Sunteți pe pagina 1din 6

Central Power Research Institute, Bangalore

DISTANCE RELAY PERFORMANCE EVALUATION ON SERIES


COMPENSATED TRANSMISSION LINE PROTECTED WITH METAL OXIDE
VARISTOR UNDER FAULTED CONDITIONS

Saptarshi Roy1 Dr. P Suresh Babu2 N V Phanendra Babu3 M Lohith4 K V Ramana Reddy5
1,3
Research Scholars, Department of Electrical Engineering, National Institute of Technology, Warangal
2
Assistant Professor ,Department of Electrical Engineering, National Institute of Technology, Warangal
4,5
PG students, Department of Electrical Engineering, National Institute of Technology, Warangal

Abstract-A compensated line imposes problems to directional relaying schemes due to Voltage and
current inversion situations and operation of metal oxide varistor (MOV) protecting series capacitor,
reactance modulation issues .In this paper the behaviour of series compensated EHV transmission
lines during faults is simulated. The use of series capacitors for compensating part of the inductive
reactance of long transmission lines increases the power transmission capacity. Emphasis is given on
the impact of modern capacitor protection techniques (MOV protection). The simulation study is
performed on series capacitor compensated transmission lines (SCCTLs) with their different
configurations and contingency combinations and the performance of the series compensated line is
observed with sending end and receiving end voltage profile .The fault impedance characteristics are
also studied. Simulation of the studied systems is implemented by PSCAD/SIMULINK/EMTDC software.

Keywords: Distance Protection, Distance relay Performance, Variation of R&X, Transmission Line,
Series Compensation, Series Capacitor Protection Unit.

I.INTRODUCTION LLL, LL, LLLG faults. The presence of the


Use of series capacitors for compensating inductive capacitor in the circuit immediately after a fault is
reactance of long transmission lines increases the very important, because it helps the transient
power transmission capacity [3-8]. It also increases stability of the system. Also in case of unbalanced
transient stability margins, optimizes load-sharing faults, only the protection devices of the faulted
between parallel transmission lines and reduces phases operate leaving the capacitor of the other
system losses [5-6-7]. Transmission line phases on line. To determine the various design
compensation implies a modification in the parameters for planning and implementing, MOV
electrical characteristic of the transmission line protected capacitors in a network; it is
with the objective of increase power transfer indispensable to be able to model such devices in a
capability [4]. In the case of series compensation, fault analysis program and predict the level of short
the objective is to cancel part of the reactance of circuit currents as well as the energy absorbed by
the line by means of series capacitors [9]. This the conducting MOV.
result is an enhanced system stability, which is
evidenced with an increased power transfer In this paper the behaviour of series compensated
capability of the line, a reduction in the EHV transmission lines during faults is simulated.
transmission angle at a given level of power The use of series capacitors for compensating part
transfer and an increased virtual natural load [10- of the inductive reactance of long transmission
11-12]. lines increases the power transmission capacity.
Fast and accurate determination of a fault in Emphasis is given on the impact of modern
electrical power system is a vital part in power capacitor protection techniques (MOV protection).
restoration [13]. In Power system majority of the The simulation study is performed on series
faults are happened to be single line to ground fault capacitor compensated transmission lines
[14]. Other important types of faults are LLG, (SCCTLs) with their different configurations and

National Conference On Power System Protection 27-28 Feb 2015 15


Central Power Research Institute, Bangalore

contingency combinations and the performance of


the series compensated line is observed with
sending end and receiving end voltage profile.
Series capacitor compensated transmission lines
(SCCTLs) simulated with
SIMULINK/PSCAD/EMTDC software. Other than
these software Matlab coding is used to do V. TEST SYSTEM :
complex and long calculations, plotting etc.

II.ADVANTAGES OF SERIES
COMPENSATION:

1) Reduces line voltage drop.


2) Limits load-dependant voltage drops.
3) Influences load flow in parallel
transmission lines.
4) Increases power transfer capability
5) Highly effective in maintaining the desired
voltage profile along the transmission line
interconnecting two busses of the ac system
and providing support to the end voltage of
radial lines in the face of increasing power
demand.
Fig1:series capacitor compensated transmission lines
III. SERIES CAPACITOR EFFECT ON (SCCTLs) with Protection Unit with capacitor at
DISTANCE MEASUREMENT: various positions

Distance relays are designed to perform correctly The above test system is simulated using
on a resistive/inductive system. When SCs are PSCAD/EMTDC/SIMULINK software and test
introduced, the normal voltage/current different cases with varying fault location, varying
relationships are affected, especially when the fault capacitor position, varying compensation, varying
levels are not sufficient to flash-over the gaps or to fault resistance, varying fault duration etc and
produce significant conduction in the MOV's. calculated and plotted faulted wave forms and
R&X curves. Sampling frequency maintained here
IV.IMPLEMENTATION 4KHZ and system frequency maintained here 50
HZ.
Fault location is computed using faulted voltage
and current samples that described as below:
Fault impedance Zf= (Vf/If) Ohm .......................(1)
Fault Location= (Zf/ Z 1) ...................................(2)

More the length increases the algorithm for fault


location identification gives more accurate value.
In case of fault impedance, during healthy state
positive sequence impedance (Z1 Ohm/Km)
present in the system and the value is given in the
paper. Vf and If are obtained from the sampling of
the waveforms after creation of different faults at
different lengths.
National Conference On Power System Protection 27-28 Feb 2015 16
Central Power Research Institute, Bangalore

Fig2:Performance of the test system during a Ph-B-G


fault at 40% line length

Fig4: Performance of the test system during a LLL fault


at 40% line length

Fig5: Performance of the test system during a LLLG


Fig3: Performance of the test system during a Ph-AB-G fault at 40% line length
fault at 40% line length

National Conference On Power System Protection 27-28 Feb 2015 17


Central Power Research Institute, Bangalore

Fig10: Variations of R &X during a b-g fault

Fig6: Performance of the test system during a LL fault


at 40% line length

Fig11: Variations of R&X During a bc-g fault

Fig7: Performance of the test system during a AG fault


at 40% line length

Fig12: Varriation of R&X during a LLLG fault

Fig8: Sending End Side Voltage Profile

Fig13: Variations of R&X in a LL fault

Fig9: Load side Voltage Profile

National Conference On Power System Protection 27-28 Feb 2015 18


Central Power Research Institute, Bangalore

Positive and zero sequence impedances for


receiving end
source are ZR1 = (1.2 + j18) Ω, ZR0 = (2.6 + j26.5)
Ω,
respectively. Load angle is 30 ◦ with receiving end
source voltage lagging.
Rated current of 2000A, equivalent of
(1750MVA), is considered for sizing SCPU. MOV
rating after considering an overload factor of 1.5 is
calculated as 273kV (= 1.5 ×2000A×91.1Ω)
Fig14: Variations of R&X during a LLL fault
REFERENCES

[1] J. D. Glover and M. S. Sarma, Power Systems:


VI.CONCLUSION:
Analysis and Design. Pacific Grove, CA:
Brooks/Cole - Thomson Learning, 2010.
The main results regarding MOV protected series [2] P. Kundur, Power System Stability and Control.
compensation, obtained by the fault simulation can New York: Mc-GrawHill, 1994.
be summarized as follows: [3] D. McNabb, M. Granger, Q. B. Van, M.
The variation of R&X is less during ground faults, Rousseau, and M. Pilot,"Transient Design Studies
compared to the phase faults. From the figures it is for the Transmantaro Series-Compensated
evident during a bg fault, the maximum value of Transmission System," Proceedings of the
R&X is confined in the order of 140 unit, while in International Conference on Power System
the case of a bcg fault, the variation is of the order Transients (IPST'01), pp. 1-6, June 2001.
of 90 units and during a LLLG fault the variation is [4] Puerto Rican Electric Power Authority
of maximum 140 unit. Standard of Construction of Overhead
But in case of phase faults, it is more than two Transmission Lines May 1992.
times. In case of LL fault, it comes beyond 1000 [5] O. Trad, G. Ratta, and M. Torres, "Experiences
unit and LLL fault it is coming beyond 300 units in in Setting Protection of Series Capacitor
negative half. Compensated Lines," Proceedings of the
International Conference on Power System
APPENDIX A Transients (IPST'01), pp. 1-6, June 2001.
[6] Q. Bui-Van, E. Portales, D. McNabb, and V.
Series Capacitor Compensated Transmission Line Gajardo, "Transient Performance of 500-kV
system data Equipment for the Chilean Series-Compensated
Length=350Km Transmission System," Proceedings of the
Voltage=500KV international Conference on Power System
Positive-sequence impedance=0.0155+j0.3719 Transients (IPST'03), pp. 1-6, October 2003.
Ohm/Km [7] IEEE 14-bus test system data available
Zero-Sequence Impedance=0.3546+j1.0670 at:http://www.ee.washington.edu/research/pstca/
Ohm/Km [8] S. Henschel, L. Kischner, and M. C. Lima,
Positive-sequence admittance= 0+j4.4099x1exp(- "Transient Recovery Voltage at Series
6) mho/Km Compensated Transmission Lines in Piauí, Brazil,"
Zero-sequence admittance= (0+j2.7844 × 10−6) Proceedings of the International Conference on
mho per km Power System Transients (IPST'05), pp. 1-6, June
Positive and zero sequence impedances for sending 2005.
end source [9] R. Zimmerman, D. Gan, Matpower 3.0, PSERC
are ZS1 = (1+j15) Ω, ZS0 = (2.4 + j25) Ω Cornell University,USA, December 1997.
respectively. Available
at:http://www.pserc.cornell.edu/matpower/
National Conference On Power System Protection 27-28 Feb 2015 19
Central Power Research Institute, Bangalore

[10] ABB Metal Oxide Surge Arresters – EXLIM


P, ABB Electrical Apparatus, May 2005.
[11] T. J. Miller, Reactive Power Control in
Electric Systems. New York: Wiley-Interscience,
1982.
[12] Q. Y. Xuan, A. T. Johns, ”Digital Simulation
of Series compensated EHV (Extra High Voltage)
Transmission Systems” , IEE Colloquium on
Simulation of Power System , 1992.
[13]Choowong-Wattanasakpubal and Teratum-
Bunyagal,”Algorithm for Detecting, Identifying,
Locating and Experience to Develop the Automate
Faults Location in Radial Distribution System”.
Journal of Electrical Engineering andTechnolog,
Vol.5, No.1, pp.36-44, 2010.
[14] A. Elmitwally, S.Mahmoud, M.H. Abdel
Rahman “Fault Identification of Overhead
Transmission Lines Terminated With
Underground Cables,” Proceeding of 14th
International Middle East Power Systems
Conference, Dec 19-21,2010,pp.452-458.
[15] Saptarshi Roy,Dr.P.Suresh Babu ,”Power
Swing Protection of series compensated
Transmission Line with Novel Fault Detection
Technique”,IEEE International Conference
ICGCCEE,2014.
[16]. N.V.PhanendraBabu, Dr.P.SureshBabu,
Saptarshi Roy, M.Lohith, K.V.Ramanna Reddy,A
Novel Approach For Faulty Phase Detection of
Series Compensated Transmission Line”,Ird
India,Vol-3,Issue-4,2014.pp-34-38.

National Conference On Power System Protection 27-28 Feb 2015 20

S-ar putea să vă placă și