateral buckling. Where any applicable design
feature is not specifically covered herein, the design shall be in accordance with the following specifications:
a) Where the steel used consists of hot-rolled shapes, bars or plates, AISC 360.
b) For members which are cold-formed from sheet or strip steel, AISI S100.

4.1.1 Design Basis: CJ-Series joist designs shall be in accordance with the provisions in this Specification using Load
and Resistance Factor Design (LRFD) as specified by the specifying professional for the project.

4.1.2 Loads, Forces and Load Combinations: The loads and forces used for the CJ-Series joist design shall be
calculated by the specifying professional in accordance with the applicable building code and specified and provided on
the structural drawings.

For nominal concentrated loads, which have been accounted for in the specified uniform loads, the addition of chord
bending moments or an added shop or field web member due to these nominal concentrated loads shall not be required
provided that the sum of the concentrated loads within a chord panel does not exceed 100 pounds and the attachments
are concentric to the chord. When exact dimensional locations for concentrated loads which do not meet the above
criteria are provided by the specifying professional, the CJ-Series joist shall be designed for the loads and load locations
provided without the need for additional field applied web members at the specified locations.

The load combinations shall be specified by the specifying professional on the structural drawings in accordance with the
applicable building code. In the absence of an applicable building code, the load combinations shall be those stipulated in
SEI/ASCE 7 Section 2.3 for Load and Resistance Factor Design.

At a minimum, the required stress for LRFD designs shall be computed for the factored loads based on the factors and
load combinations as follows:
a) Non-composite
1.4Dc (4.1-1)
1.2Dc + 1.6Lc (4.1-2)
Where:
Dc = construction dead load due to weight of the joist, the metal decking, and the fresh concrete, lb/ft2 (kPa)
Lc = construction live load due to the work crews and the construction equipment, lb/ft 2 (kPa)

b) Composite
1.4D (4.1-3)
1.2D + 1.6 (L, or Lr, or S, or R) (4.1-4)
Where:
D = dead load due to the weight of the structural elements and the permanent features of the structure, lb/ft2
(kPa)
L = live load due to occupancy and movable equipment, lb/ft2 (kPa)
Lr = roof live load, lb/ft2 (kPa)
S = snow load, lb/ft2 (kPa)
R = load due to initial rainwater or ice exclusive of the ponding contribution, , lb/ft 2 (kPa)

Page 9 of 37
American National Standard SJI 200 - 2015

4.2 DESIGN STRESSES

4.2.1 Design Using Load and Resistance Factor Design (LRFD): CJ-Series joists shall have their components so
proportioned that the required stresses, fu, shall not exceed Fn where,
fu = required stress, ksi (MPa)
Fn = nominal stress, ksi (MPa)
 = resistance factor
Fn = design stress, ksi (MPa)
Fy = specified minimum yield stress, ksi (MPa)
E = modulus of elasticity of steel, ksi (MPa)

4.2.2 Stresses: The calculation of design stress for chords shall be based on a yield strength, F y, of the material used in
manufacturing equal to 50 ksi (345 MPa). The calculation of design stress for all other joist elements shall be based on a
yield strength, Fy, of the material used in manufacturing, but shall not be less than 36 ksi (250 MPa) nor greater than 50
ksi (345 MPa). Yield strengths greater than 50 ksi shall not be used for the design of any members.

4.2.2.1 Tension: t = 0.90 (LRFD)

Design Stress = 0.9Fy (4.2-1)

4.2.2.2 Compression: c = 0.90 (LRFD)

Design Stress = 0.9Fcr (4.2-2)

Where:

For members with k  4.71 E


r QFy

  QF

y
F 
 (4.2-3)
Fcr =Q 0.658  Fy
e

 

For members with k >4.71 E


r QFy

Fcr  0.877Fe (4.2-4)

Where Fe = Elastic buckling stress determined in accordance with Equation 4.2-5


2E (4.2-5)
Fe =
k r 
2

In the above equations,  is the length, k is the effective length factor, and r is the corresponding radius of gyration of the
member as defined in Section 4.3. E is equal to 29,000 ksi (200,000 MPa).

User Note:  should be taken as the distance in inches (mm) between panel points for the chord
members and web members.

For hot-rolled sections and cold-formed angles, the form factor, Q, shall be taken as the full reduction factor for slender
compression members as determined in accordance with AISC 360-10.

Page 10 of 37
American National Standard SJI 200 - 2015

Where a compression web member, either a hot-rolled section or a cold-formed angle, is a crimped-end angle member
intersecting at the first bottom chord panel point, then Q shall be determined as follows:
Q = [5.25/(w/t)] + t  1.0 (4.2-6a)
Where:
w = angle leg length, inches
t = angle leg thickness, inches

or,
Q = [5.25/(w/t)] + (t/25.4)  1.0 (4.2-6b)
Where:
w = angle leg length, mm
t = angle leg thickness, mm

For all other cold-formed sections the method of calculating the nominal compression strength shall be in accordance with
AISI S100.

4.2.2.3 Bending: b = 0.90 (LRFD)

Bending calculations shall be based on the elastic section modulus.

For chords and web members other than solid rounds: Fn = Fy


Design Stress = b Fn = 0.9Fy (4.2-7)

For web members of solid round cross section: Fn = 1.6 Fy


Design Stress = b Fn = 1.45Fy (4.2-8)

For bearing plates used in joist seats: Fn = 1.5 Fy


Design Stress = b Fn = 1.35Fy (4.2-9)

4.2.2.4 Weld Strength: w = 0.75 (LRFD)

Shear at throat of fillet welds, flare bevel groove welds, partial joint penetration groove welds, and plug/slot welds shall be
determined as follows:
Nominal Shear Stress = Fnw = 0.6Fexx (4.2-10)
Design Shear Strength = Rn = wFnw A = 0.45Fexx Aw (LRFD) (4.2-11)

Where:
Fexx is determined as follows:
E70 series electrodes or F7XX-EXXX flux-electrode combinations Fexx = 70 ksi (483 MPa)
E60 series electrodes or F6XX-EXXX flux-electrode combinations Fexx = 60 ksi (414 MPa)

Aw = effective throat area, where:


For fillet welds, Aw = effective throat area

Other design methods demonstrated to provide sufficient strength by testing shall be permitted to be
used.

For flare bevel groove welds, the effective weld area is based on a weld throat width, T (in.) and web
Page 11 of 37
American National Standard SJI 200 - 2015
diameter, D (in.), where:
T = 0.12D + 0.11 (in.) (4.2-12a)
or,
For flare bevel groove welds, the effective weld area is based on a weld throat width, T (mm) and web
diameter, D (mm), where:
T = 0.12D + 2.8 (mm) (4.2-12b)

For plug/slot welds, Aw = cross-sectional area of the hole or slot in the plane of the faying surface provided
that the hole or slot meets the requirements of AISC 360.

User Note: For more on plugs/slot welds see Steel Joist Institute Technical Digest No. 8, “Welding of
Open-Web Steel Joists and Joist Girders”.

Strength of resistance welds and complete-joint-penetration groove or butt welds in tension or compression (only where
the stress is normal to the weld axis) shall be equal to the base metal strength:
t = c = 0.90 (LRFD)

Design Stress = 0.9 Fy (4.2-13)

4.3 MAXIMUM SLENDERNESS RATIOS

The slenderness ratios, 1.0/r and 1.0s/r of members as a whole or any component part shall not exceed the values
given in Table 4.3-1, Part A.

4.3.1 Effective Slenderness Ratios: The effective slenderness ratio, k/r to be used in calculating the nominal stresses,
Fcr and F′e, is the largest value as determined from Table 4.3-1, Part B and Part C, and modified where required with
Equation 4.3-1.

4.3.2 Compression Members: In compression members where fillers or ties are used, they shall be spaced so that the
s/rz ratio of each component does not exceed the governing /r ratio of the member as a whole. The terms used in Table
4.3-1 shall be defined as follows:
 = length center-to-center of panel points, except  = 36 inches (914 mm) for calculating /ry of the top chord
member for CJ-Series joists, in. (mm)
s = maximum length center-to-center between panel point and filler (tie), or between adjacent fillers (ties), in.
(mm)
rx = member radius of gyration about the horizontal axis of the CJ-Series joist, in. (mm)
ry = member radius of gyration about the vertical axis of the CJ-Series joist, in. (mm)
rz = least radius of gyration of a member component, in. (mm)

Compression web members shall be those web members subject to compressive axial loads under gravity loading.

4.3.3 Tension Members: Tension web members shall be those web members subject to tension axial loads under gravity
loading, and which shall be permitted to be subject to compressive axial loads under alternate loading conditions.

User Note: An example of a non-gravity alternate loading condition is net uplift.

4.3.4 Top Chords: For top chords, the end panel(s) shall be the panels between the bearing seat and the first primary
interior panel point comprised of at least two intersecting web members.

Page 12 of 37
American National Standard SJI 200 - 2015

4.3.5 Built-Up Web Members: For built-up web members composed of two interconnected shapes, where s/rz > 40, a
modified slenderness ratio  k  shall replace k in Equations 4.2-3, 4.2-4, and 4.2-5, where:
 
 ry  m ry

2
k  k  k 
2

       i s  (4.3-1)
 ry m  ry   rz 
Where:
ki = 0.50 for angles back-to-back
= 0.75 for channels back-to-back

Page 13 of 37
American National Standard SJI 200 - 2015
TABLE 4.3-1

MAXIMUM AND EFFECTIVE SLENDERNESS RATIOS


Description k/rx k/ry k/rz ks/rz
I. TOP CHORD INTERIOR PANELS
A. The slenderness ratios, 1.0/r and 1.0s/r, of members as a whole or any component part shall not exceed 90.
B. The effective slenderness ratio for CJ-Series joists, k/r, to determine Fcr where k is:
1. Two shapes with fillers or ties 0.75 0.94 --- 1.0
2. Two shapes without fillers or ties --- --- 0.75 ---
3. Single component members 0.75 0.94 --- ---
C. For bending, the effective slenderness ratio, k/r, to determine F′e where k is:
0.75 --- --- ---
II. TOP CHORD END PANELS
A. The slenderness ratios, 1.0/r and 1.0s/r, of members as a whole or any component part shall not exceed 120.
B. The effective slenderness ratio for CJ-Series joists, k/r, to determine Fcr where k is:
1. Two shapes with fillers or ties 1.0 0.94 --- 1.0
2. Two shapes without fillers or ties --- --- 1.0 ---
3. Single component members 1.0 0.94 --- ---
C. For bending, the effective slenderness ratio, k/r, to determine F′e where k is:
1.0 --- --- ---
III. ALL BOTTOM CHORD PANELS
A. The slenderness ratios, 1.0/r and 1.0s/r, of members as a whole or any component part shall not exceed 240.

B. For members subject to compression, the effective slenderness ratio for CJ-Series joists, k/r, to determine Fcr
where k is:
1. Two shapes with fillers or ties 0.9 0.94 --- 1.0
2. Two shapes without fillers or ties --- --- 0.9 ---
3. Single component members 0.9 0.94 --- ---
C. For bending, the effective slenderness ratio, k/r, to determine F′e where k is:
0.9 --- --- ---
IV. WEB MEMBERS

A. The slenderness ratios, 1.0/r and 1.0s/r, of members as a whole or any component part shall not exceed 240
for a tension member or 200 for a compression member.
For members subject to compression, the effective slenderness ratio for CJ-Series joists, k/r, to determine Fcr
B.
where k is:

1. Two shapes with fillers or ties 0.75 1.0 --- 1.0


2. Two shapes without fillers or ties --- --- 1.0 ---
3. Single component members 0.75 0.9* --- ---
*For end tension web members subject to compression, k shall equal 0.80

Page 14 of 37
American National Standard SJI 200 - 2015

4.4 MEMBERS

4.4.1 Chord Members

4.4.1.1 Non-composite Design

The bottom chord shall be designed as an axially loaded tension member.

The top chord shall resist the construction loads, at which time the joist behaves non-compositely. An analysis shall be
made using an effective depth of the joist to determine the member forces due to construction loads. The effective depth
for a non-composite joist shall be considered the vertical distance between the centroids of the top and bottom chord
members.

The minimum horizontal flat leg width and minimum thickness of the top chord shall be as specified in Table 4.4-1.

TABLE 4.4-1
MINIMUM TOP CHORD SIZES FOR INSTALLING WELDED SHEAR STUDS
Shear Stud Minimum Horizontal Minimum Leg
Diameter, in. (mm) Flat Leg Width, in. (mm) Thickness, in. (mm)
0.375 (10) 1.50 (38) 0.125 (3.2)
0.500 (13) 1.75 (44) 0.167 (4.2)
0.625 (16) 2.00 (51) 0.209 (5.3)
0.750 (19) 2.50 (64) 0.250 (6.3)

The top chord shall be designed as a continuous member subject to combined axial and bending stresses. It shall be so
proportioned that for LRFD:
At the panel point:
fau +fbu  0.9Fy (4.4-1)

At the mid panel:


 
 
for, fau  0.2 , fau 8  Cm fbu   1.0 (4.4-2)
cFcr + 
cFcr 9   fau   
 1-  ' 
QbFy 
   cFe   

 
 
for, fau <0.2 , fau  Cm fbu   1.0 (4.4-3)
cFcr +
2cFcr    fau   
 1-  ' 
QbFy 
   cFe   
Where:
fau = Pu/A = required compressive stress using LRFD load combinations, ksi (MPa)
Pu = required axial strength using LRFD load combinations, kips (N)
A = area of the top chord, in.2 (mm2)
fbu = Mu/S = required bending stress at the location under consideration using LRFD load combinations, ksi
(MPa)

Page 15 of 37
American National Standard SJI 200 - 2015
Mu = required flexural strength using LRFD load combinations, kip-in. (N-mm)
S = elastic section modulus, in.3 (mm3)
Fcr = nominal axial compressive stress in ksi (MPa) based on k/r as defined in Section 4.3
Cm = 1 - 0.3 fau/cF′e for end panels
Cm = 1 - 0.4 fau/cF′e for interior panels
Q = form factor defined in Section 4.2.2.2
c = resistance factor for compression = 0.90
b = resistance factor for flexure = 0.90
Fy = specified minimum yield strength, ksi (MPa)
F′e = 2E , ksi (MPa),
k /rx 
2

where  is the length, k is the effective length factor, and rx is the corresponding radius of gyration of the
member as defined in Section 4.3
E = modulus of elasticity, 29,000 ksi (200,000 MPa)

The joist top chord shall be considered as laterally braced by the floor slab or roof deck provided the requirements of
Section 5.9.5 are met.

The top chord and bottom chord shall be designed such that at each joint complies with Equation 4.4-4:
fvmod ≤ vFn (LRFD, v = 1.00) (4.4-4)

Where:
Fn = nominal shear stress = 0.6Fy, ksi (MPa)
ft = axial stress = P/A, ksi (MPa)
fv = shear stress = V/bt, ksi (MPa)
fvmod = modified shear stress =  12  ft2 +4fv2
b = length of vertical part(s) of cross section, in. (mm)
t = thickness of vertical part(s) of cross section, in. (mm)

It shall not be necessary to design the top chord and bottom chord for the modified shear stress, fvmod, where a round bar
web member is continuous through a joint. The minimum required shear of Section 4.4.2 (25 percent of the maximum
end reaction) shall not be required when evaluating Equation 4.4-4.

4.4.1.2 Composite Design

The distance between the centroid of the tension bottom chord and the centroid of the concrete compression block, de,
shall be computed using a concrete stress of 0.85f ′c and an effective concrete width, be, taken as the sum of the effective
widths for each side of the joist centerline, each of which shall be the least value of the following:
a) one-eighth of the joist span, center-to-center of supports;
b) one-half the distance to the center-line of the adjacent joist;
c) the distance to the edge of the slab.

a = AbFy /(0.85 f′c be )  tc, in. (mm) (4.4-5)


de = dj – ybc + hdeck + tc – a/2, in. (mm) (4.4-6)

Page 16 of 37
American National Standard SJI 200 - 2015
Where:
a = depth of concrete compressive stress block, in. (mm)
Ab = cross-sectional area of CJ-Series steel joist bottom chord, in.2 (mm2)
be = effective width of concrete slab over the joist, in. (mm)
dj = CJ-Series steel joist depth, in. (mm)
f’c = specified compressive strength of concrete, ksi (MPa)
Fy = specified minimum yield stress of CJ- Series joist bottom chord, ksi (MPa)
hdeck = height of metal deck, in. (mm)
tc = thickness of concrete slab above the metal deck, in. (mm)
ybc = vertical distance to centroidal axis of bottom chord measured from the bottom of the bottom chord, in.
(mm)

When the metal deck ribs are perpendicular to the CJ-Series joists, the concrete below the top of the metal deck shall be
neglected when determining section properties and in calculating the concrete compressive stress block.

The first top chord end panel member shall be designed for the full factored load requirements as a non-composite
member per Section 4.4.1.1.

Mu  Mn (4.4-7)
Where:
Mn = minimum design flexural strength of composite section as determined from Equations 4.4-8, 4.4-9, 4.4-
10, and 4.4-11, kip-in. (N-mm)
Mu = required flexural strength determined from applied factored loads, kip-in. (N-mm)

The design flexural strength of the composite section, Mn, shall be computed as the least value of the following limit
states:
a) Bottom Chord Tensile Yielding: t  0.90 Mn  t AbFy de (4.4-8)

b) Bottom Chord Tensile Rupture: tr  0.75 Mn  tr AnFude (4.4-9)
c) Concrete Crushing: cc  0.85 Mn  cc 0.85 f 'c be t c de (4.4-10)
d) Shear Connector Strength: stud  0.90 Mn  studNQnde (4.4-11)

Where:
Ab = cross-sectional area of CJ-Series joist bottom chord, in.2 (mm2)
An = net cross-sectional area of the CJ-Series joist bottom chord, in.2 (mm2)
be = effective width of concrete slab over the CJ-Series joist, in. (mm)
de = vertical distance from the centroid of CJ-Series joist bottom chord to the centroid of resistance of the
concrete in compression, in.(mm)
Fu = tensile strength of the CJ-Series joist bottom chord, ksi (MPa)
Fy = specified minimum yield stress of CJ-Series joist bottom chord, ksi (MPa)
N = number of shear studs between the point of maximum moment and zero moment
Qn = shear capacity of a single shear stud, kips (kN)
tc = minimum thickness of the concrete slab above the top of the metal deck, in. (mm)

Where composite flexural strength is governed by the strength of shear connection as provided by Equation 4.4-11,
the strength of shear connection, NQn, shall be no less than 50 percent of the bottom chord yield strength.

Page 17 of 37
American National Standard SJI 200 - 2015

4.4.2 Web Members

The vertical shears to be used in the design of the web members shall be determined by including all loads, i.e. from the
controlling load combination from Section 4.1.2, but such vertical shears shall be not less than the following:
a) 25 percent of the maximum end reaction from the design load combinations;
b) Tension web members controlled by (a) shall be designed for a compressive force resulting from a factored shear
value of:
(1.6 w L ) L
Vc min  (4.4-12)
8
Where:
wL = non-factored live load due to occupancy and moveable equipment, plf (kN/m)
L = design length for the CJ-Series joist as defined in Table 5.2-1, where design length = Span – 0.33 ft.
(Span (m) – 0.102 m)
Vc min = minimum factored compressive design shear in tension web members, lbs (kN)

4.4.2.1 Redundant Web Member: Interior vertical web members used in modified Warren type web systems shall be
designed to resist the gravity loads supported by the member plus 2.0 percent of the composite bottom chord axial force.

Redundant web members in end panels shall be designed to resist the gravity loads supported by the member plus an
additional load of ½ of 1.0 percent of the top chord axial force.

4.4.2.2 Single Component Web Member: In those cases where a single component web member is attached to the
outside of the stem of a tee or double angle chord or any other orientation of a single web member which creates an out-
of-plane moment, the web member design shall account for the stresses due to eccentricity.

4.4.2.2.1 Uncrimped Single Angle Web Member

For 1 inch (25 mm) uncrimped single angle web members where one leg is placed flat against one chord member in the
gap, the resulting eccentricities and the effects in loading shall be considered in the design. A minimum of 50 percent of
the required weld shall be deposited to each chord angle.

For angles subjected to tension loading, combined axial and bending stresses shall be proportioned in accordance with
Equation 4.4-1.

For angles subjected to compression loading, the following requirements shall be met:
at the panel point, combined axial and bending stresses shall be proportioned in accordance with Equation 4.4-1.
at the mid length, the strength shall meet Equations 4.4-2 or 4.4-3, and 4.4-13:
fau (4.4-13)
 1.0
cFcrz
Where:
fau = Pu/A = required tensile or compressive stress, ksi (MPa)
Pu = required axial strength using LRFD load combinations, kips (N)
A = area of the uncrimped angle web, in.2, (mm2)
fbu = Mu/S = required bending stress, ksi (MPa)

Page 18 of 37
American National Standard SJI 200 - 2015

Mu = required flexural strength = 0.5 P  chord gap  y  , kip-in. (N-mm)


u
 2 
S = elastic section modulus, in.3 (mm3)
Fcr = Fcrx, ksi (MPa)
Fcrx = nominal axial compressive stress in ksi (MPa) based on k/rx,
where  is the length, k is the effective length factor, and rx is the corresponding radius of gyration of the
member as defined in Section 4.3
Fcrz = nominal axial compressive stress in ksi (MPa) based on k/rz
where k = 1.0
Cm = 1.0
Fy = specified minimum yield strength, ksi (MPa)
F′e =  2E , ksi (MPa)
k rx 
2

Q = form factor defined in Section 4.2.2.2

Alternate methods of design shall be permitted provided they provide strength equal to or greater than those given.
Alternate design procedures shall be submitted to the Steel Joist Institute’s consulting engineer for approval.

4.4.3 Fillers and Ties

Fillers or ties added on chord or web compression members shall be designed and connected for a force equal to two
percent of the required member axial force.

4.4.4 Joist Extensions

CJ-Series joist extensions shall be designated as one of three extension types, as follows: top chord extensions (TCX),
extended ends, or full depth cantilevers.

Design criteria for CJ-Series joist extensions shall be specified using one of the following methods:
(1) A CJ-Series joist top chord extension (TCX), extended end, or full depth cantilevered end shall be designed for
the load based on the design length and designation of the specified CJ-Series joist. In the absence of other
design information, the joist manufacturer shall design the joist extension for this loading as a default.
(2) A loading diagram shall be provided for the CJ-Series joist extension, extended end, or full depth cantilevered
end. The diagram shall include the magnitude and location of the loads to be supported, as well as the applicable
load combinations.

Any deflection requirements or limits due to the accompanying loads and load combinations on the CJ-Series joist
extension shall be provided by the specifying professional, regardless of the method used to specify the extension. Unless
otherwise specified, the joist manufacturer shall check the extension for the specified deflection limit under uniform live
load acting simultaneously on both the CJ-Series joist base span and the extension.

The joist manufacturer shall consider the effects of CJ-Series joist extension loading on the base span of the steel joist.
This shall include carrying the design bending moment due to the loading on the extension into the top chord end
panel(s), and the effect on the overall steel joist chord and web axial forces. The joist extension shall support all end loads
without relying on any composite action.

Required bracing of extensions shall be clearly indicated on the structural drawings.

Design of concrete reinforcing steel in the negative moment region shall be the responsibility of the specifying
professional.
Page 19 of 37
American National Standard SJI 200 - 2015

4.5 CONNECTIONS

4.5.1 Methods
Member connections and splices shall be made by attaching the members to one another by arc or resistance
welding or other accredited methods in accordance with the following:

a) CJ-Series joist arc welded joints shall be in accordance with the American Welding Society, “Structural
Welding Code-Steel”, D1.1, and/or the “Structural Welding Code Sheet Steel”, D1.3 with the following eight
modified acceptance criteria as permitted by AWS D1.1 Clause 6.8:

1. Undercut shall not exceed 1/16 inch (2 mm) for welds oriented parallel to the principal stress.

User Note: The typical diagonal web member connection to one leg of a chord angle is considered to be
parallel to the principal stress.

2. Discontinuities outside of the weld design length shall be permitted provided no cracks exist and
undercut does not exceed the limits of item 1.

User Note: The weld design length is the minimum weld length needed for the connection force and weld
thickness. Portions of the actual weld length with imperfections or discontinuities such as porosity or lack
of a full profile are not included when comparing the actual weld length to the weld design length.

3. One unrepaired arc strike shall be permitted per joint provided it does not result in other unacceptable
defects.

User Note: Minor arc strikes do not reduce the strength of AWS Group II materials (refer to Van Malssen,
1984).

4. The effective throat for flare bevel groove welds shall be calculated in accordance with equation 4.2-
12.

User Note: The effective weld throat used by the SJI with round bars is based on SJI research and is
more conservative than AWS D1.1 for GMAW for round bars in excess of 9/16” (14 mm). See Steel Joist
Institute Technical Digest 8 - Welding of Open Web Steel Joists and Joist Girders.

5. Tack welds that are discontinuous from other welds shall meet the criteria for undercut, but shall be
exempt from all other acceptance criteria.

User Note: Joist manufacturers use tack welds in the assembly process, and so long as they do not
diminish the strength of the base metal and are not incorporated into the final weld for strength, they are
not required to meet other inspection criteria.

6. The weld profile shall be considered acceptable provided neither the weld leg nor the weld throat is
undersized less than AWS D1.1 limits within the weld design length.

7. For material with thickness less than 1/8”, AWS D1.1 or D1.3 shall be considered appropriate.

User Note: AWS D1.1 does not address thicknesses less than 1/8” for hot rolled material and AWS D1.3
does not address hot rolled material, thus SJI has extended the ranges to include these material
thicknesses.

8. A ratio of stud diameter to top chord thickness of up to 3.0 shall be permitted.

Page 20 of 37
American National Standard SJI 200 - 2015
User Note: See section 4.5.4 Shear Studs for reduction in stud capacity for ratios between 2.7 and 3.0.

b) CJ-Series joist resistance welded joints shall follow a preproduction validation procedure and a production
checking procedure and shall meet the strength requirements of this Specification.

User Note: Spot, flash or upset resistance welds should have a written welding procedure qualification record
and a systematic quality plan. For further information, see Steel Joist Institute Technical Digest 8 - Welding of
Open Web Steel Joists and Joist Girders.

c) Welded Connections for Crimped-End Angle Web Members

1) The connection of each end of a crimped angle web member to each side of the chord shall consist of a
weld group made of more than a single line of weld. The design weld length shall include an end return
of no less than two times the nominal weld size.

d) Welding Program
1) The manufacturer’s welders shall be qualified in accordance with either AWS D1.1 or AWS D1.3 for the
applicable weld type, position, and material.

2) Manufacturers shall have a program for establishing weld procedures and operator qualification, and for
weld sampling and testing. Each manufacturing facility shall have trained inspectors, and an engineer
responsible for all welding procedures.

e) Weld Inspection by Outside Agencies (See Section 5.14)


1) The agency shall arrange for visual inspection to determine that welds meet the acceptance standards of
Section 4.5.1.

User Note: Ultrasonic, X-ray, and magnetic particle testing are inappropriate for joists due to the
configurations of the components and welds.

4.5.2 Strength

4.5.2.1 Joint Connections: Joint connections shall develop the maximum force due to any of the design loads,
but not less than 50 percent of the strength of the member in tension or compression, whichever force is the
controlling factor in the selection of the member.

4.5.2.2 Shop Splices: Shop splices shall be permitted to occur at any point in chord or web members. Splices
shall be designed for the member force, but not less than 50 percent of the member strength. All component
parts comprising the cross section of the chord or web member (including reinforcing plates, rods, etc.) at the
point of the splice shall develop a nominal tensile strength of at least 1.2 times the product of the yield strength
and the full design area of the chord or web. The “full design area” shall be defined as the minimum required area
such that the required stress will be less than the design (LRFD) stress.

User Note: For more information on welding, see Steel Joist Institute Technical Digest 8 - Welding of Open Web Steel
Joists and Joist Girders.

4.5.3 Field Splices

Field Splices shall be designed by the manufacturer and shall be either bolted or welded. Splices shall be designed for the
member force, but not less than 50 percent of the member strength.

Page 21 of 37
American National Standard SJI 200 - 2015
4.5.4 Shear Studs

Shear studs, after installation, shall extend not less than 1½ in. (38 mm) above the top of the steel deck and there shall be
at least ½ in. (13 mm) of concrete cover above the top of the installed studs.

For studs in 1.5 in. (38 mm), 2 in. (51 mm), or 3 in. (76 mm) deep decks with dstud t top chord  2.7 :


Qn  Min 0.5 A stud fc Ec , RpR g A stud Fu stud  (kips) (4.5-1a)


Qn  Min 0.5A stud fc Ec , RpR g A stud Fu stud 1000 (kN)  (4.5-1b)

For studs in 1.5 in. (38 mm), 2 in. (51 mm), or 3 in. (76 mm) deep decks with 2.7  d stud t top chord  3.0 :
  d 
Qn  Min 0.5 A stud fc Ec , R pR g A stud Fu stud  1.5  stud  2.7  kips  (4.5-2a)
t 
  top chord 
  d 
Qn  Min 0.5 A stud fc Ec , R pR g A stud Fu stud 1000  6.67  stud  2.7  (kN) (4.5-2b)
t 
  top chord 
Where:
Astud = cross-sectional area of shear stud, in.2 (mm2)
dstud = diameter of shear stud, in. (mm)
Ec = modulus of elasticity of the concrete, ksi (MPa)
f ′c = specified compressive strength of concrete, ksi (MPa)
Fu stud = minimum tensile strength of stud, 65 ksi (450 MPa)
Qn = shear capacity of a single shear stud, kips (kN)
Rp = shear stud coefficient from Table 4.5-1
Rg = 1.00 for one stud per rib or staggered position studs
= 0.85 for two studs per rib side-by-side
= 0.70 for three studs per rib side-by-side
ttop chord = thickness of top chord horizontal leg or flange, in. (mm)

TABLE 4.5-1
VALUES FOR Rp
Diameter Stud
Metal Deck Height Wr @ mid-height 3
/8 in. 1
/2 in. 5
/8 in. 3
/4 in.
(10 mm) (13 mm) (16 mm) (19 mm)
1 in. (25 mm) 1.9 in. (48 mm) 0.55 0.55 0.50 0.45
1.5 in. (38 mm) 2.1 in. (53 mm) 0.55 0.50 0.45 0.40
1.5 in. (38 mm) Inverted 3.9 in. (99 mm) 0.85 0.60 0.60 0.60
2 in. (51 mm) 6 in. (152 mm) --- 0.55 0.50 0.45
3 in. (76 mm) 6 in. (152 mm) --- 0.50 0.50 0.50

Notes: Wr @ mid-height = Average metal deck rib width of deck rib containing the shear stud.
The deck is assumed to be oriented perpendicular to the joists.

Page 22 of 37
American National Standard SJI 200 - 2015
4.5.5 Eccentricity

Members connected at a joint shall have their center of gravity lines meet at a point, where practical. Ends of CJ-Series
joists shall be proportioned to resist bending produced by eccentricity at the support.

For a single component web member, the eccentricity shall be permitted to be neglected where it does not exceed the
lesser of three-quarters of the overall dimension of the chord or 2 inches (51 mm). This eccentricity, measured in the
plane of the joist, shall be the perpendicular distance from the centroidal axis of that web member to the point on the
centroidal axis of the chord which is vertically above or below the intersection of the centroidal axis of the web member(s)
forming the joint in accordance with Figure 4.5-1.

For a web member composed of at least two shapes, the eccentricity on either side of the neutral axis of chord members,
measured in the plane of the CJ-Series joist at the joint work point, shall be permitted to be neglected where the web
intersection point does not exceed one and one-half times the distance between the neutral axis and the back of the chord
in accordance with Figure 4.5-2.

If these limits are exceeded, provision shall be made for the stresses due to eccentricity.

Figure 4.5-1 Single Angle Web Members and Bottom Chord Figure 4.5-2 Multiple Web Members and Bottom Chord
Workpoint Eccentricity Workpoint Eccentricity

4.6 CAMBER

CJ-Series joists shall be cambered. The approximate camber shall be based on the deflection associated with 100
percent of the non-composite unfactored dead load plus any additional loads defined by the specifying professional.

User Note: The specifying professional shall give consideration to coordinating this approximate camber
with adjacent framing.

4.7 VERIFICATION OF DESIGN AND MANUFACTURE

User Note: This Section is included as part of this Specification since the verification of design and
manufacture is a requirement of any Steel Joist Institute member company in order to be in compliance
with this Specification. This Section applies only to a Steel Joist Institute member manufacturer.

4.7.1 Design Calculations

Companies manufacturing any CJ-Series Joists shall submit design data to the Steel Joist Institute, or an independent
agency approved by the Steel Joist Institute, for verification of compliance with this Specification. Design data shall be
submitted in detail and in the format specified by the Steel Joist Institute.

4.7.2 Tests of Chord and Web Members

Page 23 of 37
American National Standard SJI 200 - 2015

Each manufacturer shall, at the time of design review by the Steel Joist Institute, verify by tests that the design, in
accordance with Section 4.1 through Section 4.5, provides the theoretical strength of critical members. Such tests shall be
evaluated considering the actual yield strength of the members of the test CJ-Series joists.

Material tests for determining mechanical properties of component members shall be conducted.

4.7.3 Tests of Joints and Connections

Each manufacturer shall, at the time of design review by the Steel Joist Institute, verify by shear tests on representative
joints of typical CJ-Series joists that connections will meet the provision of Section 4.5.2. Chord and web members shall
be permitted to be reinforced for such tests.

4.7.4 In-Plant Inspections

Each manufacturer shall verify their ability to manufacture CJ-Series joists through periodic In-Plant Inspections.
Inspections shall be performed by an independent agency approved by the Steel Joist Institute. The frequency, manner of
inspection and manner of reporting shall be determined by the Steel Joist Institute. The Plant inspections shall not
represent a guarantee of the quality of any specific CJ-Series joists; this responsibility shall lie fully and solely with the
individual manufacturer.

SECTION 5.
APPLICATION
5.1 USAGE

5.1.1 Scope: This Specification shall apply to any type of structure where floors or roofs are to be supported directly by
CJ-Series joists installed as hereinafter specified. Where CJ-Series joists are used other than on simple spans under
uniformly distributed loading for CJ-Series joists, as prescribed in Section 4.1, they shall be designed to limit the required
stresses to those listed in Section 4.2. The magnitude and location of all loads and forces to be considered in the CJ-
Series joist design shall be provided on the structural drawings.

5.1.2 Continuous Frame Action: Where a rigid connection of the bottom chord is to be made to a column or other
structural support, the CJ-Series steel joist is then no longer simply-supported, and the system shall be investigated for
continuous frame action by the specifying professional. The specifying professional shall design the supporting structure,
including the design of columns, connections, and moment plates. This design shall account for the stresses caused by
lateral forces and the stresses due to connecting the bottom chord to the column or other structural support.

The designed detail of a rigid type connection and moment plates shall be shown on the structural drawings by the
specifying professional. The moment plates shall be furnished by other than the joist manufacturer.

User Note: For further reference concerning continuous frame action and their connections, refer to Steel
Joist Institute Technical Digest No. 11, “Design of Lateral Load Resisting Frames Using Steel Joists and
Joist Girders”.

5.2 SPAN

The span of a CJ-Series joist shall not be less than 12 times nor exceed 30 times the depth. Design length shall equal the
span minus 4 inches (102 mm) as shown in Figure 5.2-1 “Definition of Span”.

5.3 DEPTH

Page 24 of 37
American National Standard SJI 200 - 2015
CJ-Series joists shall have parallel chords. The composite joist designation depth or nominal depth shall be the vertical
distance from the top of the steel top chord to the bottom of the bottom chord.

5.4 END SUPPORTS

Consideration of the reactions, vertical and lateral, shall be taken by the specifying professional in the design of the steel
support, or the steel bearing plate on masonry or concrete. The standard location of the end reaction shall be 2 inches (51
mm) from the end of the span (exclusive of extensions) at each end of the CJ-Series joist as shown in Figure 5.2-1
“Definition of Span”.

The standard CJ-Series joist bearing seat depth, clear bearing length, minimum bearing plate width and minimum bearing
length on steel is provided in Table 5.4-1.

Page 25 of 37
American National Standard SJI 200 - 2015

NOTES:
1) DESIGN LENGTH = SPAN – 4”
2) MINIMUM BEARING LENGTHS SHALL MEET THE REQUIREMENTS OF SECTION 5.4; BEARING LENGTHS SHOWN MAY
VARY BETWEEN STANDARD CLEAR BEARING AND MINIMUM BEARING LENGTH.
3) PARALLEL CHORD CJ-SERIES JOISTS INSTALLED TO A SLOPE GREATER THAN ½ INCH PER FOOT SHALL USE A SPAN
DEFINED BY THE LENGTH ALONG THE SLOPE.
Figure 5.2-1 Definition of Span (U.S. Customary Units)

Page 26 of 37
American National Standard SJI 200 - 2015
TABLE 5.4-1
STANDARD STANDARD MINIMUM MINIMUM
GENERAL DESCRIPTION OF CJ-SERIES JOIST BEARING CLEAR BEARING BEARING
TOP CHORD SEAT BEARING PLATE LENGTH ON
DEPTH LENGTH WIDTH STEEL
Where round web end bars are used and the top chord 2½” 4” 6” 2½”
vertical angle leg is less than or equal to 2” (64 mm) (102 mm) (178 mm) (64 mm)
Where the top chord vertical angle leg is greater than 2”, 5” 6” 9” 4”
but less than 31/2” (127 mm) (152 mm) (229 mm) (102 mm)
Where the top chord vertical angle leg is greater than or 7½” 6” 14” 6”
equal to 31/2” (191 mm) (152 mm) (356 mm) (152 mm)

If the specifying professional requires the end reaction to be located at a distance from the face of support more than the
standard clear bearing length values shown in Table 5.4-1 minus 2 in. (51 mm), the structural drawings shall indicate the
required special location of the end reaction. The CJ-Series joist seat depth shall be increased proportionately.

5.4.1 Masonry and Concrete

5.4.1.1 Scope: CJ-Series joists supported by masonry or concrete shall bear on steel bearing plates and shall be
designed as steel bearing. Consideration of the end reactions and all other vertical and lateral forces shall be taken by the
specifying professional in the design of the steel bearing plate and the masonry or concrete.

The ends of CJ-Series joists shall extend over the masonry or concrete support as shown in Figure 5.2-1 and be
anchored to a steel bearing plate.

The steel bearing plate shall be located not more than ½ inch (13 mm) from the face of the wall. If the steel bearing plate
is located more than ½ inch (13 mm) from the face of the wall, or the minimum bearing over the masonry or concrete
support cannot be provided as given in Table 5.4-1, special consideration shall be given to the design of the steel bearing
plate and the masonry or concrete by the specifying professional.

The steel bearing plate is to be designed by the specifying professional and shall be furnished by other than the joist
manufacturer.

5.4.1.2 Anchorage: CJ-Series joists shall be anchored to the steel bearing plate per Section 5.7.

5.4.1.3 Composite Joist Bearing Seat

For 2½” ≤ Seat Depth < 5”:


a) The ends of CJ-Series joists shall extend a distance of not less than 4 inches (102 mm) over the masonry or
concrete support and be anchored to the steel bearing plate.
b) The width of the plate perpendicular to the span of the CJ-Series joist shall be not less than 6 inches (152
mm).
c) The CJ-Series joist shall bear a minimum of 2½ inches (64 mm) on the steel bearing plate.

For 5” ≤ Seat Depth < 7½”:


a) The ends of CJ-Series joists shall extend a distance of not less than 6 inches (152 mm) over the masonry or
concrete support and be anchored to the steel bearing plate.
b) The width of the plate perpendicular to the span of the CJ-Series joist shall be not less than 9 inches (229
mm).
c) The CJ-Series joist shall bear a minimum of 4 inches (102 mm) on the steel bearing plate.

Page 27 of 37
American National Standard SJI 200 - 2015
For Seat Depth ≥ 7½”:
a) The ends of CJ-Series joists shall extend a distance of not less than 6 inches (152 mm) over the masonry or
concrete support and be anchored to the steel bearing plate.
b) The width of the plate perpendicular to the span of the CJ-Series joist shall be not less than 14 inches (356
mm).
c) The CJ-Series joist shall bear a minimum of 6 inches (152 mm) on the steel bearing plate.

5.4.2 Steel

5.4.2.1 Scope: CJ-Series joists supported directly by steel supporting members shall be designed as steel bearing.

User Note: Due consideration of the end reactions and all other vertical and lateral forces shall be taken by the
specifying professional in the design of the steel support.

5.4.2.2 Anchorage: CJ-Series joists shall be anchored to steel supporting members per Section 5.7.

5.4.2.3 CJ-Series Joist Bearing Seat

For 2½” ≤ Seat Depth < 5”: The ends of CJ-Series joists shall extend a distance of not less than 2½ inches (64 mm)
over the steel supports.

For 5” ≤ Seat Depth < 7½”: The ends of CJ-Series joists shall extend a distance of not less than 4 inches (102 mm)
over the steel supports.

For Seat Depth ≥ 7½”: The ends of CJ-Series joists shall extend a distance of not less than 6 inches (152 mm) over
the steel supports.

Where deemed necessary to butt opposite joists over a narrow steel support with bearing less than that noted above,
special ends shall be specified, and such ends shall have positive attachment to the support, either by bolting or welding.

5.5 BRIDGING OR BRACING

CJ-Series joist top and bottom chord bridging shall be required and shall consist of one or both of either horizontal or
diagonal bridging.

User Note: See Section 5.12 for bridging or bracing required for uplift forces.

5.5.1 Horizontal Bridging


Horizontal bridging lines shall consist of continuous horizontal steel members. The /r ratio of the bridging member shall
not exceed 300, where  is the distance in inches (mm) between attachments and r is the least radius of gyration of the
bridging member.

5.5.2 Diagonal Bridging


Diagonal bridging lines shall consist of cross-bracing with an /r ratio of not more than 200, where  is the distance in
inches (mm) between connections and r is the least radius of gyration of the bracing member. Where cross-bracing
members are connected at their point of intersection, the  distance shall be taken as the distance in inches (mm)
between connections at the point of intersection of the bridging members and the connections to the chords of the CJ-
Series steel joists.

Page 28 of 37
American National Standard SJI 200 - 2015
5.5.2.1 Diagonal Erection Bridging
User Note: CJ-Series joists exhibit varying degrees of stability dependent upon the span, depth, member
sizes, self-weight and other parameters. Bolted diagonal Erection Bridging which must be installed prior
to releasing hoisting cables may be required.

Where required, bolted diagonal Erection Bridging shall be provided in accordance with the following:
a) For CJ-Series joist spans up through and including 60 feet (18.3 m) in length, welded horizontal bridging shall be
permitted to be used except where the row of bridging nearest the center is required to be bolted diagonal
Erection Bridging as indicated on the joist manufacturer’s joist placement plans.

The stability of the CJ-Series joist and the need for Erection Bridging shall be determined using Equation 5.5-1.

Erection Bridging is required if,


wu
≤ 1.00 (5.5-1)
wactual
Where:

wactual = CJ-Series joist self-weight, plf (kN/m)


W  12 plf W (kN/m)
wu = ultimate lateral buckling load, wu  wu 
L L
b  b2  4  a  c
W
2a
2
 2  3 
a   

 24 

2  3 2  4   E  I y
4
  2  3  yo 
b  P     x    

2  k  L 
3
12 16   24  2 
2
22  4  4  E  I y   2  4  4  E  Cw  2  G  J 
c  P  
 
  2  k  L 3   P    x   ae    
 2  k  L  2  k  L 
3
 16    16

Ab = area of non-composite joist bottom chord, in.2 (mm2)

At = area of non-composite joist top chord, in.2 (mm2)

d e  I yb  I yt
2
Cw = warping constant Cw 
Iy
E = modulus of elasticity = 29,000,000 psi (200,000 MPa)
G = shear modulus, psi (MPa) G  0.385E
I x  At y 2  Ab d e  y 
2
Ix = non-composite joist moment of inertia about x-axis, in.4 (mm4)

Iy = joist moment of inertia about y-axis, in.4 (mm4) I y  I yt  I yb


I yb = bottom chord moment of inertia about y-axis, in.4 (mm4)

I yt = top chord moment of inertia about y-axis, in.4 (mm4)

Page 29 of 37
American National Standard SJI 200 - 2015

J = St. Venant torsion constant, in.4 (mm4) J


1
3
 At  tt 2  Ab  tb 2 

L = joist span, in. (mm)


P = factored weight of erector = 1.2 x (assumed weight of 250 lbs.) = 300 lbs (1334 N)
ae = vertical location of load P from shear center (locate at non-composite joist center of gravity), in.
(mm), where ae  yo

x 1
x  Ab   d e  y   At  y 3   2  yo
3
= cross-sectional parameter
Ix  

de = non-composite joist effective depth, in.(mm) de  d  yt  yb


k = effective length factor = 0.85
tb = thickness of top chord, in. (mm)
tt = thickness of top chord, in. (mm)
Ab  d e
y = distance from centroid of top chord to centroid of cross section, in. (mm) y
At  Ab
I d
yo = distance from centroid of cross section to shear center, in. (mm) yo   y  yb e
Iy
yt = neutral axis of non-composite joist top chord, in. (mm)
yb = neutral axis of non-composite joist bottom chord, in. (mm)

b) For joist spans over 60 feet (18.3 meters) all rows of bridging shall be diagonal bridging with bolted connections at
the chords and intersections as indicated on the joist manufacturer’s joist placement plans. Where the CJ-Series
joist spacing is less than 0.70 x joist depth, bolted horizontal bridging shall be used in addition to bolted diagonal
Erection Bridging.

c) The bolted diagonal Erection Bridging determined by Section 5.5.2 shall be considered a minimum. This bolted
diagonal Erection Bridging shall be indicated on the joist manufacturer’s joist placement plans.

5.5.3 Quantity and Spacing of Bridging

5.5.3.1 Scope: Bridging shall be properly spaced and anchored to support the metal decking and the employees prior to
the attachment of the deck to the top chord. The maximum spacing between lines of bridging, brmax shall be the lesser of,
 dj 
 brmax  100  0.67 d j  40  ry , in. (5.5-2a)
 L

 dj 
 brmax  100  0.026 d j  0.48  ry , mm (5.5-2b)
 L
or,
brmax  170 ry (5.5-3)

Where:
dj = CJ-Series joist depth, in. (mm)
L = CJ-Series joist span length, ft. (m)
ry = radius of gyration of the top chord about the vertical axis of the joist cross section, in. (mm)

Page 30 of 37
American National Standard SJI 200 - 2015
5.5.3.2 Number of Rows: The number of rows of bottom chord bridging, including bridging required per Section 5.12,
shall not be less than the number of top chord rows. Rows of bottom chord bridging shall be permitted to be spaced
independently of rows of top chord bridging. The spacing of rows of bottom chord bridging shall meet the slenderness
requirement of Section 4.3 and any specified strength requirements.

5.5.4 Sizing of Bridging

Horizontal and diagonal bridging shall be capable of resisting the nominal unfactored horizontal compressive force, P br
given in Equation 5.5-4.
Pbr = 0.0025 n At Fconstruction , kips (N) (5.5-4)
Where:
n = 8 for horizontal bridging
n = 2 for diagonal bridging
At = cross-sectional area of joist top chord, in.2 (mm2)
Fconstruction = assumed ultimate stress in top chord to resist construction loads, determined in accordance
with the following:
2 E (5.5-5a)
Fconstruction  2
 12.2 ksi
 0.9  brm ax 
 
 r 
 y 
2 E (5.5-5b)
Fconstruction  2
 84.1 MPa
 0.9  brm ax 
 
 ry 
 
Where:
E = modulus of elasticity = 29,000 ksi (200,000 MPa)

and brmax is determined from Equations 5.5-2 or 5.5-3


ry

5.5.5 Connections

Connections to the CJ-Series joist chords shall be made by welding or mechanical means and shall be capable of
resisting the unfactored or nominal horizontal force, Pbr, of Equation 5.5-4 but not less than 700 pounds (3114 N).

5.5.6 Bottom Chord Bearing CJ-Series Joists

Where bottom chord bearing CJ-Series joists are utilized, a row of diagonal bridging shall be provided near the support(s).
This bridging shall be installed and anchored before the hoisting cable(s) is released.

5.6 INSTALLATION OF BRIDGING

Bridging shall be provided to support the top chord of CJ-Series joists during installation of the metal decking prior to the
attachment of the deck to the top chord. All bridging and bridging anchors shall be completely installed before construction
loads are placed on the CJ-Series joists. Bridging shall support the top and bottom chords against lateral movement
during the construction period and shall hold the CJ-Series joists in the approximate position as shown on the joist
placement plans. The ends of all bridging lines terminating at walls or beams shall be anchored thereto.

Page 31 of 37
American National Standard SJI 200 - 2015
5.7 BEARING SEAT ATTACHMENTS

5.7.1 Masonry and Concrete

Ends of CJ-Series steel joists resting on steel bearing plates on masonry or structural concrete shall be attached as
defined by the following criteria:
For 2½” ≤ Seat Depth < 5”: With a minimum of two 1/8 inch (3 mm) fillet welds 2 inches (51 mm) long, or with two ½
inch (13 mm) ASTM A307 bolts, or with the equivalent.

For Seat Depth ≥ 5”: With a minimum of two ¼ inch (6 mm) fillet welds 2 inches (51 mm) long, or with two 3/4 inch (19
mm) ASTM A307 bolts or the equivalent.

5.7.2 Steel

Ends of CJ-Series joists resting on steel supports shall be attached as defined by the following criteria:
For 2½” ≤ Seat Depth < 5”: With a minimum of two 1/8 inch (3 mm) fillet welds 2 inches (51 mm) long, or with two ½
inch (13 mm) ASTM A307 bolts, or with the equivalent.

For Seat Depth ≥ 5”: With a minimum of two ¼ inch (6 mm) fillet welds 2 inches (51 mm) long, or with two 3/4 inch (19
mm) ASTM A307 bolts, or with the equivalent.

In steel frames, where columns are not framed in at least two directions with solid structural steel members, CJ-Series
joists at column lines shall be field bolted and the joist bottom chords shall be restrained by a vertical stabilizer plate
attached to the column providing lateral stability during construction. Where constructability does not allow a CJ-Series
joist to be installed directly at the column, an alternate means of stabilizing the joist shall be installed on both sides near
the column (CFR). When CJ-Series joists are used to provide lateral stability to the supporting member, the final
connection shall be made by welding or as designated by the specifying professional.

5.7.3 Uplift

Where uplift forces are a design consideration, CJ-Series joists used in roof applications shall be anchored to resist such
forces and shall meet the requirements of Section 5.12.

5.8 JOIST SPACING

CJ-Series joists shall be spaced so that the loading on each joist does not exceed the design load (LRFD).

5.9 DECKS

5.9.1 Material

Floor deck shall consist of steel deck or other suitable material capable of supporting the required load at the specified
CJ-Series joist spacing.

5.9.2 Thickness

Cast-in-place slabs shall be not less than 2 inches (51 mm) thick.

5.9.3 Centering

Centering for cast-in-place slabs shall be permitted to be a suitable material capable of supporting the slab at the
designated CJ-Series joist spacing.

Centering shall not cause lateral displacement or damage to the top chord of CJ-Series joists during installation or
removal of the centering or placing of the concrete.
Page 32 of 37
American National Standard SJI 200 - 2015

5.9.4 Bearing

Slabs or decks shall bear uniformly along the top chords of the CJ-Series joists.

5.9.5 Attachments

The decking shall be attached per Steel Deck Institute requirements prior to placing construction loads on the CJ-Series
joists. The spacing of attachments along the CJ-Series joist top chord shall not exceed 36 inches (914 mm).

5.10 DEFLECTION

The deflection due to the design live load shall not exceed the following:
Floors: 1/360 of span
Roofs: 1/360 of span where a plaster ceiling is attached or suspended, or 1/240 of span for all other cases.

The specifying professional shall give consideration to the effects of deflection and vibration in the selection of CJ-Series
steel joists.

User Note: For further information on vibration, refer to Steel Joist Institute Technical Digest 5, “Vibration
of Steel Joist-Concrete Slab Floors".

5.11 PONDING

The ponding investigation shall be performed by the specifying professional.

User Note: For further reference, refer to Steel Joist Institute Technical Digest 3, “Structural Design of Steel Joist Roofs to
Resist Ponding Loads” and AISC 360.

5.12 UPLIFT

Where uplift forces due to wind are a design requirement, these forces shall be indicated on the structural drawings in
terms of net uplift in pounds per square foot (Pascals). When these forces are specified, they shall be considered in the
design of CJ-Series steel joists, and required bridging or bracing. A single line of bottom chord bridging shall be provided
near the first bottom chord panel points wherever uplift due to wind forces is a design consideration.

User Note: For further reference, refer to Steel Joist Institute Technical Digest 6, “Structural Design of
Steel Joist Roofs to Resist Uplift Loads”.

5.13 DIAPHRAGMS AND COLLECTORS

Where diaphragm collector forces due to wind or seismic forces are a design requirement, these nominal (unfactored)
forces shall be indicated on the structural drawings. The structural drawings shall also indicate the Seismic Design
Category, and the Seismic Force Resisting System type, and applicable seismic design coefficients. When this data is
specified, joist collectors or chords in horizontal diaphragm systems, shall be designed in conformance with the provisions
of Section 4 through Section 6. End connections and splices in CJ-Series steel joists incorporated into Seismic Force
Resisting System (SFRS) as horizontal diaphragms as collectors or chords shall adhere to the requirements stipulated by
the applicable building code.

5.14 INSPECTION

CJ-Series joists shall be inspected by the manufacturer before shipment to verify compliance of materials and
workmanship with the requirements of this Specification.

Page 33 of 37
American National Standard SJI 200 - 2015
User Note: If the purchaser requires an inspection of the CJ-Series joists by someone other than the
manufacturer's own inspectors, they shall be permitted to reserve the right to do so in their "Invitation to
Bid" or the accompanying "Job Specifications". Arrangements shall be made with the manufacturer for
such inspection of the CJ-Series joists at the manufacturing facility by the purchaser's inspectors at
purchaser's expense.

SECTION 6
ERECTION STABILITY
AND HANDLING
As a minimum, erection stability and handling of CJ-Series steel joists shall meet the requirements of this Section 6.

User Note: Additional requirements for erection of CJ-Series steel joists can be found in Steel Joist
Institute Technical Digest 9, “Handling and Erection of Steel Joists and Joist Girders”.

6.1 STABILITY REQUIREMENTS

User Note: It is not recommended that an erector climb on unbridged joists, extreme caution shall be
exercised since unbridged joists exhibit some degree of instability under the erector's weight.

a) In steel framing, where CJ- Series joists are utilized at column lines, the CJ-Series joists shall be field-bolted at
the column. Before hoisting cables are released and before an employee is allowed on the CJ-Series joists the
following conditions shall be met:
1) The seat at each end of the CJ-Series joists is attached in accordance with Section 5.7. Where a bolted seat
connection is used for erection purposes, as a minimum, the bolts shall be snug tightened. The snug tight
condition shall be defined as the tightness that exists where all plies of a joint are in firm contact. This shall be
attained by a few impacts of an impact wrench or the full effort of an employee using an ordinary spud
wrench.

2) Where stabilizer plates are required the CJ-Series joists bottom chord shall engage the stabilizer plate.

During the construction period, the contractor shall provide means for the adequate distribution of loads so that
the carrying capacity of any CJ-Series joist is not exceeded.

b) Before an employee is allowed on the CJ-Series joist both ends of CJ-Series joist at columns shall be attached to
its supports. For all other CJ-Series joists a minimum of one end shall be attached before the employee is allowed
on the CJ-Series joist. The attachment shall be in accordance with Section 5.7.

Where a bolted seat connection is used for erection purposes, as a minimum, the bolts shall be snug tightened.
The snug tight condition shall be defined as the tightness that exists where all plies of a joint are in firm contact.
This shall be attained by a few impacts of an impact wrench or the full effort of an employee using an ordinary
spud wrench.

c) On CJ-Series joists that do not require Erection Bridging as determined by Section 5.5.2.1 or as shown on the
joist placement plans, only one employee shall be allowed on the CJ-Series joist until all bridging is installed and
anchored.

d) Where the span of the CJ-Series joist is such that one row of Erection Bridging nearest the midspan is required in
accordance with Section 5.5.2.1 or as indicated on the joist placement plans, the following shall apply:
1) Hoisting cables shall not be released until this bolted diagonal Erection Bridging row is installed and
anchored, unless an alternate method of stabilizing the joist has been provided; and

Page 34 of 37
American National Standard SJI 200 - 2015
2) No more than one employee shall be allowed on these spans until all other bridging is installed and anchored.

e) Where the span of the CJ-Series steel joist exceeds 60’-0” (18228 mm and is less than or equal to 100’-0” (30175
mm), the following shall apply:
1) All rows of bridging shall be bolted diagonal bridging; and
2) Hoisting cables shall not be released until the two rows of bolted diagonal Erection Bridging nearest the third
points of the CJ-Series joist are installed and anchored; and
3) No more than two employees shall be allowed on these spans until all other bridging is installed and
anchored.

f) Where the span of the CJ-Series joist exceeds 100’-0” (30175 mm), the following shall apply:
1) All rows of bridging shall be bolted diagonal bridging; and
2) Hoisting cables shall not be released until all rows of bolted diagonal Erection Bridging is installed and
anchored; and
3) No more than two employees shall be allowed on these spans until all other bridging is installed and
anchored.

g) Where permanent bridging terminus points cannot be used during erection, additional temporary bridging
terminus points shall be required to provide lateral stability.

h) In the case of bottom chord bearing CJ-Series joists, the ends of the CJ-Series joist shall be restrained laterally
per Section 5.5.6 before releasing the hoisting cables.

i) After the CJ-Series joist is straightened and plumbed, and all bridging is completely installed and anchored, the
ends of the CJ-Series joists shall be fully connected to the supports in accordance with Section 5.7.

6.2 LANDING AND PLACING LOADS

a) Except as stated in Section 6.2(d), no "construction loads” shall be allowed on the CJ-Series joists until all
bridging is installed and anchored, and all joist bearing ends are attached.

User Note: For the definition of “construction load” see the Federal Register, Department of Labor,
Occupational Safety and Health Administration (2001), 29 CFR Part 1926 Safety Standards for Steel
Erection; Final Rule, §1926.757 Open Web Steel Joists - January 18, 2001, Washington, D.C.

b) During the construction period, loads placed on the CJ-Series joists shall be distributed so as not to exceed the
capacity of the CJ-Series joists.

c) The weight of a bundle of CJ-Series steel bridging shall not exceed a total of 1000 pounds (454 kilograms). The
bundle of joist bridging shall be placed on a minimum of three CJ-Series joists that are secured at one end. The
edge of the bridging bundle shall be positioned within 1 foot (0.30 m) of the secured end.

d) No bundle of metal deck shall be placed on CJ-Series joists until all bridging has been installed and anchored and
all joist bearing ends attached, unless the following conditions are met:
1) The contractor has first determined from a “qualified person” and documented in a site-specific erection plan
that the structure or portion of the structure is capable of supporting the load;
2) The bundle of metal decking is placed on a minimum of three CJ-Series joists;
3) The CJ-Series joists supporting the bundle of metal decking are attached at both ends;
4) At least one row of bridging is installed and anchored;
5) The total weight of the metal decking does not exceed 4000 pounds (1816 kilograms); and
6) The edge of the bundle of metal decking is placed within 1 foot (0.30 meters) of the bearing surface of the CJ-
Series joist end.
Page 35 of 37
American National Standard SJI 200 - 2015

User Note: For the definition of “qualified person” see the Federal Register, Department of Labor,
Occupational Safety and Health Administration (2001), 29 CFR Part 1926 Safety Standards for Steel
Erection; Final Rule, §1926.757 Open Web Steel Joists - January 18, 2001, Washington, D.C.

e) The edge of the construction load shall be placed within 1 foot (0.30 meters) of the bearing surface of the CJ-
Series joist end.

6.3 FIELD WELDING

All field welding shall be performed in accordance with the structural drawings. Field welding shall not damage the CJ-
Series joists.

On cold-formed steel members whose yield strength has been attained by cold working, and whose as-formed strength is
used in the design, the total length of weld at any one point shall not exceed 50 percent of the overall developed width of
the cold-formed section.

6.4 HANDLING

Particular attention shall be considered for the handling and erection of CJ-Series joists. Damage to the CJ-Series joists
and accessories shall be avoided. Hoisting cables shall be attached at panel point locations and those locations shall be
selected to minimize erection stresses.

Each CJ-Series steel joist shall be adequately braced laterally before any loads are applied. If lateral support is provided
by bridging, the bridging lines as defined in Section 6.1(c), 6.1(d), 6.1(e), and 6.1(f) shall be anchored to prevent lateral
movement.

6.5 FALL ARREST SYSTEMS

CJ-Series joists shall not be used as anchorage points for a fall arrest system unless written direction to do so is obtained
from a “qualified person”.

User Note: For the definition of “qualified person” see the Federal Register, Department of Labor,
Occupational Safety and Health Administration (2001), 29 CFR Part 1926 Safety Standards for Steel
Erection; Final Rule, §1926.757 Open Web Steel Joists - January 18, 2001, Washington, D.C.

SECTION 7
SHEAR CONNECTOR
PLACEMENT AND WELDING
a) Shear connectors required on each side of the point of maximum positive or negative bending moment, shall be
distributed uniformly between that point and the adjacent points of zero moment, unless otherwise specified.
However the number of shear connectors placed between any concentrated load and the nearest point of zero
moment shall be sufficient to develop the maximum moment required at the concentrated load point.
b) Studs shall be alternately placed on each chord angle section for double angle top chords. When constructability
does not allow this to occur, stud placement shall be limited as follows:
1) No more than three studs shall be placed consecutively on any one chord angle, and
2) No more than 60 percent of the total number of studs shall be placed on any one chord angle.

Studs shall have a minimum of ½ inch (13 mm) concrete cover over the head of each stud (see Section 4.5.4).

Page 36 of 37
American National Standard SJI 200 - 2015
c) The minimum center-to-center spacing of stud connectors shall be six stud diameters along the longitudinal axis
of the supporting CJ-Series joist, except that within the ribs of formed metal decks oriented perpendicular to the
CJ-Series joists, the minimum center-to-center spacing shall be four stud diameters in any direction.
d) The distance measured along the longitudinal axis of the CJ-Series joist from the free edge of the concrete slab to
the first stud shall not be less than the deck height plus four stud diameters.
e) The spacing of stud shear connectors along the length of the supporting CJ-Series joist shall not exceed eight
times the slab depth or 36 inches (914 mm).
f) To resist uplift, the metal deck shall be anchored to all supporting members at a spacing not to exceed 18 inches
(460 mm). Such anchorage shall be provided by stud connectors, a combination of stud connectors and arc spot
(puddle) welds, or other devices.

SECTION 8
SPECIAL CASES
When a method of shear transfer is used other than headed shear studs for developing composite joist behavior, the
strength of shear connectors and details of composite construction shall be established by a test program that has been
submitted to and accepted by the SJI.

Page 37 of 37

S-ar putea să vă placă și