Documente Academic
Documente Profesional
Documente Cultură
28.1
28.2 2001 ASHRAE Fundamentals Handbook
load establishes the size of the fan-coil and air distribution system In application, the area of each window is multiplied by the
for each apartment. One of the methods discussed in Chapter 29 appropriate GLF. The effects of permanent outside shading devices
may be used to calculate the block load. should be considered separately in determining the cooling load.
Shaded glass is considered the same as north-facing glass. The
Indoor Temperature Swing shade line factor (SLF) is the ratio of the distance a shadow falls
For hour-by-hour load calculations, allowing for a swing in beneath the edge of an overhang to the width of the overhang (Table
indoor temperature results in lower peak loads. Because the indoor 6). Therefore, assuming the overhang is at the top of the window, the
temperature does swing, such an allowance gives a more reasonable shade line equals the SLF times the overhang width. The shaded and
equipment capacity. The tables in this section are based on an sunlit glass areas may then be computed separately. The tabulated
assumed indoor temperature swing of no more than 3°F on a design values are the average of the shade line values for 5 h of maximum
day, when the residence is conditioned 24 h per day and the thermo- solar intensity on each wall orientation shown. Northeast- and
stat is set at 75°F. northwest-facing windows are not effectively protected by roof
overhangs; in most cases, they should not be considered shaded.
Cooling Load Due to Heat Gain Through Structure
Infiltration
The sensible cooling load due to heat gains through the walls,
floor, and ceiling of each room is calculated using appropriate Natural air leakage in residential structures is less in summer
cooling load temperature differences (CLTDs) (Tables 1 and 2) than in winter, largely because wind velocities are lower in most
and U-factors for summer conditions. For ceilings under naturally localities. The data in Tables 7 and 8 showing space air changes per
vented attics or beneath vented flat roofs, the combined U-factor hour (ACH) apply to both single- and multifamily housing,
for the roof, vented space, and ceiling should be used. The mass of
the walls is a variable in Table 2 and is important in calculating Table 2 CLTD Values for Multifamily Residencesa
energy use, but it is not used in Table 1 because of the averaging Design Temperature, °F
technique required to develop the CLTDs. Values in Tables 1 and 2 85 90 95 100 105 110
assume a dark color because color is an unpredictable variable in Daily Temperature
Rangeb L M L M H L M H M H M H
any residence.
Daily range (outdoor temperature swing on a design day) signif- Walls and doorsc
icantly affects the equivalent temperature difference. Tables 1 and 2 Light 14 11 19 16 12 24 21 17 26 22 27 32
list daily temperature ranges classified as high, medium, and low. N Medium 13 10 18 15 11 23 20 16 25 21 26 31
Tables 1, 2, and 3 in Chapter 27 list outdoor daily ranges of dry-bulb Heavy 9 6 15 11 7 20 16 12 21 17 22 27
temperature for different locations. Light 23 17 28 22 17 33 27 22 32 26 31 36
NE Medium 20 15 25 20 16 30 25 21 29 25 29 34
Cooling Load Due to Heat Gain Through Windows Heavy 16 12 21 17 13 26 22 18 26 22 26 31
Light 32 27 37 32 27 43 38 32 42 37 42 47
Direct application of procedures for calculating cooling load due E Medium 30 24 34 29 24 40 34 29 39 33 39 44
to heat gain for flat glass (discussed in Chapters 29 and 30) results Heavy 23 18 28 23 18 34 29 23 33 28 33 38
in unrealistically high cooling loads for residential installations.
Light 31 27 35 31 26 41 37 31 42 37 42 47
Window glass load factors (GLFs), modified for single- and mul-
SE Medium 28 22 32 27 22 37 32 27 37 33 38 43
tifamily residential cooling load calculations and including solar
Heavy 21 16 26 22 17 32 27 22 31 27 32 37
heat load plus air-to-air conduction, are given in Tables 3 and 4.
Table 5 lists the shading coefficients (SCs) and U-factors used to Light 25 22 29 26 22 35 31 26 36 32 37 43
compile Tables 3 and 4. S Medium 22 18 26 22 18 31 26 22 31 27 32 38
Heavy 16 11 20 16 12 26 21 17 26 21 27 33
Table 1 CLTD Values for Single-Family Detached Residencesa Light 39 36 44 40 35 50 46 40 51 47 52 58
SW Medium 33 29 37 34 29 44 40 35 45 40 46 52
Design Temperature, °F Heavy 23 18 28 24 19 36 31 25 35 30 36 42
Daily Temperature 85 90 95 100 105 110 Light 44 41 48 45 40 54 51 46 56 52 57 63
Rangeb L M L M H L M H M H M H W Medium 37 33 41 38 33 46 42 38 48 43 49 55
All walls and doors Heavy 26 22 31 27 23 37 32 27 37 32 38 44
North 8 3 13 8 3 18 13 8 18 13 18 23 Light 33 30 37 34 30 43 39 34 44 40 45 50
NW Medium 28 25 32 29 24 37 33 29 39 35 40 45
NE and NW 14 9 19 14 9 24 19 14 24 19 24 29
Heavy 20 16 25 20 16 31 26 21 31 26 32 37
East and West 18 13 23 18 13 28 23 18 28 23 28 33
Roof and ceiling
SE and SW 16 11 21 16 11 26 21 16 26 21 26 31
Attic or Light 58 53 65 60 55 70 65 60 70 65 72 77
South 11 6 16 11 6 21 16 11 21 16 21 26 flat built-up
Roofs and ceilings Flat built-up Medium 21 18 23 21 18 25 23 21 25 23 25 28
Attic or flat built-up 42 37 47 42 37 51 47 42 51 47 51 56 or heavy
Floors and ceiling
Floors and ceilings
Under or over 9 4 12 9 4 14 12 9 14 12 14 19
Under conditioned 9 4 12 9 4 14 12 9 14 12 14 19 unconditioned space,
space, over unconditioned crawl space
room, or over crawl space
Partitions
Partitions
Inside or shaded 9 4 12 9 4 14 12 9 14 12 14 19
Inside or shaded 9 4 12 9 4 14 12 9 14 12 14 19 a Cooling load temperature differences (CLTDs) for multifamily low-rise or single-
a Cooling load temperature differences (CLTDs) for single-family detached houses, family detached if zoned with separate temperature control for each zone, °F.
duplexes, or multifamily, with both east and west exposed walls or only north and b L denotes low daily range, less than 16 °F; M denotes medium daily range, 16 to 25 °F;
south exposed walls, °F. and H denotes high daily range, greater than 25 °F.
b L denotes low daily range, less than 16 °F; M denotes medium daily range, 16 to 25 °F; cLight denotes lightweight; medium denotes medium-weight; and heavy denotes
and H denotes high daily range, greater than 25°F. heavyweight construction.
Residential Cooling and Heating Load Calculations 28.3
Table 3 Window Glass Load Factors (GLFs) for Single-Family Detached Residencesa
Regular Regular Heat-Absorbing Clear Triple
Single Glass Double Glass Double Glass Glass
Design
Temperature, °F 85 90 95 100 105 110 85 90 95 100 105 110 85 90 95 100 105 110 85 90 95
No inside shading
North 34 36 41 47 48 50 30 30 34 37 38 41 20 20 23 25 26 28 27 27 30
NE and NW 63 65 70 75 77 83 55 56 59 62 63 66 36 37 39 42 44 44 50 50 53
East and West 88 90 95 100 102 107 77 78 81 84 85 88 51 51 54 56 59 59 70 70 73
SE and SWb 79 81 86 91 92 98 69 70 73 76 77 80 45 46 49 51 54 54 62 63 65
South b 53 55 60 65 67 72 46 47 50 53 54 57 31 31 34 36 39 39 42 42 45
Horizontal skylight 156 156 161 166 167 171 137 138 140 143 144 147 90 91 93 95 96 98 124 125 127
Draperies, venetian blinds, translucent roller shades, fully drawn
North 18 19 23 27 29 33 16 16 19 22 23 26 13 14 16 18 19 21 15 16 18
NE and NW 32 33 38 42 43 47 29 30 32 35 36 39 24 24 27 29 29 32 28 28 30
East and West 45 46 50 54 55 59 40 41 44 46 47 50 33 33 36 38 38 41 39 39 41
SE and SWb 40 41 46 49 51 55 36 37 39 42 43 46 29 30 32 34 35 37 35 36 38
Southb 27 28 33 37 38 42 24 25 28 31 31 34 20 21 23 25 26 28 23 24 26
Horizontal skylight 78 79 83 86 87 90 71 71 74 76 77 79 58 59 61 63 63 65 69 69 71
Opaque roller shades, fully drawn
North 14 15 20 23 25 29 13 14 17 19 20 23 12 12 15 17 17 20 13 13 15
NE and NW 25 26 31 34 36 40 23 24 27 30 30 33 21 22 24 26 27 29 23 23 26
East and West 34 36 40 44 45 49 32 33 36 38 39 42 29 30 32 34 35 37 32 32 35
SE and SWb 31 32 36 40 42 46 29 30 33 35 36 39 26 27 29 31 32 34 29 29 31
Southb 21 22 27 30 32 36 20 20 23 26 27 30 18 19 21 23 24 26 19 20 22
Horizontal skylight 60 61 64 68 69 72 57 57 60 62 63 65 52 52 55 57 57 59 56 57 59
aGlass load factors (GLFs) for single-family detached houses, duplexes, or multifam- To obtain GLF for other combinations of glass and/or inside shading: GLFa =
ily residences, with both east and west exposed walls or only north and south (SCa/SCt)(GLFt − UtDt) + UaDt , where the subscripts a and t refer to the alternate
exposed walls, Btu/h·ft2. and table values, respectively. SCt and Ut are given in Table 5. Dt = (ta − 75),
bCorrect by +30% for latitude of 48 ° and by −30% for latitude of 32°. Use linear where ta = to − (DR/2); to is the outdoor design temperature and DR is the daily
interpolation for latitude from 40 to 48 and from 40 to 32°. range.
although most of the raw data were for single-family structures Household Appliances
(McQuiston 1984). Construction may be defined as follows:
Appliance loads are concentrated mainly in the kitchen and laundry
Tight. Good multifamily construction with close-fitting doors, areas. Based on contemporary living conditions in single-family
windows, and framing is considered tight. New houses with full houses, a sensible load of 1600 Btu/h should be divided between the
vapor retarder, no fireplace, well-fitted windows, weather- kitchen and/or laundry and the adjoining room or rooms. A sensible
stripped doors, one story, and less than 1500 ft2 floor area fall into utility load of 1600 Btu/h may be added if the laundry room contains
this category. continuously operating appliances such as refrigerators and/or freez-
Medium. Medium structures include new, two-story frame ers. For multifamily units, the sensible heat gain values should be about
houses or one-story houses more than 10 years old with average 1200 Btu/h. These values assume that the cooking range and clothes
maintenance, a floor area greater than 1500 ft2, average fit windows dryer are vented. Further allowances should be considered when
and doors, and a fireplace with damper and glass closure. Below- unusual lighting intensities, computers, or other equipment is present.
average multifamily construction falls in this category.
Loose. Loose structures are poorly constructed single- and mul- Air Distribution System—Heat Loss/Gain
tifamily residences with poorly fitted windows and doors. Examples Whenever the air distribution system is outside the conditioned
include houses more than 20 years old, of average maintenance, space (i.e., in attics, crawl spaces, or other unconditioned spaces)
having a fireplace without damper or glass closure, or having more heat loss or gains to the ducts or pipes must be included in the cal-
than an average number of vented appliances. Average manufac- culated load and should be considered in equipment selection.
tured homes are in this category.
Latent Heat Sources
Ventilation
The latent cooling load has three main sources: outdoor air, occu-
Residential air-conditioning systems may introduce outdoor pants, and miscellaneous sources, such as cooking, laundry, and
air, although it is not a code requirement in most localities. Posi-
tive ventilation should be considered, however, if the anticipated Table 7 Winter Air Exchange Rates (ACH) as
infiltration is less than about 0.5 ACH. When positive means of
Function of Airtightness
introducing outdoor air are used, controls, either manual or auto-
matic, should be provided, and an energy recovery device should Outdoor Design Temperature, °F
be considered. Class 50 40 30 20 10 0 −10 −20 −30 −40
Tight 0.41 0.43 0.45 0.47 0.49 0.51 0.53 0.55 0.57 0.59
Occupancy
Medium 0.69 0.73 0.77 0.81 0.85 0.89 0.93 0.97 1.00 1.05
Even though occupant density is low, occupancy loads should be Loose 1.11 1.15 1.20 1.23 1.27 1.30 1.35 1.40 1.43 1.47
estimated. Sensible heat gain per sedentary occupant is assumed to Note: Values are for 15 mph wind and indoor temperature of 68°F.
be 230 Btu/h. To prevent gross oversizing, the number of occupants
should not be overestimated. Recent census studies recommend that Table 8 Summer Air Exchange Rates (ACH) as
the total number of occupants be based on two persons for the first Function of Airtightness
bedroom, plus one person for each additional bedroom. The occu-
Outdoor Design Temperature, °F
pancy load should then be distributed equally among the living
areas because the maximum load occurs when most of the residents Class 85 90 95 100 105 110
occupy these areas. Tight 0.33 0.34 0.35 0.36 0.37 0.38
Medium 0.46 0.48 0.50 0.52 0.54 0.56
Table 5 Shading Coefficients and U-Factors Loose 0.68 0.70 0.72 0.74 0.76 0.78
for Residential Windows Note: Values are for 7.5 mph wind and indoor temperature of 75 °F.
Inside Shade
Drapery, Venetian
Blind, or Translucent Opaque Roller
None Roller Shade Shade
Glass Type SC U SC U SC U
Single 1.00 1.04 0.50 0.81 0.38 0.81
Double 0.88 0.61 0.45 0.55 0.36 0.55
Heat-absorbing 0.58 0.45 0.37 0.44 0.33 0.44
Triple 0.80 0.44 0.44 0.40 0.36 0.40
Note: U is in Btu/h·ft2 · °F.
bathing. The miscellaneous latent loads are largely covered by out- Doors. Solid core flush with all-glass storm doors (U = 0.32
door air because most residences have exhaust fans and clothes dry- Btu/h·ft2 ·°F).
ers that vent most of the moisture from these sources. This vent air is Outdoor design conditions. Temperature of 96°F dry bulb with a
accounted for in the infiltration calculation. McQuiston (1984) esti- 24°F daily range and a humidity ratio of 0.0136 lb vapor/lb dry air
(74.6°F wet bulb).
mated latent load factors for typical houses located in geographic U-factors for all external surfaces are based on a 7.5 mph wind
regions ranging from very dry to very wet using the transfer function velocity.
method (Figure 1). A latent factor LF (LF = 1/SHF) of 1.3 or a sen- Indoor design conditions. Temperature of 75°F dry bulb and 50% rh.
sible heat factor SHF (SHF = sensible load/total load) of 0.77 Occupancy. Four persons, based on two for the master bedroom and
matches the performance of typical residential vapor compression one for each additional bedroom. Assign to the living room.
cooling systems. Homes in almost all other regions of North America Appliances and lights. Assume 1600 Btu/h for the kitchen, and
have cooling loads with an SHF greater than 0.77 and latent factors assign 50% to the living room. Assume 1600 Btu/h for the utility room,
less than 1.3. Figure 1 may be used to estimate the total cooling load and assign 25% to the kitchen and 25% to the storage room.
by reading LF as a function of the design humidity ratio and airtight- The conditioning equipment is located in the garage, and the con-
struction of the house is considered medium.
ness. Then qtotal = (LF)qsensible. If the humidity ratio is less than 0.01, Find the sensible, latent, and total cooling load; size the cooling
set LF = 1.0. unit; and compute the air quantity for each room.
LOAD CALCULATION
The cooling load calculation procedures are summarized in
Table 9.
Doors q = Ud A(CLTD) Door CLTD values are in Tables 1 and 2 according to orientation, outdoor
design temperature, and design daily temperature range.
Above-grade exterior walls q = Uw A(CLTD) Wall CLTD values are in Tables 1 and 2 based on the outdoor design
temperature, daily range, and orientation.
Partitions to unconditioned space q = Up A∆t Where ∆t is the temperature difference across the partition.
Ceilings and roofs q = Ur A(CLTD) Tables 1 and 2 for CLTD, based on outdoor design temperature and daily range.
Exposed floors q = Uf A(CLTD) Tables 1 and 2 for CLTD, based on outdoor design temperature and daily range.
Internal loads— Plan 230 Btu/h per person. Divide occupants evenly among rooms not used as bedrooms. If number of
People, appliances, lights occupants is not known, assume two people for first bedroom and one person
for each additional bedroom.
The appliance and light load of 1600 Btu/h is divided between the kitchen and
adjoining room and the laundry and adjoining room. Use 1200 Btu/h for
multifamily units.
Total loads Total cooling load = LF × Load factors are from Figure 1 according to outdoor design humidity ratio and
(Sum of individual sensible airtightness classification.
cooling load components)
q = sensible cooling load, Btu/h Q = volumetric airflow rate, cfm
∆t = design temperature difference between outside and inside ACH = air changes per hour, 1/h
air, °F GLF = glass load factor, Btu/h·ft2
A = area of applicable surface, ft2 CLTD = cooling load temperature difference, °F
U = U-factors for appropriate construction, Btu/h·ft2 · °F LF = latent load multiplier
28.6 2001 ASHRAE Fundamentals Handbook
Solution: The cooling load must be made on a room-by-room basis to For the total sensible cooling load for these two rooms and the
determine the proper distribution of air. The calculations follow the cooling load for the remaining rooms, see Table 11. At this point, the
procedure outlined in the section on Load Components. sensible cooling load for the house is 19,679 Btu/h. Depending on the
Walls, roof, windows, and doors. The calculations for the living design of the air distribution system, heat losses from the supply and
room and the kitchen, where q = UA(CLTD) for the walls, roof, and return ducts may add to the cooling load. These may be more accu-
door and q = A(GLF) for the windows, are outlined in Table 10. The rately estimated after designing the system; however, to size the cool-
glass shaded by the overhang is treated as north-facing glass, with the ing unit, duct losses should be included initially. If all ducts are in the
shaded area computed using Table 6. attic space, a duct loss of l0% of the space sensible cooling load is rea-
Internal and infiltration sensible cooling loads. Compute as follows. sonable. For a counterflow system, with ducts below the slab, a 5%
For the living room: loss is more reasonable.
Infiltration. Using Table 8, An infiltration rate of 0.5 ACH may not be adequate for good indoor
Q = ACH (room volume)/60 air quality, so some outdoor air should be introduced. This additional
cooling load may be estimated in the same way as the infiltration load.
Q = 0.5 × 3840/60 = 32
Assume that the entire duct system is in the attic; that is, the total
q = 1.1Q(to − ti) = 1.1Q∆t
sensible cooling load with a 10% duct loss is 1.1 × 19,679 = 21,647
q = 1.1 × 32(96 − 75) = 740 Btu/h
Btu/h. Also, assume that additional outdoor air is needed to assure good
Occupants. Assuming 230 Btu/h per person,
indoor air quality, so the total infiltration and outdoor ventilation air is
q = 230 × (persons)
0.75 ACH. This increases the infiltration rate by 50%, or about 1600
q = 230 × 4 = 920 Btu/h Btu/h. The total sensible cooling load is then increased to 23,247 Btu/h
Appliances. Assuming that 50% of the kitchen appliance load is (Table 11).
picked up in the living room, The total cooling load (sensible plus latent) may be estimated by
q = 0.5 × (kitchen appliance load) applying the latent factor (LF) from Figure 1. For a design humidity
q = 0.5 × 1600 = 800 Btu/h ratio of 0.0136 lb vapor per lb dry air, LF = 1.15 for a house of medium
For the kitchen: construction. Hence, the total cooling load equals 1.15 × 23,247 =
Infiltration. 26,734 Btu/h.
Q = 0.5 × 1920/60 = 16 The load raises the temperature of the cooling air 18 to 21°F as it
q = 1.1 × 16(96 − 75) = 370 Btu/h leaves the rooms. The total design flow from the air conditioner can be
No occupants. estimated by the following equation:
q =0
Appliances. Assuming that 25% of the utility appliance load is q
Q tot = ------------- (1)
picked up in the kitchen, 1.1∆t
q = (1600/2) + (1600/4) = 1200 Btu/h where
Qtot = total airflow, cfm
Table 10 Transmission Cooling Load for Example 1 q = total sensible load, Btu/h
1.1 = density times specific heat of cooling air times 60 min/h
Net Cooling ∆t = temperature difference of air entering and leaving room, °F
Area, GLF, U-Factor, CLTD, Load,
Item ft 2 2 2
Btu/h·ft Btu/h·ft ·°F °F Btu/h Reference For a temperature difference of 18°F, the total airflow is estimated
from Equation (1) as
Living Room
West wall 91 0.06 24 131 Table 1 19,679
Q tot = ------------------- = 994 cfm
Partition 1.1 × 18
(garage) 192 0.07 12 161 Table 1 The exact design flow can be determined only after the cooling unit
Roof 480 0.05 48 1152 Table 1 has been selected. Then, the supply air quantities can be computed. Air
West door 21 0.32 24 161 Table 1 should be supplied to each room on the basis of the room sensible cool-
West glass 35 44 1540 Table 3 ing load:
Shaded glass 13 19 247 Table 3 Q rm = Q tot ( q rm ⁄ q )
Kitchen where
East wall 135 0.06 24 194 Table 1 Qrm = airflow to each room, cfm
Roof 240 0.05 48 576 Table 1 qrm = room sensible cooling load, Btu/h
East glass 14 44 616 Table 3 Thus, for the example,
Shaded glass 11 19 209 Table 3
Q rm = ( 994 ⁄ 19,679 )q rm
Table 11 Summary of Sensible Cooling Load Estimate If the living space in Example 1 were a multifamily unit (assume
for Example 1 that the north, south, and east walls are not exposed surfaces), the
Total Room calculation procedure would be the same, except that Table 2 would
Roof, Walls, Appli- Infil- Btu/h cfm have been used for the CLTDs and Table 4 for the GLFs. Assump-
Room and Doors Glass People ances tration (qrm) (Qrm) tions regarding infiltration, ventilation, and appliance loads are dif-
Living room 1,605 1,787 920 800 740 5,852 296 ferent for smaller multifamily units.
Kitchen 770 825 1,200 370 3,165 160
Utility and 1,404 1,200 443 3,047 154 HEATING LOAD
storage
Bedroom No. 1 559 544 278 1,381 70 Calculating a residential heating load involves estimating the
Bedroom No. 2 686 848 278 1,812 91 maximum (block) heat loss of each room or space to be heated and
Master bedroom 1,682 816 813 3,311 167 the simultaneous maximum (block) heat loss for the building, while
and bath maintaining a selected indoor air temperature during periods of
Bath 540 276 295 1,111 56 design outdoor weather conditions. Heat losses are mainly
Total 7,246 5,096 920 3,200 3,217 19,679 994 • Transmission losses or heat transferred through the confining
Duct loss (10%) 1,968 walls, glass, ceiling, floor, or other surfaces
Outdoor ventilation air 1,600 • Infiltration losses or energy required to warm outdoor air leaking
Total 23,247 Btu/h in through cracks and crevices around doors and windows,
Residential Cooling and Heating Load Calculations 28.7
through open doors and windows, and through porous building Table 12 Summary of Loads, Equations, and References for
materials Calculating Design Heating Loads
Heating Load Equation Reference, Table, Description
GENERAL PROCEDURE
Roofs, ceilings, ➤ Chapter 25, Tables 1, 2, and 4
To calculate a design heating load, prepare the following infor- walls, glass q = U A ∆t ➤ Temperature difference between
mation about building design and weather data at design conditions. inside and outside design dry bulbs,
1. Select outdoor design weather conditions: temperature, wind Chapter 27. For temperatures in
unheated spaces, see Equation (2); for
direction, and wind speed. Winter climatic data can be found in
attic temperatures, see Equation (3).
Chapter 27, or selected weather conditions and temperatures
appropriate for the application may be used. Weather station ➤ Area calculated from plans
data may differ significantly from values in Chapter 27. Walls below ➤ See Table 14.
2. Select the indoor air temperature to be maintained in each grade q = U A ∆t ➤ Use Figure 6 to assist in determining
space during design weather conditions. ∆t.
3. Temperatures in adjacent unheated spaces, attached garages, Floors ➤ For crawl space temperatures, see
and attics can be estimated at the outdoor ambient temperature. Above grade q = U A ∆t Equation (4).
4. Select or compute heat transfer coefficients for outside walls ➤ See Table 16.
and glass; for inside walls, nonbasement floors, and ceilings if On grade q = F2 P ∆t ➤ See Equation (6).
these are next to unheated spaces; and for the roof if it is next to
➤ Perimeter of slab
heated spaces.
5. Determine the net area of outside wall, glass, and roof next to Below grade q = U A ∆t ➤ Use Figure 6 to assist in determining
∆t.
heated spaces, as well as any cold walls, floors, or ceilings next to
➤ See Table 15.
unheated spaces. These determinations can be made from
building plans or from the actual building, using inside Infiltration and ➤ Volume of outdoor air entering
ventilation air building. See Chapter 26 for
dimensions.
estimating methods for infiltration.
6. Compute transmission heat losses for each kind of wall, glass, Sensible qs = 0.018 Q ∆t
floor, ceiling, and roof in the building by multiplying the heat ➤ Humidity ratio difference, if
transfer coefficient in each case by the area of the surface and Latent qt = 80.7 Q ∆W humidification is to be added
the temperature difference between indoor air and outdoor air
or adjacent lower temperature spaces. this solution is usually uneconomical. Weather records show that
7. Compute heat losses from basement or grade-level slab floors severe weather conditions do not repeat annually. If heating sys-
using the methods in this chapter. tems were designed for maximum weather conditions, excess
8. Select unit values, and compute the energy associated with capacity would exist during most of the system’s operating life. In
infiltration of cold air around outside doors, windows, porous many cases, an occasional failure of a heating plant to maintain a
building materials, and other openings. These unit values preselected indoor design temperature during brief periods of
depend on the kind or width of crack, wind speed, and the severe weather is not critical.
temperature difference between indoor and outdoor air. An
alternative method is to use air changes (see Chapter 26). Outdoor Design Temperature
9. When positive ventilation using outdoor air is provided by an
air-heating or air-conditioning unit, the energy required to Before selecting an outdoor design temperature from Chapter 27,
warm the outdoor air to the space temperature must be the designer should consider the following for residential buildings:
provided by the unit. The principle for calculation of this load
component is identical to that for infiltration. If mechanical • Is the structure heavy, medium, or light?
exhaust from the space is provided in an amount equal to the • Is the structure insulated?
outdoor air drawn in by the unit, the unit must also provide for • Is the structure exposed to high wind?
natural infiltration losses. If no mechanical exhaust is used and • Is the load from infiltration or ventilation high?
the outdoor air supply equals or exceeds the amount of natural
• Is there more glass area than normal?
infiltration that can occur without ventilation, some reduction
in infiltration may occur. • During what part of the day will the structure be used?
10. The sum of the coincidental transmission losses or heat • What is the nature of occupancy?
transmitted through the confining walls, floor, ceiling, glass, • Will there be long periods of operation at reduced indoor
and other surfaces, plus the energy associated with cold air temperature?
entering by infiltration or the ventilation air required to replace • What is the amplitude between local maximum and minimum
mechanical exhaust, represents the total heating load. daily temperatures?
11. Include the pickup loads that may be required in intermittently
• Are there local conditions that cause significant variation from
heated buildings using night thermostat setback. Pickup loads
temperatures reported by the weather service?
frequently require an increase in heating equipment capacity to
bring the temperature of structure, air, and material contents to • What auxiliary heating devices will be in the building?
the specified temperature. See Figure 9. Before selecting an outdoor design temperature, the designer
12. Use materials and data in Chapters 25, 26, 27, and others as must keep in mind that, if the outdoor to indoor design temperature
appropriate to the calculations. See Table 12. difference is exceeded, the indoor temperature may fall, depending
on (1) the thermal mass of the structure and its contents, (2) whether
SELECTING HEATING DESIGN CONDITIONS the internal load was included in calculations, (3) the duration of the
The ideal solution to a basic heating system design is a plant cold period, and (4) internal heat generated by appliances, etc.
with a maximum output capacity equal to the heating load that The effect of wind on the heating requirements of any building
develops with the most severe local weather conditions. However, should be considered because
28.8 2001 ASHRAE Fundamentals Handbook
• Wind movement increases the heat transmission of walls, glass, Example 2. Calculate the temperature in an unheated space adjacent to a
and roof, affecting poorly insulated walls to a much greater extent heated room with surface areas (A1, A2, and A3) of 100, 120, and 140 ft2
than well-insulated walls. and overall heat transfer coefficients (U1, U2, and U3) of 0.15, 0.20, and
• Wind materially increases the infiltration of cold air through 0.25 Btu/h·ft2 · °F, respectively. The surface areas of the unheated space
exposed to the outdoors (Aa and Ab) are 100 and 140 ft2, respectively,
cracks around doors and windows and even through building and the corresponding overall heat transfer coefficients are 0.10 and
materials themselves (see Chapter 26). 0.30 Btu/h·ft2 · °F. The sixth surface is on the ground and can be
Theoretically, on a design basis, the most unfavorable combina- neglected for this example, as can the effect of introduction of outdoor
air into the unheated space. Assume ti = 70°F and to = −10°F.
tion of temperature and wind speed should be chosen. A building
may require more heat on a windy day with a moderately low out- Solution: Substituting into Equation (2),
door temperature than on a quiet day with a much lower outdoor
t u = [70 ( 100 × 0.15 + 120 × 0.20 + 140 × 0.25 )
temperature. The worst combination of wind and temperature varies
by building because wind speed has a greater effect on buildings + ( – 10 )(100 × 0.10 + 140 × 0.30 )]
with relatively high infiltration rates. The building heating load may ÷ (100 × 0.15 + 120 × 0.20 + 140 × 0.25
be calculated for several combinations of temperature and wind + 100 × 0.10 + 140 × 0.30)
speed on record, and the worst combination may be selected; how-
t u = 4660 ⁄ 126 = 37°F
ever, except for critical applications, designers generally find such
a degree of refinement unnecessary. No correlation has been shown Temperatures in unheated spaces with large glass areas and two
between the design temperatures in Chapter 27 and the simulta- or more surfaces exposed to the outdoors (e.g., sleeping porches and
neous maximum wind speed. If a designer prefers the air change sun parlors) are generally assumed to be the same as that of the out-
method for computing infiltration rates, such correlation is not doors.
important. Designers who use the crack method can use a leakage
rate at a wind speed of 15 mph, unless local experience has estab- Attic Temperature
lished that another speed is more appropriate. Abnormally high
wind speeds may have an effect on infiltration and the U-factor of An attic is a space having an average distance of 1 ft or more
the building components (see Chapter 23). between a ceiling and the underside of the roof. Estimating attic
temperature is a special case of estimating temperature in an adja-
Indoor Design Temperature cent unheated space and can be done using
The indoor temperature for comfort heating may vary depending Ac Uc tc + t o ( 60ρc p A c Vc + A r U r + A w U w + A g U g )
on building use, type of occupancy, or code requirements. Chapter t a = ------------------------------------------------------------------------------------------------------------------------- (3)
8 and ASHRAE Standards 55 and 55a define the relationship Ac ( U c + 60ρc p Vc ) + A r U r + A w U w + A g U g
between temperature and comfort.
where
ESTIMATING TEMPERATURES IN ρcp = air density times specific heat = 0.018 Btu/ft3 · °F for standard air
ADJACENT UNHEATED SPACES ta = attic temperature, °F
tc = indoor temperature near top floor ceiling, °F
Heat loss from heated rooms to unheated rooms or spaces must to = outdoor temperature, °F
be based on the estimated or assumed temperature in such Ac = area of ceiling, ft2
unheated spaces. This temperature will be in between the indoor Ar = area of roof, ft2
and outdoor temperatures. If the surface area adjacent to the heated Aw = area of net vertical attic wall surface, ft2
room and that exposed to the outdoors are equal and if the heat Ag = area of attic glass, ft2
Uc = heat transfer coefficient of ceiling, Btu/h·ft2 · °F, based on
transfer coefficients are equal, the temperature in the unheated
surface conductance of 2.2 Btu/h·ft2 · °F (upper surface, see
space may be assumed equal to the mean of the indoor and outdoor Table 2 in Chapter 25); 2.2 = reciprocal of one-half the air space
design temperatures. If, however, the surface areas and coefficients resistance
are unequal, the temperature in the unheated space should be esti- Ur = heat transfer coefficient of roof, Btu/h ·ft2 · °F, based on surface
mated by conductance of 2.2 Btu/h·ft2 · °F (upper surface, see Table 2 in
Chapter 25); 2.2 = reciprocal of one-half the air space resistance
t u = [t i ( A 1 U 1 + A2 U 2 + A3 U 3 + etc. ) Uw = heat transfer coefficient of vertical wall surface, Btu/h·ft2 · °F
Ug = heat transfer coefficient of glass, Btu/h·ft2 · °F
+ t o (60ρc p Q o + A a U a + A b U b + Ac U c + etc.)] Vc = rate of introduction of outside air into the attic space by
ventilation per square foot of ceiling area, cfm/ft2
÷ (A 1 U 1 + A 2 U2 + A 3 U 3 + etc.
Example 3. Calculate the temperature in an unheated attic assuming tc =
+ 60ρc p Q o + A a U a + A b U b + A c U c + etc.) (2)
70°F; to = 10°F; Ac = 1000 ft2; Ar = 1200 ft2; Aw = 100 ft2; Ag = 10 ft2;
Ur = 0.50 Btu/h·ft2 ·°F; Uc = 0.40 Btu/h·ft2 ·°F; Uw = 0.30
where Btu/h·ft2 ·°F; Ug = 1.13 Btu/h·ft2 ·°F; and Vc = 0.5 cfm/ft2.
ρcp = density times specific heat of air = 0.018 Btu/ft3 · °F for Solution: Substituting these values into Equation (3),
standard air
tu = temperature in unheated space, °F t a = [ ( 1000 × 0.40 × 70 ) + 10 (60 × 0.018 × 1000 × 0.5 + 1200 × 0.50
ti = indoor design temperature of heated room, °F
to = outdoor design temperature, °F + 100 × 0.30 + 10 × 1.13 )]
A1, A2, A3, etc. = areas of surfaces of unheated space adjacent to heated ÷ [1000(0.40 + 60 × 0.018 × 0.5 ) + 1200 × 0.50 + 100 × 0.30
spaces, ft2 + 10 × 1.13 ]
Aa, Ab, Ac, etc. = areas of surfaces of unheated space exposed to outdoors, ft2
U1, U2, U3, etc. = heat transfer coefficients of surfaces of A1, A2, A3, etc., t a = 39,813 ⁄ 1581 = 25.2°F
Btu/h·ft2 · °F
Ua, Ub, Uc, etc. = heat transfer coefficients of surfaces of Aa, Ab, Ac, etc., Equation (3) includes the effect of air interchange that would
Btu/h·ft2 · °F take place through attic vents or louvers intended to preclude attic
Qo = rate of introduction of outside air into unheated space by condensation. Test data from Joy et al. (1956), Joy (1958), and
infiltration and/or ventilation, cfm Rowley et al. (1940) indicate that a reduction in the temperature
Residential Cooling and Heating Load Calculations 28.9
difference between attic air and outside air is linear as attic ventila- where
tion rates increase from 0 to 0.5 cfm/ft2 of the ceiling area. When ti = indoor air temperature (i.e., air above ceiling of crawl space), °F
attic ventilation meets the requirements in Chapter 24, 0.5 cfm/ft2 to = outdoor air temperature, °F
is the approximate ventilation rate for design conditions. This tg = ground temperature (constant), °F
reduction in temperature difference affects the overall heat loss of tc = crawl space temperature, °F
a residence with an insulated ceiling by only 1 or 2%. Af = area of floor above, ft2
Ap = area of perimeter, exposed foundation wall plus sill box, ft2
Equation (3) does not consider factors such as heat exchange
Ag = area of ground below (Af = Ag), ft2
between chimney and attic or solar radiation to and from the roof. Uf = average heat transfer coefficient through floor, Btu/h·ft2 · °F
Because of these effects, attic temperatures are frequently higher Ug = average heat transfer coefficient through ground (horizontal air
than values calculated using Equation (3). However, Equation (3) can film and 10 ft of soil), Btu/h·ft2 · °F
be used to calculate attic temperature because the resulting error is Up = combined heat transfer coefficient of sill box and foundation
generally less than that introduced by neglecting the roof and assum- wall (both above and below grade), Btu/h·ft2 · °F
ing that the attic temperature is equal to the outdoor air temperature. Vc = volume of crawl space, ft3
When relatively large louvers are installed (customary in southern ρcp = volumetric heat capacity of air = 0.018 Btu/ft3 · °F
regions of the United States), the attic temperature is often assumed 0.67 = assumed air exchange rate, volumes/hour
to be the average of the indoor and outdoor air temperatures.
Example 4. A crawl space of 1200 ft2 with a 140 ft perimeter is consid-
For an approximate method of calculating heat losses through ered. The construction of the perimeter wall is shown in Figure 3. The
attics, the combined ceiling and roof coefficient may be used (see indoor, outdoor, and the deep-down ground temperatures are 70, 10,
Table 5 in Chapter 25). and 50°F, respectively. Estimate the heat loss and crawl space tempera-
ture with and without insulation. The heat transmission coefficient
CALCULATING HEAT LOSS FROM (U-factor) for each component is indicated in Table 13.
CRAWL SPACES Solution: Three cases are examined.
Case A. This base case is a vented and uninsulated crawl space. The
A crawl space can be considered a half basement. To prevent crawl space temperature approaches that of the outdoors, 10°F, and the
ground moisture from evaporating and causing a condensation heat loss is 0.25 × 1200(70 − 10) = 18,000 Btu/h.
problem, sheets of vapor retarder (e.g., polyethylene film) are used Case B. The crawl space is vented. The floor above is insulated
to cover the ground surface (see Chapter 24). Most codes require with an R-11 blanket; no insulation on the perimeter. The temperature
crawl spaces to be adequately vented all year round. However, vent- of the crawl space approaches that of the outdoors, 10°F. The heat loss
ing the crawl space in the heating season causes substantial heat loss is calculated as
through the floor.
q f = 1200 × 0.076 ( 70 – 10 ) = 5470 Btu/h
The space may be insulated in several ways: the crawl space ceil-
ing (floor above the crawl space) can be insulated, or the perimeter Case C. The crawl space is not vented during the heating season.
wall can be insulated either on the outside or on the inside. If the The floor above is not insulated, but the perimeter wall is insulated with
floor above is insulated, the crawl space vents should be kept open R-5.4 down to 3 ft below grade.
because the temperature of the crawl space is likely to be below the
dew point of the indoor space. If the perimeter wall is insulated, the
vents should be kept closed in the heating season and open the
remainder of the year.
Table 13 Estimated U-Factors for Insulated and Through Ceiling and Roof
Uninsulated Crawl Spaces
Transmission heat loss through top floor ceilings, attics, and
Uninsulated Insulateda roofs may be estimated by either of two methods:
Btu/h· °F per ft Btu/h· °F per ft
Component of Perimeter of Perimeter 1. Substitute in Equation (5) the ceiling area A, the indoor/outdoor
temperature difference (ti − to), and the proper U-factor:
16 in. exposed concrete blocks 0.7 0.18
7.5 in. sill box 0.188 0.071 Flat roofs. Use appropriate coefficients in Equation (3) if side
walls extend appreciably above the ceiling or the floor below.
1st 12 in. block wall below grade 0.355 0.127
2nd 12 in. block wall below grade 0.22 0.14 Pitched roofs. Calculate the combined roof and ceiling coeffi-
3rd 12 in. block wall below grade 0.133 0.1
cient as outlined in Chapter 25.
Total for perimeter wall 1.6 0.62 2. For pitched roofs, estimate the attic temperature (based on the
indoor and outdoor design temperatures) using Equation (3),
Btu/h·ft2 · °F Btu/h·ft2 · °F
and substitute for to in Equation (5), obtaining the value of ta,
Ground 0.077 0.077 together with the ceiling area A and the ceiling U-factor. Attic
Floor above crawl space 0.25 0.076a temperatures do not need to be calculated for flat roofs, as the
a Perimeter walls are insulated with R-5.4; the floor is insulated with R-11 blanket or ceiling-roof heat loss can be determined as suggested in
batts. Method 1 above.
q = UA ( t i – to ) (5)
where
q = heat transfer through wall, glass, roof, ceiling, floor, or other
exposed surface, Btu/h
A = area of surface, ft2
U = air-to-air heat transfer coefficient, Btu/h·ft2 · °F
ti = indoor air temperature near surface involved, °F
to = outdoor air temperature or temperature of adjacent unheated
space, °F
Example 5. Calculate the transmission loss through an 8 in. brick wall hav-
ing an area of 150 ft2, if the indoor temperature ti is 70°F, and the out-
door temperature to is −10°F.
Solution: The overall heat transfer coefficient U of a plain 8 in. brick
wall is 0.41 Btu/h·ft2 · °F. Substituting into Equation (5),
Table 15 Heat Loss Through Basement Floors If a basement is completely below grade and unheated, its tem-
perature ranges between that in the rooms above and that of the
Heat Loss Coefficient, Btu/h·ft2 · °F
ground. Basement windows lower the basement temperature when
Depth of Foundation Shortest Width of House, ft it is cold outdoors, and heat given off by the heating plant increases
Wall below Grade, ft 20 24 28 32 the basement temperature. The exact basement temperature is inde-
5 0.032 0.029 0.026 0.023 terminate if the basement is not heated. In general, heat from the
6 0.030 0.027 0.025 0.022 heating plant sufficiently warms the air near the basement ceiling to
7 0.029 0.026 0.023 0.021 make unnecessary an allowance for floor heat loss from rooms
Note: ∆t = (ta − A) located over the basement.
28.12 2001 ASHRAE Fundamentals Handbook
where
ql = heat flow required to increase moisture content of air leakage
into building from Wo to Wi, Btu/h
Q = volumetric flow of outdoor air entering building, ft3/h
ρ = density of air at temperature ti, lb/ft3
Wi = humidity ratio of indoor air, lb/lbdry air
Fig. 8 Slab-on-Grade Foundation Insulation Wo = humidity ratio of outdoor air, lb/lbdry air
hfg = latent heat of vapor at ti , Btu/lb
Sensible Heat Loss If the latent heat of vapor hfg is 1076 Btu/lb, and the air density
is 0.075 lb/ft3, Equation (7) reduces to
The energy required to warm outdoor air entering by infiltration
to the temperature of the room is given by q l = 80.7Q ( W i – W o ) (10)
the crack method rather than Equations (8) and (10) is used for esti-
mating leakage, the heat loss in terms of the crack length may be
expressed as
q s = 0.018BL ( ti – t o ) (11)
and
q l = 80.7BL ( W i – W o ) (12)
where
B = air leakage for wind velocity and type of window or door crack
involved, ft3/h per foot of crack
L = length of window or door crack to be considered, ft