Switch Cabinet Cooling Units for Side-Mounting: 820 W and 480 W

● Two separate airflow circuits ensure that no air


from the surrounding atmosphere enters the switch cabinet.
● Generous clearance between warm air inflow and cold air outflow
for optimum air circulation in the switch cabinet.
● Powerful radial fans provide optimum air circulation
inside the switch cabinet.
● Ozone-friendly R134a refrigerant.
● Sealed with protective edging.
No extra work on the installation cutout necessary.
● Recessed installation possible for DTS 7001 using our
DTZ 210/7001 built-in frames.
● Temperature regulated by integrated thermostat.

Refrigeration data:
Model DTS 7101 DTS 7001

Capacity at A 35 / A 35*) 820 W 480 W

Capacity at A 50 / A 35*) 635 W 270 W

Type of refrigerant R 134a

Quantity of refrigerant 530 g 280 g

Thermostat setting (set at factory) +35 °C, adjustable within a range of +25 °C to +45 °C

Overlap 4K

Flow volume (actual)


– Condenser ventilation 370 m3 / h 270 m3 / h
– Evaporator ventilation 270 m3 / h 150 m3 / h

Noise level ≤ 64 dB (A) ≤ 63 dB (A)

Duty cycle 100 %

*) Refrigeration according to EN 814, Part 5

Electrical data:
Model DTS 7101 DTS 7001

Rated voltage 230 V* 230 V*

Rated frequency 50Hz 60Hz 50Hz 60 HZ

Range of operation 198 V – 252 V 198 V – 252 V

Power consumption 520 W 610 W 350 W 430 W

Current capacity 2.9 A 2.5 A 2.2 A 2.1 A

Starting current 8.2 A 9.8 A 6.9 A 7.7 A

Internal control voltage 230 V 230 V

*... also available as UL-approved version for 115 V – 60 Hz.


18
Mechanical data:

DTS 7101
Air outflow
into ambience
Warm air
inflow

Air inflow
from ambience

Cold air
outflow

Condensate overflow,
outside Ø 12 mm

DTS 7001
Air outflow
into ambience
Warm air
inflow

Air inflow
from ambience

Cold air
outflow

Condensate overflow,
outside Ø 12 mm

Supplementary data:
Model DTS 7101 DTS 7001

Weight 43 kg 26 kg

Orientation vertical

Construction material sheet steel

Anti-corrosion protection galvanized / electrostatically powder-coated (200 °C)

Colour RAL 7032 (European grey); other colours available on request

Electric shock protection as per DIN 31 001

Climatic data max. ambient temperature + 55 °C


max. relative humidity 80 %, A35 / A35 (EN 814, Part 5)

Protective system IP 54 against the switch cabinet (IEC 529), when used as recommended
IP 34 against the ambience (IEC 529), when used as recommended

Standard scope of supply ready for connection to mains: 2 m power cable with fault contact line,
drilling template in 1 : 1 and sealing material

Accessories Electronic control Option 1 or 2 for DTS 7101

19
Characteristic curves: DTS 7301, DTS 7201, DTS 7101 and DTS 7001
Effective refrigeration capacity

DTS 7301 DTS 7201


Refrigeration capacity Temperature inside Refrigeration capacity Temperature inside
Pc [W] switch cabinet Ti Pc [W] switch cabinet Ti

2000 2000

1500 1500

DTS 7301 + 45 °C
1000 1000 DTS 7201
+ 35 °C
+ 45 °C
+ 25 °C + 35 °C
500 500
+ 25 °C

25 35 45 55 Ta [°C] 25 35 45 55 Ta [°C]
Ambient air temperature Ambient air temperature

DTS 7101 DTS 7001


Refrigeration capacity Temperature inside Refrigeration capacity Temperature inside
Pc [W] switch cabinet Ti Pc [W] switch cabinet Ti

1000 1000

DTS 7101 + 45 °C
750 750
+ 35 °C

500 + 25 °C 500
+ 45 °C
DTS 7001
+ 35 °C
250 250
+ 25 °C

25 35 45 55 Ta [°C] 25 35 45 55 Ta [°C]
Ambient air temperature Ambient air temperature