Operation Instruction
1.Overview
FSK569K engine speed controller is mainly
used for Cummins engine with PT pump.
On the base of Cummins EFC controller, it
has increased functions as rising speed ramp,
over speed protection as much as power on
indication.
Its working principle is:First receive speed
signal from magneto electric sensor which is
installed on the flywheel shell. Then compare
with the electric signal of rotate speed which
is beforehand set. Then it will generate error
signal. After PID operation, electric signal will
be sent to actuator. This process can control
the oil supply quantity of engine. So the engine
speed can be controlled. This whole process is a
close loop PID adjusting process.
FSK569 engine speed controller can match for
Cummins EFC actuator normally closed. There
are two working mode: synchronous and droop.

2.Technology Parameter
Fig1、The electrical connections and illustrated
1) Pulsating rate of revolution ≤±0.25%
2) Steady state speed droop 0~5%
3) Speed adjusting range 1 KHz ~ 5 KHz
3.Wiring and installation
4) Supply voltage 24VDC The electrical connections and illustrated in
5) Power consumption <5A Figure 1.
6) Speed fine-tune range(5KΩpotentiometer) The controller must be installed in the
≤500Hz protective housing without EMI (Electro
7) Rising speed time 3~6s Magnetic Interference). User can connect the
8) Over speed protection setting range actuator as the Actuator operation instruction.
2 KHz ~ 5 KHz Wring of sensor、actuator and speed fine-tune
9) Temperature drift ±0.1% potentiometer should use shield cable to avoid
10)Environmental temperature the interfere of outward electromagnetic signal.
-30℃~+70℃ Cable area must be much enough for controllers
11) Relative humidity <95% electric current. Normally use cable up 1 mm2.
4.Adjustments 5.Guideline for Governor Breakdown
1) Inspect whether the related electrical Maintenance
connections are correct.
1) Routine trouble shooting
2) First time start engine, must insure the
If system can’t normal working, generality
engine is on idle state. Then stop engine. Inspect
can perform inspection according to following
whether the pump can return oil off position
methods.
while the actuator power off.
●After powered on, inspect if the power is
3) When the engine is working on idle state,
normal. Measure the voltage at the controllers
adjust the idle potentiometer and set the speed
terminal 1 and 2 by multi-meter, and the value
at rated value. Clockwise rotate, speed increase
should be 24V, at the same time, power indicator
and anti-clockwise regulates, speed decrease.
light bright.
4) Turn speed switches to make the engine
●After powered off, measure the resistance
work at the high speed state. Adjust the high
at the controllers terminal 3 and 4, and the
speed potentiometer to set the speed at rated
normal value should be 7Ω. Resistance value at
value. Clockwise rotate, speed increase and anti-
the terminal 5 and 6 should be 300Ω.
clockwise regulates speed decrease.
2) Engine can’t start up
5) If working state engine unstable, adjust
●Inspect the voltage of battery. The starting
the gain potentiometer to adjust the stability.
voltage value can’t be under 18V.
When engine instable over 3Hz, anti-clockwise
●Inspect the voltage of rotate speed signal.
turn the gain potentiometer slowly till the engine
Power on the motor, measure the voltage at the
stable. When instable below 3Hz, clockwise
terminal 5 and 6 by multi-meter. This value
turn the gain potentiometer slowly till the engine
should be over 3VAC.
stable. Clockwise turning the gain potentiometer
●Inspect if the speed is set too low.
can increase the sensitivity of speed adjusting
●Inspect the oil.
system. The sensitivity means respond time of
3) Engine speed unsteady
adjusting system.
●The controller is not set well. Turn the gain
6) Increase load, inspect the stability and
potentiometer again till the engine stable.
character of rotate speed. Commonly if the
●Inspect the actuator installation as well as
engine is stable free load, there is no problem
the actuator itself.
when on load. In case it is unstable on load and
●Inspect the pump.
load is not enough, inspect the controller and
●The oil is not clean.
actuator as much as the pump and engine.
●Air exists in fuel piping.
7) Over speed protecting set: set the rated
● If the environment temperature is under
speed potentiometer at the protecting position
0℃, use proper grade fuel.
first, then anti-clockwise turn the over speed
4) Engine load is not enough
potentiometer slowly, till the engine stop.
● If the maximum output voltage value of
Then anti-clockwise turn the rated speed
controller on load is below this value free load,
potentiometer slowly. Restart the engine and
please replace controller.
readjust the rated speed potentiometer to speed
● There is problem with the pump, please
the engine up to rated value.
inspect and maintain the pump.
8) Rotate speed of FSK controller had
When the controller can’t work normally,
been set by the Cummins engine of 118 teeth
please treat by the before methods. If the
flywheels. Idle speed value is 700 r/m, rated
problem still exist after the before treatments,
speed value is 1500 r/m, over speed protective
and if there is no problem with the engine,
rotate speed value is 1650 r/m. There is no need
please connect with us. Users can’t remove and
to adjust while user start using.
repair blindly, for tear the problem expands.