GENERAL NOTES:
59 59
1. DIMENSIONS ARE IN MILLIMETERS.

A 2. FOR TRENCH CONSTRUCTION, SEE DRG. 5652-STD-EU-D-022 DETAILS U-005/6/7/8.


A
25886-3000-E90-0000-E1010

3. CHANGES IN DIRECTION OF CABLE TRENCHES SHALL ALLOW FOR THE MINIMUM CABLE BENDING
RADIUS AS FOLLOWS. BENDING RADIUS TO BE CONFIRMED AT EPC STAGE WHEN VENDOR INFORMATION
57 57
IS AVAILABLE:

NON-LOAD LEAD-SHEATHED HV CABLES MORE THAN 12kV:


CARRYING CABLES SINGLE CORE - 21 TIMES CABLE OD
NOT ASSOCIATED WITH NON-LOAD MULTICORE - 18 TIMES CABLE OD
5652-STD-EU-D-021

55 POWER FEEDERS CARRYING CABLES 55


LEAD-SHEATHED HV/LV CABLES 12kV OR LESS:
FINISHED SURFACE NOT ASSOCIATED WITH
LOAD CARRYING CABLES (WHEN REQUIRED) SINGLE CORE - 15 TIMES CABLE OD
POWER FEEDERS
FINISHED SURFACE MULTICORE - 14 TIMES CABLE OD
B LOAD CARRYING CABLES (WHEN REQUIRED) B
NON-LEAD-SHEATHED HV CABLES:
SINGLE CORE - 20 TIMES CABLE OD
53 53
MULTICORE - 12 TIMES CABLE OD
COMPACTED NON-LEAD-SHEATHED LV CABLES:
EARTH BACKFILL ALL - 8 TIMES CABLE OD
CABLE TILES WARNING TAPE (GENERAL NOTE 6) COMPACTED
4. ALL UNDERGROUND CABLE (EXCEPT EARTHING) SHALL BE MARKED AT INTERVALS NO GREATER THAN
750

50 (AS REQUIRED (SEE NOTE 16) EARTH BACKFILL


51
5 METERS AND AT EACH TERMINATION POINT. 51
CABLE TILES WARNING TAPE (GENERAL NOTE 6)

750
FOR UNPAVED AREAS)
50 (AS REQUIRED) (SEE NOTE 16) 5. IF TWO LAYER ARRANGEMENT OF LOAD-CARRYING CABLES IS USED, ADDITIONAL CABLE CURRENT DERATING
MAY BE REQUIRED.
C C
6. COMPACTED SAND AND EARTH SHALL BE IN ACCORDANCE WITH SPEC 5652-TPS-CU-04, "EXCAVATION AND
BECHTEL
DRG.No.

DRG.No.

75
TAKREER

EARTH CABLE
BACKFILL FOR UNDERGROUND INSTALLATIONS".
CLEAN SIEVED SAND 49
49
7. POWER CABLES UP TO 4mm2 AND ASSOCIATED CONTROL CABLES LAID IN TOUCHING FORMATION.

75
FREE FROM STONES EARTH CABLE
150 (GENERAL NOTE 6) CLEAN SIEVED SAND 8. WHERE HIGH VOLTAGE POWER DISTRIBUTION CABLES (NOT MOTOR FEEDER CABLES) AND LOW VOLTAGE
75 FREE FROM STONES CABLES ARE LAID IN THE SAME TRENCH, THE TWO CABLE TYPES SHALL BE SEPARATED BY A CONTINUOUS
(TYP)
150 (GENERAL NOTE 6) ROW OF VERTICALLY ARRANGED CABLE TILES, AS SHOWN IN DETAILS U-002A AND U-002B.
75
47 (TYP) 9. OPEN PIPE TRENCHES SHALL BE CROSSED BY MEANS OF BRIDGES OR TROUGHS OVER THE PIPE TRENCH. 47
DUMMY TRENCH GENERAL THESE BRIDGES OR TROUGHS SHALL BE BACKFILLED WITH A 20 TO 1 SAND/CEMENT MIX. WHERE CABLE
DETAIL U-001A
SEE GENERAL NOTE 7 TRENCHES CROSS ROADS, AN ADDITIONAL 3 TO 5 - 100mm PVC CONDUITS, WITH BELL MOUTH ENDS,AT
D NOTE 13 SINGLE LAYER OF LOW VOLTAGE LOAD DUMMY TRENCH GENERAL NORMAL CABLE LAYING DEPTH SHALL BE PROVIDED FOR FUTURE CABLES. THESE SPARE CONDUITS SHALL D
DETAIL U-001B
CARRYING CABLES WITH SEE GENERAL NOTE 7 BE CAPPED AT BOTH ENDS (SEE DETAIL #U-007, DWG #5652-STD-EU-D-022.
NOTE 13 TRENCHES LOCATED WITHIN TANK BERMS
45 ASSOCIATED CONTROL CABLES 10. WHERE UNDERGROUND ELECTRICAL CABLES AND PIPELINES CROSS OR RUN PARALLEL, THEY SHALL BE 45
SINGLE LAYER OF LOW VOLTAGE LOAD
SEPARATED BY A MINIMUM DISTANCE OF 300mm, INCLUDING INSULATION. CABLES SHOULD GENERALLY
NS THE PROPERTY OF TAKREER.

CARRYING CABLES WITH


CROSS BELOW BURIED PIPELINES. CABLES MAY CROSS ABOVE BURIED PIPELINES IF CONSTRUCTION
ASSOCIATED CONTROL CABLES
SCHEDULING DICTATES. (IF CLOSE CROSSING WITH HOT PIPES CANNOT BE AVOIDED, THE PIPELINE SHALL
BE INSULATED IN ORDER TO LIMIT IT’S OUTSIDE TEMPERATURE TO A MAXIMUM OF 60 DEG C AND
43 SEPARATION DISTANCE WILL INCREASE TO 600mm. IF PIPES ARE BURIED DEEP IN THE GROUND, THEN CABLES 43
ONAL BECHTEL CO.LTD.

MAY BE RUN ABOVE THE PIPES IN CONCRETE CASING SO AS TO MAINTAIN A MINIMUM CLEARANCE OF 300mm
BETWEEN TOP OF PIPE TO BOTTOM OF CONCRETE CASING AND 600mm CLEARANCE BETWEEN THE TOP OF
E E
CONCRETE CASING TO FINISHED GRADE).
11. INDIVIDUAL CABLES EMERGING FROM FLOORS OR SOIL SHALL BE PROTECTED BY MEANS OF A PIPE &
S DOCUM ENT W AS DEVELOPED FOR TAKREER FOR THE PROJECT AND REM AI

41 41
CONCRETE CURB TO AN ADEQUATE HEIGHT ABOVE THE GROUND.
ZED

12. THE ABOVE MENTIONED PROTECTION PIPES AND DUCTS SHALL BE SEALED AROUND THE CABLES TO PREVENT
LI
NTERNATI
NTELLECTUAL PROPERTY UTI

THE INGRESSS OF OIL, CHEMICALS, ETC. INTO THE CABLE TRENCH, OR THE PROPAGATION OF FIRE FROM ONE
SPACE TO ANOTHER.
N THE PROPERTY OF I

39 13. WHEN MAIN ELECTRICAL CABLE TRENCHES ARE INSTALLED IN AREAS PAVED WITH CONCRETE, PROVISIONS 39
SHALL BE MADE FOR FUTURE CABLES, BY ONE OF THE FOLLOWING METHODS:

F A). WHERE ELECTRICAL TRENCHES ARE UP TO 1000mm WIDE AND INCLUDE 25% SPARE CAPACITY, F
NO DUMMY TRENCH IS REQUIRED. CABLE TRENCH SHALL BE OF DUMMY TRENCH DESIGN
NG I

37 37
N SHALL REM AI

FINISHED SURFACE B). WHERE MAIN ELECTRICAL TRENCHES DO NOT INCLUDE 25% SPARE CAPACITY OR EXCEED 1000mm
ON OR UNDERLYI

IN WIDTH A DUMMY TRENCH WILL BE CONSTRUCTED PARALLEL, AND ADAJECENT TO THE MAIN
FINISHED SURFACE
TRENCH AND WILL BE FILLED WITH SAND. THE WIDTH OF THE DUMMY TRENCH WILL BE DETERMINED
BY THE SIZE OF THE MAIN TRENCH, IT IS ASSOCIATED WITH AS FOLLOWS:
NED HEREI

35 MAIN TRENCH WIDTH DUMMY TRENCH WIDTH 35


NFORM ATI

CABLE TILES COMPACTED UP T0 2000mm 600mm


OR SIMILAR SEPARATION EARTH BACKFILL
ON CONTAI

G G
CABLE TILES COMPACTED 50 2001mm AND ABOVE 1000mm
CABLE TILES WARNING TAPE (GENERAL NOTE 8) (GENERAL NOTE 6)
ETARY I

750
OR SIMILAR SEPARATION EARTH BACKFILL
50 (AS REQUIRED (SEE NOTE 16) C). A 15% DESIGN ALLOWANCE WILL BE MADE FOR THE MAIN ELECTRICAL TRENCH DURING ENGINEERING
CABLE TILES WARNING TAPE (GENERAL NOTE 8) (GENERAL NOTE 6)
N THI

33 33
750

FOR UNPAVED AREAS)


NFORM ATI

TO INSURE THAT THE DUMMY TRENCHES CONTAIN NO CABLE AND ARE AVAILABLE FOR FUTURE USE.
ONAL BECHTEL CO.LTD.PROPRI

(AS REQUIRED (SEE NOTE 16)


NED I

FOR UNPAVED AREAS) 14. IN CONCRETE PAVED AREAS, CABLE TRENCHES SHALL BE COVERED WITH A RED COLOURED CONCRETE TOP
GN OR PART THEREOF CONTAI

300 100 FOR ELECTRICAL CABLE TRENCHES, AND A GREEN TOP FOR INSTRUMENT CABLE TRENCHES.
GN OR I

75
15. INSTRUMENT CABLE TRENCHES SHALL BE CONSTRUCTED ACCORDING TO THE FOLLOWING:
31 NON-LOAD 31
75
ON OF THE DESI

EARTH CABLE CLEAN SIEVED SAND A) ROUTING OF TRENCHES SHALL BE KEPT AWAY FROM POWER AND LIGHTING CABLES. THE SEPARATION
CARRYING CABLES (TOP ROW) CLEAN SIEVED SAND
FREE FROM STONES 150 300 SHALL BE A MINIMUM HORIZONTAL SEPARATION OF 1500mm FROM LOW VOLTAGE CABLES (415V &
FREE FROM STONES
H LOWER) AND 4000mm FROM HIGH VOLTAGE (3300V & GREATER). WHEN POWER CABLE TRENCHES H
(GENERAL NOTE 6) (TYP) (TYP) (GENERAL NOTE 6)
300 INTERSECT INSTRUMENT CABLE TRENCHES, THE CROSSING SHALL BE AT RIGHT ANGLES, WITH A

150
50 100
150

SINGLE LAYER OF
NTERNATI
N THE CREATI

MINIMUM SEPARATION DISTANCE OF 300mm. THE INSTRUMENT CABLE TRENCH SHALL, AS A RULE,
29 (TYP) HIGH VOLTAGE LOAD 29
EARTH CABLE CROSS ON TOP OF THE POWER CABLE TRENCH.
THE DESI

CARRYING CABLE
B) TRENCHES SHALL BE KEPT AWAY FROM BURIED HOT SURFACES (e.g. pipes). THE MINIMUM SEPARATION
ALL I

150 300
75 DISTANCE SHALL BE 300mm PLUS 100mm FOR EVERY 100 DEG C TEMPERATURE OF THE
I

(TYP) (TYP) 150


UNINSULATED SURFACE.
75
27
(TYP) C) INSTRUMENT SIGNAL CABLES MAY BE LAID WITHOUT SPACING, VERTICALLY OR HORIZONTALLY, WITH 27
A MAXIMUM OF FIVE ROWS.
DUMMY TRENCH LV LOAD CARRYING CABLES HV LOAD CARRYING CABLES
SEE GENERAL DUMMY TRENCH D) FIBRE OPTIC CABLES SHALL BE GROUPED AND PLACED IN THE BOTTOM ROW OF THE INSTRUMENT
J LV LOAD CARRYING CABLES HV LOAD CARRYING CABLES J
NOTE 13 DETAIL U-002A SEE GENERAL CABLES IN THE TRENCH.
dgn

SINGLE LAYER OF HIGH VOLTAGE CABLES


25886-3000-E90-0000-E1010-Rev1-DC1.

NOTE 13 E) INSTRUMENT CABLE TRENCHES DO NOT REQUIRE "DUMMY TRENCHES" SINCE FUTURE CABLING IS BUILT
25 ADJACENT TO SINGLE LAYER LOW VOLTAGE LOAD CARRYING CABLES 25
DETAIL U-002B INTO THE SPARE CAPACITY OF THE INSTALLED MULTIPAIR CABLES.
WITH A SECOND LAYER OF NON-LOAD CARRYING CABLES SINGLE LAYER OF HIGH VOLTAGE CABLES 16. WARNING TAPES "BURIED CABLES" SHALL BE PLACED ON TOP OF CABLE TILES BEFORE BACKFILLING
25886-3000-E90-0000-E1010-Rev1-DC1.dgn

ADJACENT TO DOUBLE LAYER LOW VOLTAGE LOAD CARRYING CABLES THE TRENCH.

23 LEGEND: 23

MULTICONDUCTOR POWER CABLE


K K
ASSOCIATED CONTROL CABLE

21 21

NON-LOAD CARRYING (CONTROL, CONVENIENCE OUTLET) CABLE.

19 19
INSTRUMENT CABLE

L REF. DWG. NO. REFERENCE DRAWING TITLE L

5652-STD-EU-D-022 INSTALLATION DETAILS / STDS. - UNDERGROUND CABLE LAYING DETAIL-2


17 17
FINISHED SURFACE 5652-STD-EU-D-023 INSTALLATION DETAILS / STDS. - UNDERGROUND CABLE LAYING DETAIL-3
NON-LOAD
CARRYING CABLES
NOT ASSOCIATED WITH
POWER FEEDERS
FINISHED SURFACE
15 (WHEN REQUIRED) 15

COMPACTED
600

M M
09

EARTH BACKFILL
11-JUL-2014 09:

50
CABLE TILES WARNING TAPE (GENERAL NOTE 6) 1 11/07/14 ISSUED FOR FEED CJW JS JS MR
ORIGINAL SIGNED AND HELD IN DCC

13 (AS REQUIRED (SEE NOTE 16) 13


COMPACTED 0 23/06/14 ISSUED FOR APPROVAL (IFA) CJW JS JS MR
FOR UNPAVED AREAS)
EARTH BACKFILL
50 REV. DATE DESCRIPTION BY
LEAD CHIEF
COMPANY
WARNING TAPE (GENERAL NOTE 6) CHKD PEM PMC
CABLE TILES ENG ENG
750

(AS REQUIRED (SEE NOTE 16)


75 DRAWN: C.J.WHITE CHECKED: J.SHUKLA SCALE: N.T.S.
NONE

FOR UNPAVED AREAS)


11 11
ES

CLEAN SIEVED SAND 50


VARI

N GENERAL N
75

FREE FROM STONES


NOTE 15
(GENERAL NOTE 6)
9 9
150
INTERNATIONAL BECHTEL CO. LTD.
(TYP)
DistributionService$

150

CLEAN SIEVED SAND


FREE FROM STONES
EARTH CABLE PROJECT No. : 5652
75

7 (GENERAL NOTE 6) BECHTEL JOB No. : 25886 7


AGREEMENT No. : 13-5652-F-1

DETAIL U-003 150 O


O PROJECT TITLE
75
\\inxs95993\PW

MULTI LAYER ARRANGEMENT OF INSTRUMENT CABLE (TYP) PROCESSING OFFSHORE CRUDE PROJECT
5 (UP TO FIVE LAYER MAXIMUM)
FRONT END ENGINEERING DESIGN 5
nx

DUMMY TRENCH LV LOAD CARRYING CABLES GENERAL


s-pwi

SEE GENERAL NOTE 7 DRAWING TITLE


DETAIL U-004 ELECTRICAL INSTALLATION DETAILS
NOTE 13
DOUBLE LAYER LOW VOLTAGE LOAD CARRYING CABLES UNDERGROUND CABLE LAYING DETAILS - 1
3 3

SHEET NO. REVISION


P P
BECHTEL DRAWING NO. 3000-E90-0000-E1010 1 1
1 SHEET SIZE 1
TAKREER DRAWING NO. 5652-STD-EU-D-021 A1

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21

\\inxs95993\PWDistributionService$
s-pwinx NONE 11-JUL-2014 09:09 ORIGINAL SIGNED AND HELD IN DCC 25886-3000-E90-0000-E1010-Rev1-DC1.dgn