Step 1 Connect an SMU to an Ethernet.


Step 2 Set the IP address ( 192.168.0.9 ), subnet mask ( 255.255.255.0 ), and gateway ( 192.168.0.1 ) on the
Laptop/Computer
Step 3 Enter the IP address of the SMU ( 192.168.0.10 ) in the Internet Explorer address box and press Enter.
Step 4 On the login page shown, set User Name to admin and Password to 000001, and then press Login.

Set the Qty of Battery, Rated Capacity, Set Date and Set Time according to actual conditions. (Always set Qty of
Battery to 1 and set Half Rated Capacity to the total capacity of all battery strings.)
Set Battery Parameter by choose monitoringbattery groupRunning parameter, follow as below:
Setting Wizard Battery Parameters Battery 1 Connected Yes
Battery 2 Connected Yes
Rated Capacity 150Ah(5-10000)
Check Battery string1&2 by choose monitoring Battery groupRunning Information
Battery String1

Battery String2
Set Date and Set Time according to actual by choose System SettingsTime
Date & Time Date & Time Set to actual time
Time Zone UTC +07:00Jakarta
NTP Enable No

Check IP Address by choose System Settings-IP Address


Network Parameters IP Address 192.168.0.10
Subnet Mask 255.255.255.0
Default Gateway 192.168.0.1
Set Basic Parameter for Power System by choose MonitoringPower SystemRunning ParameterBasic
Parameter
Basic Parameters AC Type (ThreePhases)
D.G. Function (None)
LLVD1 Enable Yes

Set LLVD parameter for Power System by choose MonitoringPower SystemRunning Parameter LLVD
parameter
LLVD Parameters LLVD1 Mode (Voltage Mode)
LLVD1 Voltage (44.0V(35.0-56.0) 44.0V
LLVD1 Con. Volt (51.5V(37.0-58.0))
LLVD Delay Time (60s(5-90))
Set AC&DC Volt. Parameter for Power System by choose MonitoringPower SystemRunning Parameter
AC&DC Voltage Parameter
AC&DC Volt. Para. AC OV Thres. (60-300) 280V
AC UV Thres. (60-300) 180V
DC OV Thres. (53.0-60.0) 58.0V
DC UV Thres. (45.0V(35.0-57.0)) 45.0V
DC Ultra OV Thres. (59.0V(53.0-60.0))
DC Ultra UV Thres. (44.0V(35.0-57.0))

Set Sensor Configuration Parameter for Power System by choose MonitoringPower SystemRunning
Parameter Sensor Configuration Parameter ( default setting of water sensor, smoke sensor, Ambient Temp.
Sensor, Ambient Humidity Sensor are NONE, Please set to YES )Press submit.
Sensor Config. Para DC SPD Yes
AC SPD Yes
Door Sensor Yes
Water Sensor Yes
Smoke Sensor Yes
Ambient Temp. Sensor Yes
Ambient Humidity. Sensor Yes
Batt. Temp. Sensor 1 Yes
Set Ambient Temperature and Humidity Parameter for Power System by choose MonitoringPower
SystemRunning Parameter Ambient Temperature and Humidity Parameter
Temp&Humi Para. Amb. HT Thres. 55degC(25-80)
Amb. LT Thres. "-20degC(-20-20))
Amb. Ultra HT Thres. "70degC(25-80))
Amb. HH Thres. 80%(0-100)
Amb. LH Thres. 10%(0-100)

Check Other Parameters for Power System by choose MonitoringPower SystemRunning Parameter Other
Parameters
Other Parameters Buzzer enable No
Buzzer Alm. Duration 10Min(1-100)
Set Basic Parameters for Rectifier by choose MonitoringRectifier GroupRunning Parameter Basic
Parameters
Rectifier High Rect. Capacity 5%(0-150)
Low Rect. Capacity 75%(0-150)
Max Limited Current 121%(1-121)

Set Basic Parameters for Battery by choose MonitoringBattery GroupRunning Parameter Basic Parameters
Battery Basic Parameters Battery1 Connected Yes
Battery2 Connected Yes
Rated Capacity 150Ah(5-10000)
FC Voltage 53.5V(42.0-58.3)
EC Voltage 56.5V(42.0-58.3)
Charge Limit Coef. 0.05C10(0.05-0.25)
BLVD Enable Yes
Hibernation Enable No
Set Temperature CompensationParameters for Battery by choose MonitoringBattery GroupRunning
Parameter Temperature CompensationParameters
Temp. Comp. Para. TC Coefficient 80mV/degC(0-500)
Nominal Temperature 25degC(5-45)
TC Upper Thres. 45degC(40-45)
TC Lower Thres. 5degC(5-10)
TC Coefficient 80mV/degC(0-500)

Set BLVD Parameters for Battery by choose MonitoringBattery GroupRunning Parameter BLVD Parameters
BLVD Parameters BLVD Mode Voltage Mode
BLVD Voltage 43.0V(35.0-56.0)
BLVD Con. Volt 51.5V(37.0-58.0)
BLVD Delay Time 60s(50-90)
Set Basic Parameters for Temp.Control Group by choose Monitoring Parameters for Temp.Control Group
Running Parameter Basic Parameters
Temp. Control Group Indoor Vent Ts Yes
Outdoor Amb. TS No

Set Alarm Parameter (DI Dry contact Parameters ) for Power System by choose MonitoringPower
SystemRunning Parameter DI Dry contact Parameters
Alarm Parameter DI Dry contact para. DIN1 Alm. Cond. Close
DIN2 Alm. Cond. Close
DIN3 Alm. Cond. Close
DIN4 Alm. Cond. Close
DIN5 Alm. Cond. Close
DIN6 Alm. Cond. Close
Set Alarm Parameter (DO Dry Contact Parameters) for Power System by choose MonitoringPower
SystemRunning Parameter DO Dry Contact Parameters
DO Dry Contact Para. ALM1 Alarm Action Close
ALM2 Alarm Action Close
ALM3 Alarm Action Close
ALM4 Alarm Action Close
ALM5 Alarm Action Close
ALM6 Alarm Action Close
ALM7 Alarm Action Close
ALM8 Alarm Action Close
Set Alarm Parameter for Power System by choose System SettingAlarm Parameter select an equipment type
to Power system, Click Confirm Make Sure AC SPD Fault, Load Fuse Break, Door Alarm, Water Alarm, High
AmbTemp, Low Amb Temp, High Amb Humidity, Low Amb Humidity, LLVD Warning, LLVD1 Disconnected, DIN1-
DIN6 set to ENABLEPress Submit
Alarm Parameter Power System AC SPD Fault
Load Fuse Break Enable
Door Alarm Enable
Water Alarm Enable
High AmbTemp Enable
Low Amb. Temp Enable
High Amb. Humi. Enable
Low Amb. Humi Enable
LLVD Warning Enable
LLVD1 Disconnected Enable
DIN1 Enable
DIN2 Enable
DIN3 Enable
DIN4 Enable
DIN5 Enable
DIN6 Enable
Set Alarm Parameter for Rectifier by choose System SettingAlarm Parameter select an equipment type to
Rectifier, Click ConfirmMake sure Rectifier Fault, Rectifier Protection, Rectifier Communication Failure Set to
CRITICAL and Rectifier Power Failure, Rectifier Overvoltage set to MAJOR.

Set Alarm Parameter for Rectifier Group by choose System SettingAlarm Parameter select an equipment type
to Rectifier Group, Click ConfirmSet Rectifier Missing to DISABLE
Rectifier Group Rectifier Missing Disable

PLEASE TRY & GOOD LUCK !!!!!!!!!!!!!!!