Summary
C.3 General characteristics
C.6 Characteristics
C.13 Auxiliaries
C
1
C.16 Equipment
C.17 Interlocking
C.29 Connections
C.29 Weights
C
2
SPECTRONIC SP - Air circuit breakers
Complete range
- Fixed or withdrawable versions
- 3 or 4 poles
- Electrical or manual control
0
800 1000 1250 1600 2000 2500 Ith (A)
SPECTRONIC SP - Air circuit breakers
C 14
4
19 13 5
11 15 18
C
5
10 8
Description
The circuit breaker is mounted on a cradle fitted with slides allowing two
positions: “inserted” and “withdrawn-isolated”.
The insertion and withdrawal operations are performed by a screw-nut
system, operated by two removable cranks.
Automatic tripping of the breaker on withdrawal is ensured by a safety
device at the insertion of the cranks.
For panel mounting, a seal and a cover, permit IP3x protection with the
door closed.
2
The circuit breaker may be withdrawn either with the door closed or open.
9 Installation
3
- Fixing to the vertical uprights by rear surface or on a horizontal surface
by adding L pieces on side faces.
- Main connections (see table on page D.27).
- The auxiliary circuits disconnect automatically and simultaneously with
1 7 the main circuit.
12 - Connections to the auxiliary circuits are made laterally with
clips(maximum 24 terminals)
- Standard unit equipped with 12 terminals.
16 17
SPECTRONIC SP - Air circuit breakers
Characteristics
Circuit Breakers
SP 800 SP 1000 SP 1250 SP 1600 SP 2000 SP 2500
Rated insulation voltage Ui (V) 1000 1000 1000 1000 1000 1000
Rated impulse voltage Uimp (kV) 8 8 8 8 8 8
Rated maximum nominal voltage Ue (V) 690 690 690 690 690 690
Rated thermal current Ith 40°C (A) 800 1000 1250 1600 2000 2500
50°C (A) 800 1000 1250 1600 2000 2500
60°C (A) 800 1000 1250 1500 1900 2350
Rated ultimate short-circuit breaking capacity Icu
Alternating current 50/60Hz 240/415V (kA) 55 55 55 55 60 60
500V (kA) 35 35 35 35 35 35
690V(1) (kA) 40 40 40 40 40 40
Rated service short-circuit breaking capacity Ics
C Alternating current 50/60Hz 240/415V
500V
(kA)
(kA)
50
35
50
35
50
35
50
35
55
35
55
35
6
690V(1) (kA) 40 40 40 40 40 40
Rated peak short-circuit making capacity (max) Icm (kA peak) 120 120 120 120 130 130
Rated short time withstand current Icw: 1 sec.
415V (kA eff.) 50 50 50 50 55 55
500V (kA eff.) 35 35 35 35 35 35
Utilization category B B B B B B
Number of poles 3-4 3-4 3-4 3-4 3-4 3-4
Suitable for isolation (visible breaking indication) • • • • • •
Endurance (number of operating cycles)
Mechanical (total) # operating cycles 10000 10000 10000 10000 10000 10000
Electrical (at 415V)(2) # operating cycles 10000 10000 10000 10000 5000 3500
Mean time between maintenances # operating cycles 1500 1500 1500 1500 1500 1500
Power dissipation (withdrawable, 3 poles) (W) 150 200 300 400 450 500
4th pole conventional thermal current (A) 800 1000 1250 1600 1250(3) 1250(3)
Pollution degree 3 3 3 3 3 3
Dimensions in mm (fixed version)
3 poles Height (mm) 462 462 462 462 462 462
Width (mm) 370 370 370 370 464 464
Depth (mm) 273.5 273.5 273.5 273.5 273.5 273.5
4 poles Height (mm) 462 462 462 462 462 462
Width (mm) 458 458 458 458 52 562
Depth (mm) 273.5 273.5 273.5 273.5 273.5 273.5
(1) On request. (2) To guarantee this number of operations, it is necessary to check the spark
(3) Neutral reduced to the left. arrestors and the arc chutes as shown in the table above (Replace them when necessary)
This can be done easily on site
Switches
SP 800 SP 1000 SP 1250 SP 1600 SP 2000 SP 2500
Rated thermal current at 40°C Ith (A) 800 1000 1250 1600 2000 2500
Rated peak short-circuit making current Icm (kA peak) 120 120 120 120 130 130
Rated short time withstand current Icw: 1 sec.
415V (kA eff.) 50 50 50 50 55 55
500V (kA eff.) 35 35 35 35 35 35
Dimensions in mm (fixed circuit breaker):
See circuit breaker table above
SPECTRONIC SP - Air circuit breakers
Setting ranges
Setting points
LT (x In) 0.4 - 0.5 - 0.6 - 0.7 - 0.8 - 0.85 - 0.9 - 0.95 - 1
LTD (s) 5 - 10 - 15 - 20 - 25 - 30 - 35 - 40 delay at 7.2 lr
ST (x ln) 1.5 - 2 - 3 - 4 - 5 - 7 - 9 - 10 - 12 - 14
Time delay (ms) 30 - 60 - 90 - 120 - 150 - 180 - 210 - 240- 270 - 300
I (x ln) 1.5 - 2 - 3 - 5 - 7 - 10 - 15 - OFF
GF (x In) SP800 - SP2000: 0.2 - 0.3 - 0.4 - 0.5 - 0.6 - 0.7 - 0.8
SP2500: 0.2 - 0.3 - 0.35 - 0.45 - 0.55 - 0.6 - 0.7
Time delay (ms) 100 - 200 - 300
Ir = k x In C
Note 7
If the GF function is selected, the fourth CT's must be of the same rating as
the ones of the phases.
Options
Distinct fault signalling (LT, ST-I, GF)
This option displays locally by LED the origin of the fault.
Tamper proofing
A transparent screen avoids the access to the settings.
Description
The RMS 7 unit meets the requirements of the IEC 947.2 standard.
This unit is powered by the current transformers and performs all the
necessary three or four pole overcurrent protections.
The RMS 7 is designed to receive interchangeable rating plugs:
- 3 pole or 4 pole protection: 3P/3P+N
- 3 pole with half neutral protection: 3P+N50%
- 3 pole or 4 pole ground fault protection
SPECTRONIC SP - Air circuit breakers
1.05
Operating limits - IEC
1.3
LT Threshold in k x In
LT Time delay
5 - 15 - 40 s. at 6Ir
Time in seconds
ST Threshold
2 - 3 - 4 - 6 - 8 - 10 times
the LT value (Ir)
ST Time delay
0.050 - 0.100 -
0.200 - 0.300 - 0.500 s
Setting ranges
Setting points
LT (x In) 0.5 - 1 (steps of 0.05)
LTD (s) 3 - 6 - 12 - 25 / to 6 lr
ST (x lr) 1.5 - 9 (steps of 0.05)
Time delay (ms) 100 - 210 - 350
I (x lr) 1.5 - 15 (steps of 0.5)
GF (x In) 0.2 - 0.6 (steps of 0.01)
Time delay (ms) 100 - 210 - 350
C
9
Ir = k x In
Note
If the GF function is selected, the 4th transformer must have the same
rating as the one of the phases.
microprocessor
B
Distinct fault signalisation
RMS 9
C
By local display with the RMS 9 unit in 'Status' mode the condition of the
breaker is indicated. Also the time and number releases under fault:
keyboard - LT, ST, I, GF
- undervoltage, overvoltage, ..., reversal power.
LCD display
SPECTRONIC SP - Air circuit breakers
To ensure a permanent display, the RMS 9 unit must be supplied by an auxiliary power supply of
24V DC - 15W regulated. The monitor collects all the information
available in the Spectronic circuit breakers
equipped with a RMS 9 2000C protection and
measurement unit.
auxiliary The communication is performed by the “Power
power supply Leader” protocol which is supported by a twisted
24V dc pair of wires.
voltage
The monitor performs:
conditioner (1,76V) - remote network parameter measurements:
- phase currents,
actuator - voltages direct and apparent,
A/D converter
sampler
current
- frequency,
microprocessor
1.05
Operating limits - IEC
1.3
LT Threshold in k x In
0.5 to 1 times the current
transformer rating
C
11
LT Time delay
3 - 6 - 12 - 25 s. at 6 Ir
Time in seconds
ST Threshold
1.5 to 9 times
the LT value (Ir)
ST Time delay
0.100 - 0.210 - 0.350 s
Electrical control
The electrical control is integrated within the overall dimensions of the circuit breaker.
An easy adaption can be made to manual control.
Note
In case of continuous signal to close, interrupt this signal during 0.3 sec minimum, to allow electrical
control to reset properly.
C Characteristics
12
Rated service voltage Un
Alternating current 50Hz V 48-110-127-220-240-380
Alternating current 60Hz V 48-110-220-240-380
Direct current V 48-60-110-220V
Operating voltage from 0.85 to 1.1 Un
Operating time at making ms 150 at Un
Power consumption
Breaker type SP800 to1600 SP2000 and 2500
Alternating current VA 1600 2000
Direct current W 800 1000
Voltmetric releases
Two types of releases enable the remote controlled operation of the circuit breaker.
SHUNT TRIP RELEASE EA-EA1-EB
Actuates the breaking of the circuit breaker (the power supply is cut by an auxiliary contact).
Maximum equipment
1st possibility • - • -
2nd possibility - • • -
3rd possibility - - • •(2)
(1) Circuit breaker “making” ensured from 0.85 Un.
(2) or UVRD
SPECTRONIC SP - Auxiliaries
C Characteristics
14 AS SAS
Thermal current Ith (A) 20 17.5
Interrupting capacity
Alternating current cos ϕ 0.3
48V (A eff.) 12 -
127V (A eff.) 12 -
220V (A eff.) 12 -
380V (A eff.) 5 -
Direct current L/R 0.01s
48V (A) 3 10
120V (A) 0.7 8
220V (A) 0.45 5
Characteristics BA
Thermal current Ith (A) 20
Interrupting capacity
Alternating current cos ϕ 0.3
48V (A eff.) 12
127V (A eff.) 12
220V (A eff.) 12
380V (A eff.) 5
Direct current L/R 0.01s
48V (A) 3
120V (A) 0.7
220V (A) 0.45
SPECTRONIC SP - Air circuit breakers
Includes a fixed part (female sockets) mounted on the cradle and a moving C
part (male sockets) mounted on the circuit breaker 15
Safety contact in “connected” position CAE 12 - Device permits connection of 6 circuits of 10 A per block.
Indicates that the closing of the breaker can be actuated; the breaker is in - Mounting of 4 devices maximum.
“Connected” position, operating cranks not inserted.
Possibility of a changeover switch. Isolating shutter
Connection by clips of 6.35 mm.
Characteristics
Thermal current Ith (A) 20
Interrupting capacity
Alternating current cos ϕ 0.3
48V (A eff.) 12 Reinforces the natural electrical continuity between the cradle mass and
127V (A eff.) 12 the circuit breaker (Icc 25kA - 0.5 s).
220V (A eff.) 12 Remove the lower right wire secondary disconnection block.
380V (A eff.) 5
Direct current L/R 0.01s
48V (A) 3
120V (A) 0.7
220V (A) 0.45
SPECTRONIC SP - Air circuit breakers
Description
The source changeover switches have the same characteristics and possibilities of adaptation for the
circuits being protected as the circuit breakers of which they are built. C
In the withdrawable version, the “out of service” breaker can be withdrawn and removed without 17
affecting the operation of the “in service” breaker. When fitted with interlocking in “withdrawn” position,
the unit complies with the NF C 13-100 standard.
The source changeover switches consist of:
1. Two or three circuit breakers
- designed to be mechanically interlocked
- fitted with auxiliaries, wired and brought to the auxiliary terminal as needed for the chosen diagram
- may be identical, or may differ in the following:
- circuit breaker
- type
- protection system
- structure (possible combination of fixed and withdrawable types)
2. A mechanical locking system with linkage (two or three circuit breakers) or cables (two circuit
breakers)
3. An automatic controller comprising the relays necessary for operation of the source changeover
switches (not supplied) .
Installation
The circuit breakers are installed in a stacked arrangement (with cables only).
The changeover switches are delivered with circuit breakers and mechanical interlocking separated.
Characteristics
Rated service voltage (V) 50Hz 220 - 380
Automatic power without auxiliary
supply supply (V) 50Hz 220 - 380
with auxiliary (V) 50Hz 48 - 127 - 220 - 380
supply 24 - 48 - 110 - 220
Consumption breaker ratings SP 800 to 1600 SP 2000 and 2500
during transfer (VA) 1740 214
(W) 820 1020
permanent (VA) 26 26
(W) 37 37
Minimum transfer normal → with shunt trip release 2 s(1)
time replacement with undervoltage trip release 2 s(1)
replacement with shunt trip release 2s
normal → with undervoltage trip release 2 s
(1) Whenever required, add the generator start-up time.
SPECTRONIC SP - Source changeover switches
return of Un return of Un
switching switching
alternative → normal alternative→ normal
T4 = 0.6s to 60 min(3) T3 = 250 ms
(1)
Refer to the equipment specification.
(2) (3)
Operation Auxiliaries to add
Two normal sources possible To be fitted on EACH circuit breaker switch
normal 1 0 x 0 0 x voltmetric release EA or UVRD 1 1
remplacement 0 0 x 0 0 auxiliary switches AS 5 5
normal 2 0 0 0 x x fault contact BA 1 1 -
x: closed circuit breaker To be fitted on EACH WITHDRAWABLE circuit breaker
- safety contact in “connected “position CAE 12
- “connected” position contact CAE 51
Note
On request: supplied with a cabling diagram.
SPECTRONIC SP - Order codes
Circuit breakers
Without Protection
SP 800 SP 1000 SP 1250 SP 1600 SP 2000 SP 2500
FIXED with rear 3P 756303 756313 756323 756333 756343 756353
horizontal terminals
4P 756304 756314 756324 756334 756344 756354
WITHDRAWABLE
3P 756301 756311 756321 756331 756341 756351
Moving part
4P 756302 756312 756322 756332 756342 756352
+
Fixed part 3P 756100 756100 756100 756100 756102 756102
cradle with front
4P 756101 756101 756101 756101 756103 756103
C terminals
3P 756105 756105 756105 756105 756107 756107
Cradle with rear
20
horizontal terminals 4P 756106 756106 756106 756106 756108 756108
Higher value for 690V version 3P 756136 756136 756136 756136 756138 756138
4P 756137 756137 756137 756137 756139 756139
+ 2500 - - - - - 755505
Fourth pole equipment Rating A SP 800 SP1000 SP 1250 SP 1600 SP 2000 SP 2500
800 755510 - - - - -
1000 - 755511 - - 755514 -
1250 - - 755512 - - 755515
1600 - - - 755513 - -
SPECTRONIC SP - Order codes
Rating plug
3P/3P+N 100% Rating A SP 800 SP1000 SP 1250 SP 1600 SP 2000 SP 2500
400 755554 - - - - -
600 755553 - - - - -
800 755550 755563 - 755584 - -
1000 - 755560 - - - -
1200 - - - 755583 755593 -
1250 - - 755570 - - -
1600 - - - 755580 - 755603
2000 - - - - 755590 -
2500 - - - - - 755600
755372 Monitor
Note
Do not forget the auxiliary power supply (not
supplied)
SPECTRONIC SP - Order codes
FIXED with rear horizontal 3P 756403 756413 756423 756433 756443 756453
terminals
4P 756404 756414 756424 756434 756444 756454
WITHDRAWABLE
3P 756401 756411 756421 756431 756441 756451
Moving part
+ 4P 756402 756412 756422 756432 756442 756452
Fixed part 3P 756100 756100 756100 756100 756102 756102
cradle with front
terminals 4P 756101 756101 756101 756101 756103 756103
Cradle with rear
horizontal
terminals
3P
4P
756105
756106
756105
756106
756105
756106
756105
756106
756107
756108
756107
756108
C
23
Higher value for 690V version
3P 756136 756136 756136 756136 756138 756138
4P 756137 756137 756137 756137 756139 756139
SPECTRONIC SP - Order codes
Electrical auxiliaries
Electrical control Shunt trip release Undervoltage trip release
SP EA UVR
AC 50Hz AC 50-60Hz AC 50Hz
C 756200
756201
48V
110V
752200
752201
24V
48V
752254
752255
24V
48V
24
756224 127V 752202 110/127V 752256 110/127V
756233 220V 752203 220V 752257 220V
756231 240V 752204 380/500V 752258 380V
756205 380V DC 752259 415V
752240 24V 752260 500V
AC 60Hz
752241 48V
756206 48V AC 60Hz
752242 110/120V
756201 110V 752254 24V
752243 220/500V
756233 220V 752255 48V
756225 240V EA1 752256 110/127V
756211 380V AC 50Hz 752261 220V
752205 127V 752258 380/415V
DC 752206 220V 752259 500V
756212 48V 752207 380/415V
756228 60V 752208 500V DC
756213 110V 752288 24V
756215 220V EB 752289 48V
AC 50Hz
752290 110V
752210 24V
752291 120V
752211 48V
752292 220V
752212 110/127V
752293 440V
752213 220V
752294 500V
752214 380/415V
752215 500V
UVRD 250 ms
AC 60Hz
AC 50Hz
752248 220V
752216 220V
752249 380V
752217 380V
DC
752244 24V UVRD 0,6 s
752245 48V AC 50Hz
752246 110/120V 752220 220V
752247 220V 752221 380V
SPECTRONIC SP - Order codes
Auxiliaries Accessories
Signalling contacts Secondary terminals Interlocking
Fixed circuit breaker: block of 12 terminals Tripped position
(maximum 1 additional block).
753203 By Ronis lock (supplied)
756096 Left mounting
753204 By lock (not supplied)
Withdrawable circuit breaker: block of 6 terminals
(2 additional blocks maximum). 753205 By padlocks (not supplied)
NO NC NO/NC 755909 Fixed and moving part assembly 753207 By lock (not supplied)
756061 756060 756062 AS 1
Isolating shutter Source changeover mechanical interlock
756064 756063 756065 AS 2
3P 4P Linkage permitting interlock:
C
756067 756066 756068 AS 3 25
- 2 circuit breakers at 660 mm
756070 756069 756071 AS 4 756110 756111 SP 800-1600 - 3 devices (on request)
756073 756072 756074 AS 5 756112 756113 SP 2000 - 2500 756119 Fixed circuit breaker
756076 756075 756077 AS 6 756120 Withdrawable circuit breaker
Reinforced ground plug 25kA - 0.5 s
756081 756080 756082 SAS 1(1)
Cable system permitting interlock between:
756084 756083 756085 SAS 2(1) 756132 For withdrawable circuit breaker
756087 756086 756088 SAS 3(1) 756141 2 fixed circuit breaker
“Test” position cord
752815 752816 752817 BA 1 756142 2 withdrawable circuit breaker
- - 752820 BA 2 756127 Replace the secondary
disconnection device Operation counter
(1)
To fit 1, 2 or 3 SAS contacts, Circuit breaker contact positions in
use adaption no. 756098 the cradle
Connection terminals or secondary 756095 "Connected” position contact CAE,
disconnections to use: one changeover contact NO/NC
- by NO or NC contact: 2 terminals
- by NO/NC contact switches: 3 terminals 756094 "Withdrawn” position contact CAD, 756133
one changeover contact NO/NC
Factory fitted
For each position two contacts are possible.Use
an adaption no. 756095 for 2 CAE + 2 CAD Door gasket
Use 3 secondary terminals per contact.
752818 Permits IP3x protection
when panel mounted
“Connected cranks not inserted”
contact CAE 12
Neutral Door
E
Gasket
4x Ø9
C
26 4x Ø9
Panel cut out for fitting gasket Rear horizontal Front connections
connections
300
3
352
Legend
Type Number A B C D SP 2000 - 2500 SP 2000 - 2500
of poles
SP 800 to 1600 3 318 98 75 -
SP 2000-2500 3 412 130 90 -
4 510 130 90 114
4 x Ø10,5
Gasket
C
27
Withdrawable 2 Ø 12
door closed
300
Door cut-out
Connection terminals
Legend
Type Number A B C D SP 800 to 1600 SP 2000 - 2500
of poles
neutral of SP 2000 - 2500
SP 800 to 1600 3 374 98 89 -
SP 2000-2500 3 468 130 104 -
4 566 130 104 114
Source changeover
switches IDS
Fixed circuit breakers without chassis
Type Number A
of poles
SP 800 to 1600 3 334
SP 2000 - 2500 3 428
4 526
White area: overall dimensions of interlocking
system.
⊗ left alignment of circuit breaker fixation.
C
28
Ph.1 +
Secondary
disconnector 50 49
C N
C
30
Fault RMS7
signalling
EX
Secondary
disconnector
Ph.2 -
Option Protection unit Fault contacts
Legend
CAE 51 . 52 Contact 'connected' position RMS 7 Trip unit
CAD 61 . 62 Contact 'withdraw' position Voltmetric Maximum equipment:
CAE 12 Contact 'withdraw' position, cranks not inserted release – MV or MVR + EB
– EA or EA1
CD1 . CD2 Fault contact, overload and short-circuit with local reset
after fault Rated thermal current: 20A
CA1 to CA6 Breaking capacity:
MV Undervoltage release – alternating current cos ϕ 0.3
MVR Time delayed undervoltage release 48V - 12A
RA Resistor for selected voltages in direct current 127V - 12A
EA1 . EA . EB Shunt trip 220V - 12A
380V - 5A
K Circuit breaker closing relay – direct current L/R 0.01 s
FCE1 . 2 Limit switch close 48V - 3A
FCD Limit switch reset 120V - 0.7A
220V - 0.45A
M.m Motor
Rated thermal current: 17.5A
RH50 Resistor for 380V CAS1 to CAS3 Breaking capacity:
C21 Interlock contact coupled with emergency control – direct current L/R 0.01 s
CA . CAS Auxiliary contacts 220V - 5A
BP0 'Tripped' position contacts Rated thermal current: 20A
BPF 'Closed' position contacts CD1 - CD2 Breaking capacity:
CAE12 – alternating current cos ϕ 0.3
CAE51 48V - 12A
CAE52 127V - 12A
CAD61 220V - 12A
CAD62 380V - 5A
SPECTRONIC SP - RMS 7 diagram
Disconnected
Open Closed cranks not-
Connected Disconnected
inserted
42 44
4
or or or
or or M
or
C
green 31
red
Voltmetric
Electrical control Auxiliary contacts Positioning contacts
releases
LEFT RIGHT
LEFT RIGHT
50
CN
49
MV or MVR
REAR
CD2
CD1 E
F Electrical
FRONT G control
EA1 or EA H
or EB
or MV .MVR
SPECTRONIC SP - RMS 9 diagram
Ph.1 +
Fault
N
S1
Ph1
Voltage R
Transmission
Ph2
Ph3
conditioner S
T
505 49E 15 14 32 29
Secondary
disconnector C N T S R S1
C
32
5 6 RMS9
T S R S1
MONITOR 17 33 16 28
EX
Secondary
disconnector
Legend
CAE 51 . 52 “connected” position contact
CAD 61 . 62 “withdrawn” position contact
CAE 12 “cranks not inserted” contact
BA1 - BA2 fault contact, overload and short-circuit with local reset after fault tripping
UVR undervoltage release
UVRD time delayed undervoltage release
RA resistor for selected voltages in direct current
EA1 - EA - EB shunt trip release
K relay
FCE1 . 2 limit switch close
FCD limited switch reset
M.m motor
RH 50 resistor for 380V
C 21 interlock contact coupled with emergency control
AS - SAS auxiliary switches
BPO “Tripping” push-button
BPF “Closing” push-button
SPECTRONIC SP - RMS 9 diagram
yellow
blue
EA UVRD
or or or
or or
EA1
or
UVR
M
C
EB 33
green
red
LEFT RIGHT
LEFT RIGHT
plate plate
REAR RMS 9 13 17
CN
9 21
UVR or UVRD R
S
T
RMS 9
FRONT
CD2
35 -
36 +
CD1 E
F Electrical
EA1 or EA G control
or EB H
reserved terminal(s)
or UVR/UVRD
direction of wiring
Notes
C
34
SPECTRONIC S/L - Air circuit breakers
Summary
C.37 General characteristics
C.49 Auxiliaries
C.53 Equipment
C.54 Interlocking
C.90 Connections
C.90 Weights
Notes
C
36
SPECTRONIC S/L - Air circuit breakers
Anti-corrosion treatment
0
For special atmospheres, consult us. 640 800 1000 1250 1600 2000 2500 3200 4000 5000
6400
Ith (A)
SPECTRONIC S/L - Air circuit breakers
11
10
C 3
38 13
7 8 14 12
Description 1 Recess section for adaption of interlock in the “tripped” position by lock.
2 Recess section for interlocking, in the “tripped” position by padlock.
Equipped at the factory with a panel ensuring a IP43 protection degree.
By fitting a gasket and a seal, a IP43 is obtained (door closed). 3 Electrical control handle.
4 Trip and reset local push button.
Installation 5 Circuit breaker position indicator: Red = closed - Green = open.
- Fixed by side L-pieces with built-in ground connection. By cross 6 Closing push button.
members on circuit breakers S 5000-6400 (vertical or horizontal).
7 Electrical control position indicator:
- Main connections (see table on page D.88). Yellow = tripped - Blue = reset.
- Auxiliary circuit connections by terminals located at the rear of the 8 Mechanical fault indicator: White = fault - Black = normal.
curcuit breaker.
9 Arc chute.
- 20 connection terminals supplied as standard, positioned at the rear.
10 Auxiliary switch.
11 Electrical control.
Power Supply
12 RMS 7 or RMS 9 trip units.
- Up to 500V (415V for L circuit breakers), connections are made either 13 Distinct fault signalling.
on the upper or the lower terminals
14 EX trip actuator.
- Above 500V, connect to the upper terminals or right terminal clamps
on the vertical S 5000-6400 breakers (breakers seen from the front). 15 Ground plug.
16 Voltmetric releases.
17 Current transformer.
18 Fixed auxiliary terminal block.
19 Mobile auxiliary terminal block.
20 “Withdrawn” - “connected” signalling contacts.
21 “Withdrawn” - “connected” interlocking positions.
22 “Withdrawn” position padlocking.
23 “Withdrawn” - “test” - “connected” position indicator.
24 Primary jaw.
25 Push button interlocking shutters.
26 Chassis.
27 Dashboard.
SPECTRONIC S/L - Air circuit breakers
17
25
C
39
26
24 16 15
Description
- Ratings H 4000A
Cradle equipped with retractible rails enabling 3 circuit breaker positions:
“connected”, “test, “withdrawn-isolated”, as well as an “extracted”
position.
- Ratings 5000-6400A (vertical)
18 Cradle equipped with guide rails in which the circuit breaker rollers are
engaged, enabling 2 circuit breaker positions: “connected”, “withdrawn-
isolated”.
By fitting of a gasket and a seal, a IP3x is obtained. (door closed)
The plug-in operation, which can be done with the door closed, uses a
1 screw-nut system, actuated by a removable crank. Tripping of the circuit
2 breaker before introducing the crank guarantees safety when withdrawing.
Installation
- Fixed to the lower part of the cradle. The upper part on the 5000-6400A
27 20 ratings (vertical versions) has to be maintained.
19 - Main connections (see table page D.88).
- Lateral auxiliary circuit connections:
- by disconnectable clips for S 800 to S 4000 and L640 to L 2000
- by connectors for S 5000-6400.
15 - Two blocks of 6 terminals are supplied as standard.
Power supply
- Up to 500V, (415V for circuit breakers L), connections are made either
on the upper or lower terminals.
- Above 500V, connect to the upper terminals or right terminal clamps on
the vertió!l breakers S 5000-6400 (breakers seen from the front).
22
23
21
SPECTRONIC S - Air circuit breakers
Main characteristics of
selective S circuit breakers
Full interrupting capacity kept in all Total selectivity guaranteed even at Special design providing a long
selectivity cases closing on short-circuit service of the main contacts
C
40
The original pole design insures a very high Independant closing directly on main contacts When opening, the unique pole design enables
withstand to short-circuit currents in “closed” (patented) is obtained by using the energy the transition from the main contacts to the
position. stored in the springs and released by a lock. arcing contacts. The structure of the spark
arrester considerably reduces external effects
even at maximum interrupting capacity.
Switch
S 800 S 1000 S 1250 S 1600 S 2000 S 2500 S 3200 S 4000 S 5000 S 6400
Rated thermal current Ith 40°C (A) 800 1000 1250 1600 2000 2500 3200 4000 5000 6400
Rated peak short circuit making capacity Icm
(max) (kA peak) 125 125 125 125 140 150 190 200 270 270
RMS short time withstand current Icw (at 415V)
0.5 s. (kA eff.) 55 55 55 55 65 70 - - - -
1 s. (kA eff.) 55 55 55 55 65 70 85 90 120 120
Dimensions in mm (fixed circuit breaker):
see table above
SPECTRONIC L - Air circuit breakers
Main characteristics of
limiting L circuit breakers
Installation safety Economy: high limitation of short circuit current
peak The high limitation of short-circuit current allows significant savings on conductors (cables or ducts)
I kA
240
and on the mechanical structure of the networks.
50
I2t 106 A2 sec
70
40
- 2000
t L 1600
C 30
42
L 1250
20
00
10 L 640 - 10
Setting ranges
Setting points
LT (x In) 0.4 - 0.5 - 0.6 - 0.7 - 0.75 - 0.8 - 0.85 - 0.9 - 0.95 - 1
LTD (s) 5 - 10 - 15 - 20 - 25 - 30 - 35 - 40 delay at 7.2 lr
ST (x ln) 1.5 - 2 - 3 - 4 - 5 - 7 - 9 - 10 - 12 - 14
Time delay (ms) 30 - 60 - 90 - 120 - 150 - 180 - 210 - 240- 270 - 300
I (x ln) 1.5 - 2 - 3 - 5 - 7 - 10 - 15 - OFF
GF (x In) S 800 - S 2000: 0.2 - 0.3 - 0.4 - 0.5 - 0.6 - 0.7 - 0.8
S 2500: 0.2 - 0.3 - 0.35 - 0.45 - 0.55 - 0.6 - 0.7
S 3200 - S 6400: 0.2 - 0.3 - 0.35 - 0.45
L 640 - L 2000: 0.2 - 0.3 - 0.4 - 0.5 - 0.6 - 0.7 - 0.8
C Time delay (ms) 100 - 200 - 300
44 Ir = k x In
Note
If the GF function is selected, the fourth CT's must be of the same rating
as the ones of the phases.
Options
Distinct fault signalling (LT, ST-I, GF)
This option displays locally by LED the origin of the fault.
Tamper proofing
A transparent screen avoids the access to the settings.
Each pole is factory equipped with ultra-rapid releases set at 7.5 times the
nominal intensity.
The trip operation threshold may be set to a different value on
request (see table above).
0.7
1.05
1,05 Operating limits UTE - IEC
1,3
1.3
LT threshold in k x In
k = 0.4 - 0.5 - 0.6 - 0.7 - 0.75 -
C
0.8 - 0.85 - 0.9 - 0.95 - 1.0 45
times the current transformer rating
40
LT time delay 5 - 10 - 15 - 20 -
25 - 30 - 35 - 40 s. at 7.2Ir
35
30
25
Time in seconds
20
15
10
ST threshold 1.5 - 2 - 3 -
4 - 5 - 7 - 9 - 10 - 12 - 14
times the LT value (Ir)
30
Setting ranges
Setting points
LT (x In) 0.5 - 1 (steps of 0.05)
LTD (s) 3 - 6 - 12 - 25 / at 6 lr
ST (x lr) 1.5 - 9 (steps of 0.5)
Time delay (ms) 100 - 210 - 350
I (x lr) 1.5 - 15 - OFF (steps of 0.5) RMS 9 2000
A actuator Each function can be time delayed within a range from 1 to 15 seconds
sampler
(+ OFF position).
microprocessor
B
RMS 9
C
Distinct fault signalisation
By local display with the RMS 9 unit in 'Status' mode the condition of the
keyboard breaker is indicated. Also the time and number releases under fault:
LCD display - LT, ST, I, GF
- undervoltage, overvoltage, ..., reversal power.
SPECTRONIC S/L - Air circuit breakers
auxiliary
power supply
24V dc
voltage
conditioner (1,76V)
actuator
A/D converter
sampler
current
microprocessor
transformers (3 or 4)
RMS 9
relay
keyboard
LCD display
communication
(Power Leader Network)
Structure
I max (A) without communication with communication
2000 RMS 9 2000 RMS 9 2000C
3200 RMS 9 3200 RMS 9 3200C
4000 RMS 9 4000 RMS 9 4000C
SPECTRONIC S/L - Air circuit breakers
1.05
Operating limits according to IEC
1.3
C LT thresholds in k x In
0.5 to 1 times the current transformer
48 rating (0.05 steps)
LT time delay
3 - 6 - 12 - 25 s at 6 Ir
Time in seconds
ST thresholds
1.5 to 9 times
the LT value (lr)
ST time delay
0.100 - 0.210 - 0.350 s
Electrical control
Description
Integrated within the overall dimensions of the circuit breaker the adaptation of the electical motor
operator can be easily done on site.
Stored energy type: a universal motor loads a spring through a reduction gear. The spring stores the
energy necessary for closing the air circuit breaker.
The closing of the air circuit breaker can be done:
- remotely, a closing coil EE.
- locally by a pushbutton located on the control panel.
The opening of the circuit breaker can be done:
- remotely, by undervoltage or shunt release,
- locally by a pushbutton located on the control panel.
The spring is automatically reset after closing of the air circuit breaker enabling successive operations
without energy supply of:
- 1 tripping operation
- 1 closing operation
- 1 tripping operation
Anti-pumping device in case of sustained closing command.
Visible indication, on the face plate of the spring state:
C
- yellow: spring unloaded 49
- blue: spring loaded.
Closing prevention device (FE) if the voltage is too low. (Option)
Characteristics
Resetting time of the electrical control: 7 s.
Closing time: 0.06 s.
Motor
Rated voltages
Alternating current 50-60Hz 48 - 127 - 220V Main diagram
380V (on request)
Direct current 24 - 48 - 110 - 220V
Power dissipated 640 to 3200 to
2500A 6400A R
Alternating current 175VA 400VA
Direct current 150W 350W
FCA
Operation voltage from 0.85 to 1.1 Un U1 M U2
CA8
C1 EA C2
Voltmetric releases
Characteristics
shunt trip undervoltage
release release
EA EA1 UVR
Rated voltage Un
alternating current 50Hz (V) 24 - 48 - 127 - 220 - 127 - 220 - 380 - 24 - 48 - 127 - 220 -
380/500 415 - 500 380 - 415 - 500
alternating current 60Hz (V) 24 - 48 - 127 - 220 - 127 - 220 - 380 - 24 - 48 - 127 - 220 -
380/500 415 - 500 380/415 - 500
direct current (V) 24 - 48 - 110/120 - - 24 - 48 - 110 - 120 -
220 220 - 440 - 500
Operating voltage from 0.7 to 1.1 Un from 0.1 to 1.3 Un from 0.35 to 0.7Un(1)
Power absorbed
alternating current closing (VA) 80 to 100 800 23
holding (VA) - - 10
direct current ≤ 220V (W) 30 - 6
440-500V (W) 275 - 21
Opening time of the circuit (ms) 60 60 85
C Two types of voltmetric releases permit remote
operation of the circuit breaker. Maximum equipment
50
Shunt trip releases EA-EA1 1st possibility 1 1 –
2nd possibility – 1 1
Open the circuit breaker (power supply out by an 3rd possibility 1 – 1(2)
auxiliary contact). 4th possibility – – 2(2)
(1) Closing of the circuit breaker ensured from 0.85. (2) or UVRD
Undervoltage releases UVR-UVRD
Open the circuit breaker when the supply voltage
falls to a value between 35 and 70% of its rated
value.
UVR: instantaneous action.
UVRD: delayed action of 250 ms or 0,6 s
alternating current power supply.
Other delaying devices on request.
Consumption
Alternating current
closing (VA) 23
holding (VA) 10
Direct current
± 220V (W) 6
440-550V (W) 21
500V (W) 21
SPECTRONIC S/L - Auxiliaries
Auxiliary switches
Possibility of eight auxiliary switches NO + NC accessible from the front of the circuit breaker:
- four switches (AS1, AS2, AS3, AS4) operate at the same time as the main poles,
- four switches (AS5, AS6, AS7, AS8) operate at the beginning of the breaker closing movement.
Characteristics
Thermal current Ith 20A
Breaking capacity
alternative current cos ϕ 0.3
500V 6A
direct current L/R ≤ 0.01 s
110V 2.5A
250V 0.8A
Low voltage contacts 4 to 30V - 1 to 100mA
on S 800 to 6400 and L 640 to 2000
Diagram
C
51
13 14
CA1
11 12
23 24
CA2
21 22
not available
if EA or EA1 used
83 84
CA8
81 82
SPECTRONIC S/L - Auxiliaries
L1
B1 3
4 K1 1
CD S1
Rejection feature
Mechanical device preventing plugging in a breaker with a rating different to the one normally
used in the cradle.
Ground plug
C
53
Optional equipment for “Connected” position contact
withdrawable circuit breakers Indicates the position of the circuit breaker in its cradle.
Possibility of two changeover switches C 51, C 52, activated at the end of plugg-in operation.
Low voltage contacts possible on circuit breakers L 640 to 2000 and S 800 to 4000:
4 to 30V - 1 to 100mA. Connection by clips of 6.35 mm.
Safety contact
Indicates that the closing of the circuit breaker may be actioned; this being in the connected position,
cranks not inserted.
Possibility of switch contact C 71.
Connection by clips of 6.35 mm.
Isolating shutter
Access to live parts of the circuit breaker is
inhibited in the “withdrawn” position (IP20) with a Contact characteristics
padlock system (padlocks not supplied). 640 to 4000A 5000 - 6400A
Thermal current Ith A 20 25
Breaking capacity
alternating current
220V A - 10
250V A 16 -
380V A - 5.4
direct current
30V A - 8
110V A 0.4 0.5
220V A 0.2 0.4
Circuit breakers L 640 to L 2000 and S 800 to 4000 Circuit breakers S 5000 and S 6400
Fixed circuit breakers Fixed circuit breakers
Interlocking in “tripped” position by lock Interlocks in “tripped” position by lock
(not supplied) (not supplied)
Possibilities: Possibilities:
- a Ronis lock, type 1104, 1/4 turn, opening to the left, - a Ronis lock, type 1104, 1/4 turn, opening to the left
- or a Profalux lock, type KS 5B G4Y - or a Profalux lock, type KS 5B G4Y
- or a CASTELL type lock FS 1. - or 1 CASTELL lock type FS 1.
Interlocking in “tripped” position by padlocks Interlocking in “tripped” position by padlock
Possibility: three padlocks. Possibility: three padlocks.
Interlocking of local control by padlocks Interlocking of local control by padlocks
For electrically operated circuit breaker: padlockable shutter preventing For electrically operated circuit breaker: padlockable shutter preventing
access to the closing and trip pushbutton. access to the closing and trip pushbuttons.
Possibility: two padlocks. Possibility: two padlocks.
D E F
Description
Source changeover switches have the same characteristics and adaptability to the circuits to be
protected as the circuit breakers with which they are built. C
In the withdrawable version, the inoperative breaker can be disconnected without affecting the 55
operation of the breaker “In service”.
The device, when equipped with interlock in the “withdrawn” position conforms to the NF C 13-100
standard.
Source changeover switches consist of:
1. Two or three circuit breakers
- designed to be mechanically interlocked
- fitted with auxiliaries, wired and brought to the auxiliary terminal as needed for the chosen
diagram
- may be identical, or may differ in the following:
- circuit breaker
- type
- protection system
- structure (possible combination of fixed and withdrawable types)
2. A mechanical interlocking system
3. A mounting frame
4. An automatic controller comprising the relays necessary for operation of the source changeover
switches (not supplied)
Installation
The circuit breakers are superposed or placed side by side (with cables interlocking).
Changeover devices can be supplied in the following forms:
- either complete and mounted on a frame, ready to connect (selector switch not wired).
- or mounted on a frame, without automatism,
- or circuit breakers and mechanical interlocking delivered separately.
Characteristics
Operating voltage (VAC) 50Hz 220 - 380
Automatic without
power supply auxiliary supply (VAC) 50Hz 220 - 380
with (VAC) 50Hz 48 - 127 - 220 - 380
auxiliary supply (VDC) 24 - 48 - 110 - 220
Consumption circuit breaker ratings S 800 to 1600 S 2000 and 2500 S 3200 and 4000
during changeover (VA) 500 500 720
(W) 450 450 650
continuous (VA) 26 26 26
(W) 37 37 37
Minimum normal © with shunt trip release 2 s(1)
changeover replacement with undervoltage release 2 s(1)
time replacement with shunt trip release 2s
normal © with undervoltage release 2s
(1) If necessary, add the start up time of the generator.
SPECTRONIC S/L - Source Changeover Switches
(1)
Refer to the circuit breaker specification
(2)
Operation
Two normal supplies possible One normal supply (on request)
normal 1 0 x 0 0 x normal 1 0 x 0 0
remplacement 0 0 x 0 0 replacement 0 0 x 0
normal 2 0 0 0 x x normal 2 0 0 0 x
x: closed circuit breaker x: closed circuit breaker
Notes
1. For a different installation an
interlocking by cables can be provided.
2. S 5000 - 6400: consult the sales
office.
SPECTRONIC S/L - Air Circuit Breakers
Circuit breakers
Without protection S800 S1000 S1250 S1600 S2000 S2500 S3200 S4000
FIXED with rear horizontal 3P 754303 754313 754323 754333 754343 754353 754363 754373
terminals
4P 754304 754314 754324 754334 754344 754354 754364 754374
WITHDRAWABLE
3P 754301 754311 754321 754331 754341 754351 754361 754371
Moving part
4P 754302 754312 754322 754332 754342 754352 754362 754372
+
Fixed part 3P 754451 754451 754453 754455 754457 754459 754461 754463
Cradle with rear
4P 754452 754452 754454 754456 754458 754460 754462 754464
horizontal terminals
Cradle with rear 3P 754471 754471 754473 754475 754477 754479 - -
C
vertical terminals 59
4P 754472 754472 754474 754476 754478 754480 - -
Cradle with 3P 754481 754481 754483 754485 754487 754489 754491 754493
front terminals
4P 754482 754482 754484 754486 754488 754490 754492 754494
WITHDRAWABLE
Moving part 3P 754260 754262
+ 4P 754261 754263
Fixed part:
cradle with rear 3P 751222 751223
vertical terminals 4P 751224 751225
SPECTRONIC S - Order codes
Current transformer
Three pole equipment Rating A S 800 S1000 S 1250 S 1600 S 2000 S 2500 S 3200 S 4000 S 5000 S 6400
800 755460 - - - - - - - - -
1000 - 755461 - - - - - - - -
1250 - - 755462 - - - - - - -
C 1600 - - - 755463 - - - - - -
60
2000 - - - - 755464 - - - - -
2500 - - - - - 755465 - - - -
3200 - - - - - - 755466 - - -
4000 - - - - - - - 755467 - -
5000 - - - - - - - - 755468 -
+ 6400 - - - - - - - - - 755469
Equipment for the fourth pole Rating A S 800 S1000 S 1250 S 1600 S 2000 S 2500 S 3200 S 4000 S 5000 S 6400
800 755470 - - - - - - - - -
1000 - 755471 - - - - - - - -
1250 - - 755472 - - - - - - -
1600 - - - 755473 - - - - - -
2000 - - - - 755474 - - - - -
2500 - - - - - 755475 - - - -
3200 - - - - - - 755476 - - -
4000 - - - - - - - 755477 - -
5000 - - - - - - - - 755478 -
6400 - - - - - - - - - 755479
SPECTRONIC S - Order codes
Rating plug
3P/3P+N 100% Rating A S 800 S1000 S 1250 S 1600 S 2000 S 2500 S 3200 S 4000 S 5000 S 6400
400 755554 - - - - - - - - -
600 755553 - - - - - - - - -
800 755550 755563 - 755584 - - - - - -
1000 - 755560 - - - - - - - -
1200 - - - 755583 755593 - - - - -
1250 - - 755570 - - - - - - -
1600 - - - 755580 - 755603 755613 - - -
2000 - - - - 755590 - - - - -
2500 - - - - - 755600 - 755623 - -
3200 - - - - - - 755610 - - -
4000 - - - - - - - 755620 - -
C
61
5000 - - - - - - - - 755630 -
6400 - - - - - - - - - 755640
3P+N 50% Rating A S 800 S1000 S 1250 S 1600 S 2000 S 2500 S 3200 S 4000 S 5000 S 6400
800 755552 - - - - - - - - -
1000 - 755562 - - - - - - - -
1250 - - 755572 - - - - - - -
1600 - - - 755582 - - - - - -
2000 - - - - 755592 - - - - -
2500 - - - - - 755602 - - - -
3200 - - - - - - 755612 - - -
4000 - - - - - - - 755622 - -
5000 - - - - - - - - 755632 -
6400 - - - - - - - - - 755642
With integrated GF Rating A S 800 S1000 S 1250 S 1600 S 2000 S 2500 S 3200 S 4000 S 5000 S 6400
400 755555 - - - - - - - - -
600 755556 - - - - - - - - -
800 755557 755565 - 755585 - - - - - -
1000 - 755566 - - - - - - - -
1200 - - - 755586 755595 - - - - -
1250 - - 755575 - - - - - - -
1600 - - - 755587 - 755605 755615 - - -
2000 - - - - 755596 - - - - -
2500 - - - - - 755606 - 755625 - -
3200 - - - - - - 755616 - - -
4000 - - - - - - - 755626 - -
5000 - - - - - - - - 755635 -
6400 - - - - - - - - - 755645
SPECTRONIC S - Order codes
RMS 9 protection The RMS 9 is always composed of two references: RMS 9 + adaptor plate
Current transformer
C Three pole equipment rating A S 800 S 1000 S 1250 S 1600 S 2000 S 3200 S 4000
62 800 755410 - - - - - -
1000 - 755411 - - - - -
1250 - - 755412 - - - -
1600 - - - 755413 - - -
2000 - - - - 755414 - -
3200 - - - - - 755440 -
+ 4000 - - - - - - 755441
Equipment for 4th pole 800 755420 - - - - -
(100% or reduced neutral)
1000 - 755421 - - - - -
1250 - - 755422 - - - -
1600 - - - 755423 - - -
2000 - - - - 755424 - -
3200 - - - - - 755442 -
4000 - - - - - - 755443
SPECTRONIC S - Order codes
Note
Don’t forget the auxiliary power supply
(not supplied)
Number of secondary disconnections to use:
- voltage conditioner 4 wires
- auxiliary power supply 2 wires
- communication 2 wires
SPECTRONIC S - Order codes
WITHDRAWABLE
Moving part 3P 754305 754315 754325 754335 754345 754355 754365 754375
+ 4P 754306 754316 754326 754336 754346 754356 754366 754376
Fixed part
3P 754451 754451 754453 754455 754457 754459 754461 754463
Cradle with rear
horizontal terminals 4P 754452 754452 754454 754456 754458 754460 754462 754464
C Cradle with rear
3P 754471 754471 754473 754475 754477 754479 - -
64 vertical terminals
4P 754472 754472 754474 754476 754478 754480 - -
Cradle with front 3P 754481 754481 754483 754485 754487 754489 754491 754493
terminals
4P 754482 754482 754484 754486 754488 754490 754492 754494
Withdrawable circuit breaker 3P 754155 754155 754155 754155 754165 754175 754185 754185
4P 754156 754156 754156 754156 754166 754176 754186 754186
SPECTRONIC L - Order codes
Current transformer
Three pole equipment Rating A L 640 L 1000 L 1250 L 1600 L 2000
640 755481 - - - -
1000 - 755482 - - -
1250 - - 755483 - -
1600 - - - 755484 -
2000 - - - - 755485
+
Equipment for the fourth pole Rating A L 640 L 1000 L 1250 L 1600 L 2000
640 755491 - - - -
1000 - 755492 - - -
1250 - - 755493 - -
1600 - - - 755494 -
2000 - - - - 755495
SPECTRONIC L - Order codes
Rating plug
3P/3P+N 100% Rating A L 640 L 1000 L 1250 L 1600 L 2000
400 755530 - - - -
640 755540 - - - -
800 - 755563 - 755584 -
1000 - 755560 - - -
1200 - - - 755583 755593
1250 - - 755570 - -
1600 - - - 755580 -
2000 - - - - 755590
Options
For RMS 7 unit
755457 Distinct fault signalling
Electrical auxiliaries
Electrical control
Use 4 connection
terminals or secondary
disconnection devices
S 800 to S 2500
L 640 to L 2000
S 3200 - S 4000
S 5000 - S 6400
C
67
Motor Coil Motor Coil
AC 50Hz
751855 751950 751849 751962 48V
751857 751951 751851 751963 127V
751858 751952 751852 751964 220V
754060 751977 751852 751978 240V
- 751953 751853 751965 380V
AC 60Hz
751855 751954 751849 751966 48V
751857 751955 751851 751967 127V
751858 751956 751852 751968 220V
754060 - - - 240V
- 751957 751853 751969 380V
DC
751854 751958 751848 751970 24V
751855 751959 751849 751971 48V
755275 755276 - - 60V
751856 751960 751850 751972 110V
751857 755890 751851 751986 127V
751858 751961 751852 751973 220V
754060 751975 - - 240V
SPECTRONIC S/L - Order codes
Electrical auxiliaries
Shunt trip release Undervoltage trip Closing prevention device
UVRD 250 ms
AC 50Hz
752318 220V
752319 380V
MVR 0.6 s
AC 50Hz
752322 220V
752323 380V
SPECTRONIC S/L - Order codes
Accessories
S800 S1000 S1250 S1600 S2000 S2500 S3200 S4000 S5000 S6400
Isolating shutter
3P 752524 752524 752524 752524 752525 752526 752529 752529 752531 752531
4P 752525 752525 752525 752525 752527 752528 752530 752530 752532 752532
C
71
SPECTRONIC S - Overall dimensions
Gasket
C
72
Gasket
Legend
Circuit breaker Number A B C D E Front or rear horizontal connection terminals
of poles
S 800-1000-1250 3 318 98 101.5 81 15
S 1600 4 406 98 96.5 76 15 S800 to 1000 S1250 to 1600
S 2000 3 406 130 113.5 93 10
4 540 130 115.5 95 10
S 2500 3 474 150 127.5 107 15
4 620 150 125.5 105 15
S2000 S2500
F = minimum clearance distance above the arc chutes.
Ue ≤ 500V Ue ≤ 690V
I = insulated screen 150 mm 200 mm
M = metallic screen 150 mm 150 mm
SPECTRONIC S/L - Overall dimensions
a = door gasket
b = withdrawable door
closed
c = withdrawable door
open
(2) connected circuit
breaker
4 holes ) 10,2
C
Connections 73
Rear horizontal Rear vertical Front terminals Disconnected- Withdrawn
terminals (R.H.T.) terminals (R.V.T.) (T.D.) isolated position position
insulator
(2) connected
(3) disconnected
(4) withdrawn
F.T.: Front terminals R.V.T.: Rear vertical terminals R.H.T.: Rear horizontal terminals
SPECTRONIC S/L - Overall dimensions
Gasket
C
74
F G
S 3200 3x5 127
S 4000 5x5 121.5
192
60
Legend
S 3200 S 4000
Circuit breaker Number A B C D
of poles Ø13 Ø13
S 3200-4000 3 628 238.5 132 201.5
4 826 436.5 130 399.5 50 25 50 25
E = minimum clearance distance above the arc chutes.
12,5 25 25 25 25 12,5 25 25 25 25 25 17,5
Ue ≤ 500V Ue ≤ 690V
125 160
I = insulated screen 200 mm 200 mm
M = metallic screen 200 mm 200 mm
SPECTRONIC S/L - Overall dimensions
Withdrawn
Withdrawn isolated
Gasket
C
75
Connected
Withdrawable Withdrawable
door closed door open
Panel cut-out for gasket fitting Front or rear horizontal connection terminals
F G
S 3200 3x5 266.5
S 4000 5x5 261.5
Legend
Rear connections Front connections
Circuit breaker Number A B C D
of poles
S 3200-4000 3 711 235 130.5 198 Ø13
125
4 909 433 129.5 396 62,5 Ø18
50 25
E = minimum clearance distance above the arc chutes. 31,25
C
76
Gasket
C
77
Panel cut-out for gasket fitting Panel cut-out for gasket fitting
Gasket
Legend
holes
C
78
Connected
Disconnected
Connection terminals
S 6400
4 holes ) 14
Gasket
Legend
Circuit breaker Number
of poles A B C
S 5000-6400 3 1428 714 1320
4 1792 896 1684
E = minimum clearance distance above the arc chutes.
Ue ≤ 500V Ue ≤ 690V
I = insulated screen 100 mm 200 mm
M = metallic screen 200 mm 200 mm
Notes
C
79
SPECTRONIC S/L - Overall dimensions
C
80
Legend
Circuit breaker Number A B C D
of poles
L 640 - 1000 3 318 98 101.5 81
4 406 98 96.5 76
L 1250 3 406 115 128.5 108
4 474 115 105 84.5
L 1600 3 406 130 113.5 93
4 540 130 115.5 95
L 2000 3 474 150 127.5 107
4 620 150 125.5 105
a = door gasket
b = withdrawable
door closed
c = withdrawable
door open
(2) connected
circuit breaker
4 holes ) 10.2
Connections
C
81
Rear horizontal Rear vertical Front terminals Disconnected- Withdrawn
terminals (R.H.T.) terminals (R.V.T.) (F.T.) isolated position
position
isolator
(2) Connected
(3) Disconnected
(4) Withdrawn
C
82
Circuit breaker A B C D
3P 4P 3P 4P fixed W/D fixed W/D White area: interlocking brackets dimensions
S 800 to 1600 351 439 77.5 72.5 15.5 79 (3) 417.5
L 640 - L 1000
L 1250 439 507 104.5 81 15.5 79 412.5 417.5
S 2000 - L 1600 439 573 89.5 91.5 15.5 79 412.5 417.5
S 2500 - L 2000 507 653 103.5 101.5 15.5 79 (3) 417.5
S3200 - S 4000 661 859 (1) (2) 52.5 154.5 (3) 474.5
C
83
Circuit breaker A B C D
3P 4P 3P 4P fixed W/D fixed W/D White area: interlocking brackets dimensions
S 800 to 1600 351 439 77.5 72.5 15.5 79 (3) 347.5
L 640 - L 1000
L 1250 439 507 104.5 81 15.5 79 342.5 347.5
S 2000 - L 1600 439 573 89.5 91.5 15.5 79 342.5 347.5
S 2500 - L 2000 507 653 103.5 101.5 15.5 79 (3) 347.5
S3200 - S 4000 661 859 (1) (2) 52.5 154.5 (3) 404.5
C
84
Circuit breaker A B C D E
fixed W/D fixed W/D fixed W/D
3P 4P 3P 4P 3P 4P 3P 4P
S 800 to 1600 696 696 666 666 111.8 127.3 141 136 141.5 136.5 (3) 417.5
L 640 - L 1000
L 1250 696 696 666 666 111.8 127.3 168 144.5 168.5 145 412.5 417.5
S 2000 - L 1600 696 842 666 812 111.8 127.3 153 155 153.5 155.5 412.5 417.5
S 2500 - L 2000 696 842 668 812 111.8 127.3 167 165 167.5 165.5 (3) 417.5
S 3200 - S 4000 1048 1048 1018 1018 312.3(1) 327.3(2) 191 189 193 192 (3) 474
C
85
Circuit breaker A B C D E
fixed W/D fixed W/D fixed W/D
3P 4P 3P 4P 3P 4P 3P 4P
S 800 to 1600 696 696 666 666 111.8 127.3 141 136 141.5 136.5 (3) 417.5
L 640 - L 1000
L 1250 696 696 666 666 111.8 127.3 168 144.5 168.5 145 412.5 417.5
S 2000 - L 1600 696 842 666 812 111.8 127.3 153 155 153.5 155.5 412.5 417.5
S 2500 - L 2000 696 842 668 812 111.8 127.3 167 165 167.5 165.5 (3) 417.5
S 3200 - S 4000 1048 1048 1018 1018 312.3(1) 327.3(2) 191 189 193 192 (3) 474
Ph.1 +
Secondary
Fault
disconnector 50 49
C N
C
86
Fault RMS7
signalling
EX
Ph.2 -
Fault signalling
Option Protection unit by relay Faults contacts
Legend
Overcurrent releases Operation with energy storage
CD Overload and short-circuit fault contact M Motor
K1 Fault signalling relay FCA Resetting limit switch
R1 Booster voltage for 220V Manual setting
S1 Fault cancelling push-button CA 1-8 Auxiliary contacts
GF Ground fault indicator lamp EE Closing coil
ST-I Instantaneous or short duration (short-circuit) S2 Remote tripping control
tripping indicator lamp S5 Remote closing control
LT Long time trip (overload) tripping indicator lamp S3 Remote closing and tripping control changeover switch
Voltmetric releases C22 Reset contact of the spring
C41 Trip contact MV-MVR C20 Contact coupled with local reset tripping push-button
C43 Undervoltage contact MV-MVR FE Closing prevented on undervoltage
C31 Trip contact EA Withdrawable
Ra-R6 Booster resistor for certain direct current voltages C51.52 Contacts 'connected' position
S1 Optional disconnecting switch MV-MVR (break out of service) C61.62 Contacts 'withdrawn' position
C71 Pre-trip contact coupled with insertion control
SPECTRONIC S/L - RMS 7 diagram
44
222 42
224
C
87
C22
221 41
43
0C1
0C2
LEFT RIGHT
442
444
441
421
424
422
321
324
322
432
434
431
411
414
412
311
314
312
D1
D2
C1
C2
MV - MVR EA 50
CN
49
MV or MVR
14 11 12 CD2
E2
E1
CD1 U2 Electrical
U1
EA1 or EA A2 control
A1
or MV .MVR
SPECTRONIC S/L - RMS 9 diagram
Ph. 1 +
N
Ph1
S1
R
Transmission
Voltage
Ph2 Fault S1
Ph3
conditioner S
T
50 49 32 29
Secondary
T S R S1 15 14
disconnectors
C 5 6
88
RMS9
T S R S1
MONITOR
17 33 16 28
4
EX
Secondary
disconnectors
Ph. 2
RMS 9 Fault signalling
protection unit by relay
Legend
Ammetric releases Stored energy control
CD Short-circuit and overload fault signalling contact M Motor
K1 Short-circuit signalling relay FCA Reset limit switch
S1 Fault reset push button Manual reset
GF Ground fault display AS 1-8 Auxiliary switches
ST-I Instantaneous (short circuit) tripping display Ra Economy resistor for selected voltages in direct current
LT Long time (overload) tripping display EE Closing coil
Voltmetric releases S2 Remote trip push-button
C41 Trip contact UVR-UVRD S5 Remote closing push-button
C43 Minimum voltage contact UVR-UVRD S3 Remote closing and tripping changeover switch
C31 Trip contact EA C22 Spring reset contact
R5-R6 Economy resistor for selected direct current voltages C20 Contact coupled with local resetting push-button
S4 Optional switch to disable UVR-UVRD FEa Closing prevention device
(circuit breaker disconnected)
Withdrawable
C51.52 “Connected” position contact
C61.62 “Withdrawn” position contact
C71 Pre-tripping contact associated with plug-in control device
SPECTRONIC S/L - RMS 9 diagram
M UVR
C
89
BA2
BA1
RMS9
29+ 15-
32- 14+
UVR or UVRD RMS9
BA2
E2
E1
BA1 U2 Electrical
U1 control
ST1 or ST A2
A1
or UVR . UVRD
reserved terminal(s)
direction of wiring
SPECTRONIC S/L - Connections/weights
C S 800-1000 3P
4P
51
55
56
60
90
98
95
103
90 S 1250 3P 53 58 97 102
4P 59 64 108 113
S 1600 3P 58 63 104 109
4P 67 72 117 122
S 2000 3P 65 70 119 124
4P 74 79 124 129
S 2500 3P 67 72 125 130
4P 82 87 132 137
S 3200 3P 112 116 185 189
4P 142 146 232 236
S 4000 3P 118 122 191 195
4P 150 154 240 244
S 5000 3P 200(1) 210(1) 376 380
(1)
4P 240 250(1) 458 462
(1)
S 6400 3P 230 240(1) 411 415
(1)
4P 290 300(1) 506 510
(1) For vertical circuit breakers.
For horizontal circuit breakers, deduct 10 kg.