ADL series guide rail electric energy

meters

1 General

Terminal electricity meters adopt 35mm standard guide rail installing mode 、 LCD
display ,measure electric energy and other electrical parameters, electricity pulse output
function , Clock,rate period parameters can be set also. Data swap with the super
ordination machine Via RS485 Communication.
This power meter has advantages of smaller volume, high precision, good reliability,
easily installing etc, meet the related technical requirements of electronic power meter in
the GB/T 17215、GB/T 17883 and DL/T 614 standards.
It can be used to measure electric energy in Government agencies and large public
buildings ,and to manage electric energy for enterprises and institutions.
2、Technical features

Model ADL10-E ADL100-ET ADL100-E ADL300-E ADL3000-E

Single
phase √ √ √
circuit
Applications

Three √ √
phase
circuit
5(30)A √
10(60)A √
Current 1.5(6)A √ √ √
specification 5(20)A √ √ √
10(40)A √ √ √
20(80)A √ √ √
Direct
√ √ √ √ √
connecting
Connection
Via CT
√ √ √
connecting
3、Product function

Model
ADL10-E ADL100-ET ADL100-E ADL300-E ADL3000-E
Function
Current/Voltage ■ ■ ■ ■
Kw/Kvar/KVA ■ ■
Electrica PF/Hz ■ ■
l
measur Maximum demand □
ement
Electric
energy
Active power ■ ■ ■ ■ ■
measur
ement
Reactive power ■
Complex rate
□ □ □ □
power
Peak, flat, valley □ □
Peak, peak, flat,
Comple □ □
valley
x rate
eight eight
period Period eight periods eight periods
periods periods
Time、Date □ □ □ □
Commu Modbus-RTU □ □ □ □
nication( DL/T645 □ □ □ □
chose
one)

Note:1.■:standard function;□:optional function)


2.When choose the Maximum demand, Complex rate period must be chose at the
same time.
4、Technical features

Technical parameters
ALD10-
ADL100-ET ADL100-E ADL300-E ADL3000-E
E
Model

Power supply None


The rated
AC220V AC 3×220/380V、AC3×380V
voltage
Voltage Frequency 50HZ
input Power
≤5VA ≤2VA ≤5VA ≤2VA
Consumption
Input current 5(30)A 10(60)A 1.5(6)A、5(20)A、10(40)A、20(80)A
Starting

Current current 0.004Ib


input
c
Power
≤1VA
Consumption
Reactive
Accuracy Active power,1.0 class
power,0.5S class
Accuracy clock
class precision
None Error≤0.5s/d

Photo-coupler,Open collector, Passive output,Battery powered


Output
DC+5V~24V
Pulse
80ms±20ms
Pulse width
output pulse
(imp/Kwh)(C 12800、
orresponding 3200 1600 3200、1600、 6400、1600、800、400
to the input 800
current )
interface RS485(A+、B-)
Communic
Medium None Shielded twisted pair cable
ation
protocol MODBUS-RTU
Long x width x 18×9
Dimensions 36×89×62 76×89×74 126×91×74
height 1×64
Installation Guide 35mm
Wiring Flexible cable
capaci 6 16 25
ty (mm²)
Working
﹣20℃~﹢60℃
temperature
Temp
eratur
e Storage
﹣30℃~﹢70℃
range temperature

Humidity ≤95%(No condensation)


Altitude <2000m

5、Terminals

●ADL10-E
●ADL10-E single phase electric energy meter
Load

KWH

直接接入
Direct access

●ADL100-ET single phase electric energy meter


Load

Electric energy pulse

Direct access
●ADL100-E single phase electric energy meter

Load
Electric energy pulse

Electric energy pulse Access with CT

Direct access

●ADL300-E、ADL3000-E three phase electric energy meter

Load

3P4W direct access 3P3W access with CT


Load

3P3W direct access 3P3W access with CT

Clock pulse Electric energy pulse


6 Dimensions and installation

6.1 Dimensions
(1)ADL10-E
Front view Side view

Figure 1 ADL10 outline drawing

(2)ADL100-ET

Figure 2 ADL100-ET outline drawing


(3)ADL100-E

Front view Side view

single phase energy meter

Pulse peak flat valley

Figure 3 ADL100-E outline drawing

(4)ADL300-E /ADL3000-E

Front view Side view

Acrel
DTSD1352 三相多功能电能表 报警 相序 失压 有功 无功

GB/T17215 有功 0.5S
Active
three phase energy meter DL/T614 无功 2.0
50HZ/60HZ reactive
UI PQ E
SET
Figure 6 ADL300-E /ADL3000-E outline drawing

7. Ordering example

(1)ADL100-EF
Model: ADL100-EF

Requirements: input single phase 220v; input current 5(20) A; direct access;1.0class

Communication protocol: None


Power supply: None

(2) Model: ADF100


Requirements :input single phase 220V;input current 10(40)A; direct access;6 single
phase electric energy measurement; 1.0 class

Communication protocol: RS485 interface , Modbus/RTU protocol


Power supply :None

(3) Model:ADL300-EF
Requirement :input voltage 3*220/380V; input current 10(40) A;3P4W;direct access ;XX
area industrial period;1.0 class

Communication protocol: RS485 interface, Modbus /RTU protocol


Power supply :None

(4) Model:ADL3000-E/C
Requirements:input 3*220/380V;input current 1.5(6)A;3P4W;access with CT;1.0
class
Communication protocol:RS485 interface,Modbus/RTU protocol
Power supply : None

8 Communication protocol

8.4 Communication description


8.4.1 RS485/MODBUS-RTU Communication mode
● Communication interface:RS485
● Communication connection mode:two-wire(RS485+, RS485-), shielded twisted pair
conductors
● Communication working mode:half- duplex
● Communication speed:9600bps(default)、4800bps、2400bps、1200bps optional

8.4.2 Communication connection


● Linear connection mode with Communication connection
converter
Computer
communication
port
resistance
● Ring connection mode with Communication connection

converter

Computer
communication
port

8.4.3 Communication protocol


ADL Series guide rail power meters MODBUS-RTU Communication protocol,
MODBUS protocol todefine the check code, data sequence etc. in detail, they are
necessary content for specific data exchange .MODBUS protocol use master/slave
responding connection (half duplex) on the same Communication line. After signal from
host computer addressing of the only one terminal device (slave computer),the terminal
device sends answering signal and transmit to host computer.
MODBUS protocol can only permitted to used between host computer (PC,PLC etc.)
and terminal device, thus to prohibit the data exchange between independent terminal
devices. In this way, every terminal device does not occupy Communication line in their
initialization, only responding to the enquiry signal from host
(1) Transmission mode
The information transmit in asynchronous mode in bytes, the Communication
information transmitting between the host computer and the slave computer is the 10 bits
format, including one Initial bit, 8 data bit (Firstly Transmitting the least effective bit),
without parity check bit,1 stop bit.
(2) Data frame format

Address Function Data CRC check


code code area code
1 byte 1 byte n byte 2 byte
Address code:address code is located at beginning of frame, composed of one byte
(8 bit binary system code), decimal system is 0~255,in the ACR meters, just 1~247 is
used, other address is Reserved. these bits indicate terminal device address specified by
users, this device will receive the connecting host computer data .Every terminal device
has only one address, only the addressing terminal respond to enquiry including this
address. When terminal is transmitting one responding, the responding slave address
data tell host computer that which terminal is it.
Function code:function code tell the target terminal to execute what function. Below
table list: function code used in this Series meters, and their meaning and function.

Function Definition Operation


Read data register Obtain current binary system
value of one or multiple
03H/04H register
Preset multi-register Set binary system value into a
10H series of multi-registe
Data area : data area includes the data needed by terminal for executing specific
function, or the collected data when terminal is responding enquiry. Content of these data
could be value ,reference address or setting value. For example :The function code tell
terminal to Read one register ,the data area need to specify the starting register and Read
how many data, the built-in address and data have different content depending on type
and slave computer.
CRC check code:Error check (CRC) domain occupies 2 byte, including one 16 bit
binary system value. CRC value is calculated by transmission device, and then attached
to the data frame, the receiving device, while receiving, it calculates the CRC value again,
then comparing it with the receiving CRC domain value, if these two values are not equal,
it an error occurs.

8.4.4 Expatiating for communication applicable format


(1)Function 03H: read register
This function allow user to obtain data and parameters collected and recorded by
equipment .Data amount of once requested by host computer have no limit. but the
address should be in range.
Following example is one basic data read from 01 slave (each address in data frame
occupy 2 bytes). The collected data is the total electric energy E (occupy 4 bytes), other
address is 00H
(2)Function code 10H: writing register
Function code 10H allows the user to change the contents of multiple registers .Time,
date, rate period of time etc. in meter can be written by this function code. The one shot
maximum write in data (32 byte) of host computer is 16.
Below meter example show: Preset address01,date, time : 12:00:00, 01/02/2008.

Transmitte
d Returning
Master transmitting Slave returning
informatio information
n
Address code 01H Address code 01H
Function code 10H Function code 10H
High
Initial High byte 00H nitial 00H
byte
address address
Low byte 12H Low byte 12H
High
Register High byte 00H Register 00H
byte
No. No.
Low byte 03H Low byte 03H
High
Byte number 06H CRC 20H
byte
check code
0012H High byte 08H Low byte 0DH
Data to be
Low byte 02H
written
0013H High byte 01H
Data to be
Low byte 0CH
written
0014H High byte 00H
Data to be
Low byte 00H
written
CRC High byte FFH
check
Low byte A8H
code

8.4.5 Communication parameter address table and application details


(1) ADL100 address table
Belong Data
Address Variable Data format
to R/W Model
0000H Each electric energy occupy 4
Current total electricity R/W Dword
0001H byte
0002H Each electric energy occupy 4
Current peak electric energy R/W Dword
0003H byte
0004H Each electric energy occupy 4
Current flat electric energy R/W Dword
0005H byte
0006H Each electric energy occupy 4
Current valley electric energy R/W Dword
0007H byte
0008H Each electric energy occupy 4
Reversing electric energy R/W Dword
0009H byte
000AH
Reactive electric energy R/W Reserved Dword
000BH
000CH Voltage R XXX.X V word
000DH Current R XX.XX A word
000EH Active power R Reserved word
000FH Reactive power R Reserved word
0010H Power factor R Reserved word
0011H Frequency R Reserved word
0012H Year, month R/W word
yy.mm.dd
0013H Day, hour R/W word
hh:mm:ss
0014H Minute,second R/W word
0015H
Communication address R/W 001-247 char
High byte
01 —— 9600bps(default)
0015H 02 —— 4800bps
Communication baudrate R/W char
Low byte 03 —— 2400bps
04 —— 1200bps
0016H~ 8-period of time Parameters Each period of time occupys
R/W char
0021H setting information Three bytes nn mm hh
0022H This month total electric Each electric energy occupy 4
R/W Dword
0023H energy byte
0024H peak electric energy of this Each electric energy occupy 4
R/W Dword
0025H month byte
0026H flat electric energy of this Each electric energy occupy 4
R/W Dword
0027H month byte
0028H valley electric energy of this Each electric energy occupy 4
R/W Dword
0029H month byte
002AH total electric energy of last Each electric energy occupy 4
R/W Dword
002BH month byte
002CH peak electric energy of last Each electric energy occupy 4
R/W Dword
002DH month byte
002EH flat electric energy of last Each electric energy occupy 4
R/W Dword
002FH month byte
0030H Each electric energy occupy 4
Ultimo valley electric energy R/W Dword
0031H byte
0032H Before ultimo total electric Each electric energy occupy 4
R/W Dword
0033H energy byte
0034H Before ultimo peak electric Each electric energy occupy 4
R/W Dword
0035H energy byte
0036H Before ultimo flat electric Each electric energy occupy 4
R/W Dword
0037H energy byte
0038H Before ultimo valley electric Each electric energy occupy 4
R/W Dword
0039H energy byte
(2)ADL300 address table
Belong Data
Address Variable Data format
to R/W Model
0000H Each electric energy occupy 4
Current total electric energy R/W Dword
0001H bytes
0002H Each electric energy occupy 4
Current spike electric energy R/W Dword
0003H bytes
0004H Each electric energy occupy 4
Current peak electric energy R/W Dword
0005H bytes
0006H Each electric energy occupy 4
Current flat electric energy R/W Dword
0007H bytes
0008H Each electric energy occupy 4
Current valley electric energy R/W word
0009H bytes
000AH Year, month R/W word
yy.mm.dd
000BH Day, hour R/W word
hh:mm:ss
000CH Minute,second R/W word
000DH
Communication address R/W 0001~0247 char
High byte
01 —— 9600bps(default)
000DH 02 —— 4800bps
Communication baudrate R/W char
Low byte 03 —— 2400bps
04 —— 1200bps
000EH~ 8-period of time parameters Each period of time occupys
R/W char
0019H setting information Three bytes nn mm hh
001AH Reserved
001BH This month total electric Each electric energy occupy 4
R/W Dword
001CH energy byte
001DH This month Each electric energy occupy 4
R/W Dword
001EH spike electric energy byte
001FH This month Each electric energy occupy 4
R/W Dword
0020H peak electric energy byte
0021H This month Each electric energy occupy 4
R/W Dword
0022H flat electric energy byte
0023H valley electric energy of This Each electric energy occupy 4
R/W Dword
0024H month byte
0025H Reserved
0026H total electric energy of last Each electric energy occupy 4
R/W Dword
0027H month byte
0028H spike electric energy of last Each electric energy occupy 4
R/W Dword
0029H month byte
002AH peak Each electric energy occupy 4
R/W Dword
002BH Electric energy of last month byte
002CH flat Each electric energy occupy 4
R/W Dword
002DH Electric energy of last month byte
002EH valley Each electric energy occupy 4
R/W Dword
002FH Electric energy of last month byte
0030H Reserved
0031H total electric energy of the Each electric energy occupy 4
R/W Dword
0032H month before last byte
0033H Before ultimo Each electric energy occupy 4
R/W Dword
0034H spike electric energy byte
0035H Before ultimo Each electric energy occupy 4
R/W Dword
0036H peak electric energy byte
0037H Before ultimo flat electric R/W Each electric energy occupy 4 Dword
0038H energy byte
0039H Before ultimo valley electric Each electric energy occupy 4
R/W Dword
003AH energy byte
(3)ADL3000 address table

Belong Data
Address Variable Data format
to R/W Model
0000H Current total active Electric Each electric energy occupy 4
R/W Dword
0001H energy byte
0002H Current total spike Electric Each electric energy occupy 4
R/W Dword
0003H energy byte
0004H Current total active peak Each electric energy occupy 4
R/W Dword
0005H electric energy byte
0006H Current total active flat Each electric energy occupy 4
R/W Dword
0007H Electric energy byte
0008H Current total active valley Each electric energy occupy 4
R/W Dword
0009H electric energy byte
000AH Current forward active total Each electric energy occupy 4
R/W Dword
000BH electric energy byte
000CH Current forward active spike Each electric energy occupy 4
R/W Dword
000DH electric energy byte
000EH Current forward active peak Each electric energy occupy 4
R/W Dword
000FH electric energy byte
0010H Current forward active flat Each electric energy occupy 4
R/W Dword
0011H electric energy byte
0012H Current forward active valley Each electric energy occupy 4
R/W Dword
0013H electric energy byte
0014H Current reversing active total Each electric energy occupy 4
R/W Dword
0015H electric energy byte
0016H Current reversing active Each electric energy occupy 4
R/W Dword
0017H spike electric energy byte
0018H Current reversing Active Each electric energy occupy 4
R/W Dword
0019H peak electric energy byte
001AH Current reversing active flat Each electric energy occupy 4
R/W Dword
001BH electric energy byte
001CH Current reversing Active Each electric energy occupy 4
R/W Dword
001DH valley electric energy byte
001EH Current total reactive Each electric energy occupy 4
R/W Dword
001FH electric energy byte
0020H Current total reactive Each electric energy occupy 4
R/W Dword
0021H spike electric energy byte
0022H Current total reactive peak Each electric energy occupy 4
R/W Dword
0023H electric energy byte
0024H Current total reactive flat R/W Each electric energy occupy 4 Dword
0025H electric energy byte
0026H Current total reactive valley Each electric energy occupy 4
R/W Dword
0027H electric energy byte
0028H Current forward reactive total Each electric energy occupy 4
R/W Dword
0029H electric energy byte
002AH Current forward reactive Each electric energy occupy 4
R/W Dword
002BH spike electric energy byte
002CH Current forward reactive Each electric energy occupy 4
R/W Dword
002DH spike electric energy byte
002EH Current forward reactive flat Each electric energy occupy 4
R/W Dword
002FH electric energy byte
0030H Current forward reactive Each electric energy occupy 4
R/W Dword
0031H valley electric energy byte
0032H Current reversing reactive Each electric energy occupy 4
R/W Dword
0033H total electric energy byte
0034H Current reversing reactive Each electric energy occupy 4
R/W Dword
0035H spike electric energy byte
0036H Current reversing reactive Each electric energy occupy 4
R/W Dword
0037H peak electric energy bytes
0038H Current reversing reactive Each electric energy occupy 4
R/W Dword
0039H flat electric energy bytes
003AH Current reversing reactive Each electric energy occupy 4
R/W Dword
003BH valleyelectric energy bytes
003CH Year, month R/W word
yy.mm.dd
003DH Day, hour R/W word
hh.mm.ss
003EH Minute,second R/W word
003FH
Communication address R/W 0001-0247 char
High byte
01—9600bps (default)
003FH 02—4800bps
Communication baudrate R/W char
Low byte 03—2400bps
04—1200bps
0040H Pulse constant R occupy 2 byte word
0041H Period of time R/W occupy 2 byte word
0042H Period of time R/W occupy 2 byte word
0043H period of time R/W occupy 2 byte word
0044H period of time R/W occupy 2 byte word
0045H period of time R/W occupy 2 byte word
0046H period of time R/W occupy two bytes word
0047H Each period of time occupys
table for 1st period of time R/W char
0048H Three bytes nn.mm.hh
0049H Each period of time occupys
table for 1st period of time R/W char
004AH Three bytes nn.mm.hh
004BH Each period of time occupys
table for 1st period of time R/W char
004CH Three bytes nn.mm.hh
004DH Each period of time occupys
table for 1st period of time R/W char
004EH Three bytes nn.mm.hh
004FH table for 1st period of time R/W Each period of time occupys
char
0050H table for 1st period of time R/W Three bytes nn.mm.hh
0051H Each period of time occupys
table for 1st period of time R/W char
0052H Three bytes nn.mm.hh
0053H reserved word
0054H Each period of time occupys
table for 2nd period of time R/W char
0055H Three bytes nn.mm.hh
0056H Each period of time occupys
table for 2nd period of time R/W char
0057H Three bytes nn.mm.hh
0058H Each period of time occupys
table for 2nd period of time R/W char
0059H Three bytes nn.mm.hh
005AH
table for 2nd period of time R/W nn.mm.hh char
005BH
005CH Each period of time occupys
table for 2ed period of time R/W char
005D Three bytes nn.mm.hh
005EH Each period of time occupys
table for 2ed period of time R/W char
005FH Three bytes nn.mm.hh
0060H reserved word
0061H voltage of A phase R XXX.XV word
0062 voltage of B phase R XXX.XV word
0063H voltage of C phase R XXX.XV word
0064H electricity of A phase R XX.XXA word
0065H electricity of B phase R XX.XXA word
0066H electricity of C phase R XX.XXA word
0067H active power of A phase R XXX.XXkW word
0068H active power of B phase R XXX.XXkW word
0069H active power of C phase R XXX.XXkW word
006AH total active power R XXX.XXkW word
006BH reactive power of A phase R XXX.XXkVar word
006CH reactive power of B phase R XXX.XXkVar word
006DH reactive power of C phase R XXX.XXkVar word
006EH total reactive power R XXX.XXkVar word
006FH apparent power of A phase R XXXX.XVA word
0070H apparent power of b phase R XXXX.XVA word
0071H apparent power of c phase R XXXX.XVA word
0072H total apparent power R XXXX.XVA word
0073H power factor of A phase R X.XX word
0074H power factor of B phase R X.XX word
0075H power factor of C phase R X.XX word
0076H total power factor R X.XX word
0077H frequency R XX.XHz word
0078H reserved R word
0-No alarm
1-Measurement data error
0079H status indication R char
2- Wrong phase sequence
3- Table data wrong
007AH reserved R word
007BH Each electric energy occupy 4
active maximum demand R Dword
007CH bytes
007DH Maximum demand for Each electric energy occupy 4
R Dword
007EH reactive power bytes
007FH Time of occurrence for the mm.dd
R word
0080H active maximum amount hh.mm
0081H Time of occurrence for the mm.dd
R word
0082H reactive maximum amount hh.mm
0083H
reversed R Dword
0084H
0085H
reversed R Dword
0086H
0087H
The number of voltage lost R occupy 4 byte Dword
0088H
0089H
reversed R Dword
008AH
008BH Time of occurrence for mm.dd
R word
008CH voltage lost hh.mm
008DH
reversed R Dword
008EH
008FH Current month total active Each electric energy occupy 4
R/W Dword
0090H electric energy byte
0091H Current month total active Each electric energy occupy 4
R/W Dword
0092H spike electric energy byte
0093H Current month total active Each electric energy occupy 4
R/W Dword
0094H peak electric energy byte
0095H Current month total active Each electric energy occupy 4
R/W Dword
0096H flat electric energy byte
0097H Current month total active Each electric energy occupy 4
R/W Dword
0098H valley electric energy byte
0099H Current month forward active Each electric energy occupy 4
R/W Dword
009AH total electric energy byte
009BH Current month forward active Each electric energy occupy 4
R/W Dword
009CH spike electric energy byte
009DH Current month forward active Each electric energy occupy 4
R/W Dword
009EH peak electric energy bytes
009FH Current month forward active Each electric energy occupy 4
R/W Dword
00A0H flat electric energy bytes
00A1H Current month forward active Each electric energy occupy 4
R/W Dword
00A2H valley electric energy bytes
00A3H Current month reversing Each electric energy occupy 4
R/W Dword
00A4H active total electric energy bytes
00A5H Current month reversing Each electric energy occupy 4
R/W Dword
00A6H active spike electric energy bytes
00A7H Current month reversing Each electric energy occupy 4
R/W Dword
00A8H active peak electric energy bytes
00A9H Current month reversing Each electric energy occupy 4
R/W Dword
00AAH active flat electric energy byte
00ABH Current month reversing Each electric energy occupy 4
R/W Dword
00ACH active valley electric energy byte
00AD Current month total reactive Each electric energy occupy 4
R/W Dword
00AEH electric energy byte
00AFH Current month total reactive Each electric energy occupy 4
R/W Dword
00B0H spike electric energy byte
00B1H Current month total reactive Each electric energy occupy 4
R/W Dword
00B2H peak electric energy byte
00B3H Current month total reactive Each electric energy occupy 4
R/W Dword
00B4H flat electric energy byte
00B5H Current month total reactive Each electric energy occupy 4
R/W Dword
00B6H valley electric energy bytes
00B7H Current month forward Each electric energy occupy 4
R/W Dword
00B8H reactive total electric energy bytes
00B9H Current month forward Each electric energy occupy 4
R/W Dword
00BAH reactive spike electric energy bytes
00BBH Current month forward Each electric energy occupy 4
R/W Dword
00BCH reactive peak electric energy bytes
00BDH Current month forward Each electric energy occupy 4
R/W Dword
00BEH reactive flat electric energy bytes
Current month forward
00BFH Each electric energy occupy 4
reactive valley electric R/W Dword
00C0H bytes
energy
00C1H Current month reversing Each electric energy occupy 4
R/W Dword
00C2H reactive total electric energy byte
00C3H Current month reversing Each electric energy occupy 4
R/W Dword
00C4H reactive spike electric energy byte
00C5H Current month reversing Each electric energy occupy 4
R/W Dword
00C6H reactive peak electric energy byte
00C7H Current month reversing Each electric energy occupy 4
R/W Dword
00C8H reactive flat electric energy byte
Current month reversing
00C9H Each electric energy occupy 4
reactive valley electric R/W Dword
00CAH byte
energy
00CBH total active electric energy of Each electric energy occupy 4
R/W Dword
00CCH last month byte
00CDH total active spike electric Each electric energy occupy 4
R/W Dword
00CEH energy of last month bytes
00CFH total active peak electric Each electric energy occupy 4
R/W Dword
00D0H energy of last month bytes
00D1H total active flat electric Each electric energy occupy 4
R/W Dword
00D2H energy of last month bytes
00D3H total active valley electric Each electric energy occupy 4
R/W Dword
00D4H energy of last month bytes
00D5H forward active total electric Each electric energy occupy 4
R/W Dword
00D6H energy of last month bytes
00D7H forward active spike electric Each electric energy occupy 4
R/W Dword
00D8H energy of last month bytes
00D9H Ultimo forward active peak Each electric energy occupy 4
R/W Dword
00DAH electric energy byte
00DBH forward active flat electric Each electric energy occupy 4
R/W Dword
00DCH energy of last month byte
00DDH forward active valley electric Each electric energy occupy 4
R/W Dword
00DEH energy of last month byte
00DFH reversing active total electric Each electric energy occupy 4
R/W Dword
00E0H energy of last month byte
00E1H reversing active spike Each electric energy occupy 4
R/W Dword
00E2H electric energy of last month byte
00E3H reversing active peak electric Each electric energy occupy 4
R/W Dword
00E4H energy of last month bytes
00E5H reversing active flat electric Each electric energy occupy 4
R/W Dword
00E6H energy of last month bytes
00E7H reversing active valley Each electric energy occupy 4
R/W Dword
00E8H electric energy of last month bytes
00E9H total reactive electric energy Each electric energy occupy 4
R/W Dword
00EAH of last month bytes
00EBH ototal reactive spike electric Each electric energy occupy 4
R/W Dword
00ECH energy of last month bytes
00EDH total reactive peak electric Each electric energy occupy 4
R/W Dword
00EEH energy of last month bytes
00EFH total reactive flat electric Each electric energy occupy 4
R/W Dword
00F0H energy of last month bytes
00F1H total reactive valley electric Each electric energy occupy 4
R/W Dword
00F2H energy of last month byte
00F3H forward reactive total Each electric energy occupy 4
R/W Dword
00F4H electric energy of last month byte
00F5H forward reactive spike Each electric energy occupy 4
R/W Dword
00F6H electric energy of last month byte
00F7H forward reactive peak Each electric energy occupy 4
R/W Dword
00F8H electric energy of last month byte
00F9H forward reactive flat electric Each electric energy occupy 4
R/W Dword
00FAH energy of last month byte
00FBH forward reactive valley Each electric energy occupy 4
R/W Dword
00FCH electric energy of last month byte
reversing reactive total
00FDH Each electric energy occupy 4
electric energy of the last R/W Dword
00FEH byte
month
reversing reactive spike
00FFH Each electric energy occupy 4
electric energy of the last R/W Dword
0100H byte
month
reversing reactive peak
0101H Each electric energy occupy 4
electric energy of the last R/W Dword
0102H byte
month
0103H reversing reactive flat electric Each electric energy occupy 4
R/W Dword
0104H energy of the last month byte
reversing reactive valley
0105H Each electric energy occupy 4
electric energy of the last R/W Dword
0106H byte
month
0107H total active electric energy of Each electric energy occupy 4
R/W Dword
0108H the month before last byte
total active spike electric
0109H Each electric energy occupy 4
energy of the month before R/W Dword
010AH byte
last
total active peak electric
010BH Each electric energy occupy 4
energy of the month before R/W Dword
010CH byte
last
total active flat electric
010DH Each electric energy occupy 4
energy of the month before R/W Dword
010EH byte
last
total active valley electric
010FH Each electric energy occupy 4
energy of the month before R/W Dword
0110H byte
last
forward active total electric
0111H Each electric energy occupy 4
energy of the month before R/W Dword
0112H byte
last
0113 forward active spike electric R/W Each electric energy occupy 4 Dword
0114H energy of the month before byte
last
forward active peak electric
0115H Each electric energy occupy 4
energy of the month before R/W Dword
0116H bytes
last
forward active flat electric
0117H Each electric energy occupy 4
energy of the month before R/W Dword
0118H bytes
last
forward active valley electric
0119H Each electric energy occupy 4
energy of the month before R/W Dword
011AH bytes
last
reversing active total electric
011BH Each electric energy occupy 4
energy of the month before R/W Dword
011CH bytes
last
reversing active spike
011DH Each electric energy occupy 4
electric energy of the month R/W Dword
011EH bytes
before last
reversing active peak electric
011FH Each electric energy occupy 4
energy of the month before R/W Dword
0120H byte
last
reversing active flat electric
0121H Each electric energy occupy 4
energy of the month before R/W Dword
0122H byte
last
reversing active valley
0123H Each electric energy occupy 4
electric energy of the month R/W Dword
0124H byte
before last
0125H total reactive electric energy Each electric energy occupy 4
R/W Dword
0126H of the month before last byte
total reactive spike electric
0127H Each electric energy occupy 4
energy of the month before R/W Dword
0128H byte
last
total reactive peak electric
0129H Each electric energy occupy 4
energy of the month before R/W Dword
012AH bytes
last
total reactive flat electric
012BH Each electric energy occupy 4
energy of the month before R/W Dword
012CH bytes
last
total reactive valley electric
012DH Each electric energy occupy 4
energy of the month before R/W Dword
012EH bytes
last
forward reactive total electric
012FH Each electric energy occupy 4
energy of the month before R/W Dword
0130H bytes
last
0131H forward reactive spike R/W Each electric energy occupy 4 Dword
0132H electric energy of the month bytes
before last
forward reactive peak
0133H Each electric energy occupy 4
electric energy of the month R/W Dword
0134H bytes
before last
0135H forward reactive flat electric Each electric energy occupy 4
R/W Dword
0136H energy byte
forward reactive valley
0137H Each electric energy occupy 4
electric energy of the month R/W Dword
0138H byte
before last
reversing reactive total
0139H Each electric energy occupy 4
electric energy of the month R/W Dword
013AH byte
before last
reversing reactive spike
013BH Each electric energy occupy 4
electric energy of the month R/W Dword
013CH byte
before last
reversing reactive peak
013DH Each electric energy occupy 4
electric energy of the month R/W Dword
013EH byte
before last
reversing reactive flat electric
014FH Each electric energy occupy 4
energy of the month before R/W Dword
0140H byte
last
reversing reactive valley
0141H Each electric energy occupy 4
electric energy of the month R/W Dword
0142H byte
before last
Attachment:
1, Belong to Read/ Write: “R” read only ,read this parameter use 03H
command ;”R/W” Readable, writable, write parameter use 10H command. write in address
of non-listed, or non-writable address is forbidden.
2, The Communication address of electric energy meter is given with delivery, also
read out through the software provided by our company.
3, The voltage value detected by electric energy meter is fixed by 2 bit decimal
number ,data format is XXX.XX, unit is V, if Communication read out voltage value is
55EEH (21998), then voltage actual value is 219.98v; the measured current value is fixed
by 3 bit decimal number, data format is XX.XXX, unit is A, if Communication read out
Current value is 50DBH (1499), then Current actual value is 1.499A;
4, The active and reactive power value by electric energy meter is fixed by 2 bits
decimal number, data format is XXX.XX,unit is kW, if communication read out the active
and reactive power value is 0020H(0032),then the active and reactive power actual
value is 0.32kW(kVar);the apparent power value is fixed by 1 bit decimal number, data
format is XXXX.X , unit is VA ,if communication read out the apparent power value is
CE44H(3300) ,then the apparent power actual value is 330.0VA.
5, The electric energy value measured by electric energy meter occupy 4 bytes, unit
is kWh. The high bit is before the low bit, if the reading value is 0012D687H (1234567),
then electric energy Metering value is 1234567×0.01=12345.67kWh.
6, Order of 8-period of time Parameters setting information of above Address Table:
8-period of time Parameters setting Note
information
Rate number for 1st period of time NN 1.Starting time for 1st period of time 00:00
Terminal time for 1st period of time - minute 2.
Terminal time for 1st period of time -hour In DDSF1352(ADL100), corresponding relation
Rate number for 2st period of time NN between rate No. and rate period:01-peak, 02-flat,
Terminal time for 2st period of time - minute 03-valley
Terminal time for 2st period of time - hour 3.In DTSF1352(ADL300)and DTSD1352(ADL3000),
Rate number for 8st period of time NN corresponding relation between rate No. and rate
Terminal time for 8st period of time - minute period:
Terminal time for 8st period of time - hour 01-spike, 02-peak, 03-flat,04-valley