ETAP

Project: Page: 1
12.6.0H
Location: Date: 29-11-2019
Contract: SN:
Engineer: Revision: Base
Study Case: LF
Filename: modul 3 Config.: Normal

Electrical Transient Analyzer Program

Load Flow Analysis

Loading Category (1): Design

Generation Category (1): Design

Load Diversity Factor: None

Swing V-Control Load Total


Number of Buses: 2 0 14 16

XFMR2 XFMR3 Reactor Line/Cable Impedance Tie PD Total


Number of Branches: 9 0 0 7 0 1 17

Method of Solution: Adaptive Newton-Raphson Method

Maximum No. of Iteration: 99

Precision of Solution: 0.0001000

System Frequency: 50.00 Hz

Unit System: Metric

Project Filename: modul 3

Output Filename: C:\Users\etap\Desktop\PRAKTIKUM\201611278_Timothy W S Ngantung\MODUL


3\Load Flow\Untitled.lfr
ETAP
Project: Page: 2
12.6.0H
Location: Date: 29-11-2019
Contract: SN:
Engineer: Revision: Base
Study Case: LF
Filename: modul 3 Config.: Normal

Adjustments

Apply Individual
Tolerance Adjustments /Global Percent

Transformer Impedance: Yes Individual

Reactor Impedance: Yes Individual

Overload Heater Resistance: No

Transmission Line Length: No

Cable Length: No

Apply Individual
Temperature Correction Adjustments /Global Degree C

Transmission Line Resistance: Yes Individual

Cable Resistance: Yes Individual


ETAP
Project: Page: 3
12.6.0H
Location: Date: 29-11-2019
Contract: SN:
Engineer: Revision: Base
Study Case: LF
Filename: modul 3 Config.: Normal

Bus Input Data

Load
Bus Initial Voltage Constant kVA Constant Z Constant I Generic

ID kV Sub-sys % Mag. Ang. MW Mvar MW Mvar MW Mvar MW Mvar

Bus1 150.000 1 100.0 0.0

Bus2 150.000 1 100.0 0.0

Bus3 13.800 1 100.0 0.0

Bus4 13.800 1 100.0 0.0

Bus5 0.400 1 100.0 0.0 2.124 1.823 0.531 -0.044

Bus6 20.000 1 100.0 0.0

Bus7 20.000 1 100.0 0.0

Bus8 2.400 1 100.0 0.0 2.376 2.424 0.000 -1.600

Bus10 20.000 1 100.0 0.0

Bus11 2.400 1 100.0 0.0 7.000 -0.200

Bus14 150.000 1 100.0 0.0

Bus17 13.800 1 100.0 0.0

Bus18 13.800 1 100.0 0.0 0.000 -1.500

Bus19 2.400 1 100.0 0.0 3.400 2.107 0.850 -1.473

Bus20 13.800 1 100.0 0.0

Bus21 2.400 1 100.0 0.0

Total Number of Buses: 16 7.900 6.354 8.381 -4.818 0.000 0.000 0.000 0.000

Generation Bus Voltage Generation Mvar Limits


ID kV Type Sub-sys % Mag. Angle MW Mvar % PF Max Min

Bus3 13.800 Swing 1 100.0 0.0

Bus17 13.800 Swing 1 100.0 0.0

Bus20 13.800 Mvar/PF Control 1 100.0 0.0 3.000 1.658 87.5

3.000 1.658
ETAP
Project: Page: 4
12.6.0H
Location: Date: 29-11-2019
Contract: SN:
Engineer: Revision: Base
Study Case: LF
Filename: modul 3 Config.: Normal

Line/Cable Input Data

Ohms or Siemens/1000 m per Conductor (Cable) or per Phase (Line)

Line/Cable Length

ID Library Size Adj. (m) % Tol. #/Phase T (°C) R X Y

Cable2 15NCUS3 150 10000.0 0.0 1 75 0.151650 0.102000

Cable3 15NCUS3 150 15000.0 0.0 1 75 0.151650 0.102000

Cable5 15NCUS3 300 15000.0 0.0 1 75 0.076302 0.092200

Cable10 15NCUS3 185 15000.0 0.0 1 75 0.122083 0.098600

Cable11 3.3NCUN3 70 5000.0 0.0 1 75 0.325333 0.084000

Line1 158 10000.0 0.0 1 75 4.853680 0.366980 0.0000036

Line2 158 10000.0 0.0 1 75 4.853680 0.366980 0.0000036

Line / Cable resistances are listed at the specified temperatures.


ETAP
Project: Page: 5
12.6.0H
Location: Date: 29-11-2019
Contract: SN:
Engineer: Revision: Base
Study Case: LF
Filename: modul 3 Config.: Normal

2-Winding Transformer Input Data

Transformer Rating Z Variation % Tap Setting Adjusted Phase Shift

ID Phase MVA Prim. kV Sec. kV % Z1 X1/R1 + 5% - 5% % Tol. Prim. Sec. %Z Type Angle

T1 3-Phase 6.250 150.000 13.800 7.15 8.50 0 0 0 0 0 7.1500 Dyn 0.000

T2 3-Phase 6.250 150.000 20.000 7.15 8.50 0 0 0 0 0 7.1500 Dyn 0.000

T3 3-Phase 5.000 13.800 0.400 7.15 8.50 0 0 0 -2.500 0 7.1500 Dyn 0.000

T4 3-Phase 5.000 20.000 2.400 7.15 8.50 0 0 0 0 0 7.1500 Dyn 0.000

T6 3-Phase 10.000 20.000 2.400 8.35 13.00 0 0 0 0 0 8.3500 Dyn 0.000

T10 3-Phase 9.375 150.000 20.000 8.35 13.00 0 0 0 0 0 8.3500 Dyn 0.000

T11 3-Phase 12.500 150.000 13.800 8.35 13.00 0 0 0 0 0 8.3500 Dyn 0.000

T13 3-Phase 7.000 13.800 2.400 8.35 13.00 0 0 0 -2.500 0 8.3500 Dyn 0.000

T14 3-Phase 12.500 150.000 13.800 8.35 13.00 0 0 0 0 0 8.3500 Dyn 0.000
ETAP
Project: Page: 6
12.6.0H
Location: Date: 29-11-2019
Contract: SN:
Engineer: Revision: Base
Study Case: LF
Filename: modul 3 Config.: Normal

Branch Connections

CKT/Branch Connected Bus ID % Impedance, Pos. Seq., 100 MVA Base


ID Type From Bus To Bus R X Z Y

T1 2W XFMR Bus2 Bus3 13.37 113.62 114.40

T2 2W XFMR Bus2 Bus6 13.37 113.62 114.40

T3 2W XFMR Bus4 Bus5 16.29 138.47 139.43

T4 2W XFMR Bus7 Bus21 16.71 142.02 143.00

T6 2W XFMR Bus10 Bus11 6.40 83.25 83.50

T10 2W XFMR Bus14 Bus6 6.83 88.80 89.07

T11 2W XFMR Bus14 Bus17 5.12 66.60 66.80

T13 2W XFMR Bus18 Bus19 8.92 115.96 116.30

T14 2W XFMR Bus1 Bus20 5.12 66.60 66.80

Cable2 Cable Bus3 Bus4 79.63 53.56 95.97

Cable3 Cable Bus6 Bus7 56.87 38.25 68.54

Cable5 Cable Bus6 Bus10 28.61 34.58 44.88

Cable10 Cable Bus17 Bus18 96.16 77.66 123.60

Cable11 Cable Bus19 Bus11 2824.07 729.17 2916.68

Line1 Line Bus1 Bus2 21.57 1.63 21.63 0.8039318

Line2 Line Bus1 Bus14 21.57 1.63 21.63 0.8039318

CB19 Tie Breakr Bus21 Bus8


ETAP
Project: Page: 7
12.6.0H
Location: Date: 29-11-2019
Contract: SN:
Engineer: Revision: Base
Study Case: LF
Filename: modul 3 Config.: Normal

LOAD FLOW REPORT

Bus Voltage Generation Load Load Flow XFMR

ID kV % Mag. Ang. MW Mvar MW Mvar ID MW Mvar Amp %PF %Tap

Bus1 150.000 100.555 -1.6 0 0 0 0 Bus2 1.604 0.456 6.4 96.2

Bus14 1.390 1.126 6.8 77.7

Bus20 -2.994 -1.582 13.0 88.4

Bus2 150.000 100.197 -1.5 0 0 0 0 Bus1 -1.597 -1.265 7.8 78.4

Bus3 -2.304 0.476 9.0 -97.9

Bus6 3.901 0.789 15.3 98.0

* Bus3 13.800 100.000 0.0 5.034 1.584 0 0 Bus4 2.723 1.997 141.3 80.6

Bus2 2.311 -0.413 98.2 -98.4

Bus4 13.800 96.762 0.1 0 0 0 0 Bus3 -2.632 -1.936 141.3 80.6

Bus5 2.632 1.936 141.3 80.6 -2.500

Bus5 0.400 96.091 -2.0 0 0 2.614 1.782 Bus4 -2.614 -1.782 4752.4 82.6

Bus6 20.000 98.876 -4.0 0 0 0 0 Bus7 2.430 1.108 78.0 91.0

Bus10 6.565 0.505 192.2 99.7

Bus2 -3.880 -0.610 114.7 98.8

Bus14 -5.115 -1.003 152.2 98.1

Bus7 20.000 97.050 -4.2 0 0 0 0 Bus6 -2.388 -1.080 78.0 91.1

Bus21 2.388 1.080 78.0 91.1

Bus8 2.400 95.116 -6.2 0 0 2.376 0.977 Bus21 -2.376 -0.977 649.7 92.5

Bus10 20.000 96.823 -5.3 0 0 0 0 Bus6 -6.438 -0.351 192.2 99.9

Bus11 6.438 0.351 192.2 99.9

Bus11 2.400 96.253 -8.6 0 0 6.485 -0.185 Bus19 -0.075 0.168 45.9 -41.0

Bus10 -6.410 0.018 1602.0 100.0

Bus14 150.000 100.232 -1.4 0 0 0 0 Bus1 -1.381 -1.936 9.1 58.1

Bus6 5.134 1.250 20.3 97.2

Bus17 -3.753 0.686 14.7 -98.4

* Bus17 13.800 100.000 0.0 8.267 -1.035 0 0 Bus18 4.506 -0.445 189.5 -99.5

Bus14 3.761 -0.590 159.3 -98.8

Bus18 13.800 96.092 -2.3 0 0 0.000 -1.385 Bus17 -4.309 0.604 189.5 -99.0

Bus19 4.309 0.781 190.7 98.4 -2.500

Bus19 2.400 97.349 -5.4 0 0 4.206 0.711 Bus11 0.086 -0.165 45.9 -46.1

Bus18 -4.291 -0.546 1069.0 99.2

Bus20 13.800 101.773 -0.6 3.000 1.658 0 0 Bus1 3.000 1.658 140.9 87.5

Bus21 2.400 95.116 -6.2 0 0 0 0 Bus7 -2.376 -0.977 649.7 92.5

Bus8 2.376 0.977 649.7 92.5


* Indicates a voltage regulated bus (voltage controlled or swing type machine connected to it)
# Indicates a bus with a load mismatch of more than 0.1 MVA
ETAP
Project: Page: 8
12.6.0H
Location: Date: 29-11-2019
Contract: SN:
Engineer: Revision: Base
Study Case: LF
Filename: modul 3 Config.: Normal

Bus Loading Summary Report

Directly Connected Load Total Bus Load

Bus Constant kVA Constant Z Constant I Generic


Percent
ID kV Rated Amp MW Mvar MW Mvar MW Mvar MW Mvar MVA % PF Amp Loading

Bus1 150.000 0 0 0 0 0 0 0 0 3.386 88.4 13.0

Bus2 150.000 0 0 0 0 0 0 0 0 4.101 95.1 15.8

Bus3 13.800 0 0 0 0 0 0 0 0 5.416 93.0 226.6

Bus4 13.800 0 0 0 0 0 0 0 0 3.268 80.6 141.3

Bus5 0.400 2.124 1.823 0.490 -0.041 0 0 0 0 3.445 75.9 5174.8

Bus6 20.000 0 0 0 0 0 0 0 0 9.138 98.4 266.8

Bus7 20.000 0 0 0 0 0 0 0 0 2.621 91.1 78.0

Bus8 2.400 2.376 2.424 0 -1.448 0 0 0 0 3.394 70.0 858.5

Bus10 20.000 0 0 0 0 0 0 0 0 6.448 99.9 192.2

Bus11 2.400 0 0 6.485 -0.185 0 0 0 0 6.488 100.0 1621.5

Bus14 150.000 0 0 0 0 0 0 0 0 5.487 93.6 21.1

Bus17 13.800 0 0 0 0 0 0 0 0 8.332 99.2 348.6

Bus18 13.800 0 0 0 -1.385 0 0 0 0 4.526 95.2 197.1

Bus19 2.400 3.400 2.107 0.806 -1.396 0 0 0 0 5.021 85.5 1240.7

Bus20 13.800 0 0 0 0 0 0 0 0 3.428 87.5 140.9

Bus21 2.400 0 0 0 0 0 0 0 0 2.569 92.5 649.7

* Indicates operating load of a bus exceeds the bus critical limit ( 100.0% of the Continuous Ampere rating).

# Indicates operating load of a bus exceeds the bus marginal limit ( 92.0% of the Continuous Ampere rating).
ETAP
Project: Page: 9
12.6.0H
Location: Date: 29-11-2019
Contract: SN:
Engineer: Revision: Base
Study Case: LF
Filename: modul 3 Config.: Normal

Branch Loading Summary Report

Transformer
CKT / Branch Cable & Reactor
Ampacity Loading Capability Loading (input) Loading (output)

ID Type (Amp) Amp % (MVA) MVA % MVA %

T1 Transformer 5.000 2.353 47.1 2.348 47.0

T2 Transformer 5.000 3.980 79.6 3.928 78.6

T3 Transformer 4.000 3.268 81.7 3.164 79.1

T4 Transformer 4.000 2.621 65.5 2.569 64.2

T6 Transformer 8.000 6.448 80.6 6.410 80.1

T10 Transformer 7.500 5.284 70.5 5.212 69.5

T11 Transformer 10.000 3.815 38.2 3.807 38.1

T13 Transformer 7.000 4.379 62.6 4.326 61.8

T14 Transformer 10.000 3.428 34.3 3.386 33.9

* Indicates a branch with operating load exceeding the branch capability.


ETAP
Project: Page: 10
12.6.0H
Location: Date: 29-11-2019
Contract: SN:
Engineer: Revision: Base
Study Case: LF
Filename: modul 3 Config.: Normal

Branch Losses Summary Report

Vd
CKT / Branch From-To Bus Flow To-From Bus Flow Losses % Bus Voltage
% Drop
ID MW Mvar MW Mvar kW kvar From To in Vmag

Line1 1.604 0.456 -1.597 -1.265 7.1 -809.5 100.6 100.2 0.36

Line2 1.390 1.126 -1.381 -1.936 9.1 -809.6 100.6 100.2 0.32

T14 -2.994 -1.582 3.000 1.658 5.8 75.5 100.6 101.8 1.22

T1 -2.304 0.476 2.311 -0.413 7.4 62.6 100.2 100.0 0.20

T2 3.901 0.789 -3.880 -0.610 21.1 179.3 100.2 98.9 1.32

Cable2 2.723 1.997 -2.632 -1.936 90.8 61.1 100.0 96.8 3.24

T3 2.632 1.936 -2.614 -1.782 18.1 154.0 96.8 96.1 0.67

Cable3 2.430 1.108 -2.388 -1.080 41.5 27.9 98.9 97.1 1.83

Cable5 6.565 0.505 -6.438 -0.351 126.9 153.3 98.9 96.8 2.05

T10 -5.115 -1.003 5.134 1.250 19.0 246.8 98.9 100.2 1.36

T4 2.388 1.080 -2.376 -0.977 12.2 103.6 97.1 95.1 1.93

T6 6.438 0.351 -6.410 0.018 28.4 369.2 96.8 96.3 0.57

Cable11 -0.075 0.168 0.086 -0.165 10.3 2.7 96.3 97.3 1.10

T11 -3.753 0.686 3.761 -0.590 7.4 96.5 100.2 100.0 0.23

Cable10 4.506 -0.445 -4.309 0.604 197.2 159.2 100.0 96.1 3.91

T13 4.309 0.781 -4.291 -0.546 18.1 234.8 96.1 97.3 1.26

620.3 307.6
ETAP
Project: Page: 11
12.6.0H
Location: Date: 29-11-2019
Contract: SN:
Engineer: Revision: Base
Study Case: LF
Filename: modul 3 Config.: Normal

Alert Summary Report

% Alert Settings
Critical Marginal
Loading
Bus 100.0 92.0

Cable 100.0 92.0

Reactor 100.0 92.0

Line 100.0 92.0

Transformer 100.0 92.0

Panel 100.0 92.0

Protective Device 100.0 92.0

Generator 100.0 92.0

Inverter/Charger 100.0 92.0

Bus Voltage
OverVoltage 105.0 102.0

UnderVoltage 92.0 95.0

Generator Excitation
OverExcited (Q Max.) 100.0 95.0

UnderExcited (Q Min.) 100.0

Critical Report

Device ID Type Condition Rating/Limit Unit Operating % Operating Phase Type

Gen3 Generator Under Excited 0.00 Mvar -1.03 0.0 3-Phase


ETAP
Project: Page: 12
12.6.0H
Location: Date: 29-11-2019
Contract: SN:
Engineer: Revision: Base
Study Case: LF
Filename: modul 3 Config.: Normal

SUMMARY OF TOTAL GENERATION , LOADING & DEMAND

MW Mvar MVA % PF

Source (Swing Buses): 13.302 0.549 13.313 99.91 Lagging

Source (Non-Swing Buses): 3.000 1.658 3.428 87.53 Lagging

Total Demand: 16.302 2.207 16.450 99.10 Lagging

Total Motor Load: 7.900 6.354 10.138 77.92 Lagging

Total Static Load: 7.781 -4.455 8.966 86.78 Leading

Total Constant I Load: 0.000 0.000 0.000

Total Generic Load: 0.000 0.000 0.000

Apparent Losses: 0.620 0.308

System Mismatch: 0.000 0.000

Number of Iterations: 2