DOL STARTER
1 Tighten all the MCB connections & measure input and output voltages.
415 V
SPINDLE MOTOR
1
Check motor insulation resistance. Megger >500MΏ
3 Tighten stater & motor earthing connection and record the neutral to earth Vg
Less than 1 Volt AC
REMARKS
PAGE NO:1
RESULT
OLR set
Ώ
Vg
R Y B
VAC
d by
QUARTERLY
PREVENTIVE MAINTENANCE CHECKLIST REV NO:1
DOL STARTER
Tighten all the MCB connections & measure input and output
1 voltages. 415 V
MOTOR
REMARKS
SPECIFICATION RESULT
415 V V
OLR=6-10 Amps
Cont coil=0.87 Ώ OLR set
Ώ
MΏ
ger >500 MΏ Ώ
motor=6.5Ώ
motor Vg=415 V Vg
tor Amps=5.2 Amps R Y B
< 1 VAC VAC
Approved by
QUARTERLY
PREVENTIVE MAINTENANCE CHECKLIST REV NO:1 PA
MOTOR
1 Tighten all Motor terminals .Record its value.
Remove motor fan cover,Clean fan and cover needly
Megger >500 MΏ
Motor=0.7Ώ
Motor Vg=415 V
Motor Amps=14.2 Amps
Main C1 coil= 0.38Ώ
Delta C2 coil=0.38Ώ
Star C3 coil=0.51Ώ
REMARKS
SPECIFICATION RESULT
415 V V
Megger >500 MΏ
Motor=0.7Ώ
Motor Vg=415 V
Motor Amps=14.2 Amps
Main C1 coil= 0.38Ώ
Delta C2 coil=0.38Ώ
Star C3 coil=0.51Ώ
Approved by
QUARTERLY
PREVENTIVE MAINTENANCE CHECKLIST
REV NO:1 PAG
REMARKS
QUARTERLY
PREVENTIVE MAINTENANCE CHECKLIST REV NO:1 PAG
HMC ELECTRICAL DATE:
MAINTANENCE
MACHINE NO:HS 001 STABILIZER
S.NO DESCRIPTION SPECIFICATION
1 Tighten MCB IN/OUT terminals and record the voltage 415 VAC
2 Checking and cleaning auto transformers
3 Tighten indicating lamps and push botton connections
4 Checking output voltage 3 phases voltages 220 VAC
5 Checking output voltage 1 phases voltages 110 VAC
6 Checking neutral to earth voltages <1V
REMARKS
1 PAGE NO:1
SPECIFICATION RESULT
415 VAC VAC
<1V
Approved by
QUARTERLY
1 PAGE NO:1
SPECIFICATION RESULT
415 VAC VAC
220 VAC
110 VAC
<1V
Approved by
PREVENTIVE MAINTENANCE CHECKLIST
FOUNDRY ELECTRICAL
MAINTANENCE
MACHINE NO -VCCM03 CENTRIFUGAL MACHINE
S.NO DESCRIPTION
DOL STARTER
1 Tighten all the MCB connections & measure input and output voltages.
SPINDLE MOTOR
1
Check
Tightenmotor insulation resistance.
2 all Motor terminals .Record its value.
Remove motor fan cover,Clean fan and cover needly
3 Tighten stater & motor earthing connection and record the neutral to earth Vg
REMARKS
Prepared by Checked by
DOL STARTER
1 Tighten all the MCB connections & measure input and output voltages.
2 Tighten all in/out connection of contactor,OLR.
Check contactor tips condition by press &
seeing the continuity @in/out terminals.
SPINDLE MOTOR
1
Check motor insulation resistance.
2 Tighten all Motor terminals .Record its value.
Remove motor fan cover,Clean fan and cover needly
3 Tighten stater & motor earthing connection and record the neutral to earth Vg
REMARKS
Prepared by Checked by
MONTHLY
NTRIFUGAL MACHINE
SPECIFICATION RESULT
415 V V
Megger >500MΏ
motor=6.2Ώ Ώ
motor Vg=415 V Vg
motor Amps=3.2 Amps R Y B
Approved by
MONTHLY
REV NO:1 PAGE NO:1
DATE:
NTRIFUGAL MACHINE
SPECIFICATION RESULT
415 V V
OLR=2.5 TO 4 Amps OLR set
cont coil=0.87 Ώ Ώ
Megger >500MΏ
motor=6.2Ώ Ώ
motor Vg=415 V Vg
motor Amps=3.2 Amps R Y B
Approved by
DOC NO: VSPL_LAB
PREVENTIVE MAINTENANCE CHECKLIST-QUATERLY REV NO:1
MECHANICAL LAB ELECTRICAL DATE:
MAINTANENCE
MACHINE NO:DWB 001 UT MACHINE
S.NO DESCRIPTION
1 Tighten all the MCB connections & measure input and output
voltages.
CONTROL PANEL
Tighten all the wire connections @ TB'S at the bottom & Check all fuse terminals.
1
Check transformer IN/OUT Voltage
2
AXIS MOTOR
MOTOR
HYDRAULIC MOTOR
MOTOR
Tighten stater & motor earthing connection and record the neutral to earth Vg
2
REMARKS
DATE:
SPECIFICATION RESULT
415V V
MΏ
Megger >500 MΏ Ώ
motor=0.04Ώ
motor Vg=415 V Vg
motor Amps=0.06 R Y B
MΏ
Megger >500 MΏ Ώ
motor=9.7 Ώ
motor Vg=415 V Vg
motor Amps=1.8 R Y B
Approved by
DOC NO: VSPL_
PREVENTIVE MAINTENANCE CHECKLIST-QUATERLY REV NO:1
MECHANICAL LAB ELECTRICAL DATE:
MAINTANENCE
MACHINE NO: HARDNESS TESTER
S.NO DESCRIPTION
Tighten all the MCB connections & measure input and output
1 voltages.
CONTROL PANEL
1 Tighten all the wire connections @ TB'S at the bottom & Check all fuse terminals.
2 Check transformer IN/OUT Voltage
AXIS MOTOR
Tighten all in/out connection of contactor,OLR and
1 Check contactor tips condition by press & seeing the continuity @in/out terminals.
MOTOR
2 Tighten stater & motor earthing connection and record the neutral to earth Vg
REMARKS
Prepared by Checked by Ap
DOC NO: VSPL_LAB_PM_UTM_E01-00
REV NO:1 PAGE NO:1
DATE:
SPECIFICATION RESULT
415V V
Megger >500 MΏ MΏ
motor=57.7 Ώ Ώ
motor Vg=415 V Vg
motor Amps=0.95 R Y B
Approved by