SPECTRONIC SP - Air circuit breakers

Summary
C.3 General characteristics

C.4 Fixed circuit breaker

C.5 Withdrawable circuit breakers

C.6 Characteristics

C.7 RMS 7: protection and control unit

C.10 RMS 9: protection and measurement unit

C.13 Auxiliaries
C
1

C.13 Electrical control

C.14 Shunt and undervoltage releases

C.15 Signalling and fault contacts

C.16 Equipment

C.17 Interlocking

C.18 Source changeover switches

C.21 Order codes

C.26 Overall dimensions

C.29 Connections

C.29 Weights

C.30 RMS 7 diagram

C.32 RMS 9 diagram

For more information, please contact: C.35 Spectronic type S/L


MAJESTIC GLOBAL LTD. www.mgl.hk
Notes

C
2
SPECTRONIC SP - Air circuit breakers

Circuit Breakers 800 to 2500A - Series SP


Rated short-circuit breaking capacity: Ics 50 to 55kA (415V)

Complete range
- Fixed or withdrawable versions
- 3 or 4 poles
- Electrical or manual control

The SPECTRONIC range combines the legendary reliability


of our air circuit breakers with:
- A design adapted to the new panel boards
- Two types of protection relays: RMS 7 and RMS 9
Main advantages
- Clever design combining longevity and reliability
C
3
- Maximum service: total selectivity is ensured, even at
closing on short circuit
- Simple and efficient servicing on site
- Safety ensured by fully visible breaking.
Conformity
The circuit breakers SP are built according to the following
standards: IEC 947-2, BS, CEI, NBN, NFC and VDE.
Certification: Bureau Véritas, Lloyd’s Register of Shipping,
ASEFA. Rated short-circuit breaking capacity
Certification: Germanischer Lloyd (in accordance with following IEC 947-2 (415V)
IEC 157.1) Icu (kA)
Tropicalisation 60
SP SP
- Class I (standard): Relative humidity of 55 2000 2500
SP SP SP SP
80% at 40°C
800 1000 1250 1600
(Hot and dry or damp climate of temperature zones).
- Class II: Relative humidity of 95% at 45°C
(hot and damp climate).
Anti-corrosion treatment
For special atmospheres, consult us.

0
800 1000 1250 1600 2000 2500 Ith (A)
SPECTRONIC SP - Air circuit breakers

Fixed circuit breaker

C 14
4

19 13 5

Description 1 Local trip and reset push button (BPDL).


2 Circuit breaker position indicator. Red = closed - Green = open.
Fitted at the factory with a control panel providing an IP30 degree of
protection. For panel mounting, a seal and a cover permit IP3X protection 3 Trip lever prior to withdrawal or plugged-in operations.
with the door closed.
4 Auxiliary switches.
Installation 5 RMS 7 or RMS 9 releases.
- Fixed to vertical uprights or on horizontal surface. 6 Volmetric releases: shunt and undervoltage releases.
- Main connections (see table page D.27). 7 Locking in “connected” position or locking in “withdrawn” position.
- Connections to auxiliary circuits by terminals located at the front of the 8 Fixed auxiliary terminal block.
unit (max 24 terminals).
- Supplied with 12 terminals as standard, mounted on the right. 9 Mobile auxiliary terminal block
10 Electrical control.
Power supply orientation
11 Current transformer.
Up to 415V, connections are made either to the upper or lower terminal
12 Position contact ‘withdrawn-inserted’.
clamps. Above 415V, connect to the upper terminals.
13 EX trip actuator.
14 Distinct fault signalling.
15 Arc chute.
16 Isolating shutter.
17 Reinforced ground plug.
18 Primary jaw.
19 Fault contact.
SPECTRONIC SP - Air circuit breakers

Withdrawable circuit breaker

11 15 18

C
5

10 8

Description
The circuit breaker is mounted on a cradle fitted with slides allowing two
positions: “inserted” and “withdrawn-isolated”.
The insertion and withdrawal operations are performed by a screw-nut
system, operated by two removable cranks.
Automatic tripping of the breaker on withdrawal is ensured by a safety
device at the insertion of the cranks.
For panel mounting, a seal and a cover, permit IP3x protection with the
door closed.
2
The circuit breaker may be withdrawn either with the door closed or open.

9 Installation
3
- Fixing to the vertical uprights by rear surface or on a horizontal surface
by adding L pieces on side faces.
- Main connections (see table on page D.27).
- The auxiliary circuits disconnect automatically and simultaneously with
1 7 the main circuit.
12 - Connections to the auxiliary circuits are made laterally with
clips(maximum 24 terminals)
- Standard unit equipped with 12 terminals.

Power supply orientation


8 Up to 415V, connections are made either to the upper or lower terminal
clamps. Above 415V, connect to the upper terminals.

16 17
SPECTRONIC SP - Air circuit breakers

Characteristics
Circuit Breakers
SP 800 SP 1000 SP 1250 SP 1600 SP 2000 SP 2500
Rated insulation voltage Ui (V) 1000 1000 1000 1000 1000 1000
Rated impulse voltage Uimp (kV) 8 8 8 8 8 8
Rated maximum nominal voltage Ue (V) 690 690 690 690 690 690
Rated thermal current Ith 40°C (A) 800 1000 1250 1600 2000 2500
50°C (A) 800 1000 1250 1600 2000 2500
60°C (A) 800 1000 1250 1500 1900 2350
Rated ultimate short-circuit breaking capacity Icu
Alternating current 50/60Hz 240/415V (kA) 55 55 55 55 60 60
500V (kA) 35 35 35 35 35 35
690V(1) (kA) 40 40 40 40 40 40
Rated service short-circuit breaking capacity Ics
C Alternating current 50/60Hz 240/415V
500V
(kA)
(kA)
50
35
50
35
50
35
50
35
55
35
55
35
6
690V(1) (kA) 40 40 40 40 40 40
Rated peak short-circuit making capacity (max) Icm (kA peak) 120 120 120 120 130 130
Rated short time withstand current Icw: 1 sec.
415V (kA eff.) 50 50 50 50 55 55
500V (kA eff.) 35 35 35 35 35 35
Utilization category B B B B B B
Number of poles 3-4 3-4 3-4 3-4 3-4 3-4
Suitable for isolation (visible breaking indication) • • • • • •
Endurance (number of operating cycles)
Mechanical (total) # operating cycles 10000 10000 10000 10000 10000 10000
Electrical (at 415V)(2) # operating cycles 10000 10000 10000 10000 5000 3500
Mean time between maintenances # operating cycles 1500 1500 1500 1500 1500 1500
Power dissipation (withdrawable, 3 poles) (W) 150 200 300 400 450 500
4th pole conventional thermal current (A) 800 1000 1250 1600 1250(3) 1250(3)
Pollution degree 3 3 3 3 3 3
Dimensions in mm (fixed version)
3 poles Height (mm) 462 462 462 462 462 462
Width (mm) 370 370 370 370 464 464
Depth (mm) 273.5 273.5 273.5 273.5 273.5 273.5
4 poles Height (mm) 462 462 462 462 462 462
Width (mm) 458 458 458 458 52 562
Depth (mm) 273.5 273.5 273.5 273.5 273.5 273.5
(1) On request. (2) To guarantee this number of operations, it is necessary to check the spark
(3) Neutral reduced to the left. arrestors and the arc chutes as shown in the table above (Replace them when necessary)
This can be done easily on site

Switches
SP 800 SP 1000 SP 1250 SP 1600 SP 2000 SP 2500
Rated thermal current at 40°C Ith (A) 800 1000 1250 1600 2000 2500
Rated peak short-circuit making current Icm (kA peak) 120 120 120 120 130 130
Rated short time withstand current Icw: 1 sec.
415V (kA eff.) 50 50 50 50 55 55
500V (kA eff.) 35 35 35 35 35 35
Dimensions in mm (fixed circuit breaker):
See circuit breaker table above
SPECTRONIC SP - Air circuit breakers

RMS 7: Protection unit for SP800 to SP2500


Standard protection
- Overload protection (LT)
- Short-circuit protection (ST-I)
- Optional ground fault protection (GF)

Setting ranges
Setting points
LT (x In) 0.4 - 0.5 - 0.6 - 0.7 - 0.8 - 0.85 - 0.9 - 0.95 - 1
LTD (s) 5 - 10 - 15 - 20 - 25 - 30 - 35 - 40 delay at 7.2 lr
ST (x ln) 1.5 - 2 - 3 - 4 - 5 - 7 - 9 - 10 - 12 - 14
Time delay (ms) 30 - 60 - 90 - 120 - 150 - 180 - 210 - 240- 270 - 300
I (x ln) 1.5 - 2 - 3 - 5 - 7 - 10 - 15 - OFF
GF (x In) SP800 - SP2000: 0.2 - 0.3 - 0.4 - 0.5 - 0.6 - 0.7 - 0.8
SP2500: 0.2 - 0.3 - 0.35 - 0.45 - 0.55 - 0.6 - 0.7
Time delay (ms) 100 - 200 - 300
Ir = k x In C
Note 7
If the GF function is selected, the fourth CT's must be of the same rating as
the ones of the phases.

Options
Distinct fault signalling (LT, ST-I, GF)
This option displays locally by LED the origin of the fault.
Tamper proofing
A transparent screen avoids the access to the settings.

Description
The RMS 7 unit meets the requirements of the IEC 947.2 standard.
This unit is powered by the current transformers and performs all the
necessary three or four pole overcurrent protections.
The RMS 7 is designed to receive interchangeable rating plugs:
- 3 pole or 4 pole protection: 3P/3P+N
- 3 pole with half neutral protection: 3P+N50%
- 3 pole or 4 pole ground fault protection
SPECTRONIC SP - Air circuit breakers

RMS 7: Protection unit for SP800 to SP2500


Setting and operating current values

1.05
Operating limits - IEC
1.3

LT Threshold in k x In

C k = 0.5 - 0.6 - 0.7 - 0.8 - 0.9 -


1.0 times the current
8 transformer rating

LT Time delay
5 - 15 - 40 s. at 6Ir
Time in seconds

ST Threshold
2 - 3 - 4 - 6 - 8 - 10 times
the LT value (Ir)

ST Time delay
0.050 - 0.100 -
0.200 - 0.300 - 0.500 s

Instantaneous threshold (I)


2 - 3 - 5 - 8 - 10 times
the LT value (lr)

Multiples of current setting


SPECTRONIC SP - Air circuit breakers

RMS 9: Protection and measurement unit


Basic protection functions
- Overload protection (LT)
- Short circuit protection (ST and I)
- Ground fault protection (GF)

Setting ranges
Setting points
LT (x In) 0.5 - 1 (steps of 0.05)
LTD (s) 3 - 6 - 12 - 25 / to 6 lr
ST (x lr) 1.5 - 9 (steps of 0.05)
Time delay (ms) 100 - 210 - 350
I (x lr) 1.5 - 15 (steps of 0.5)
GF (x In) 0.2 - 0.6 (steps of 0.01)
Time delay (ms) 100 - 210 - 350
C
9
Ir = k x In
Note
If the GF function is selected, the 4th transformer must have the same
rating as the one of the phases.

Additional programmable functions


All or part of the programmable functions can be selected:
- under voltage < V (B)
- over voltage > V (B)
- voltage unbalance ∆V (B)
- current unbalance ∆I (A)
- reverse power Pi (B)
Description
(A) = Without voltage conditioner
Powered by the current transformers, Imax = 2000A, the RMS 9 2000 unit
(B) = with voltage conditioner
performs all the necessary current protections as well as measuring (RMS)
all the parameters.
As well as providing the above functions, the RMS 9 2000 can also perform Function Range (%) Step
remote event measurement and recording. <V 50 - 90 1
>V 110 - 150 1
∆V 10 - 50 1
∆I 10 - 50 1
Pi 10-990kW 10kW
current
transformers
N Each function can be time delayed with a range of 1 to 15 seconds sec.
A/D converter

A actuator (+ position OFF).


sampler

microprocessor

B
Distinct fault signalisation
RMS 9

C
By local display with the RMS 9 unit in 'Status' mode the condition of the
breaker is indicated. Also the time and number releases under fault:
keyboard - LT, ST, I, GF
- undervoltage, overvoltage, ..., reversal power.
LCD display
SPECTRONIC SP - Air circuit breakers

RMS 9: Protection and measurement unit Communication interface


“High precision” measurements Monitor
Without voltage conditioner
- Current on each phase (A, kA)
With voltage conditioner
- Current on each phase (A, kA)
- Voltage between phase and neutral (V)
- Voltage between phases (V)
- Energy (kWh, MWh)
- Active power per phase(1) (kW)
- Total active power (kW, MW)
- Total power per phase (1) (kVA, MVA)
- Total power (kVA, MVA)
- Average power demand (kW, MW)
C - Maximum power demand (kW, MW)
10 - Frequency (Hz)
(1) If the neutral is connected

To ensure a permanent display, the RMS 9 unit must be supplied by an auxiliary power supply of
24V DC - 15W regulated. The monitor collects all the information
available in the Spectronic circuit breakers
equipped with a RMS 9 2000C protection and
measurement unit.
auxiliary The communication is performed by the “Power
power supply Leader” protocol which is supported by a twisted
24V dc pair of wires.
voltage
The monitor performs:
conditioner (1,76V) - remote network parameter measurements:
- phase currents,
actuator - voltages direct and apparent,
A/D converter
sampler

current
- frequency,
microprocessor

transformers (3 or 4) - active, reactive and apparent power,


RMS 9

relay - maximum reached power,


keyboard
- energy.
- Remote recording of events and their origin:
- trippings (LT, ST-I, GF, ...),
LCD display - alarms (voltage or current unbalance, under
communication
voltage, ...).
(Power Leader Network)
The monitor can interface directly with 30
RMS 9 units at a distance of 2 kilometers.
Auxiliary supply
- 115V/230V AC - 50VA - 50/60Hz
- or 125V DC - 50W
SPECTRONIC SP - Air circuit breakers

RMS 9: Protection and measurement unit


Setting and operating current values

1.05
Operating limits - IEC
1.3

LT Threshold in k x In
0.5 to 1 times the current
transformer rating
C
11

LT Time delay
3 - 6 - 12 - 25 s. at 6 Ir
Time in seconds

ST Threshold
1.5 to 9 times
the LT value (Ir)

I²t OUT I²t IN

ST Time delay
0.100 - 0.210 - 0.350 s

Instantaneous threshold (I) 1.5 to


15 times the LT value (lr)
(in steps of 0.5)

Multiples of current setting


SPECTRONIC SP - Auxiliaries

Electrical control
The electrical control is integrated within the overall dimensions of the circuit breaker.
An easy adaption can be made to manual control.

Breaker mechanism driven by a device with a universal motor.


Automatic disconnection of the motor at the end of the operation.
”Making” via a relay.
Tripping by shunt trip or undervoltage release.
Manual emergency control.
Automatic reset.
Manual reset after tripping due to fault.

Note
In case of continuous signal to close, interrupt this signal during 0.3 sec minimum, to allow electrical
control to reset properly.
C Characteristics
12
Rated service voltage Un
Alternating current 50Hz V 48-110-127-220-240-380
Alternating current 60Hz V 48-110-220-240-380
Direct current V 48-60-110-220V
Operating voltage from 0.85 to 1.1 Un
Operating time at making ms 150 at Un
Power consumption
Breaker type SP800 to1600 SP2000 and 2500
Alternating current VA 1600 2000
Direct current W 800 1000

Electrical control 48V: section of the supply


cables to be specified in accordance with the
distance from the supply

Section (mm˝) Distance from supply (m)


2.5 4
4 7,5
6 11
10 21
SPECTRONIC SP - Auxiliaries

Voltmetric releases
Two types of releases enable the remote controlled operation of the circuit breaker.
SHUNT TRIP RELEASE EA-EA1-EB
Actuates the breaking of the circuit breaker (the power supply is cut by an auxiliary contact).

UNDERVOLTAGE RELEASE UVR-UVRD


Actuates the breaking of the circuit breaker when the power supply voltage falls to a value
between 35 and 70% of its rated value.
UVR: Instantaneous action.
UVRD: action delayed by 250 ms or 0.6 s, alternating current power supply.

Other delaying devices available upon request.


C
13
Characteristics Shunt trip Undervoltage release
EA EA1 EB UVR
Rated voltage Un
Alternating current 50Hz (V) 24-48-110/127-220- 127-220-380/415- 24-48-110/127-220- 24-48-110/127-220-
380/500 500 380/415-500 380-415-500
Alternating current 60Hz (V) 24-48-110/127-220- - 220-380 24-48-110/127-220-
380/500 380
Direct current (V) 24-48-110/120- - 24-48-110/120-220 24-48-110-120-220-
220/500 440-500
Operating voltage from 0.7 to 1.1Un from 0.1 to 1.3 Un from 0.7 to 1.1 Un from 0.35 to 0.7 Un(1)
Power Consumption
Alternating current closing (VA) 80 to 100 800 450 23
holding (VA) - - - 10
Direct current ≤ 220V (W) 30 - 180 (660 for 48V) 6
440-500V (W) 275 - - 21
Circuit breaker open time (ms) 60 60 60 85

Maximum equipment
1st possibility • - • -
2nd possibility - • • -
3rd possibility - - • •(2)
(1) Circuit breaker “making” ensured from 0.85 Un.
(2) or UVRD
SPECTRONIC SP - Auxiliaries

Auxiliary switches AS - SAS


Actuated at the same time as the main poles, the auxiliary contacts indicate the open or
closed position of the circuit breaker.
Mounting possibilities:
- Either 6 AS changeover switches
- or 3 SAS special changeover switches for DC applications
(it is not possible to combine AS and SAS).
For low voltage contacts, 4 to 30V - 1 to 100mA, consult the sales office.

C Characteristics
14 AS SAS
Thermal current Ith (A) 20 17.5
Interrupting capacity
Alternating current cos ϕ 0.3
48V (A eff.) 12 -
127V (A eff.) 12 -
220V (A eff.) 12 -
380V (A eff.) 5 -
Direct current L/R 0.01s
48V (A) 3 10
120V (A) 0.7 8
220V (A) 0.45 5

Fault contact (Bell alarm) BA


Common fault signals for overload and short-circuit.
Possibility of two changeover switches BA1, BA2 activated by RMS 7 or RMS 9.
After release it is necessary to reset the contacts by pushing the local mechanical push button
situated on the control panel (BPDL).

Characteristics BA
Thermal current Ith (A) 20
Interrupting capacity
Alternating current cos ϕ 0.3
48V (A eff.) 12
127V (A eff.) 12
220V (A eff.) 12
380V (A eff.) 5
Direct current L/R 0.01s
48V (A) 3
120V (A) 0.7
220V (A) 0.45
SPECTRONIC SP - Air circuit breakers

Position contacts for Equipment for withdrawable circuit breakers


withdrawable circuit breakers Auxiliary secondary disconnect system

Includes a fixed part (female sockets) mounted on the cradle and a moving C
part (male sockets) mounted on the circuit breaker 15
Safety contact in “connected” position CAE 12 - Device permits connection of 6 circuits of 10 A per block.
Indicates that the closing of the breaker can be actuated; the breaker is in - Mounting of 4 devices maximum.
“Connected” position, operating cranks not inserted.
Possibility of a changeover switch. Isolating shutter
Connection by clips of 6.35 mm.

Prevents access to energised parts when the circuit breaker is in


“withdrawn”position.
Provided with a padlocking system (padlock not provided).
“Connected” position contact CAE Test position cord
Indicates the position of the circuit breaker in its cradle. Use in place of secondary disconnects.
Possibility of 2 changeover switches CAE 51, CAE 52. Possibility of equipping the circuit breaker with a connector for testing the
Connection by clips of 6.35 mm. auxiliaries in the “disconnected” position.

Withdrawn position contact CAD Reinforced ground plug

Indicates the position of the circuit breaker in its cradle.


Possibility of 2 changeover switches CAD 61, CAD 62.
Connection by clips of 6.5 mm.

Characteristics
Thermal current Ith (A) 20
Interrupting capacity
Alternating current cos ϕ 0.3
48V (A eff.) 12 Reinforces the natural electrical continuity between the cradle mass and
127V (A eff.) 12 the circuit breaker (Icc 25kA - 0.5 s).
220V (A eff.) 12 Remove the lower right wire secondary disconnection block.
380V (A eff.) 5
Direct current L/R 0.01s
48V (A) 3
120V (A) 0.7
220V (A) 0.45
SPECTRONIC SP - Air circuit breakers

Interlocking Specify on the order


Fixed circuit breakers Device ❏ circuit breaker
❏ switch
Interlocking in “tripped” position
Type ❏ SP 800 ❏ SP 1000 ❏ SP 1250 ❏ SP 1600 ❏ SP 2000 ❏ SP 2500
- By Ronis lock (supplied)
Number of poles ❏ 3 poles
- Or by lock (not supplied): ❏ 4 poles
three possibilities:
Structure ❏ fixed ❏ rear horizontal terminals ❏ front terminals
- A Ronis lock, type 1104, 1/4 turn, opening ❏ withdrawable ❏ rear horizontal terminals ❏ front terminals
to the left
Protection ❏ RMS 7
- A Profalux lock, ❏ current transformers (3 or 4)
type KS 5B 24 G4Y ❏ RMS 7 option:
- A CASTELL lock type FS1. ❏ fault signalling
- Or by padlocks (not supplied): ❏ RMS 9
possibility: two padlocks ❏ current transformers (3 or 4)
❏ voltage conditioner
Type of control ❏ manual
C Withdrawable circuit breakers ❏ electrical (indicate voltage and frequency)
16 Interlocking in “connected” position Control Shunt trip release (indicate voltage and frequency)
- By Ronis lock (supplied) auxiliaries ❏ EA
❏ EA1
- Or by lock (not supplied): ❏ EB
two possibilities: Undervoltage release (indicate voltage and frequency)
- A Ronis lock 1104, 1/4 turn, ❏ UVR
opening to the left ❏ UVRD
- A Profalux lock, Signalling Auxiliary switches
type KS 5B 24 G4Y auxiliaries ❏ AS
- By padlocks (not supplied): (indicate the number ❏ SAS
of contacts) Fault contact (bell alarm)
possibility: three padlocks ❏ BA
Padlocking device is always supplied on basic Equipment ❏ Auxiliary secondary disconnect system
circuit breakers. for withdrawable ❏ isolating shutter
circuit breakers ❏ reinforced ground plug
Interlocking in “tripped” position ❏ “Test“ position cord
(Adaptation possible if no mechanical interlock- ❏ “connected”position contact CAE
ing by lock is present in the “withdrawn” position) ❏ “withdrawn” position contact CAD
❏ “safety” contact position CAE 12
- By Ronis lock (supplied)
Interlocking Fixed circuit breaker:
- Or by lock (not supplied): ❏ “Tripped” position by lock (type of lock)
three possibilities: ❏ “Tripped” position by padlock
- A Ronis lock, type 1104, 1/4 turn, Withdrawable circuit breaker:
opening to the left ❏ “Disconnected” position by lock (type of lock)
- A Profalux lock, ❏ “Tripped” position by lock (type of lock)
type KS 5B 24 G4Y Instruction manual ❏ English
- A CASTELL lock type FS1 ❏ French
- By padlocks (not supplied):
possibility: two padlocks
SPECTRONIC SP - Source changeover switches

Source changeover switches IDS


General
Source changeover switches provide the power supply continuity of an installation with minimum
interruption time, either from a normal supply, or from a replacement source, with automatic
changeover from one source to the other.
They are particularly appropriate for industrial or tertiary sector installations having a single
replacement supply:
- either permanent
- independent operating generator set
- mains
- or non permanent:
- generator set which uses stop and start control signals transmitted by the source changeover
switch.

Description
The source changeover switches have the same characteristics and possibilities of adaptation for the
circuits being protected as the circuit breakers of which they are built. C
In the withdrawable version, the “out of service” breaker can be withdrawn and removed without 17
affecting the operation of the “in service” breaker. When fitted with interlocking in “withdrawn” position,
the unit complies with the NF C 13-100 standard.
The source changeover switches consist of:
1. Two or three circuit breakers
- designed to be mechanically interlocked
- fitted with auxiliaries, wired and brought to the auxiliary terminal as needed for the chosen diagram
- may be identical, or may differ in the following:
- circuit breaker
- type
- protection system
- structure (possible combination of fixed and withdrawable types)
2. A mechanical locking system with linkage (two or three circuit breakers) or cables (two circuit
breakers)
3. An automatic controller comprising the relays necessary for operation of the source changeover
switches (not supplied) .

Installation
The circuit breakers are installed in a stacked arrangement (with cables only).
The changeover switches are delivered with circuit breakers and mechanical interlocking separated.

Characteristics
Rated service voltage (V) 50Hz 220 - 380
Automatic power without auxiliary
supply supply (V) 50Hz 220 - 380
with auxiliary (V) 50Hz 48 - 127 - 220 - 380
supply 24 - 48 - 110 - 220
Consumption breaker ratings SP 800 to 1600 SP 2000 and 2500
during transfer (VA) 1740 214
(W) 820 1020
permanent (VA) 26 26
(W) 37 37
Minimum transfer normal → with shunt trip release 2 s(1)
time replacement with undervoltage trip release 2 s(1)
replacement with shunt trip release 2s
normal → with undervoltage trip release 2 s
(1) Whenever required, add the generator start-up time.
SPECTRONIC SP - Source changeover switches

Source changeover switches


Operation
The source changeover switch enables: Source changeover switches with two breakers (1)
- switching the power supply of circuits from the Breaking, using shunt trip device EA Breaking, using undervoltage trip release UVRD
normal supply to the replacement supply in - Installation without auxiliary supply - installation without auxiliary supply
case of loss of the normal supply - installation with auxiliary supply - installation with auxiliary supply on
- switching the power supply circuit from the request.
replacement supply to the normal supply upon
return of the normal voltage and generating
load shedding and load resumption com-
mands for non priority circuits by using
auxiliary contacts fitted to each breaker automatic operation automatic operation
Un present Un present
- selection of the operating mode by using a N closed N closed
switch which provides the following positions: R open R open
- off
- automatic
C - normal power supply operation
- replacement power supply operation
absence of Un absence of Un
18
- in the three units version, select the power switching switching
supply of circuits from: normal → alternative normal → alternative
- normal supply 1
T1 = 0.1 to 30 s T1 = 250 ms
- normal supply 2
- normal sources 1+2 by means of a
duration < T1 duration > T1 duration < T1 duration > T1
preselector switch.
no effect no effect
The automatic controller is powered from:
standby equipment opening of N
- either the mains to be monitored
continuous start-up continuous
- or an auxiliary supply.
alternative alternative
The changeover is prevented on tripping by fault.
supply supply standby equipment
Automatic re-starting after fault tripping and start up
or
elimination of the fault is carried out by pressing
presence of Ur or
the reset pushbutton on the control panel of the
breaker concerned.The breaker in service can T2 = 0.1 to 30 s(2) presence of Ur
be tripped by pressing the local trip pushbutton
located on the control panel. duration < T2 duration > T2
The breaker is restarted by operating the no effect
selector switch, going from the “OFF” position to opening of N
the “Automatic” position. T2 = 0.1 to 30 s(2)
T3 = 0.1 to 30 s(2) closing of R
closing of R

return of Un return of Un

switching switching
alternative → normal alternative→ normal
T4 = 0.6s to 60 min(3) T3 = 250 ms

duration < T4 duration > T4 duration < T3 duration > T3


no effect no effect
opening of R opening of R

T5 = 0.1 to 30 s(2) T4 = 0.1 to 30 s(2)


closing of N closing of N
standby standby off
equipment off

(1) In “3 breakers alternative”, same operating


T = time delay principle.
Un = normal voltage (2) Min. 1 s.
(3) Min. 10 s.
Ur = alternative voltage
N = normal supply breaker
R = replacement supply breaker
SPECTRONIC SP - Source changeover switches

Specify on the order


Source Changeover Switch ❏ automatic
❏ manual
Rated voltage:
❏ 220V 50Hz ❏ 380V 50Hz
Upper unit1) ❏ on normal power supply
❏ on replacement power supply
device ❏ circuit breaker
❏ switch
type ❏ SP 800 ❏ SP 1000 ❏ SP 1250 ❏ SP 1600 ❏ SP 2000 ❏ SP 2500
number of poles ❏ 3 poles ❏ 4 poles
structure ❏ fixed ❏ withdrawable
protection unit ❏ RMS 7 (+ options if any)
❏ RMS 9
Lower unit1) ❏ on normal power supply
❏ on replacement power supply
device ❏ circuit breakers
❏ switch
C
type ❏ SP 800 ❏ SP 1000 ❏ SP 1250 ❏ SP 1600 ❏ SP 2000 ❏ SP 2500 19
number of poles ❏ 3 poles ❏ 4 poles
structure ❏ fixed ❏ withdrawable
protection unit ❏ RMS 7 (+ options if any)
❏ RMS 9
Medium unit(1) ❏ for 3 unit source changeover switch, on replacement source
device ❏ circuit breakers
❏ switch
type ❏ SP 800 ❏ SP 1000 ❏ SP 1250 ❏ SP 1600 ❏ SP 2000 ❏ SP 2500
number of poles ❏ 3 poles ❏ 4 poles
structure ❏ fixed ❏ withdrawable
protection unit ❏ RMS 7 (+ options if any)
❏ RMS 9
interlocking See operation(2)
Auxiliaries(3) ❏ Source changeover switch units conforming to our diagrams cannot be fitted with other auxiliaries:
An NO/NC common point contact, pre-installed, is available for each breaker.
❏ The breakers for manual changeover switches can be equipped with auxiliaries within the limits of
the capabilities of each.
Equipment Fixed circuit breaker:
and interlocks ❏ “tripped” position
Withdrawable circuit breaker
❏ “tripped” position
❏ "Withdrawn” position
❏ Isolating shutter

(1)
Refer to the equipment specification.
(2) (3)
Operation Auxiliaries to add
Two normal sources possible To be fitted on EACH circuit breaker switch
normal 1 0 x 0 0 x voltmetric release EA or UVRD 1 1
remplacement 0 0 x 0 0 auxiliary switches AS 5 5
normal 2 0 0 0 x x fault contact BA 1 1 -
x: closed circuit breaker To be fitted on EACH WITHDRAWABLE circuit breaker
- safety contact in “connected “position CAE 12
- “connected” position contact CAE 51

Note
On request: supplied with a cabling diagram.
SPECTRONIC SP - Order codes

Circuit breakers
Without Protection
SP 800 SP 1000 SP 1250 SP 1600 SP 2000 SP 2500
FIXED with rear 3P 756303 756313 756323 756333 756343 756353
horizontal terminals
4P 756304 756314 756324 756334 756344 756354

Front terminal kit 3P 756150 756150 756152 756152 756154 756154


4P 756151 756151 756153 756153 756155 756155

WITHDRAWABLE
3P 756301 756311 756321 756331 756341 756351
Moving part
4P 756302 756312 756322 756332 756342 756352
+
Fixed part 3P 756100 756100 756100 756100 756102 756102
cradle with front
4P 756101 756101 756101 756101 756103 756103
C terminals
3P 756105 756105 756105 756105 756107 756107
Cradle with rear
20
horizontal terminals 4P 756106 756106 756106 756106 756108 756108

Higher value for 690V version 3P 756136 756136 756136 756136 756138 756138
4P 756137 756137 756137 756137 756139 756139

RMS 7 755452 RMS 7


protection unit

Current transformer RMS 7


Three pole equipment Rating A SP 800 SP1000 SP 1250 SP 1600 SP 2000 SP 2500
800 755500 - - - - -
1000 - 755501 - - - -
1250 - - 755502 - - -
1600 - - - 755503 - -
2000 - - - - 755504 -

+ 2500 - - - - - 755505

Fourth pole equipment Rating A SP 800 SP1000 SP 1250 SP 1600 SP 2000 SP 2500
800 755510 - - - - -
1000 - 755511 - - 755514 -
1250 - - 755512 - - 755515
1600 - - - 755513 - -
SPECTRONIC SP - Order codes

Rating plug
3P/3P+N 100% Rating A SP 800 SP1000 SP 1250 SP 1600 SP 2000 SP 2500
400 755554 - - - - -
600 755553 - - - - -
800 755550 755563 - 755584 - -
1000 - 755560 - - - -
1200 - - - 755583 755593 -
1250 - - 755570 - - -
1600 - - - 755580 - 755603
2000 - - - - 755590 -
2500 - - - - - 755600

3P+N 50% Rating A SP 800 SP1000 SP 1250 SP 1600 SP 2000 SP 2500 C


800 755552 - - - - - 21
1000 - 755562 - - - -
1250 - - 755572 - - -
1600 - - - 755582 - -

With integrated GF Rating A SP 800 SP1000 SP 1250 SP 1600 SP 2000 SP 2500


400 755555 - - - - -
600 755556 - - - - -
800 755557 755565 - 755585 - -
1000 - 755566 - - - -
(1)
1200 - - - 755586 755595 -
1250 - - 755575 - - -
1600 - - - 755587 - 755605(1)
2000 - - - - 755596(1) -
2500 - - - - - 755606(1)

(1) Only for 3 pole breaker


SPECTRONIC SP - Order codes

RMS 9 protection Protection unit (Imax. = 2000A)


RMS 9 is always made up of two references: RMS 9 + adaptator plate

755370 RMS 9 3P 755371 RMS 9 3P


2000 2000C
755400 3P + N/2 755401 3P + N/2
755374 4P 755378 4P

755375 Adaptor plate 755375 Adaptor plate

Current transformer RMS 9


C Three pole equipment
Rating A
800
SP 800
755500
SP1000
-
SP 1250
-
SP 1600
-
SP 2000
-
SP 2500
-
22
1000 - 755501 - - - -
1250 - - 755502 - - -
1600 - - - 755503 - -
2000 - - - - 755504 -
2500 - - - - - -
+
Equipment for fourth pole Rating A SP 800 SP1000 SP 1250 SP 1600 SP 2000 SP 2500
800 755510 - - - - -
1000 - 755511 - - 755514 -
1250 - - 755512 - - -
1600 - - - 755513 - -

Options For RMS 7 unit For RMS 9 unit

755457 Distinct fault signalling 755450 Voltage conditioner

755458 Sealable cover 741007 Fuses for


conditioner
- three fuseholders 10 x 38
- 2A type gG

Number of secondary disconnections required:


- voltage conditioner 4 wires
- auxiliary power supply 2 wires
- communication 2 wires

755372 Monitor

755376 Connection cable for monitor

Note
Do not forget the auxiliary power supply (not
supplied)
SPECTRONIC SP - Order codes

Switches SP 800 SP 1000 SP 1250 SP 1600 SP 2000 SP 2500

FIXED with rear horizontal 3P 756403 756413 756423 756433 756443 756453
terminals
4P 756404 756414 756424 756434 756444 756454

Front terminals 3P 756150 756150 756152 756152 756154 756154


kit
4P 756151 756151 756153 756153 756155 756155

WITHDRAWABLE
3P 756401 756411 756421 756431 756441 756451
Moving part
+ 4P 756402 756412 756422 756432 756442 756452
Fixed part 3P 756100 756100 756100 756100 756102 756102
cradle with front
terminals 4P 756101 756101 756101 756101 756103 756103
Cradle with rear
horizontal
terminals
3P
4P
756105
756106
756105
756106
756105
756106
756105
756106
756107
756108
756107
756108
C
23
Higher value for 690V version
3P 756136 756136 756136 756136 756138 756138
4P 756137 756137 756137 756137 756139 756139
SPECTRONIC SP - Order codes

Electrical auxiliaries
Electrical control Shunt trip release Undervoltage trip release

Use 4 Use 2 Use 2


connection connection connection
terminals or terminals or terminals or
secondary secondary secondary
disconnections disconnections disconnections

SP EA UVR
AC 50Hz AC 50-60Hz AC 50Hz

C 756200
756201
48V
110V
752200
752201
24V
48V
752254
752255
24V
48V
24
756224 127V 752202 110/127V 752256 110/127V
756233 220V 752203 220V 752257 220V
756231 240V 752204 380/500V 752258 380V
756205 380V DC 752259 415V
752240 24V 752260 500V
AC 60Hz
752241 48V
756206 48V AC 60Hz
752242 110/120V
756201 110V 752254 24V
752243 220/500V
756233 220V 752255 48V
756225 240V EA1 752256 110/127V
756211 380V AC 50Hz 752261 220V
752205 127V 752258 380/415V
DC 752206 220V 752259 500V
756212 48V 752207 380/415V
756228 60V 752208 500V DC
756213 110V 752288 24V
756215 220V EB 752289 48V
AC 50Hz
752290 110V
752210 24V
752291 120V
752211 48V
752292 220V
752212 110/127V
752293 440V
752213 220V
752294 500V
752214 380/415V
752215 500V
UVRD 250 ms
AC 60Hz
AC 50Hz
752248 220V
752216 220V
752249 380V
752217 380V
DC
752244 24V UVRD 0,6 s
752245 48V AC 50Hz
752246 110/120V 752220 220V
752247 220V 752221 380V
SPECTRONIC SP - Order codes

Auxiliaries Accessories
Signalling contacts Secondary terminals Interlocking
Fixed circuit breaker: block of 12 terminals Tripped position
(maximum 1 additional block).
753203 By Ronis lock (supplied)
756096 Left mounting
753204 By lock (not supplied)
Withdrawable circuit breaker: block of 6 terminals
(2 additional blocks maximum). 753205 By padlocks (not supplied)

755907 Moving part Withdrawn position

755908 Fixed part 753206 By Ronis lock (supplied)

NO NC NO/NC 755909 Fixed and moving part assembly 753207 By lock (not supplied)
756061 756060 756062 AS 1
Isolating shutter Source changeover mechanical interlock
756064 756063 756065 AS 2
3P 4P Linkage permitting interlock:
C
756067 756066 756068 AS 3 25
- 2 circuit breakers at 660 mm
756070 756069 756071 AS 4 756110 756111 SP 800-1600 - 3 devices (on request)
756073 756072 756074 AS 5 756112 756113 SP 2000 - 2500 756119 Fixed circuit breaker
756076 756075 756077 AS 6 756120 Withdrawable circuit breaker
Reinforced ground plug 25kA - 0.5 s
756081 756080 756082 SAS 1(1)
Cable system permitting interlock between:
756084 756083 756085 SAS 2(1) 756132 For withdrawable circuit breaker
756087 756086 756088 SAS 3(1) 756141 2 fixed circuit breaker
“Test” position cord
752815 752816 752817 BA 1 756142 2 withdrawable circuit breaker
- - 752820 BA 2 756127 Replace the secondary
disconnection device Operation counter
(1)
To fit 1, 2 or 3 SAS contacts, Circuit breaker contact positions in
use adaption no. 756098 the cradle
Connection terminals or secondary 756095 "Connected” position contact CAE,
disconnections to use: one changeover contact NO/NC
- by NO or NC contact: 2 terminals
- by NO/NC contact switches: 3 terminals 756094 "Withdrawn” position contact CAD, 756133
one changeover contact NO/NC
Factory fitted
For each position two contacts are possible.Use
an adaption no. 756095 for 2 CAE + 2 CAD Door gasket
Use 3 secondary terminals per contact.
752818 Permits IP3x protection
when panel mounted
“Connected cranks not inserted”
contact CAE 12

752830 A changeover contact NO/NC


Use 3 secondary disconnection
terminals
SPECTRONIC SP - Overall dimensions

Fixed circuit breaker

Front connection Rear horizontal connection

Neutral Door
E
Gasket

4x Ø9

C
26 4x Ø9

Panel cut out for fitting gasket Rear horizontal Front connections
connections

SP 800 - 1000 SP 800 - 1000

300

3 SP 1250 - 1600 SP 1250 - 1600


neutral of SP 2000 - 2500 neutral of SP 2000 - 2500

3
352

Legend
Type Number A B C D SP 2000 - 2500 SP 2000 - 2500
of poles
SP 800 to 1600 3 318 98 75 -
SP 2000-2500 3 412 130 90 -
4 510 130 90 114

E = minimum clearance distance above the arc chutes.


Ue ≤ 500V Ue ≤ 690V
I = Insulating screen 150 mm 150 mm
M = Metallic screen 150 mm 200 mm
SPECTRONIC SP - Overall dimensions

Withdrawable circuit breaker Front connection

D B B C 2000-2500 800 to 1600


Neutral Withdrawable
4 x Ø 10,5 door open
E
Withdrawable
door closed

4 x Ø10,5

Gasket
C
27

Panel cut out for gasket fitting Rear horizontal connection

800 to 1600 2000-2500

Withdrawable 2 Ø 12
door closed

300

Door cut-out

Connection terminals

Legend
Type Number A B C D SP 800 to 1600 SP 2000 - 2500
of poles
neutral of SP 2000 - 2500
SP 800 to 1600 3 374 98 89 -
SP 2000-2500 3 468 130 104 -
4 566 130 104 114

E = minimum clearance distance above the arc chutes.


Ue ≤ 500V Ue ≤ 690V
I = Insulating screen 100 mm 100 mm
M = Metallic screen 150 mm 200 mm
SPECTRONIC SP - Overall dimensions

Source changeover
switches IDS
Fixed circuit breakers without chassis
Type Number A
of poles
SP 800 to 1600 3 334
SP 2000 - 2500 3 428
4 526
White area: overall dimensions of interlocking
system.
⊗ left alignment of circuit breaker fixation.

C
28

Withdrawable circuit breaker


without chassis
Type Number A
of poles
SP 800 to 1600 3 334
SP 2000 - 2500 3 428
4 526
White area: overall dimensions of interlocking
system.
⊗ left alignment of circuit breaker fixation.
SPECTRONIC SP - Connections/Weights

Connection possibilities Fixed versions SP


Rear horizontal terminals X
Rear vertical terminals O
Front terminals X
Withdrawable versions SP
Rear horizontal terminals X
Rear vertical terminals O
Front terminals X
X = standard
O = on request

Weight of circuit breakers Fixed circuit breaker Withdrawable circuit breaker


(in kg) manual control electrical control manual control electrical control
SP 800 3P 45 51 47 53
4P 57 63 59 65
SP 1000 3P
4P
45
57
51
63
47
59
53
65
C
29
SP 1250 3P 45 51 47 53
4P 57 63 59 65
SP 1600 3P 45 51 48 54
4P 57 63 60 66
SP 2000 3P 54 60 58 64
4P 66 72 70 76
SP2500 3P 54 60 59 65
4P 66 72 71 77

Weight of switches Fixed circuit breaker Withdrawable circuit breaker


(in kg) manual control electrical control manual control electrical control
SP 800 3P 44 49 46 52
4P 56 61 58 64
SP 1000 3P 44 49 46 52
4P 56 61 58 64
SP 1250 3P 44 49 46 52
4P 56 61 58 64
SP 1600 3P 44 49 47 53
4P 56 61 59 65
SP 2000 3P 52 58 56 62
4P 64 70 68 74
SP2500 3P 52 58 57 63
4P 64 70 69 75
SPECTRONIC SP - RMS 7 diagram

RMS 7: Protection and monitoring unit


Diagrams are shown with de-energized circuits, circuit breaker open, connected, reset, handles not inserted.

Ph.1 +

Secondary
disconnector 50 49
C N

C
30

Fault RMS7
signalling

EX

Secondary
disconnector
Ph.2 -
Option Protection unit Fault contacts

Legend
CAE 51 . 52 Contact 'connected' position RMS 7 Trip unit
CAD 61 . 62 Contact 'withdraw' position Voltmetric Maximum equipment:
CAE 12 Contact 'withdraw' position, cranks not inserted release – MV or MVR + EB
– EA or EA1
CD1 . CD2 Fault contact, overload and short-circuit with local reset
after fault Rated thermal current: 20A
CA1 to CA6 Breaking capacity:
MV Undervoltage release – alternating current cos ϕ 0.3
MVR Time delayed undervoltage release 48V - 12A
RA Resistor for selected voltages in direct current 127V - 12A
EA1 . EA . EB Shunt trip 220V - 12A
380V - 5A
K Circuit breaker closing relay – direct current L/R 0.01 s
FCE1 . 2 Limit switch close 48V - 3A
FCD Limit switch reset 120V - 0.7A
220V - 0.45A
M.m Motor
Rated thermal current: 17.5A
RH50 Resistor for 380V CAS1 to CAS3 Breaking capacity:
C21 Interlock contact coupled with emergency control – direct current L/R 0.01 s
CA . CAS Auxiliary contacts 220V - 5A
BP0 'Tripped' position contacts Rated thermal current: 20A
BPF 'Closed' position contacts CD1 - CD2 Breaking capacity:
CAE12 – alternating current cos ϕ 0.3
CAE51 48V - 12A
CAE52 127V - 12A
CAD61 220V - 12A
CAD62 380V - 5A
SPECTRONIC SP - RMS 7 diagram

Disconnected
Open Closed cranks not-
Connected Disconnected
inserted

42 44

4
or or or
or or M

or
C
green 31
red

Voltmetric
Electrical control Auxiliary contacts Positioning contacts
releases

Electrical control Auxiliary contacts 3 CAS 4


2
External wiring: wire cross section 2.5 mm (for 48V power supply, the Six normal or three
wire length is max. 20 m). special auxiliary contacts. 1 2
For 48V: connection of electrical control on the circuit breaker and the
C2 contact by 2.5 mm2 wires.
Bridge connected
End user connections during installation
Withdrawable circuit breaker
Fixed circuit breaker Connections by terminals 6.3 x 0.8
Connection by terminals 6.3 x 0.8 For the electrical control of EA1, EA, EB, CD1, CD2, MVR, MV, RMS 7,
24 terminals maximum use the allocated terminals. Other accessories: numbers are increasing
Letters in alphabetical order followed by increasing numbers clockwise (use reserved terminals if they are available).

LEFT RIGHT

LEFT RIGHT
50
CN
49
MV or MVR

REAR

CD2

CD1 E
F Electrical
FRONT G control
EA1 or EA H
or EB
or MV .MVR
SPECTRONIC SP - RMS 9 diagram

RMS 9: Protection and measurement unit


Diagrams are shown without power supply, circuit breaker open, connected, reset and cranks not inserted.

Ph.1 +
Fault

N
S1
Ph1
Voltage R

Transmission
Ph2
Ph3
conditioner S
T

505 49E 15 14 32 29
Secondary
disconnector C N T S R S1

C
32
5 6 RMS9
T S R S1

MONITOR 17 33 16 28

EX

Secondary
disconnector

Ph.2 - Protection unit


RMS 9 Fault contact

Legend
CAE 51 . 52 “connected” position contact
CAD 61 . 62 “withdrawn” position contact
CAE 12 “cranks not inserted” contact
BA1 - BA2 fault contact, overload and short-circuit with local reset after fault tripping
UVR undervoltage release
UVRD time delayed undervoltage release
RA resistor for selected voltages in direct current
EA1 - EA - EB shunt trip release
K relay
FCE1 . 2 limit switch close
FCD limited switch reset
M.m motor
RH 50 resistor for 380V
C 21 interlock contact coupled with emergency control
AS - SAS auxiliary switches
BPO “Tripping” push-button
BPF “Closing” push-button
SPECTRONIC SP - RMS 9 diagram

open closed connected disconnected connected


cranks not
inserted

yellow
blue

EA UVRD
or or or
or or
EA1
or
UVR
M
C
EB 33
green
red

Voltmetric Electrical Positioning


Auxiliary switches
releases control contacts

End user connections


Fixed circuit breaker Withdrawable circuit breaker
Accessible from the front (protection plate withdrawn) Connections by terminals 6.3 x 0.8.
Connections by terminals 6.3 x 0.8. For the electrical control of EA1, EA, EB, BA1, BA2, UVRD, UVR, RV, C,
24 terminals maximum use the allocated terminals. Other accessories: numbers are increasing
Letters in alphabetical order followed by increasing numbers clockwise (use reserved terminals if they are available).

LEFT RIGHT
LEFT RIGHT
plate plate

REAR RMS 9 13 17
CN
9 21
UVR or UVRD R
S
T

RMS 9
FRONT
CD2
35 -
36 +
CD1 E
F Electrical
EA1 or EA G control
or EB H
reserved terminal(s)
or UVR/UVRD
direction of wiring
Notes

C
34
SPECTRONIC S/L - Air circuit breakers

Summary
C.37 General characteristics

C.38 Fixed circuit breakers

C.39 Withdrawable circuit breakers

C.41 S circuit breaker characteristics

C.42 L circuit breaker characteristics

C.44 RMS 7: protection and control unit

C.46 RMS 9: protection and measurement unit


C
35

C.49 Auxiliaries

C.49 Electrical control

C.50 Shunt and undervoltage releases

C.51 Auxiliary switches

C.52 Fault signalling contacts and indicators

C.53 Equipment

C.54 Interlocking

C.55 Source changeover switches

C.59 Order codes

C.72 Overall dimensions

C.86 RMS 7 diagram

C.88 RMS 9 diagram

C.90 Connections

C.90 Weights
Notes

C
36
SPECTRONIC S/L - Air circuit breakers

Selective circuit breakers S 800 to 6400A


with total discrimination guarantee
Short-circuit breaking capacity: Ics 55 to 120kA (415V)

Limiting circuit breakers L 640 to 2000A


with very high interrupting capacity
Short-circuit breaking capacity: Ics 130kA (415V)
Complete range
- Fixed or withdrawable versions
- 3 or 4 poles
- Electrical or manual control.

The SPECTRONIC range combines the legendary reliability C


of our air circuit breakers with: 37
- A design adapted to the new panelboards
- Two types of protection relays: RMS 7 and RMS 9

With multiple adaptations, they are recommended for


important installations where high performances and severe
operating conditions are required. Short-circuit breaking capacity
following IEC 947-2 (415V)
Conformity Icu (kA)

The circuit breakers are built according to the following 130


standards: IEC 947-2, BS, CEI, NBN, NFC and VDE. 120
L L L L L
Certificates: Bureau Véritas, Lloyd’s Register of Shipping, 640 1000 1250 1600 2000 S
90 5000
ASEFA. 85 S &
Certification: Germanischer Lloyd (in accordance with S 4000 6400
IEC 157.1) 70 3200
65 S
55 S 2500
Tropicalization S S S S
2000
800 1000 1250 1600
- Class I (standard): relative humidity of 80% at 40°C (hot and
dry or damp climate of temperature zones).
- Class II: relative humidity of 95% at 45°C (hot and damp
climate).

Anti-corrosion treatment
0
For special atmospheres, consult us. 640 800 1000 1250 1600 2000 2500 3200 4000 5000
6400
Ith (A)
SPECTRONIC S/L - Air circuit breakers

Fixed circuit breaker

11

10
C 3
38 13

7 8 14 12

Description 1 Recess section for adaption of interlock in the “tripped” position by lock.
2 Recess section for interlocking, in the “tripped” position by padlock.
Equipped at the factory with a panel ensuring a IP43 protection degree.
By fitting a gasket and a seal, a IP43 is obtained (door closed). 3 Electrical control handle.
4 Trip and reset local push button.
Installation 5 Circuit breaker position indicator: Red = closed - Green = open.
- Fixed by side L-pieces with built-in ground connection. By cross 6 Closing push button.
members on circuit breakers S 5000-6400 (vertical or horizontal).
7 Electrical control position indicator:
- Main connections (see table on page D.88). Yellow = tripped - Blue = reset.
- Auxiliary circuit connections by terminals located at the rear of the 8 Mechanical fault indicator: White = fault - Black = normal.
curcuit breaker.
9 Arc chute.
- 20 connection terminals supplied as standard, positioned at the rear.
10 Auxiliary switch.
11 Electrical control.
Power Supply
12 RMS 7 or RMS 9 trip units.
- Up to 500V (415V for L circuit breakers), connections are made either 13 Distinct fault signalling.
on the upper or the lower terminals
14 EX trip actuator.
- Above 500V, connect to the upper terminals or right terminal clamps
on the vertical S 5000-6400 breakers (breakers seen from the front). 15 Ground plug.
16 Voltmetric releases.
17 Current transformer.
18 Fixed auxiliary terminal block.
19 Mobile auxiliary terminal block.
20 “Withdrawn” - “connected” signalling contacts.
21 “Withdrawn” - “connected” interlocking positions.
22 “Withdrawn” position padlocking.
23 “Withdrawn” - “test” - “connected” position indicator.
24 Primary jaw.
25 Push button interlocking shutters.
26 Chassis.
27 Dashboard.
SPECTRONIC S/L - Air circuit breakers

Withdrawable circuit breaker

17
25

C
39

26
24 16 15

Description
- Ratings H 4000A
Cradle equipped with retractible rails enabling 3 circuit breaker positions:
“connected”, “test, “withdrawn-isolated”, as well as an “extracted”
position.
- Ratings 5000-6400A (vertical)
18 Cradle equipped with guide rails in which the circuit breaker rollers are
engaged, enabling 2 circuit breaker positions: “connected”, “withdrawn-
isolated”.
By fitting of a gasket and a seal, a IP3x is obtained. (door closed)
The plug-in operation, which can be done with the door closed, uses a
1 screw-nut system, actuated by a removable crank. Tripping of the circuit
2 breaker before introducing the crank guarantees safety when withdrawing.

Installation
- Fixed to the lower part of the cradle. The upper part on the 5000-6400A
27 20 ratings (vertical versions) has to be maintained.
19 - Main connections (see table page D.88).
- Lateral auxiliary circuit connections:
- by disconnectable clips for S 800 to S 4000 and L640 to L 2000
- by connectors for S 5000-6400.
15 - Two blocks of 6 terminals are supplied as standard.

Power supply
- Up to 500V, (415V for circuit breakers L), connections are made either
on the upper or lower terminals.
- Above 500V, connect to the upper terminals or right terminal clamps on
the vertió!l breakers S 5000-6400 (breakers seen from the front).
22
23
21
SPECTRONIC S - Air circuit breakers

Main characteristics of
selective S circuit breakers
Full interrupting capacity kept in all Total selectivity guaranteed even at Special design providing a long
selectivity cases closing on short-circuit service of the main contacts

C
40

The original pole design insures a very high Independant closing directly on main contacts When opening, the unique pole design enables
withstand to short-circuit currents in “closed” (patented) is obtained by using the energy the transition from the main contacts to the
position. stored in the springs and released by a lock. arcing contacts. The structure of the spark
arrester considerably reduces external effects
even at maximum interrupting capacity.

Simple, efficient maintenance


possible on site

Safety ensured by fully visible


isolation
SPECTRONIC S - Air circuit breakers

Selective S circuit breaker characteristics


Circuit breaker
S 800 S 1000 S 1250 S 1600 S 2000 S 2500 S 3200 S 4000 S 5000 S 6400
Rated insulation voltage Ui (V) 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000
Rated impulse voltage Uimp (kV) 8 8 8 8 8 8 8 8 8 8
Rated maximum nominal voltage Ue (V) 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000
Rated thermal current Ith 40°C (A) 800 1000 1250 1600 2000 2500 3200 4000 5000 6400
50°C (A) 800 1000 1250 1600 2000 2500 3000 3650 4600(1) 6000(2)
60°C (A) 800 1000 1250 1500 1900 2350 2850 3250 4100(1) 5200(2)
Rated ultimate short-circuit breaking capacity Icu
Alternating current 50/60Hz 240/415V (kA) 55 55 55 55 65 70 85 90 120 120
500V (kA) 55 55 55 55 55 65 70 85 100 100
600V (kA) 42 42 42 42 50 50 65 65 100 100
690V(3) (kA) 40 40 40 40 40 40 50 50 70 70
1000V(4) (kA) 15 15 15 15 25 25
Rated service short-circuit breaking capacity Ics
Alternating current 50/60Hz 240/415V (kA) 55 55 55 55 55 65 70 85 100 100
500V
600V
(kA)
(kA)
55
42
55
42
55
42
55
42
55
50
65
50
70
65
85
65
100
100
100
100
C
690V(3) (kA) 40 40 40 40 40 40 50 50 70 70 41
1000V(4) (kA) 15 15 15 15 25 25
Rated peak short-circuit making capacity Icm
(max) (kA peak) 125 125 125 125 140 150 190 200 270 270
Rated short-time withstand current Icw (415V)
0.5 s. (kA eff.) 55 55 55 55 65 70 - - - -
1 s. (kA eff.) 55 55 55 55 65 70 85 90 120 120
Utilization category B B B B B B B B B B
Number of poles 3-4 3-4 3-4 3-4 3-4 3-4 3-4 3-4 3-4 3-4
Suitability for isolation (visible breaking) • • • • • • • • • •
Endurance (number of cycles)
mechanical # cycles 20000 20000 20000 20000 20000 20000 10000 10000 5000 5000
electrical (under 415V)(5) # cycles 20000 20000 20000 20000 20000 20000 10000 10000 5000 5000
mean time between maintenance # cycles 2000 2000 2000 2000 1500 1500 1500 1500 1500 1500
Power dissipation (withdrawable 3 pole) (W) 150 200 300 400 450 500 920 1000 1320 1320
4th pole conventional thermal current(A) 800 1000 1250 1600 2000 2500 3200 4000 5000 6400
Pollution degree 3 3 3 3 3 3 3 3 3 3
Dimensions in mm (fixed circuit breaker)
3 poles Height (mm) 389 389 389 389 389 389 532 532 568 568
Width (mm) 378 378 378 378 466 534 688 688 1210(6) 1210(6)
Depth (mm) 420 420 420 420 420 420 458 458 458 458
4 poles Height (mm) 389 389 389 389 389 389 532 532 568 568
Width (mm) 466 466 466 466 600 680 886 886 1574(6) 1574(6)
Depth (mm) 420 420 420 420 420 420 458 458 458 458
(1) S 5000 horizontal: 4800A to 50°C (5) To guarantee this number of operations, it is necessary to check
4400A to 60°C the spark arrestors and the arc chutes at the maintenance periods as shown above
(2) S 6400 horizontal: 6200A to 50°C (replace when necessary). This can be done easily on site.
5800A to 60°C (6) Horizontal
(3) Structures as required: Ue 690V for all ratings
(4) Ue 1000V for all ratings ≤ 2500A

Switch
S 800 S 1000 S 1250 S 1600 S 2000 S 2500 S 3200 S 4000 S 5000 S 6400
Rated thermal current Ith 40°C (A) 800 1000 1250 1600 2000 2500 3200 4000 5000 6400
Rated peak short circuit making capacity Icm
(max) (kA peak) 125 125 125 125 140 150 190 200 270 270
RMS short time withstand current Icw (at 415V)
0.5 s. (kA eff.) 55 55 55 55 65 70 - - - -
1 s. (kA eff.) 55 55 55 55 65 70 85 90 120 120
Dimensions in mm (fixed circuit breaker):
see table above
SPECTRONIC L - Air circuit breakers

Main characteristics of
limiting L circuit breakers
Installation safety Economy: high limitation of short circuit current
peak The high limitation of short-circuit current allows significant savings on conductors (cables or ducts)
I kA
240
and on the mechanical structure of the networks.
50
I2t 106 A2 sec

70
40

- 2000
t L 1600

C 30

42
L 1250

20

00
10 L 640 - 10

The combined effect of repulsive action of I kA eff.


contacts and ultra-rapid releases create a drastic 0 10 20 30 40 50 60 70 80 90 100
limitation of short circuit current. The result is a
substantial reduction of electrodynamic stress
and thermal effects applied on the conductors Current limitation: Thermal stresses:
during short circuits. Economy on the installation by reducing the effects Economy on conductors by reducing
of electrodynamic stresses. the thermal effects
Elimination of a short-circuit of 130kA
in 8 milliseconds

Even though the circuit breaker provides a very


high breaking capacity, the external physical
effects are considerably reduced thanks to the
special arrangement of the arc chutes in the
arcing chambers.
SPECTRONIC L - Air circuit breakers

Limiter L circuit breaker characteristics


Circuit breaker
L 640 L 1000 L 1250 L 1600 L 2000
Rated insulation voltage Ui (V) 1000 1000 1000 1000 1000
Rated impulse voltage Uimp (kV) 8 8 8 8 8
Rated maximum nominal voltage Ue (V) 690 690 690 690 690
Rated thermal current Ith 40°C (A) 640 1000 1250 1600 2000
50°C (A) 640 1000 1250 1600 2000
60°C (A) 640 1000 1250 1500 1900
Rated ultimate short circuit breaking capacity Icu
Alternating current 50/60Hz 415V (A) 130 130 130 130 130
500V (A) 100 100 100 100 100
600V (A) 85 85 85 85 85
690V (A) 60 60 60 60 60
Rated service short-circuit
breaking capacity Ics
Alternating circuit 50/60Hz 415V (kA) 130 130 130 130 130
500V
600V
(kA)
(kA)
100
85
100
85
100
85
100
85
100
85 C
690V (kA) 60 60 60 60 60 43
Rated peak short-circuit
making capacity Icm (max) (kA peak) 290 290 290 290 290
Fault elimination time (ms.) 8 8 8 8 8
Utilization category A A A A A
Number of poles 3-4 3-4 3-4 3-4 3-4
Suitability for isolation (visible breaking) • • • • •
Endurance (number of cycles)
mechanical # cycles 20000 20000 20000 20000 20000
electrical (at 415V)(1) # cycles 20000 20000 20000 20000 20000
mean time between maintenance # cycles 1500 1500 1500 1500 1500
Power dissipated (withdrawable, 3 pole) (W) 135 230 250 270 420
4th pole conventional thermal current (A) 640 1000 1250 1600 2000
Pollution degree 3 3 3 3 3
Dimensions in mm (fixed circuit breaker)
3 poles Heigth (mm) 425 425 425 425 425
Width (mm) 378 378 466 466 534
Depth (mm) 420 420 420 420 420
4 poles Height (mm) 425 425 425 425 425
Width (mm) 466 466 534 600 680
Depth (mm) 420 420 420 420 420
(1) To guarantee this number of operations, it is
necessary to check the spark arrestors and the arc
chutes at the maintenance periods as shown above
(replace when necessary). This can be done on site.
SPECTRONIC S/L - Air circuit breakers

RMS 7: Protection unit for S800 to S6400 and


L640 to L 2000 Standard protection
- Overload protection (LT)
- Short-circuit protection (ST-I)
- Optional ground fault protection (GF)

Setting ranges
Setting points
LT (x In) 0.4 - 0.5 - 0.6 - 0.7 - 0.75 - 0.8 - 0.85 - 0.9 - 0.95 - 1
LTD (s) 5 - 10 - 15 - 20 - 25 - 30 - 35 - 40 delay at 7.2 lr
ST (x ln) 1.5 - 2 - 3 - 4 - 5 - 7 - 9 - 10 - 12 - 14
Time delay (ms) 30 - 60 - 90 - 120 - 150 - 180 - 210 - 240- 270 - 300
I (x ln) 1.5 - 2 - 3 - 5 - 7 - 10 - 15 - OFF
GF (x In) S 800 - S 2000: 0.2 - 0.3 - 0.4 - 0.5 - 0.6 - 0.7 - 0.8
S 2500: 0.2 - 0.3 - 0.35 - 0.45 - 0.55 - 0.6 - 0.7
S 3200 - S 6400: 0.2 - 0.3 - 0.35 - 0.45
L 640 - L 2000: 0.2 - 0.3 - 0.4 - 0.5 - 0.6 - 0.7 - 0.8
C Time delay (ms) 100 - 200 - 300
44 Ir = k x In
Note
If the GF function is selected, the fourth CT's must be of the same rating
as the ones of the phases.

Options
Distinct fault signalling (LT, ST-I, GF)
This option displays locally by LED the origin of the fault.
Tamper proofing
A transparent screen avoids the access to the settings.

Magnetic setting current values of Ultra-Rapid releases


Circuit breaker Ultra rapid release (short-circuit)
Description Standard threshold Low threshold
(± 20%) (± 20%)
The RMS 7 unit meets the requirements of the IEC 947.2 standard. Operating current
This unit is powered by the current transformers and performs all the setting range (A)
necessary three or four pole overcurrent protections. 7.5 Ith from to 3 Ith from to
The RMS 7 is designed to receive interchangeable rating plugs: L 640 5000 4500 7500 2000 2000 4500
L 1000 7500 4500 7500 3000 2000 4500
- 3 pole or 4 pole protection: 3P/3P+N
L 1250 10000 6000 15000 4000 3000 6000
- 3 pole with half neutral protection: 3P+N50% L 1600 12000 6400 20000 5000 5000 6400
- 3 pole or 4 pole ground fault protection L 2000 15000 6400 20000 6000 5000 6400

Each pole is factory equipped with ultra-rapid releases set at 7.5 times the
nominal intensity.
The trip operation threshold may be set to a different value on
request (see table above).

Total breaking time


In ST:
- selected time delay + 90 ms
(if tripping by RV unit)
- or 8 ms (if tripping by ultra-rapid release)
SPECTRONIC S/L - Air circuit breakers

RMS 7: Protection unit for S800 to S6400 and L640 to L 2000


Setting and operating current values

0.7

1.05
1,05 Operating limits UTE - IEC
1,3
1.3

LT threshold in k x In
k = 0.4 - 0.5 - 0.6 - 0.7 - 0.75 -
C
0.8 - 0.85 - 0.9 - 0.95 - 1.0 45
times the current transformer rating

40
LT time delay 5 - 10 - 15 - 20 -
25 - 30 - 35 - 40 s. at 7.2Ir
35

30

25
Time in seconds

20

15

10

ST threshold 1.5 - 2 - 3 -
4 - 5 - 7 - 9 - 10 - 12 - 14
times the LT value (Ir)

270 300 ST time delay 30 -


210 240 60 - 90 - 120 - 150 -
180
150 180 - 210 - 240 -
120 270 - 300 ms
90
60

30

Inst. threshold 1.5 - 2 - 3


- 5 - 7 - 9 - 10 - 13 - 15
times the LT value 5Ir)
12 14
0.7 1.5 13 15

Multiples of current setting


SPECTRONIC S/L - Air circuit breakers

RMS 9: protection and measurement unit for


circuit breakers S 800 to S 4000
Standard protection
- overload protection (LT)
- short circuit protection (ST and I)
- ground fault protection (GF)

Setting ranges
Setting points
LT (x In) 0.5 - 1 (steps of 0.05)
LTD (s) 3 - 6 - 12 - 25 / at 6 lr
ST (x lr) 1.5 - 9 (steps of 0.5)
Time delay (ms) 100 - 210 - 350
I (x lr) 1.5 - 15 - OFF (steps of 0.5) RMS 9 2000

C 1.5 - 15 - OFF (steps of 0.5) RMS 9 3200


1.5 - 15 - OFF (steps of 0.5) RMS 9 4000
46 GF (x In) 0.2 - 0.6 (steps of 0.01) RMS 9 2000
0.2 - 0.37 (steps of 0.01) RMS 9 3200
0.2 - 0.3 (steps of 0.01) RMS 9 4000
Time delay (ms) 100 - 210 - 350
Ir = k x Ir
Note.
If the GF function is selected, the fourth current transformer must be of the
same rating as the one of the phases.

Additional programmable functions


All or part of the following programmable functions may be
selected:
- current unbalance ∆l (A)
- undervoltage < V (B)
- overvoltage > V (B)
Description - voltage unbalance ∆V (B)
- reverse power Pi (B)
The RMS 9 unit is powered by the current transformers, Imax = 4000A, the
unit performs all the necessary current protections as well as the
(A) = without voltage conditioner
measurement (RMS) of the network parameters.
(B) = with voltage conditioner
As well as providing the above functions the communicating model of the
RMS 9 (2000C, 3200C, 4000C) can also operate remote event measure-
ment and recording. Function Range (%) Step
<V 50 - 90 1
>V 110 - 150 1
∆V 10 - 50 1
current ∆I 10 - 50 1
transformers Pi 10-990kW 10kW
N
A/D converter

A actuator Each function can be time delayed within a range from 1 to 15 seconds
sampler

(+ OFF position).
microprocessor

B
RMS 9

C
Distinct fault signalisation
By local display with the RMS 9 unit in 'Status' mode the condition of the
keyboard breaker is indicated. Also the time and number releases under fault:
LCD display - LT, ST, I, GF
- undervoltage, overvoltage, ..., reversal power.
SPECTRONIC S/L - Air circuit breakers

RMS 9: protection and measurement unit


“High precision” measurements
Without voltage conditioner
- Current on each phase (A, kA)
With voltage conditioner
- Current on each phase (A, kA)
- Voltage between phase and neutral: max. 600V
- Voltage between phases: max. 600V
- Energy (kWh, MWh)
- Active power per phase(1) (kW)
- Total active power (kW, MW)
- Total power per phase (1) (kVA, MVA)
- Total power (kVA, MVA)
- Average power demand (kW, MW)
- Maximum power demand (kW, MW) C
- Frequency (Hz) 47
(1) If the neutral is connected
To ensure a permanent display, the RMS 9 unit must be supplied by an auxiliary power supply of
24V DC - 15W regulated.

auxiliary
power supply
24V dc

voltage
conditioner (1,76V)
actuator
A/D converter
sampler

current
microprocessor

transformers (3 or 4)
RMS 9

relay
keyboard

LCD display
communication
(Power Leader Network)

Structure
I max (A) without communication with communication
2000 RMS 9 2000 RMS 9 2000C
3200 RMS 9 3200 RMS 9 3200C
4000 RMS 9 4000 RMS 9 4000C
SPECTRONIC S/L - Air circuit breakers

RMS 9: protection and measurement unit


Setting and operating current values

1.05
Operating limits according to IEC
1.3

C LT thresholds in k x In
0.5 to 1 times the current transformer
48 rating (0.05 steps)

LT time delay
3 - 6 - 12 - 25 s at 6 Ir
Time in seconds

ST thresholds
1.5 to 9 times
the LT value (lr)

I²t OUT I²t IN

ST time delay
0.100 - 0.210 - 0.350 s

Instantaneous thresholds (I)


1.5 to 15 times the LT value (lr)
(in steps of 0.5)

Multiples of current setting


SPECTRONIC S/L - Auxiliaries

Electrical control
Description
Integrated within the overall dimensions of the circuit breaker the adaptation of the electical motor
operator can be easily done on site.
Stored energy type: a universal motor loads a spring through a reduction gear. The spring stores the
energy necessary for closing the air circuit breaker.
The closing of the air circuit breaker can be done:
- remotely, a closing coil EE.
- locally by a pushbutton located on the control panel.
The opening of the circuit breaker can be done:
- remotely, by undervoltage or shunt release,
- locally by a pushbutton located on the control panel.
The spring is automatically reset after closing of the air circuit breaker enabling successive operations
without energy supply of:
- 1 tripping operation
- 1 closing operation
- 1 tripping operation
Anti-pumping device in case of sustained closing command.
Visible indication, on the face plate of the spring state:
C
- yellow: spring unloaded 49
- blue: spring loaded.
Closing prevention device (FE) if the voltage is too low. (Option)

Characteristics
Resetting time of the electrical control: 7 s.
Closing time: 0.06 s.
Motor
Rated voltages
Alternating current 50-60Hz 48 - 127 - 220V Main diagram
380V (on request)
Direct current 24 - 48 - 110 - 220V
Power dissipated 640 to 3200 to
2500A 6400A R
Alternating current 175VA 400VA
Direct current 150W 350W
FCA
Operation voltage from 0.85 to 1.1 Un U1 M U2

Closing electro magnet BPEL


Rated voltages
Alternating current 50-60Hz 48 - 127 - 220 - 380V AM
Direct current E1 FE E2
24V - economy resistor 11Ω
48V - economy resistor 60Ω
110V - economy resistor 330Ω
220V - economy resistor 1000Ω
Power dissipated S5 S2
A1 EE A2
Alternating current closing: 320VA
holding: 50VA
Direct current closing: 450W
holding: 50W MV
D1 D2
Operation voltage from 0.85 to 1.1 Un <U

CA8
C1 EA C2

BPEL = local closing pushbutton with


electrical motor operator
EE = closing coil
FE = closing prevention device
AM = manual reset
R = accumulation spring energy
FCA = reset limit switch
M = motor
S5 = remote closing push-button
S2 = remote trip push-button
SPECTRONIC S/L - Auxiliaries

Voltmetric releases
Characteristics
shunt trip undervoltage
release release
EA EA1 UVR
Rated voltage Un
alternating current 50Hz (V) 24 - 48 - 127 - 220 - 127 - 220 - 380 - 24 - 48 - 127 - 220 -
380/500 415 - 500 380 - 415 - 500
alternating current 60Hz (V) 24 - 48 - 127 - 220 - 127 - 220 - 380 - 24 - 48 - 127 - 220 -
380/500 415 - 500 380/415 - 500
direct current (V) 24 - 48 - 110/120 - - 24 - 48 - 110 - 120 -
220 220 - 440 - 500
Operating voltage from 0.7 to 1.1 Un from 0.1 to 1.3 Un from 0.35 to 0.7Un(1)
Power absorbed
alternating current closing (VA) 80 to 100 800 23
holding (VA) - - 10
direct current ≤ 220V (W) 30 - 6
440-500V (W) 275 - 21
Opening time of the circuit (ms) 60 60 85
C Two types of voltmetric releases permit remote
operation of the circuit breaker. Maximum equipment
50
Shunt trip releases EA-EA1 1st possibility 1 1 –
2nd possibility – 1 1
Open the circuit breaker (power supply out by an 3rd possibility 1 – 1(2)
auxiliary contact). 4th possibility – – 2(2)
(1) Closing of the circuit breaker ensured from 0.85. (2) or UVRD
Undervoltage releases UVR-UVRD
Open the circuit breaker when the supply voltage
falls to a value between 35 and 70% of its rated
value.
UVR: instantaneous action.
UVRD: delayed action of 250 ms or 0,6 s
alternating current power supply.
Other delaying devices on request.

Closing prevention device FE Manually or electrically operated circuit breakers:


(on request) obtained upon request, by an undervoltage closing prevention device FE.
Operating voltage from 0.35 to 0.7 Un(1) / from 0.35 to 0.85 Un(2)
Rated voltage
alternating current 50Hz (V) 24 - 48 - 127 - 220 - 380 - 415 - 500
alternating current 60Hz (V) 24 - 48 - 127 - 220 - 380 - 415 - 500
direct current (V) 24 - 48 - 110 - 120 - 220 - 440 - 500
(1) L 640 - 2000 and S 800 - 2500
(2) S 3200 - 6400

Consumption
Alternating current
closing (VA) 23
holding (VA) 10
Direct current
± 220V (W) 6
440-550V (W) 21
500V (W) 21
SPECTRONIC S/L - Auxiliaries

Auxiliary switches
Possibility of eight auxiliary switches NO + NC accessible from the front of the circuit breaker:
- four switches (AS1, AS2, AS3, AS4) operate at the same time as the main poles,
- four switches (AS5, AS6, AS7, AS8) operate at the beginning of the breaker closing movement.

Characteristics
Thermal current Ith 20A
Breaking capacity
alternative current cos ϕ 0.3
500V 6A
direct current L/R ≤ 0.01 s
110V 2.5A
250V 0.8A
Low voltage contacts 4 to 30V - 1 to 100mA
on S 800 to 6400 and L 640 to 2000

Diagram
C
51

13 14
CA1
11 12

23 24
CA2
21 22

not available
if EA or EA1 used
83 84
CA8
81 82
SPECTRONIC S/L - Auxiliaries

Fault signalling contacts and indicators Signalling contact


Indicates ‘reinforced spring’ position.
Common “short circuit” and “overload” signalling
Signalling tripping by UVR, UVRD, EA, EA1
Possibility of two changeover contacts with common point NO + NC (BA)
activated by RMS 7 or RMS 9 relays: NO + NC changeover contacts, by temporary action:
- contact for local resetting by trip push-button - C 31 activated by EA AND EA1
Alarm is cancelled by pushing the local push-button: - C 41 activated by UVR or UVRD.
- contact momentarily activated by electrically operated circuit breaker
(automatic reset on request).
Characteristics
Thermal current Ith 25A
95
BA
98 Breaking capacity
alternating current 220V 10A
96 380V 5.5A
direct current 30V 8A
BA 110V 0.5A
05 08
220V 0.4A
06
C Common fault signalling for overload and short-circuit
52
Common “short-circuit” and “overload” recall signal Only if the release can be locally reset.
(by relays). Black: normal
White: fault
Factory mounted on S or L electrically operated circuit breakers
(automatic reset) Operation counter
Alarm is cancelled by pushbutton S1.
The fault signal does not prevent the circuit breaker from reclosing.
S1 = cancelling alarm push-button

L1
B1 3

4 K1 1
CD S1

BA = common ‘overload’ and ‘short-circuit’ signalling contact


K1 = relay

Voltage present on voltmetric release UVR, UVRD.


Factory mounted.
Possibility of one changeover contact NO + NC with common point (C 43)
activated directly by the coil. The contact mounted on the UVR release
ensures an electrical interlock when the UVR supply voltage is incorrect.

Common electrical signal contact characteristics for ‘overload and short


circuit’, ‘voltage present’ on the voltmetric release UVR or UVRD, "stored
energy" signalling contact.
Thermal current 20A
Breaking capacity
alternating current 220V –
250V 16A
380V –
direct current L/R H 0.01 s
48V 0.7A
110V 0.2A
220V –
SPECTRONIC S/L - Auxiliaries

Standard equipment for Auxiliary secondary disconnection


withdrawable circuit breakers Device permits to connect:
- On circuit breakers L 640 to L 2000 and S 800 to S 4000:
6 circuits of 15A by 6.35 plugs (2 per terminal) or by plates (2 wires of 1.5 mm˝)
Standard circuit breaker supplied with two blocks of 6 circuits
Maximum mounting possible: four blocks of 6 circuits + two blocks of 3 circuits.
- On circuit breakers S 5000 - 6400:
24 circuits of 16A by screw terminals (capacity 2.5 mm˝) manually unplugged.
Auxiliary wiring is in service in the “connected” and “test” positions.

Rejection feature
Mechanical device preventing plugging in a breaker with a rating different to the one normally
used in the cradle.

Ground plug

C
53
Optional equipment for “Connected” position contact
withdrawable circuit breakers Indicates the position of the circuit breaker in its cradle.
Possibility of two changeover switches C 51, C 52, activated at the end of plugg-in operation.
Low voltage contacts possible on circuit breakers L 640 to 2000 and S 800 to 4000:
4 to 30V - 1 to 100mA. Connection by clips of 6.35 mm.

“Withdrawn” position contact


Indicates the position of the circuit breaker in its cradle.
Possibility of two changeover switches C 61, C 62, activated at the end of withdrawal.
Low voltage contacts possible on the circuit breakers L 640 to 2000 and S 800 to 4000:
4 to 30V - 1 to 100mA.
Connections by clips of 6.35 mm.

Safety contact
Indicates that the closing of the circuit breaker may be actioned; this being in the connected position,
cranks not inserted.
Possibility of switch contact C 71.
Connection by clips of 6.35 mm.

Isolating shutter
Access to live parts of the circuit breaker is
inhibited in the “withdrawn” position (IP20) with a Contact characteristics
padlock system (padlocks not supplied). 640 to 4000A 5000 - 6400A
Thermal current Ith A 20 25
Breaking capacity
alternating current
220V A - 10
250V A 16 -
380V A - 5.4
direct current
30V A - 8
110V A 0.4 0.5
220V A 0.2 0.4

Reinforced ground plug


S800 - 4000 and L 640 - 2000 - Icc 25kA - 0.5 s
Reinforces the natural electrical continuity
between the mass of the cradle and the mass of
the circuit breaker.
SPECTRONIC S/L - Interlocks

Circuit breakers L 640 to L 2000 and S 800 to 4000 Circuit breakers S 5000 and S 6400
Fixed circuit breakers Fixed circuit breakers
Interlocking in “tripped” position by lock Interlocks in “tripped” position by lock
(not supplied) (not supplied)
Possibilities: Possibilities:
- a Ronis lock, type 1104, 1/4 turn, opening to the left, - a Ronis lock, type 1104, 1/4 turn, opening to the left
- or a Profalux lock, type KS 5B G4Y - or a Profalux lock, type KS 5B G4Y
- or a CASTELL type lock FS 1. - or 1 CASTELL lock type FS 1.
Interlocking in “tripped” position by padlocks Interlocking in “tripped” position by padlock
Possibility: three padlocks. Possibility: three padlocks.
Interlocking of local control by padlocks Interlocking of local control by padlocks
For electrically operated circuit breaker: padlockable shutter preventing For electrically operated circuit breaker: padlockable shutter preventing
access to the closing and trip pushbutton. access to the closing and trip pushbuttons.
Possibility: two padlocks. Possibility: two padlocks.

Withdrawable circuit breakers Withdrawable circuit breaker


C Interlocking in “tripped” position by locks Interlocking in “tripped” position by lock
54 (not supplied) (not supplied)
Possibilities: Possibilities:
- a Ronis lock, type 1104, 1/4 turn, opening to the left - a Ronis lock, type 1104, 1/4 turn, opening to the left,
- or a Profalux lock, type KS 5B G4Y - or a Profalux lock, type KS 5B G4Y
- or a CASTELL type lock. - or a CASTELL type lock FS 1.
Interlock in “tripped” position by padlocks Interlocking in “tripped” position by padlock
Possibility: three padlocks. Possibility: three padlocks.
Interlocking of local control by padlocks Interlocking of local control by padlocks
For electrically operated circuit breaker: padlockable shutter preventing For electrically operated circuit breaker, a padlockable shutter prevents
access to the closing and trip pushbuttons. access to the close and trip pushbuttons.
Possibility: two padlocks. Possibility: two padlocks.
Interlocking in “withdrawn” positions by lock (E) or (F) Interlocking in “withdrawn” position by lock(1)
(lock not supplied) (lock not supplied)
Possibilities: Possibilities:
- a Ronis lock, type 1104, 1/4 turn, opening to the left or a Profalux lock, - a Ronis lock, type 1104, 1/4 turn, opening to the left
type KS 5B 20 D4Y - or a Profalux lock, type KS 5B 20 G4Y.
- two Ronis locks, type 1104, 1/4 turn, opening to the right or two Profalux Interlocking in “all positions” by lock(1)
locks, type KS 5B 20 D4Y (lock not supplied)
Interlocking in “connected” position by lock (E) Possibility:
(lock not supplied)
- 1 Ronis lock, type 1104, 1/4 turn, opening to the right.
Possibilities:
Interlocking in “withdrawn” position by padlocks
- a Ronis lock, type 1104, 1/4 turn, opening to the right, (not supplied)
- or a Profalux lock, type KS 5B 20 D4Y. Possibility: 3 padlocks.
Interlocking in “withdrawn” position by padlocks (D)
(padlocks not supplied)
Standard on basic circuit breakers
Door interlocking in “connected” position for
S 800 to 4000 (on request)

D E F

(1) Circuit breaker without isolating shutter.


SPECTRONIC S/L - Source Changeover Switches

Source changeover switches


General
Source changeover switches ensure continuity of power supply with a minimum of interruption time by
either automatically switching from a normal supply, or from an alternative supply with a changeover
transfer from one supply to the other.
They are particularly appropriate for industrial or tertiary sector installations having a single replace-
ment supply:
- either permanent
- independent operating generator set
- mains
- or non permanent:
- generator set which uses stop and start control signals transmitted by the source changeover
switch.

Description
Source changeover switches have the same characteristics and adaptability to the circuits to be
protected as the circuit breakers with which they are built. C
In the withdrawable version, the inoperative breaker can be disconnected without affecting the 55
operation of the breaker “In service”.
The device, when equipped with interlock in the “withdrawn” position conforms to the NF C 13-100
standard.
Source changeover switches consist of:
1. Two or three circuit breakers
- designed to be mechanically interlocked
- fitted with auxiliaries, wired and brought to the auxiliary terminal as needed for the chosen
diagram
- may be identical, or may differ in the following:
- circuit breaker
- type
- protection system
- structure (possible combination of fixed and withdrawable types)
2. A mechanical interlocking system
3. A mounting frame
4. An automatic controller comprising the relays necessary for operation of the source changeover
switches (not supplied)

Installation
The circuit breakers are superposed or placed side by side (with cables interlocking).
Changeover devices can be supplied in the following forms:
- either complete and mounted on a frame, ready to connect (selector switch not wired).
- or mounted on a frame, without automatism,
- or circuit breakers and mechanical interlocking delivered separately.

Characteristics
Operating voltage (VAC) 50Hz 220 - 380
Automatic without
power supply auxiliary supply (VAC) 50Hz 220 - 380
with (VAC) 50Hz 48 - 127 - 220 - 380
auxiliary supply (VDC) 24 - 48 - 110 - 220
Consumption circuit breaker ratings S 800 to 1600 S 2000 and 2500 S 3200 and 4000
during changeover (VA) 500 500 720
(W) 450 450 650
continuous (VA) 26 26 26
(W) 37 37 37
Minimum normal © with shunt trip release 2 s(1)
changeover replacement with undervoltage release 2 s(1)
time replacement with shunt trip release 2s
normal © with undervoltage release 2s
(1) If necessary, add the start up time of the generator.
SPECTRONIC S/L - Source Changeover Switches

Source changeover switches


Operation
The source changeover switch enables: Source changeover switches with two breakers (1)
- switching the power supply of circuits from the Breaking, using shunt trip device ST Breaking, using undervoltage trip release UVRD
normal supply to the replacement supply in - Installation without auxiliary supply - installation without auxiliary supply
case of loss of the normal supply - installation with auxiliary supply - installation with auxiliary supply on
- Switching the power supply circuit from the request.
replacement supply to the normal supply upon
return of the normal voltage and generating
load shedding and load resumption com-
mands for non priority circuits by using
auxiliary contacts fitted to each breaker automatic operation automatic operation
Un present Un present
- Selection of the operating mode by using a N closed N closed
switch which provides the following positions: R open R open
- off
- automatic
C - normal power supply operation
- replacement power supply operation
absence of Un absence of Un
56
- in the three unit version, select the power switching switching
supply of circuits from: normal ♦ alternative normal ♦ alternative
- normal supply 1
T1 = 0.1 to 30 s T1 = 250 ms
- normal supply 2
- normal sources 1+2 by means of a
duration < T1 duration > T1 duration < T1 duration > T1
preselector switch.
no effect no effect
The automatic controller is powered from:
standby equipment opening of N
- either the mains to be monitored
continuous start-up continuous
- or an auxiliary supply.
alternative alternative
The changeover is prevented on tripping by fault.
supply supply standby equipment
Automatic re-starting after fault tripping and start up
or
elimination of the fault is carried out by pressing
presence of Ur or
the reset pushbutton on the dashboard of the
breaker concerned.The breaker in service can T2 = 0.1 to 30 s(2) presence of Ur
be tripped by pressing the local trip pushbutton
located on the dashboard. duration < T2 duration > T2
The breaker is restarted by operating the no effect
selector switch, going from the “OFF” position to opening of N
the “Automatic” position. T2 = 0.1 to 30 s(2)
T3 = 1 to 30 s closing of R
closing of R
return of Un
return of Un
switching
switching alternative♦ normal
alternative ♦ normal T3 = 250 ms
T4 = 0.6 s to 60 min.(3)
duration < T3 duration > T3
duration < T4 duration > T4
no effect
no effect opening of R
opening of R
T4 = 0.1 to 30 s(2)
T5 = 0.1 to 30 s(2)
closing of N
closing of N
standby
standby equipment off
equipment off

(1) Same operating principle for the a ‘3 breakers'


T = time delay alternative
Un = normal voltage (2) Min. 1 s
Ur = alternative voltage (3) Min. 10 s
N = normal supply breaker
R = replacement supply breaker
SPECTRONIC S/L - Source Changeover Switches

Specify on the order


Source changeover switch ❏ automatic
❏ manual
Rated voltage:
❏ 220V 50Hz - 380V 50Hz
Chassis ❏ supplied ❏ not supplied
Automatic device (automatism) ❏ supplied ❏ not supplied
power supply ❏ without auxiliary supply: voltage identical to service voltage
❏ with auxiliary supply: voltage: 48 - 127 - 220 - 380V 50Hz
24 - 48 - 110 - 220V
opening by ❏ shunt trip release EA
❏ undervoltage release UVRD
selector switch ❏ supplied ❏ not supplied
Upper unit(1) ❏ on normal supply ❏ on replacement supply
type ❏ S 800 ♦ S 4000 ❏ L 640 ♦ L 2000
number of poles ❏ 3 poles ❏ 4 poles
structure
protection unit
❏ fixed
❏ RMS 7
❏ withdrawable
❏ RMS 9
C
57
Lower unit(1) ❏ on normal supply ❏ on replacement supply
type ❏ S 800 ♦ S 4000 ❏ L 640 ♦ L 2000
number of poles ❏ 3 poles ❏ 4 poles
structure ❏ fixed ❏ withdrawable
protection unit ❏ RMS 7 ❏ RMS 9
Medium unit(1) ❏ for automatic transfer switches on replacement supplies
type ❏ S 800 ♦ S 4000 ❏ L 640 ♦ L 2000
number of poles ❏ 3 poles ❏ 4 poles
structure ❏ fixed ❏ withdrawable
protection unit ❏ RMS 7 ❏ RMS 9
interlocking ❏ see operation(2)
Auxiliaries ❏ Source changeover switches built according to our diagrams cannot be fitted with other auxiliaries:
2 changeover contacts NO/NC, are available at circuit breaker secondary terminals.
❏ Other changeover devices can be fitted with auxiliaries within the limits of the possibilities
offered by each.
Accessories Automatic changeover devices are fitted with interlocking by padlock (not supplied) for preventing
access to the pushbuttons.
They can be provided with:
Fixed circuit breaker:
❏ “Tripped” interlocking
Withdrawable circuit breaker:
❏ “Tripped”, “Withdrawn”, “Connected” interlocking
❏ Vertical connecting terminals (horizontal as standard)
❏ Isolating shutter

(1)
Refer to the circuit breaker specification
(2)
Operation
Two normal supplies possible One normal supply (on request)
normal 1 0 x 0 0 x normal 1 0 x 0 0
remplacement 0 0 x 0 0 replacement 0 0 x 0
normal 2 0 0 0 x x normal 2 0 0 0 x
x: closed circuit breaker x: closed circuit breaker

Notes
1. For a different installation an
interlocking by cables can be provided.
2. S 5000 - 6400: consult the sales
office.
SPECTRONIC S/L - Air Circuit Breakers

Specify on the order


Device ❏ circuit breaker (S or L type)
❏ switch (S type)
Type ❏ S 800 ❏ S 2500 ❏ L 640
❏ S 1000 ❏ S 3200 ❏ L 1000
❏ S 1250 ❏ S 4000 ❏ L 1250
❏ S 1600 ❏ S 5000 ❏ L 1600
❏ S 2000 ❏ S 6400 ❏ L 2000
Number of poles ❏ 3 poles ❏ 4 poles
Structure
S 800 to S 4000 - L 640 to L 2000 ❏ fixed ❏ front connections ❏ rear horizontal connections
❏ withdrawable ❏ front connections ❏ rear horizontal connections
S5000 - S 6400 ❏ horizontal ❏ fixed ❏ rear horizontal connections
❏ vertical ❏ fixed ❏ rear horizontal connections
❏ withdrawable ❏ rear vertical connections
Protection ❏ RMS 7 ❏ current transformer (3 or 4)
❏ RMS 7 options ❏ fault signalling
C ❏ RMS 9
❏ sealable cover
❏ current transformer (3 or 4)
58 ❏ voltage conditioner
Type of control ❏ manual
❏ electrical (indicates voltage and frequency)
Voltmetric releases Shunt trip release (indicate voltage and frequency)
❏ EA
❏ EA1
Undervoltage trip (indicate voltage and frequency)
❏ UVR
❏ UVRD
❏ closing prevention device
Signal auxiliaries Indicates the number of contacts
auxiliary switches
❏ AS
fault contact
❏ BA
❏ fault signalling by relay
"stored energy" signalling contact
❏ C22
Contact coupled with local push-button
❏ C20
Tripping signalling contact on EA, EA1, UVR, UVRD
❏ C31 (EA or EA1)
❏ C41 (UVR or UVRD)
Voltage present contact
❏ C43 (UVR or UVRD)
Equipment Withdrawable circuit breaker
❏ auxiliary secondary disconnection device
❏ isolating shutter
❏ reinforced ground plug
❏ “connected” position contact: C51/C52
❏ “withdrawn” position contact: C61/C62
❏ safety contact: C71
Interlocks Fixed circuit breaker:
❏ “tripped” position by lock (type of lock)
❏ “Tripped” position by padlocks
❏ local control (push buttons) by padlocks
Withdrawable circuit breaker:
❏ “tripped” position by lock (type of lock)
❏ “tripped” position by padlocks
❏ local control (push buttons) by padlocks
❏ withdrawn position by lock (type of lock)
❏ “withdrawn” position by padlock (standard)
❏ “connected” position by lock (type of lock) on S 800 to S 4000 and L 640 to L 2000
❏ door interlocking in “connected” position for S 800 to 4000 (on request)
❏ all positions by lock on S 5000 - S 6400
Users guide ❏ English
❏ French
❏ German
SPECTRONIC S - Order codes

Circuit breakers
Without protection S800 S1000 S1250 S1600 S2000 S2500 S3200 S4000
FIXED with rear horizontal 3P 754303 754313 754323 754333 754343 754353 754363 754373
terminals
4P 754304 754314 754324 754334 754344 754354 754364 754374

Front terminals kit 3P 751320 751320 751322 751322 751324 751326 - -


4P 751321 751321 751323 751323 751325 751327 - -

WITHDRAWABLE
3P 754301 754311 754321 754331 754341 754351 754361 754371
Moving part
4P 754302 754312 754322 754332 754342 754352 754362 754372
+
Fixed part 3P 754451 754451 754453 754455 754457 754459 754461 754463
Cradle with rear
4P 754452 754452 754454 754456 754458 754460 754462 754464
horizontal terminals
Cradle with rear 3P 754471 754471 754473 754475 754477 754479 - -
C
vertical terminals 59
4P 754472 754472 754474 754476 754478 754480 - -

Cradle with 3P 754481 754481 754483 754485 754487 754489 754491 754493
front terminals
4P 754482 754482 754484 754486 754488 754490 754492 754494

Higher value for 690V version


Fixed circuit breaker 3P 754153 754153 754153 754153 754163 754173 754183 754183
4P 754154 754154 754154 754154 754164 754174 754184 754184

Withdrawable 3P 754151 754151 754151 754151 754161 754171 754181 754181


circuit breaker
4P 754152 754152 754152 754152 754162 754172 754182 754182

Higher value for 1000V version


Contact us

S5000 to S6400 circuit breakers


Without protection S5000 S6400
FIXED with rear 3P 754280 754282
horizontal terminals
4P 754281 754283
FIXED with rear 3P 754270 754272
vertical terminals
4P 754271 754273

WITHDRAWABLE
Moving part 3P 754260 754262
+ 4P 754261 754263
Fixed part:
cradle with rear 3P 751222 751223
vertical terminals 4P 751224 751225
SPECTRONIC S - Order codes

RMS 7 755452 RMS 7


protection unit

Current transformer
Three pole equipment Rating A S 800 S1000 S 1250 S 1600 S 2000 S 2500 S 3200 S 4000 S 5000 S 6400
800 755460 - - - - - - - - -
1000 - 755461 - - - - - - - -
1250 - - 755462 - - - - - - -
C 1600 - - - 755463 - - - - - -
60
2000 - - - - 755464 - - - - -
2500 - - - - - 755465 - - - -
3200 - - - - - - 755466 - - -
4000 - - - - - - - 755467 - -
5000 - - - - - - - - 755468 -

+ 6400 - - - - - - - - - 755469

Equipment for the fourth pole Rating A S 800 S1000 S 1250 S 1600 S 2000 S 2500 S 3200 S 4000 S 5000 S 6400
800 755470 - - - - - - - - -
1000 - 755471 - - - - - - - -
1250 - - 755472 - - - - - - -
1600 - - - 755473 - - - - - -
2000 - - - - 755474 - - - - -
2500 - - - - - 755475 - - - -
3200 - - - - - - 755476 - - -
4000 - - - - - - - 755477 - -
5000 - - - - - - - - 755478 -
6400 - - - - - - - - - 755479
SPECTRONIC S - Order codes

Rating plug
3P/3P+N 100% Rating A S 800 S1000 S 1250 S 1600 S 2000 S 2500 S 3200 S 4000 S 5000 S 6400
400 755554 - - - - - - - - -
600 755553 - - - - - - - - -
800 755550 755563 - 755584 - - - - - -
1000 - 755560 - - - - - - - -
1200 - - - 755583 755593 - - - - -
1250 - - 755570 - - - - - - -
1600 - - - 755580 - 755603 755613 - - -
2000 - - - - 755590 - - - - -
2500 - - - - - 755600 - 755623 - -
3200 - - - - - - 755610 - - -
4000 - - - - - - - 755620 - -
C
61
5000 - - - - - - - - 755630 -
6400 - - - - - - - - - 755640

3P+N 50% Rating A S 800 S1000 S 1250 S 1600 S 2000 S 2500 S 3200 S 4000 S 5000 S 6400
800 755552 - - - - - - - - -
1000 - 755562 - - - - - - - -
1250 - - 755572 - - - - - - -
1600 - - - 755582 - - - - - -
2000 - - - - 755592 - - - - -
2500 - - - - - 755602 - - - -
3200 - - - - - - 755612 - - -
4000 - - - - - - - 755622 - -
5000 - - - - - - - - 755632 -
6400 - - - - - - - - - 755642

With integrated GF Rating A S 800 S1000 S 1250 S 1600 S 2000 S 2500 S 3200 S 4000 S 5000 S 6400
400 755555 - - - - - - - - -
600 755556 - - - - - - - - -
800 755557 755565 - 755585 - - - - - -
1000 - 755566 - - - - - - - -
1200 - - - 755586 755595 - - - - -
1250 - - 755575 - - - - - - -
1600 - - - 755587 - 755605 755615 - - -
2000 - - - - 755596 - - - - -
2500 - - - - - 755606 - 755625 - -
3200 - - - - - - 755616 - - -
4000 - - - - - - - 755626 - -
5000 - - - - - - - - 755635 -
6400 - - - - - - - - - 755645
SPECTRONIC S - Order codes

RMS 9 protection The RMS 9 is always composed of two references: RMS 9 + adaptor plate

755370 RMS 9 3P 755380 RMS 9 3P 755390 RMS 9 3P


2000 3200 4000
755400 3P + N/2 755402 3P + N/2 755404 3P + N/2
755374 4P 755384 4P 755394 4P

755371 RMS 9 3P 755381 RMS 9 3P 755391 RMS 9 3P


2000C 3200C 4000C
755401 3P + N/2 755403 3P + N/2 755405 3P + N/2
755378 4P 755388 4P 755398 4P

755385 Adaptor plate

Current transformer
C Three pole equipment rating A S 800 S 1000 S 1250 S 1600 S 2000 S 3200 S 4000
62 800 755410 - - - - - -
1000 - 755411 - - - - -
1250 - - 755412 - - - -
1600 - - - 755413 - - -
2000 - - - - 755414 - -
3200 - - - - - 755440 -
+ 4000 - - - - - - 755441
Equipment for 4th pole 800 755420 - - - - -
(100% or reduced neutral)
1000 - 755421 - - - - -
1250 - - 755422 - - - -
1600 - - - 755423 - - -
2000 - - - - 755424 - -
3200 - - - - - 755442 -
4000 - - - - - - 755443
SPECTRONIC S - Order codes

Options 755457 Distinct fault signalling

For RMS 7 unit 755458 Sealable cover

For RMS 9 unit


C
63
755450 Voltage conditioner

741009 Conditioner fusible


plug for
- three fuse holders 10 x 38
- 2A type gG

755373 Test set for RMS 9

Note
Don’t forget the auxiliary power supply
(not supplied)
Number of secondary disconnections to use:
- voltage conditioner 4 wires
- auxiliary power supply 2 wires
- communication 2 wires
SPECTRONIC S - Order codes

S 800 to S 4000 switches


S800 S1000 S1250 S1600 S2000 S2500 S3200 S4000
FIXED with rear horizontal 3P 754309 754319 754329 754339 754349 754359 754369 754379
terminals
4P 754308 754318 754328 754338 754348 754358 754368 754378

Front terminals kit 3P 751320 751320 751322 751322 751324 751326 - -


4P 751321 751321 751323 751323 751325 751327 - -

WITHDRAWABLE
Moving part 3P 754305 754315 754325 754335 754345 754355 754365 754375
+ 4P 754306 754316 754326 754336 754346 754356 754366 754376
Fixed part
3P 754451 754451 754453 754455 754457 754459 754461 754463
Cradle with rear
horizontal terminals 4P 754452 754452 754454 754456 754458 754460 754462 754464
C Cradle with rear
3P 754471 754471 754473 754475 754477 754479 - -
64 vertical terminals
4P 754472 754472 754474 754476 754478 754480 - -

Cradle with front 3P 754481 754481 754483 754485 754487 754489 754491 754493
terminals
4P 754482 754482 754484 754486 754488 754490 754492 754494

Higher value for 690V version


Fixed circuit breaker 3P 754157 754157 754157 754157 754167 754177 754187 754187
4P 754158 754158 754158 754158 754168 754178 754188 754188

Withdrawable circuit breaker 3P 754155 754155 754155 754155 754165 754175 754185 754185
4P 754156 754156 754156 754156 754166 754176 754186 754186
SPECTRONIC L - Order codes

L 640 to L 2000 circuit breaker


Circuit breaker without protection L640 L1000 L1250 L1600 L2000
FIXED with rear horizontal 3P 754403 754413 754423 754433 754443
terminals
4P 754404 754414 754424 754434 754444

WITHDRAWABLE 3P 754401 754411 754421 754431 754441


Mobile part 4P 754402 754412 754422 754432 754442
+
Cradle with rear 3P 754451 754451 754495 754497 754499
horizontal terminals 4P 754452 754452 754496 754498 754500
Cradle with rear 3P 754471 754471 754501 754503 754505
vertical terminals
4P 754472 754472 754502 754504 754506

Front terminals 3P 754481 754481 754507 754509 754511 C


4P 754482 754482 754508 754510 754512 65

RMS 7 755452 RMS 7


protection unit

Current transformer
Three pole equipment Rating A L 640 L 1000 L 1250 L 1600 L 2000
640 755481 - - - -
1000 - 755482 - - -
1250 - - 755483 - -
1600 - - - 755484 -
2000 - - - - 755485
+
Equipment for the fourth pole Rating A L 640 L 1000 L 1250 L 1600 L 2000
640 755491 - - - -
1000 - 755492 - - -
1250 - - 755493 - -
1600 - - - 755494 -
2000 - - - - 755495
SPECTRONIC L - Order codes

Rating plug
3P/3P+N 100% Rating A L 640 L 1000 L 1250 L 1600 L 2000
400 755530 - - - -
640 755540 - - - -
800 - 755563 - 755584 -
1000 - 755560 - - -
1200 - - - 755583 755593
1250 - - 755570 - -
1600 - - - 755580 -
2000 - - - - 755590

3P+N 50% Rating A L 640 L 1000 L 1250 L 1600 L 2000


C 640 755542 - - - -
66 1000 - 755562 - - -
1250 - - 755572 - -
1600 - - - 755582 -
2000 - - - - 755592

With integrated GF Rating A L 640 L 1000 L 1250 L 1600 L 2000


400 755535 - - - -
640 755545 - - - -
800 - 755565 - - -
1000 - 755566 - - -
1200 - - - 755586 755595
1250 - - 755575 - -
1600 - - - 755587 -
2000 - - - - 755596

Options
For RMS 7 unit
755457 Distinct fault signalling

755458 Sealable cover


SPECTRONIC S/L - Order codes

Electrical auxiliaries
Electrical control

Use 4 connection
terminals or secondary
disconnection devices

S 800 to S 2500
L 640 to L 2000
S 3200 - S 4000
S 5000 - S 6400
C
67
Motor Coil Motor Coil
AC 50Hz
751855 751950 751849 751962 48V
751857 751951 751851 751963 127V
751858 751952 751852 751964 220V
754060 751977 751852 751978 240V
- 751953 751853 751965 380V

AC 60Hz
751855 751954 751849 751966 48V
751857 751955 751851 751967 127V
751858 751956 751852 751968 220V
754060 - - - 240V
- 751957 751853 751969 380V

DC
751854 751958 751848 751970 24V
751855 751959 751849 751971 48V
755275 755276 - - 60V
751856 751960 751850 751972 110V
751857 755890 751851 751986 127V
751858 751961 751852 751973 220V
754060 751975 - - 240V
SPECTRONIC S/L - Order codes

Electrical auxiliaries
Shunt trip release Undervoltage trip Closing prevention device

Use 2 Use 2 Use 2


connection connection connection
terminals or terminals or terminals or
secondary secondary secondary
disconnection disconnection disconnection
devices devices devices

EA UVR S 800 to S 2500 S 3200 - S 4000


AC 50/60Hz AC 50Hz L 640 to L 2000 S 5000 - S 6400

C 752226 24V 752271 24V


AC 50Hz

68 752227 48V 753000 753021 24V


752272 48V
752228 127V 753001 753022 48V
752273 127V
752229 220V 753002 753023 127V
752274 220V
752230 380/500V 753003 753024 220V
752209 240V
753004 - 380V
752275 380V
DC
753005 753026 415V
752276 415V
752231 24V
753006 753027 500V
752277 500V
752232 48V
752233 110/120V AC 60Hz
AC 60Hz
752234 220/500V 753007 753028 24V
752271 24V
753008 753029 48V
752272 48V
EA1 753009 753030 127V
752273 127V
AC 50/60Hz 753010 753031 220V
752287 220V
752235 127V 753011 753032 380/415V
752275 380/415V
752236 220V 753012 753033 500V
752276 500V
752237 380/415V
DC
752238 500V DC
753013 753034 24V
752296 24V
753014 753035 48V
752297 48V
753015 755065 110V
752298 110V
753016 755066 120V
752299 120V
753017 - 220V
752300 220V
753018 753039 440V
752301 440V
753019 753040 500V
752302 500V

UVRD 250 ms
AC 50Hz
752318 220V
752319 380V

MVR 0.6 s
AC 50Hz
752322 220V
752323 380V
SPECTRONIC S/L - Order codes

Signalling contacts Tripping signalling contact by EA, EA1, UVR, UVRD

Auxiliary switches 1 NO 1 NC 1 NO/NC

752700 752701 752702 C31 (on 1st or 2nd EA or EA1)


752700 752701 752702 C41 (on 1st or 2nd UVR or UVRD)

Voltage presence contact


1 NO 1 NC 1 NO/NC

752703 752704 752705 C43 (on 1st or 2nd UVR or UVRD)


Use 2 secondary terminals or disconnections for
1 x NO or 1 x NC.
Use 3 secondary terminals or disconnections
1 NO 1 NC 1 NO/NC 1 NO+NC for 1 x NO/NC.
S 800 to S 4000 and L 640 to L 2000
752660 752661 752662 752690 AS 1 Accessories S 800 to S 4000 - L 640 to L 2000 C
752663 752664 752665 752691 AS 2 69
752666 752667 752668 752692 AS 3 Secondary terminals
752669 752670 752671 752693 AS 4 Fixed circuit breaker
752672 752673 752674 752694 AS 5
752675 752676 752677 752695 AS 6 755900 Terminals (20 additional terminals max)
752678 752679 752680 752696 AS 7 753937 Support (obligatory)
752681 752682 752683 752697 AS 8
752874 752875 752876 - BA 1 Withdrawable circuit breaker
752877 752878 752879 - BA 2 Block of 6 circuits (max two additional blocks)
S 5000 to S 6400 755901 Mobile secondary disconnection
752764 752765 752766 - BA 1 755911 Fixed secondary disconnection
752849 752850 752851 - BA 2
755912 Complete secondary disconnection
Secondary terminals or disconnection device to include:
- per contact 1 x NO or 1 x NC: 2 terminals
- per contact 1 x NO/NC: 3 terminals Block of 3 circuits (two additional blocks (max))
- per contact 1 x NO+NC: 4 terminals 755949 Left mobile secondary disconnection

Fault signalling relay 755946 Right mobile secondary disconnection


755948 Left fixed secondary disconnection
24V 48V 110V 127V 220V
755945 Right fixed secondary disconnection
S 800 to S 2500 - L 640 to 2000
755950 Left complete secondary disconnection
- 752880 - 752881 752882 AC 50Hz
- 752887 - 752888 - AC 60Hz 755947 Right complet secondary disconnection
752883 752884 752885 - 752886 DC
Maximum number of secondary terminals or
S3200 - S4000 disconnections
- 752909 - 752892 752893 AC 50Hz Fixed circuit breaker Withdrawable circuit breaker
- 752898 - 752899 - AC 60Hz S 800 to S4000 S 800 to S 4000
752894 752895 752896 - 752897 DC L 640 to L 2000 L 640 to L 2000
40 = 2 x 20 30 = 4 x 6 + 2 x 3
Use 3 connection terminals or secondary disconnections.
Factory equipped with 20 terminals Fitted with
Signalling contacts two blocks of 6 circuits

1 NO/NC Accessories S 5000 to S 6400


753554 C22 (S800 to S 2500 - L640 to L 2000) Secondary terminals
Use 3 connection terminals or secondary disconnection devices.
Withdrawable circuit breaker
Contact coupled with local tripping push-button
755904 Mobile secondary disconnection (male plug)
1 NO/NC
755906 Complete secondary disconnection (male + female plug)
753900 C20 (S800 to S 2500 - L640 to L2000)
753902 C20 (S 3200 - S 4000 + S 5000 - S6400)
SPECTRONIC S/L - Order codes

Accessories
S800 S1000 S1250 S1600 S2000 S2500 S3200 S4000 S5000 S6400
Isolating shutter
3P 752524 752524 752524 752524 752525 752526 752529 752529 752531 752531
4P 752525 752525 752525 752525 752527 752528 752530 752530 752532 752532

L640 L1000 L1250 L1600 L2000


3P 752524 752524 752525 752525 752526
4P 752525 752525 752526 752527 752528

Reinforced ground plug 25kA - 0.5 s Interlocking Interlocking


S 800 to S 4000 - L 640 to L 2000 S 5000 to S 6400
756140 For withdrawable circuit breakers
In ''tripped'' position In ''withdrawn'' position
C 753224 by padlocks (not supplied)
3P 4P
70 Positioning contacts 753235 753245 by Ronis lock (supplied)
S 800 to S 4000 - L 640 to L 2000 753223 by Ronis lock (not supplied)
753234 753244 by Ronis lock (not supplied)
AC DC 753220 by Ronis or
Profalux lock (not supplied) 753236 753246 by padlock
752841 752843 “Connected” position
C51 - C52
753221 by padlocks (not supplied)+ 753237 753247 by Ronis lock
Ronis lock (not supplied) (not supplied) + padlock
752841 752843 “Withdrawn” position
C61 - C62
753222 by padlocks (not supplied)+ 753238 753248 by Ronis lock (supplied) +
Two contacts possible in each position. Ronis or Profalux lock (not supplied) padlock
752840 752842 Use an adaptor 752890 by Castell lock (not supplied) In all positions
for 4 contacts
S 800 to S 2500 - 753225 by Ronis lock (not supplied)
In “withdrawn” position
L 640 to L 2000
753226 by Ronis lock (supplied)
753213 by Ronis lock (supplied)
752846 752848 Use an adaptor
for 4 contacts 753214 by Ronis or Profalux lock
S 3200 - S 4000 (not supplied)
Positioning contacts In “connected” position
S 5000 to S 6400
753215 by Ronis lock (supplied)
752080 ''Connected'' position
753216 by Ronis or Profalux lock
752080 “Withdrawn” position (not supplied)
Two contacts possible in each position
Local control interlocking
752831 Use an adaptor for 4 contacts
S 5000 a S 6400 752832 by padlocks
Crank insertion safety
contact Door gasket

752870 C71 for S 800 - S 2500 752824 Provides an IP3x degree of


L 640 - L 2000 protection to the panel

752871 C71 for S 3200 - S 4000 Ronis lock

Operation counter 755960 Opening to the right

753899 755961 Opening to the left


Notes

C
71
SPECTRONIC S - Overall dimensions

Fixed circuit breaker S 800 to S 2500 Front connection

Gasket

C
72

Panel cut-out for gasket fitting Rear horizontal connection

Gasket

Minimum distance for insulating clamp

Legend
Circuit breaker Number A B C D E Front or rear horizontal connection terminals
of poles
S 800-1000-1250 3 318 98 101.5 81 15
S 1600 4 406 98 96.5 76 15 S800 to 1000 S1250 to 1600
S 2000 3 406 130 113.5 93 10
4 540 130 115.5 95 10
S 2500 3 474 150 127.5 107 15
4 620 150 125.5 105 15
S2000 S2500
F = minimum clearance distance above the arc chutes.
Ue ≤ 500V Ue ≤ 690V
I = insulated screen 150 mm 200 mm
M = metallic screen 150 mm 150 mm
SPECTRONIC S/L - Overall dimensions

Withdrawable circuit breaker S 800 to S 2500

a = door gasket
b = withdrawable door
closed
c = withdrawable door
open
(2) connected circuit
breaker

4 holes ) 10,2

Minimum distance for insulating clamp

C
Connections 73
Rear horizontal Rear vertical Front terminals Disconnected- Withdrawn
terminals (R.H.T.) terminals (R.V.T.) (T.D.) isolated position position

insulator

(2) connected
(3) disconnected
(4) withdrawn

Panel cut-out for gasket fitting Legend


Circuit breaker Nr. of A B C D E F G
poles
S 800-1000 3 399 98 101.5 77.5 217.5 87 10
1250-1600 4 487 98 96.5 72.5 217.5 87 10
S 2000 3 487 130 113.5 89.5 207.5 107 10
4 621 130 115.5 91.5 207.5 107 10
S 2500 3 555 150 127.5 103.5 197.5 127 15
4 701 150 125.5 101.5 197.5 127 15

door open H = minimum clearance distance above the arc chutes.


door closed
Ue ≤ 500V Ue ≤ 690V
I = insulated screen 100 mm 150 mm
Connection terminals M = metallic screen 150 mm 200 mm

F.T. S800 - 1000 S1250 S1600 S2000 S2500


R.V.T. S800-1000 S1250-1600 S2000 S2500
R.H.T. S800 - 1000 S1250 S1600 S2000 S2500

F.T.: Front terminals R.V.T.: Rear vertical terminals R.H.T.: Rear horizontal terminals
SPECTRONIC S/L - Overall dimensions

Fixed circuit breaker S 3200 - S 4000

Gasket

C
74

Panel cut-out for gasket fitting Rear horizontal terminals

F G
S 3200 3x5 127
S 4000 5x5 121.5

192

60

Legend
S 3200 S 4000
Circuit breaker Number A B C D
of poles Ø13 Ø13
S 3200-4000 3 628 238.5 132 201.5
4 826 436.5 130 399.5 50 25 50 25
E = minimum clearance distance above the arc chutes.
12,5 25 25 25 25 12,5 25 25 25 25 25 17,5
Ue ≤ 500V Ue ≤ 690V
125 160
I = insulated screen 200 mm 200 mm
M = metallic screen 200 mm 200 mm
SPECTRONIC S/L - Overall dimensions

Withdrawable circuit breaker S 3200 - S 4000

Withdrawn

Withdrawn isolated

Gasket

C
75
Connected

Withdrawable Withdrawable
door closed door open

Panel cut-out for gasket fitting Front or rear horizontal connection terminals

F G
S 3200 3x5 266.5
S 4000 5x5 261.5

Front connections Rear horizontal connections

Door open Door closed

Legend
Rear connections Front connections
Circuit breaker Number A B C D
of poles
S 3200-4000 3 711 235 130.5 198 Ø13
125
4 909 433 129.5 396 62,5 Ø18
50 25
E = minimum clearance distance above the arc chutes. 31,25

Ue ≤ 500V Ue ≤ 690V 12,5 25 25 25 25 25 17,5 42 42 38


I = insulated screen 100 mm 150 mm 160 160

M = metallic screen 150 mm 200 mm


SPECTRONIC S/L - Overall dimensions

Fixed circuit breaker S 5000 - 6400 horizontal

C
76

Side elevation Panel cut-out for fitting gasket

Gasket

Legend Connection terminals


Circuit breaker Number A B C
of poles Ø13
S 5000-6400 3 1120 450 501.5
4 1484 814 865.5 50 25

E = minimum clearance distance above the arc chutes.


12,5 25 25 25 25 25 25 25 25
Ue ≤ 500V Ue ≤ 690V
125 125
I = insulated screen 200 mm 200 mm 18.5 18.5
M = metallic screen 200 mm 200 mm
SPECTRONIC S/L - Overall dimensions

Fixed circuit breaker S 5000 - 6400 vertical

C
77

Panel cut-out for gasket fitting Panel cut-out for gasket fitting

Gasket

Legend

E = minimum clearance distance between the arc chute and the


inside of the panel.
Connection terminals
Ue ≤ 500V Ue ≤ 690V
I = insulated screen 200 mm 200 mm See page C.73

M = metallic screen 200 mm 200 mm


SPECTRONIC S/L - Overall dimensions

Withdrawable circuit breaker S 5000 - 6400


Panel cut-out for gasket
fitting

holes

C
78

Connected
Disconnected

(1) Hole for crank

Connection terminals

Panel cut-out for gasket fitting S 5000

S 6400

4 holes ) 14

Gasket

Legend
Circuit breaker Number
of poles A B C
S 5000-6400 3 1428 714 1320
4 1792 896 1684
E = minimum clearance distance above the arc chutes.
Ue ≤ 500V Ue ≤ 690V
I = insulated screen 100 mm 200 mm
M = metallic screen 200 mm 200 mm
Notes

C
79
SPECTRONIC S/L - Overall dimensions

Fixed circuit breaker L 640 to L 2000

C
80

Minimum distance for insulating clamp

Door panel cut-out for gasket fitting Connection terminals

L640 - 1000 L1250 L1600 - 2000

Legend
Circuit breaker Number A B C D
of poles
L 640 - 1000 3 318 98 101.5 81
4 406 98 96.5 76
L 1250 3 406 115 128.5 108
4 474 115 105 84.5
L 1600 3 406 130 113.5 93
4 540 130 115.5 95
L 2000 3 474 150 127.5 107
4 620 150 125.5 105

E = minimum clearance distance above the arc chutes


Ue ≤ 500V Ue ≤ 690V
I = insulated screen 150 mm 150 mm
M = metallic screen 150 mm 150 mm
SPECTRONIC S/L - Overall dimensions

Withdrawable circuit breaker L 640 to 2000

a = door gasket
b = withdrawable
door closed
c = withdrawable
door open
(2) connected
circuit breaker

4 holes ) 10.2

Minimum distance for insulating clamp

Connections
C
81
Rear horizontal Rear vertical Front terminals Disconnected- Withdrawn
terminals (R.H.T.) terminals (R.V.T.) (F.T.) isolated position
position

isolator

(2) Connected
(3) Disconnected
(4) Withdrawn

Circuit breaker Number A B C D


Panel cut-out for gasket fitting of poles
L 640 - 1000 3 399 98 101,5 77.5
4 487 98 96,5 72.5
L 1250 3 487 115 128,5 104.5
4 555 115 105 81
L 1600 3 487 130 113.5 89.5
4 621 130 115.5 103
L 2000 3 555 150 127.5 103.5
4 701 150 125.5 101.5
door open E = minimum clearance distance above the arc chutes
door closed
Ue ≤ 500V Ue ≤ 690V
I = insulated screen 100 mm 150 mm
Connection terminals M = metallic screen 150 mm 200 mm

F.T. L640 -1000 L1250 L1600 L2000 F.T.: Front terminals


R.V.T. L640 - 1000 L1250-1600 L2000 R.V.T.: Rear vertical terminals
R.H.T. L640 -1000 L1250 L1600 L2000 R.H.T.: Rear horizontal terminals
SPECTRONIC S/L - Overall dimensions

Source changeover switches


Fixed or withdrawable, two circuit breakers without frame

C
82

Circuit breaker A B C D
3P 4P 3P 4P fixed W/D fixed W/D White area: interlocking brackets dimensions
S 800 to 1600 351 439 77.5 72.5 15.5 79 (3) 417.5
L 640 - L 1000
L 1250 439 507 104.5 81 15.5 79 412.5 417.5
S 2000 - L 1600 439 573 89.5 91.5 15.5 79 412.5 417.5
S 2500 - L 2000 507 653 103.5 101.5 15.5 79 (3) 417.5
S3200 - S 4000 661 859 (1) (2) 52.5 154.5 (3) 474.5

(1) fixed: 128.5 - withdrawable: 130.5 mm


(2) fixed: 126.5 - withdrawable: 129.5 mm
(3) S 800 to S 1600 - S 2500: 417.5 mm
L 640 - L 1000 - L 2000: 412.5 mm
S 3200: 466.5 mm
S 4000: 471.5 mm
(4) S 3200 - S 4000
(5) L 640 to L 2000
(6) for S 800 to S 2500
- step of 660 possible for fixed circuit breaker
- step of 600 and 660 possible for withdrawable circuit breaker
(7) S 3200 - S 4000: - 3P: 326 mm
- 4P: 524 mm
left hand alignment of breaker monitoring axes
SPECTRONIC S/L - Overall dimensions

Source changeover switches


Fixed or withdrawable, three circuit breakers without frame

C
83

Circuit breaker A B C D
3P 4P 3P 4P fixed W/D fixed W/D White area: interlocking brackets dimensions
S 800 to 1600 351 439 77.5 72.5 15.5 79 (3) 347.5
L 640 - L 1000
L 1250 439 507 104.5 81 15.5 79 342.5 347.5
S 2000 - L 1600 439 573 89.5 91.5 15.5 79 342.5 347.5
S 2500 - L 2000 507 653 103.5 101.5 15.5 79 (3) 347.5
S3200 - S 4000 661 859 (1) (2) 52.5 154.5 (3) 404.5

(1) fixed: 128.5 - withdrawable: 130.5 mm


(2) fixed: 126.5 - withdrawable: 129.5 mm
(3) S 800 to S 1600 - S 2500: 417.5 mm
L 640 - L 1000 - L 2000: 412.5 mm
S 3200: 466.5 mm
S 4000: 471.5 mm
(4) S 3200 - S 4000
(5) L 640 to L 2000
(6) for S 800 to S 2500
- step of 660 possible for fixed circuit breaker
- step of 600 and 660 possible for withdrawable circuit breaker
(7) S 3200 - S 4000: - 3P: 326 mm
- 4P: 524 mm
left hand alignment of breaker monitoring axes
SPECTRONIC S/L - Overall dimensions

Source changeover switches


Fixed or withdrawable, two circuit breakers with frame

C
84

Circuit breaker A B C D E
fixed W/D fixed W/D fixed W/D
3P 4P 3P 4P 3P 4P 3P 4P
S 800 to 1600 696 696 666 666 111.8 127.3 141 136 141.5 136.5 (3) 417.5
L 640 - L 1000
L 1250 696 696 666 666 111.8 127.3 168 144.5 168.5 145 412.5 417.5
S 2000 - L 1600 696 842 666 812 111.8 127.3 153 155 153.5 155.5 412.5 417.5
S 2500 - L 2000 696 842 668 812 111.8 127.3 167 165 167.5 165.5 (3) 417.5
S 3200 - S 4000 1048 1048 1018 1018 312.3(1) 327.3(2) 191 189 193 192 (3) 474

(1) S 3200 - S 4000, 4P: 636.5 mm


(2) S 3200 - S 4000, 4P: 652.5 mm
(3) S 800 to S 1600 - S 2500: 417.5 mm
L 640 - L 1000 - L 2000: 412.5 mm
S 3200: 466.5 mm
S 4000: 471.5 mm
(4) S 3200 - S 4000
(5) L 640 to L 2000
SPECTRONIC S/L - Overall dimensions

Source changeover switches


Fixed or withdrawable, three circuit breakers with frame

C
85

Circuit breaker A B C D E
fixed W/D fixed W/D fixed W/D
3P 4P 3P 4P 3P 4P 3P 4P
S 800 to 1600 696 696 666 666 111.8 127.3 141 136 141.5 136.5 (3) 417.5
L 640 - L 1000
L 1250 696 696 666 666 111.8 127.3 168 144.5 168.5 145 412.5 417.5
S 2000 - L 1600 696 842 666 812 111.8 127.3 153 155 153.5 155.5 412.5 417.5
S 2500 - L 2000 696 842 668 812 111.8 127.3 167 165 167.5 165.5 (3) 417.5
S 3200 - S 4000 1048 1048 1018 1018 312.3(1) 327.3(2) 191 189 193 192 (3) 474

(1) S 3200 - S 4000, 4P: 636.5 mm


(2) S 3200 - S 4000, 4P: 652.5 mm
(3) S 800 to S 1600 - S 2500: 417.5 mm
L 640 - L 1000 - L 2000: 412.5 mm
S 3200: 466.5 mm
S 4000: 471.5 mm
(4) S 3200 - S 4000
(5) L 640 to L 2000
SPECTRONIC S/L - RMS 7 diagram

RMS 7: protection and monitoring unit


Diagram showing de-energised circuits, open circuit breaker, connected, reset, handles not inserted.

Ph.1 +

Secondary
Fault
disconnector 50 49
C N

C
86
Fault RMS7
signalling

EX

Ph.2 -
Fault signalling
Option Protection unit by relay Faults contacts

Legend
Overcurrent releases Operation with energy storage
CD Overload and short-circuit fault contact M Motor
K1 Fault signalling relay FCA Resetting limit switch
R1 Booster voltage for 220V Manual setting
S1 Fault cancelling push-button CA 1-8 Auxiliary contacts
GF Ground fault indicator lamp EE Closing coil
ST-I Instantaneous or short duration (short-circuit) S2 Remote tripping control
tripping indicator lamp S5 Remote closing control
LT Long time trip (overload) tripping indicator lamp S3 Remote closing and tripping control changeover switch
Voltmetric releases C22 Reset contact of the spring
C41 Trip contact MV-MVR C20 Contact coupled with local reset tripping push-button
C43 Undervoltage contact MV-MVR FE Closing prevented on undervoltage
C31 Trip contact EA Withdrawable
Ra-R6 Booster resistor for certain direct current voltages C51.52 Contacts 'connected' position
S1 Optional disconnecting switch MV-MVR (break out of service) C61.62 Contacts 'withdrawn' position
C71 Pre-trip contact coupled with insertion control
SPECTRONIC S/L - RMS 7 diagram

44
222 42
224

C
87

C22

221 41
43

Electrical control Voltmetric release Auxiliary switches Positioning contacts

End user connections


FIXED circuit breaker
(22)
(21)
(20)
(19)
(18)
(17)
(16)
(15)
(14)
(13)
(12)
(11)
(10)
(9)
(8)
(7)
(6)
(5)
(4)
(3)
(2)
(1)

Letters in alphabetical order Increasing numbers

Withdrawable circuit breaker


Connection by terminals 6.3 x 0.8
For electrical operation of EA1, EA, CD1, CD2, MVR, MV, RMS, use the allocated numbers.
Other accessories: numbers are increasing clockwise (use reserved terminals if they are available).
0D1
0D2

0C1
0C2

LEFT RIGHT
442
444
441
421

424
422

321

324
322
432
434
431
411

414
412

311

314
312
D1
D2

C1
C2

MV - MVR EA 50
CN
49
MV or MVR

14 11 12 CD2
E2
E1
CD1 U2 Electrical
U1
EA1 or EA A2 control
A1
or MV .MVR
SPECTRONIC S/L - RMS 9 diagram

RMS 9: protection and monitoring unit


Diagram showing circuit de-energised, open circuit breaker, connected, reset, crank not inserted.

Ph. 1 +

N
Ph1
S1
R

Transmission
Voltage
Ph2 Fault S1
Ph3
conditioner S
T
50 49 32 29
Secondary
T S R S1 15 14
disconnectors

C 5 6
88
RMS9
T S R S1

MONITOR
17 33 16 28

4
EX

Secondary
disconnectors
Ph. 2
RMS 9 Fault signalling
protection unit by relay

Legend
Ammetric releases Stored energy control
CD Short-circuit and overload fault signalling contact M Motor
K1 Short-circuit signalling relay FCA Reset limit switch
S1 Fault reset push button Manual reset
GF Ground fault display AS 1-8 Auxiliary switches
ST-I Instantaneous (short circuit) tripping display Ra Economy resistor for selected voltages in direct current
LT Long time (overload) tripping display EE Closing coil
Voltmetric releases S2 Remote trip push-button
C41 Trip contact UVR-UVRD S5 Remote closing push-button
C43 Minimum voltage contact UVR-UVRD S3 Remote closing and tripping changeover switch
C31 Trip contact EA C22 Spring reset contact
R5-R6 Economy resistor for selected direct current voltages C20 Contact coupled with local resetting push-button
S4 Optional switch to disable UVR-UVRD FEa Closing prevention device
(circuit breaker disconnected)
Withdrawable
C51.52 “Connected” position contact
C61.62 “Withdrawn” position contact
C71 Pre-tripping contact associated with plug-in control device
SPECTRONIC S/L - RMS 9 diagram

M UVR

C
89

BA2
BA1

Faults Electrical Voltmetric Positioning


contacts control release Auxiliary switches contacts

End user connections


LEFT RIGHT
Withdrawable circuit breaker plate plate
For electrical operation of EA1 or EA, BA1, BA2, UVRD, UVR, RV, use the
allocated numbers. Other accessories: numbers are increasing clockwise
(use reserved terminals if they are available. R
CN 49 S
CN 50 T

RMS9

29+ 15-
32- 14+
UVR or UVRD RMS9

BA2
E2
E1
BA1 U2 Electrical
U1 control
ST1 or ST A2
A1
or UVR . UVRD

reserved terminal(s)
direction of wiring
SPECTRONIC S/L - Connections/weights

Connection possibilities S 800 to 4000 / L 640 to 2000


Fixed versions S L
Rear horizontal connections X X
Rear vertical connections O
Front connections X
Withdrawable versions S L
Rear horizontal connections X X
Rear vertical connections X X
Front connections X X
X = standard
O = on request

Weight of circuit breakers S Fixed circuit breaker Withdrawable circuit breaker


(in kg) manual control electrical control manual control electrical control

C S 800-1000 3P
4P
51
55
56
60
90
98
95
103
90 S 1250 3P 53 58 97 102
4P 59 64 108 113
S 1600 3P 58 63 104 109
4P 67 72 117 122
S 2000 3P 65 70 119 124
4P 74 79 124 129
S 2500 3P 67 72 125 130
4P 82 87 132 137
S 3200 3P 112 116 185 189
4P 142 146 232 236
S 4000 3P 118 122 191 195
4P 150 154 240 244
S 5000 3P 200(1) 210(1) 376 380
(1)
4P 240 250(1) 458 462
(1)
S 6400 3P 230 240(1) 411 415
(1)
4P 290 300(1) 506 510
(1) For vertical circuit breakers.
For horizontal circuit breakers, deduct 10 kg.

Weight of circuit breakers L Fixed circuit breaker Withdrawable circuit breaker


manual control electrical control manual control electrical control
(in kg) L 640-1000 3P 55 60 85 90
4P 63 68 95 100
L 1250 3P 65 70 101 106
4P 75 80 115 120
L 1600 3P 73 78 111 116
4P 85 90 128 133
L 2000 3P 78 83 124 128
4P 93 98 145 150

Weight of source changeover


switches S/L
Deduct 2 kg from the weight of the circuit
breaker.