Descriptive Bulletin
Relay Division 41-122M
Coral Springs, FL
Allentown, PA
Frequency Standards
• ANSI C37.90
50 or 60 Hertz selectable
• IEC 255 series
Indications Temperature Range
• Time delay trip (light emitting diode) flashes when input • Operate: –20° to +55°C
current is above pickup setting
• Storage: –40° to +70°C
• Time overcurrent trip
• Instantaneous trip Style Number Selections
• Monitor provided for power-on and self-check indication Time Unit DC Control Style
Range Voltage Number
Timing Characteristics 0.5 – 12A 48/125 1354D01A01
• Provides seven separate time overcurrent curves as out- 0.1 – 2.4A 48/125 1354D01A02
lined in I.L. 41-120 0.5 – 12A 250 1354D01A03
• Reset time–2 cycles 0.1 – 2.4A 250 1354D01A04
• Optional delayed instantaneous feature For Delayed Instantaneous option, add suffix “–FUS” to style
(“–FUS” catalog suffix) number.
Fixed Delays: 0, 0.05, 0.10 sec.
Additional Information: Instruction Book IL 41-120, Trans-
Adjustable Delay: 0.2-0.83 sec. parent Time-current Curves.
TD
RR
Figure 1: MCO Internal Connections
TD/
AL TD IT IT
RED HANDLE
TEST SWITCH
CURRENT
X
TEST JACK
TERMINAL
1 3 5 7 9
2 V+ 4 6 8 10 ABB Power T&D Company Inc.
Relay Division
COM
I in 7036 Snowdrift Road
Allentown, PA 18106