STRUCTURAL CALCULATION FOR BALCONY 
 

 
HANDRAIL 
 

   

 
 
 
 
 
 
 
STRUCTURAL CALCULATION FOR BALCONY HANDRAIL Rev : 1

 
1. CODES  AND  SPECIFICATIONS 
  The Structural calculations are Performed in accordance with the following  
  codes / specifications. 
IS 875‐1987 PART 3   : Code of Practice for Design Loads in Buildings and Structures 
          (Wind Load). 
 IS 8147‐1976     : for Design of Aluminum structures. 
IS 800 – 2007 : Indian code for Structural steel design

2. MATERIAL SPECIFICATIONS

Steel

Bending Stress  
2500 kg/cm2
Elastic Modulus 
2.1E+06 kg/cm2
Poissons ratio 
0. 3
 
 
DESIGN OF STEEL SUB STRUCTURE

 
A. LOADING

WIND LOAD                       

The Designed wind pressure over the steel sub frame shall be 1.4 kpa. 
   
 
  Designed Wind Pressure  =1.4 kpa         
  Glass panel Size = 0.835 x 1.617
= 1.35 Sq. Meter
Wind load on panel = 1.35 x 140
= 189 kg
Point load per glass support = 189 / 4 = 47.25 Kg 

 
 
 
STRUCTURAL CALCULATION FOR BALCONY HANDRAIL Rev : 1

With this loading conditions The  MS Framework  is Analysed using STAAD and Results are computed as follows. 

Maximum Bending stress in the steel framework as per STAAD 

Analysis = 261.6 kg/sqcm < 1650 kg/sqcm


Maximum Combined Bending stress in the MS framework as per STAAD 
Analysis = 261.6 kg/sqcm < 1650 kg/sqcm  
Maximum Deflection as per STAAD Analysis along 3.354 m span = 4.395 mm.  
Maximum Deflection as per STAAD Analysis along 1.005 m span = 4.395 mm. 

 
 
 
STRUCTURAL CALCULATION FOR BALCONY HANDRAIL Rev : 1

 
Permissible Deflection = Span /175 = 3354 / 175 = 19.165 mm. 
Permissible Deflection = Span /175 = 1005 / 175 = 5.74 mm. 
 

The steel framework  is made up of  Main Vertical frame of  steel Box section of SHS 40 x 40 x 2.6mm and  Tie 
members of RHS 60 x 40 x 2.9mm thk. is safe in Bending stress, Deflection criteria.  
   
 
   
 
 
 
 

 
 
 