Documente Academic
Documente Profesional
Documente Cultură
( Py?rT !pe.bm )
Indian Standard
COPPER ALLOY FANCY SINGLE TAPS,
COMBINATION TAP ASSEMBLY AND STOP
VALVES FOR WATER SERVICES -
SPECIFICATION
( First Revision )
Q BIS 1993
FOREWORD
This Indian Standa .rd ( First Revision ) was adopted by the Bureau of Indian Standards, after the
draft finalized by the Sanitary Fittings and Water Fittings Sectionaf Committee had been
approved by the Civil Engineering Division Council.
Pillar tap. bib taps and stop valves are extensively used as water fittings for domestic water
supplies. Bib taps and stop valves and pillar taps were covered separately in IS 8931 and IS 8934
respectively. Since the functional requirements of these taps and valves are identical, the
committee c!ecided to merge these two specifications. In its first revision this standard besides
merging the two specifications, incorporates the following major modifications:
a) Combination tap assembly has been included.
b) Only the critical dimensions have been given so that the design flexibilities as may be
required by the manufacturer are incorporated.
c) Material specifications for various components/parts of taps and valves have been elabo-
rated.
d) Since the taps of nominal size of 10, 20 and 25 mm and valves of 10 and 25 mm are not
commonly used, these have been withdrawn.
e) Some additional performance tests have been included, as these were found necessary.
Requirements cf screw down rising spindle bib tap.;, stop valves and pillar taps have been covered
in IS 781 : 1984 and IS 179.5 : 1982 respectively.
In the formulation of this standard, considerable assistance has been derived from EN 200 : 1989
‘Sanitary tapware : General technical specifications for single taps and mixer taps ( nominal size
l/2 ) PN 10 : Minimum flow pressure 0f0.05 MPa ( 0.5 bar )‘, pub!ished by European Committee
for standardization. However, mechanical endurance characteristics and acoustic characteristics
as covered in EN 200 have not been included, as the test facilities for these tests do not exist irt
the country. These are intented to be included in due coure of time.
The committee responsible for the preparation of this standard is given at Annex F.
For the purpose of deciding whether a particular requirement of this standard is complied with
the final value, observed or calculated, expressing the result of a test or analysis, shall be rounded
off in accordance with IS 2 : 1960 ‘Rules for rounding off numerical values ( revised )‘. The
number of significant places retained in the rounded off value should be the same as that of the
specified, value in this standard.
iS 8931 : 199.3
Indian Standard
COPPER ALLOY FANCY SINGLE TAPS,
COMBINATION TAP ASSEMBLY AND STOP
VALVES FOR WATER SERVICES -
SPECIFICATION
( First Revision )
I SCOPE taps llild ValVCs81’C normally fitted. The hon~i-
nal size shall be as foIlro\vs:
This standard lays down the requirements
regarding materials, manufacture, workmanship, Pillar tap I5 111111
assembly and Valves, suitable for operation Stop valve 15 :I ntl 20 ml11
from 0. I MPa to 0.5 MPa pressure at maximum Angle stop valve I 5 ;; 11c! 20 Ill Ill
temperature of 65%.
5 MATERIAL
2 REFERENCES
5.1 Material used for different components/
The Indian Standards listed in Annex A are the parts of taps and valves shall be in accordance
necessary adjuncts to this standard. with Table 1.
3 TERMINOLOGY 6 MANUFACTURE, WORKMANSHIP AND
3.0 For the p11rpose of this stal:dard, the defi- CONS’I’RUCTION
nitions give!1 in IS 10446 : 1983 shall apply, in
6.1 General
addition to the following.
Figures appearing in thi:< standard are iiluitrative
3.1 Combination Tap Assemblies
and do not specify tlccign features. Mowevcr,
3.1.1 Pillar Motmting Combination dimcnsiorls a4 specified shall be comp!ied witlt.
The tap assembly with a vertical inlet nnd a 6.2 Caatittg shall in all respec1\ be 4(‘LlIlCl and
nozzle arranged to discharge in a downward free frown dcfccts like laps. blowholes and
direction ( such as sir,gle hole and three hole pittiilg. EXtcrtl:ll and internal aurfaces shall b:
combination tap assemblies far wash basin ) clean, smooth and fret from sand. They shall
and is suitable f<rr mounting on a horizonta! be neatly dressed and no casting shall bc but-ncd,
surface. plug& stopped and palched.
3.1.2 wall iVIounting Combination 6.3 Forging shall be \cund without lamination,
smooth and well finished.
The tap assembly with a horizontal inlet and a
nozzle arranged to discharge in a downward 6.4 Plastic mouldcd knobs shall be sound and
direction ( such as bath and sink combination free from cracks, spots and blow holes. How-
tap asscmblics ) and is suitable for mounting ever. shrinkage marks appearing due to mould-
an vertical sui-fact. ing process ;Lre permissible on internal pclsilions
of the surface whereby these will not ell‘cct the
3.2 Angle Stop Valve appearance :~nd per-formances of the knobs.
A valve with the inlet and outlet a~ right angles
to each other and is intended to facilitate scrvi- 6.5 Machining
cir;g of water fittings or appli,inccs. The boclv, bonl;ei, spindle ar!cl other pat-t\ \11;111
be mach”ineci true, SO that I\ hen ::>hc~~~bicci, I I!c
4 NOMINAL SIZES parts shall be axial ~~~rallcl and cyl~nd~-ical,
Tllc nominal size shall he dcstgnatcd by the \vilh surface snioothiy finished \IIihlll the limit\
nominal bore of the pipe o~~tlct to which the of dimensions specified for various componcnl~.
IS 8931 : 1993
Table 1 Material for Components Parts of Single Taps, Combination Tap Assemblies and Valves
( Chise 5.1 )
2
IS 8931 : 1993
3
c OPTIONAL RECESSED TO A DEPTH
NO, EXCEEOING 2’/2 THREADS
5zl----w
1. Bore of inlet shank, A - 14.5
2. Thread of inlet shank, B *G l/2 B
3. Diameter or size across flats, C 42 -
4. Horizontal length from center of body to center of 80 -
outlet, D
5. Height from flange to center outlet, E 25 -
6. Length of thread, F 42 -
Length of shank, G 50 -
7.
8. Diameter of flange, H 38
Thickness of flange, J 2 -
9.
10. Size across Hats, K 25 -
7 -
Il. Height of flats, L
NOTE - The nozzle may either be manufactured frJ,m cast or from wrought material ( brass tube ).
*Conforming to IS 2643 ( Part 3 ) : 1915.
NOZZLE
NOTE - 111~ r.0271~ may cithcl be manuFactwed from cast or from c roug!lt material ( brass tub: ).
*C‘onforming to IS 2643 ( Part 3 ) : 1975 or IS 554 : 1985.
FIG. 4 !~IIIIES FOR Srop VALVFS AND ANGLE Sror~ VALVES ( TYPICAL DETAILS )
Table 5 Dimensions of Bodies for Stop Valve and Angle Stop Valve
( Chtsc 7.2.5 )
All dimrrrsions in millimctres.
SI No. Legend Dimensions for Nominal Size
( sw Irig. 4 ) ~-.--__-_--_ ___.-- ~------_-~-_-__7
15 20
_- -_.-h_-__- .‘~
.&fir1 .\lrr \
*<; 3 1 II\? 3,4*
‘(i 3’3H II 3 ‘I*
IO.5
12 -
h
OOSE FLANGE --
/’
,/ ,’I’
I tY NO2 ZL E
E
1 L----l
LOOSE FLANGE
Table 6 Dimensions of Bodies for Wall Mounting Combination Tap Assembly, Size 15 mm
( Clause 7.2.6 )
All dimensions in m~llinlctws.
SI No. Particulars ( see Fig. 5 ) Dimensions
~~_~~__-~~~~~
h4in MflX
1. Thrcad of ivlet shank, 11 *Ci l/2 B
2. Lergth of shank, B 25 -
3. Adjllstment range of S-union, C 5 -
so -
4. Diameter of range. D
5. Distance betMc:n ccntres of inlets, E 148 -
6. Lcllgth fIOJ~1 flargc to cciltre of spoIIt, I; 13s
200 -
7. Lwgrh from flange to ccutrc of zpout, G
NOR! - 711~ ~;oz;llc may ciihcr be mnnufacturcci flon1 cast 01 fl(>m wi~~ght nl:tel ial ( hr;is\ luh ).
*C‘onforming to iS 2643 \ Part 3 ) : 1975
LOOSE FLANGE
PERMITTED
c
INLET TUBES Mr 1
Table 7 Dimensions of Bodies for Pillar Mounting Combination Tap Assembly, Size 15 mm
( Clause 7.2.6 )
( All dimensions in millimetres. )
SI No. Particulars ( we Fig. 6 ) Dimensions
r-----_-_A______,
Mifr MUX
1. Dimension 01 b’ase from ccntrc of body, A 21 31
2. Diameter of shank, II - 29
3. Outer dimension, C - 33.5
4. Smallest dimension of Kinge, D 42 -
5. Hori&ntal length from c:ntrc of body to w) _-
ccnlre of outlet, E
6. Height from flange to ccntrc of outlet, I’ 25 124
7. ~xngth of threaded shank, LI 40 .I.
8. Deplh of iicxagol-I., ff 7 -
9. Dinrvetcr of flar;gz, .I 42 -
10. Length of connection, K 350 -
11. Mean outside diameter of copper tube, L. 9.5 -
12. Mean thickness of tube, hl 0.6 .-
NOTES
1 The nwrlc may cithcr be nianufacturcd from cast or from wrOught material ( brars tube )”
2 The inlet tubes made of soft annealed copper tubes.
PERMITTED
FIG. 7 BOIXES FOR PILLAR MOUNTING COMDINATION TAP ASSEMBLY ( TYPICAL DETAILS )
Table 8 Dimension of Bodies for Pillar Mounting Combination Tap Assembly, Size 15 mm
( CIatrse 7.2.6 )
( All dimensions in villimetrec )
SI No. Particulars ( we Fig. 7 ) Dimensions
r---_ h---__-T
Mbr MUX
1. Bore of inlet shank, A - 14.5
2. Thread of inlet shank, B G l/2 R*
3. Length of cxtcrnal threaded shank, C 8 -
4. Height for tightening ( adjustable ), D 5 30
5. Diamctcr of shank, E - 29
6. Smallest dimension of flange, F 42 62
7. Diamctcr of flange, G 42 -
8. Distance between centres of inlet. Ii 195 210
9. Horizontal length from center of body to 90 -
centrc of outlet, J
10. IIcight from flange to cenire of outlet, K 25 125
Mean outsi:l: diameter o! copper tube, L 9.5 -
11.
12. Mean thickness of tube, M 0.6 -
NOTE _ The nozzle may either be man.ufacturcd from cast or from wrought material ( brass tub- ).
*Conforming to IS 2643 ( Part 3 ) : 1975.
WASHER PLAT
F----+---i
Flc. 8 BONNET ASSEMBLY( TYPICAL DETAILS )
Table 9 Dimensions of Bonnet Assembly
( Cluuse 7.3.2 )
( All dimensi0r.s in millimetres )
SI No. Particulars ( see Fig. 8 ) Dimensions for Nominal Size
r--_--4--
15 3.7
1. Diameter, A ( Min ) 25 31
2. Thickness, R ( Mitt ) 2.5 2-s
3. Diameter of seat washer, C ( Min ) 15 6 20.6
4. Projection from edge of washer plate, D ( Min ) 1 1
( applicable for shrouded type oiily )
5. Thickness of seat washer, E ( Min ) 4 4
6. Length of closing thurst collar of bonnet, F( Min ) 2.0 2.5
I. Thread, G *G l/2 B *G 3/J B
8. Length, II ( MUX ) 9 9
9. Diameter of spindle, J ( Mire ) 7 9
10. Diameter of thur.st collor, K (Mire ) 11.8 13.8
11. Thickress of thurst collar, L ( Min ) 1.5 1.5
12. Ccrc diameter of spindle actuating thread, M ( Mitt ) 6.0 8-O
13. Outside diameter of washer plate, N (Max ) 18.5 24
*Conforming to 1s 2643 ( Part 3 ) : 1975.
IS 8931 : 1993
8.1.1 Dejinition of Signi$cant Surfaces 9.2.1.4 The test equipment, duration and
procedure as specified in Annex B shall be
Significant surfaces are all parts of the article followed.
( taps, valves and combination tap assembly )
covered or to be covered by the coating and 9.2.2 pressure Resistance Characteristic
for which the coating is essential for servicea-
bility and/or appearance of the fitted article. 9.2.2.1 This test consists of revealing any defor-
For example, internal sufaces of hollow parts mation in the tap and valve that may result
such as cross pieces, caps, knobs are not under the action of cold water at a relatively
deemed significant. high pressure. The test shall be carried out
LIpstream and downstream of the taps and
8.2 The taps and valves shall be nickle- valves.
chromium plated complying with service grade 9.2.2.2 Criteria for conformity shall be that no
No. 2 of IS 4827 : 1983.
permanent deformation in the part of the taps
8.3 The knobs and knob components of plastic and valves situated upstream or downstream
material may be used in as moulded finish, or shall be produced.
11
IS 8931 : 1993
9.2.2.3 The test cquip:nent, p:occdurc and 9.2.4.3 The Lap with its operating mechanism
duration as specified in Annex C shall be ( bonnet assembly ) shall not be supplied with
followed. water during the test.
9.2.3 Hydraulic Characteristics ( Flow Ru!e ) 9.2.4.4 Throughout the duration of test and at
the end of test there shall be no permanent
9.2.3.1 Tllis test is pcrforn-ied to dcterminc the deformation or loosing of any part of the tap
value of the flow rate corresp:>nding to rcftrc!icC and valve.
pressure equal to 0.3 MPa. The measurement
is carried out with taps and valves fully opan. 10 SAMPLING AND CRITERIA FOR
If it if fitib:d with flo\+ straightening or aerating CONFORMITY
device the same may bc removed for the The sampling procedure to be adopted and
purpose. criteria for conformity shall be as given in
9.2.3.2 The value of flow rate shall not be less Annex E.
than: 11 MARKING
a) 12 l/mitt f0r 15 mm nominal size single 11.1 Each pillar tap, bib tap, combination tap
and comhinntion tap and valve assembly, stop valve alld angIe stop v,llvc shall
b) 23 l/min for 20 mm nominal size. be legibly marked with the followiitg informa-
tion:
ANNEX A
( Clmse 2.1 )
1.1% OF REFERRED INDIAN STANDARDS
IS No. Title IS No. Title
292 : 1953 Specification f0r leaded brass 554 : 198.5 Dimensions for pipe t hrcads
ingots and castings where pressure-right joinls
are made on threads
31s : 1981 Specilicaticln for leaded tin
b:.onze ingots and castings 742 : 1981 Specification for /inc base
alloys die casting
319 : 1989 Specification for free cutting 7sl . 1984 Specification for cast cc)ppcr
leaded bra\a bars, rods and ’
alloys screw down bib tap,
sections
and stop valves for water
407 : 1989 Specificatiotl for brass tube\ services
for gcnct-al purpose 1264 : 1989 Specification for brass gravity
410 : 1977 Specification for cold rolled die cast inos
i‘ ( ingot5 and
brass k,heets, strip and f!lil cattings )
12
IS 8931 : 1993
ANNEX B
( Clause 9.2.1.4 )
WATERTIGHTNESS CHARACTERISTICS
13
IS sp31 : 1993
i) Connect the tap/valve specimen to the v) Put the diverter in the shower position,
test circuit. the shower outlet being artificially closed
and the bath outlet being open the gener-
ii) With the outlet orifice closed and gener- ally turned downards.
ally turned downwards? open the seat
( bonnet assembly ). vi) Apply a static water pressure of 0.4 MPa
for 60 s. Check that watertightness is
iii) Apply to the tap/valve specimen, a water maintained on the bath side.
pressure of 0.4 MPa for 60 S.
vii) In addition, if the watertightness of the
iv) In addition, for tap and valves where the diverter is ensured by one or more 0
watertightness of the spindle is ensured
by one or more O-rings, apply a water apply a static water pressure of
F8vIPa for 20 s. In the latter case, begin
pressure of 0802 MPa for 60 s.
by applying the highest pressure, then
v) ln the latter case, begin by applying O-4 gradually reducing down to the lowest
MPa gradually reducing down to the pressure of 0.02 MPa. Check that water-
test pressure of 0.02 MPa. tightness is maintained on the bath side.
14
IS 8931:1993
B-5.2 Air Test Under Water 0.02 MPa for 20 s. In the latter case
begin by applying the highest prcssurc
i) Connect the tap in its normal positions then gradually reducing down to the
of use to the test circuit. lowest pressure of 0.02 MPa. Check
that watertightnrss is mnin:aincd 011 the
ii) Place the diverter in the bath position, bath side.
with the bath outlet being artificially
closed and shower 0utlet being open
B-5.3 Procedure for Checking the Watertightness
generally turned upwards.
of Automatic Diverters
iii) Immerse the tap ir. the water contained
in the tank. ( The test shall be carried out with water only. )
iv) Apply a static air pressure of 0.2 MPa i) Conlieci the tap, in its normal position
for 20 s. Check that watertightness is of LLC~. to the test circuit with outlet
maintained on the bhowcr side. orifices open and geneI-ally tul~nz(! Jown-
wards. Connect the flow regulator ( SEP
B-2.3 ), to the shower outlet.
v) In addition, if the watertightness of the
divertor is ensured by one or more 0
ii) Put the diverter in the bat.h position, and
I ings, apply a static air pressure cf 0.02
apply a dynamic water pressure of 0 4
MPa for 20 s. In the latter case begin
Ml% for 60 s. Check that wztertightness
by applying the highest pressure of 0.02
is maintained on the shower side.
MPa. Cheek that watertightncss is main-
taincc! on the shower side.
iii) Put the diverter in sho\ver position, check
vi) Put the divertor in the shower position that watcrtightncss is maintained on the
with the shower side outlet being arti- bath side.
ficially closed and the bath side outlet
being Opelid and generally turned iv) With the diverter still in shower posi-
upwards. tions, reduce the dynamic p:-esswe to
0.05 MPa. Check that the diverter has
vii) Immerse the tap in the water contained not disengaged. Maintain this pressure
in the tank. for 60 s and cheek [hat wntcrtightness is
maintained on the bath side.
viii) Apply a static air pressure of 0.2 MPa
for 2O s. Check that watertightness is V) Stnp the water, check that th,_ c!ivcrtcl
maintai~icd on the bath side. returns to the bath positions.
ix) 111 addition, if the watertightness of the vi) Rs-apply the dynamic p:c;;urz of 0.05
divcrtor is ensured by 0ne or more MPa fur 60 s. Cheek Ihat wate;tightness
0 rings, apply a static air pressure of is maintained on the shower side.
I5
IS 8931 : 1993
ANNEX C
( Clause 9.2.2.3 )
PRESSURE RESISTANCE CHARACTERISTICS
C-l GENERAL Apply for 60 s a static water pressure of 2.5
This annex specifies the test method for MPa.
checking the mechanical behaviour with cold
water of the body of the taps and valves and C-4 PROCEDURE FOR CHECKING THE
lays down rhe test criteria. MECHANICAL BEHAVIOUR
DOWNSTREAM, SEAT ( BONNET
C-2 TEST EQUIPMENT
ASSEMBLY ) IN OPEN POSITION
Use a hydraulic test circuit capable of pro-
ducing the static and dynamic pressures Apply for 60 s a dynamic water pressure of 0.4
required and of mail?taining them for the test MPa, this pressure being measured at the
duration. junction of the tap and the pipe. Carry out the
C-3 PROCEDURE FOR CHECKING OF test on the tap and valve as supplied. For taps
MECHANICAL BEHAVIOUR UPSTREAM containing a removable aerating device in the
SEAT ( BONNET ASSEMBLY ) IN SHUT nozzle carry out an additional test with the
POSITION device removed.
ANNEX D
( Clause 9.2.3.3 )
HYDRAULIC CHARACTERISTICS
D-l GENERAL 0 a straight portion of tube, having a
minimum internal diameter 13 mm and
This annex specifies the test method which 19 mm for 15 and 20 nominal size of taps
enables the flow rate of single and combination and valve respectively, with a pressure
taps and velve together with their standard tapping, as shown in Fig. IO.
accessories to be measured for a given pressure.
D-2 APPARATUS ( see Fig. 9 ) ii) a tap and valve connecting nut or socket
of suitable size;
The apparatus consists of a supply circuit and a
test circuit. iii) a pressure circuit, connected to the pre-
D-2.1 The supply circuit assembly consists of : ssure take off tee and to the pressure
measuring device.
a) a device ( A ) enabling the required pre-
ssure to be achieved; NOTE - The connection between the pressure
circuit and measuring apparatus is situated.
b) piping ( B ) with a cross section such
that the test circuit without the tap and a) at the connection level, for all taps ( Fig.
valve to be tested, enables a flow rate of 10a and 1Oc ) except for tap with combined
visible bodies and all mixers with copper inlet
50 percent greater than the flow rate to pipe of 250 mm minimum length ( Fig. lob ).
be measured to be achieved.
b) 200mm above the connection level for all
c) a device ( C ) to measure the flow rate. types of tap.
NOTE - This device may also be placed
downstream of the test circuit, provided it is Example of the fitting of the tap and valve to
separate from the test circuit. the test circuit are shown in Fig. 10.
D-3 TEST CIRCUIT ( see Fig. 10 )
D-3.1 Pipes
The circuit shown in Fig. 10 is suitable what-
ever the type of the tap and valve to be tested. The pipes shall be of metal and their internal
It consists of : surface shall be smooth.
16
IS 8931 : 1993
JJ$+_______Hj
,______?_g
SUPKY ClRCUIT j, TESTCIRCUIT \1 TEST CIRCUIT
/lX
/I--
FIG. 9 SUPPLY AND TEST (hXJIT
61
‘_
: !
D-3.2 Pressure Take off Tee D-4.2.5 Open the valve to its maximum.
‘The pressure take off tees shall b,: made of D-4.2.6 Supply the test circuit and adjust the
brass and machined to the dimension as speci- dynamic pressure to 0.3 MPu.
fied in Table 10.
D-4.2.7 When a stable, continuous few has
D-4 TEST CONDITIONS been established, measure the corresponding
flow rate.
D-4.1 Precision of the Measurements
D-4.2.8 For greater accuracy, the following
The precicion c:f the device for measuring the procedure is rccommcndcd:
flow rates and pressures shall be & 2 percent.
carry our several measurements of the
D-4,2 Procedure
flow rate ai different v:~lucs of prcssurc
D-4.2.1 Fit the tap and valve to be tested orito ( for example between 0. I MPa and 0.5
the test circuit. MI’s ).
using logarithmic coorclinatcs, plot the
D-4.2.2 For combination taps with two inlets,
curve of the flow rate ( Q ) ;I!, a function
the test shall he carried out on each of these
of the piescurc ( P );
inlets separately.
determine 0li this curve Ihe value of the
D-4.2.3 For combination tap with combined fl<)w rate correspondiny to the prcssul-e
visible body, reduce, if necessary the 1el:gth of of 0.3 MPiI.
the supply tubes to a value of 250 mm.
D-S CALIBRATION
D-4.2.4 For the tap., and valves which cannot
be connected (directly to the test circuit It i$ recommended that the mea\uring applla-
connector, use iritermctfiatc COIlilCCtill~ device: ncc< and the test circuit be c;llihr-aleil at rcgulai
which have minimum hcnd Iohs. intcrvnl\.
17
IS 8931 : 1993
ANNEX E
( Clfltrse 10 )
SAMPLING AND CRITERIA FOR CONFORMITY
E-l SCALE OF SAMPLING selection, procedures given in JS 4905 : 1968
may be followed.
E-l.1 Cot
E-2 NIJMBER OF TESTS AND CRITERIA
111any consig:!mcnt, all the items ( Pillar taps FOR CONFORMITY
bib taps, combination tap assembly, stop valves
and atlgle stop valves ) made of the same E-2.1 All the taps and valves selected according
material, of the same nominal size and from to E-l.3 shall be examined for material ( 5.5.1 ),
the same batch of manufacture shall be grouped manufacture, workmarrship and construction
together to constitute a lot. ( 6 ), ciimensions ( 7), and finish ( 8). A sample
item failing to satisfy one or more of these
E-l.2 For ascertaining the conformity of mate-
requirements shall he considered as defective.
rial in the lot to the requirements of this speci-
fication, sample shall be tested from each lot E-2.1.1 The lot shall be consictcled to have
separately. satixficd thcsc requirements if the nunlhcr of
defective itcn;s found in the san~plc is less than
E-l.3 The number of items to he selecttd from
or Equal to the corresponding acccptancc
the lot shall depend on the size of the lot and number given in co1 3 of Tsble Il.
shall be accord in& to Table 11.
E-2.2 The lot having been fount! satisfactory
Table 11 Scale of Sampling and Criteria according to E-2.1 shall be further tcstcci for
for Coriformity performance test specified under 9.2. For thi,
No. of Taps and Sample Acccplancr: Sub- purpose, as sub-sample of taps and Valves given
Valves io the Lot Size Number Sample in co1 4 of Table 1 I shall he take!; and subjected
(1) ( 2; (3) (4) to these tests. The number of items J.cquireci
up to 150 0 S in the sub-sample may be taken from those
151 to 300 0 13
301 to 500 :: 13 alre;tdv exam i II ed and found sat isfactor)
501 to 1 000 : 20 accorciing to E-2.1.
1 001 to 3 oco :: 32 E-2.2.1 The lot shall be consiticred to have
3 001 and above 80 : 32
satibfLzd the requirement\ for these tchta rf
E-1.3.1 These items shall he selected at rarldom none of tap and valve\ in the sub-sample f:liIs irl
from the lot, in order to ensure randomness of any of these tests.
IS 8931 : 1993
ANNEX F
( foreword )
COMMITTEE COMPOSlTION
Sanitary Appliances and Water Fittings Sectional Committee, CED 3
C/airman Representing
SIJRI S. PRAKASH Delhi Water Supply and Sewage Disposal Undertaking, New
Delhi
Menlbcr
SHRI P. K. JAIN I Akwrate to
Shri S. Prakash )
ADVISOR ( PHE ) Central Public Health and Environmental Engineering Orgniza-
Dr ADVISFR ( PHE ) ( AIternatc ) tion, New Delhi
SHRI J. K. AGGARWAL M/s Govardhan Das P. A. ( Calcutta), Calcutta
SHRI SANJAY AGCZARWALL ( Aftmate )
SIJIU ARIJN KANTI BISWAS Natio;o~~;ironmentnl Engineering Research Institute (CSIR).
i)R T. K. DAN Central Glass and Ceramic Research Insitute (CSIR), Calcutta
SHRI G. DHAMODARAM E.I.D. Parry ( India ) Limited, Madras
SHRI V. GOPAL ( Altcvwatr )
HYDRAULIC ENGINEER Municipal Corporation of Greater Bombay, Bombay
DY HYDRAULIC ENGINEER ( Ahcrnatc I
SHRI D. K. KANUNGO National Test House, Calcutta
SHRI R. KAPOOR ( Alternate )
SHRI K. LAKSHMI NARAYAnA Hindustan Shipyard Ltd, Visakhapatnam
SHRI A. SHARIFF ( Alternntc )
MANAGING DIRECTOR Kerala Water Authority, Trivandrum
CHIEF ENGINEER ( PB & G ) ( A[fermte )
SHRI M. M. MISTRY National Buildings Organization, New Delhi
SHRI A. G. DHONGADE ( Altfrtlnte )
SHRI S. K. NEOC~I lnstitution of Public Health Engineers ( India ), Calcutta
SHRI A. K. SFNGUPTA ( Alterwtr )
SIIRI Y. N. RAO Engineer-in-Chief’s Branch, Army Headquarters, New Delhi
MAJ P. NAC; ( Altc~rmte)
SFJRIR. H. ROTITHOR Kirloskar Brothers Limited, Pune
SHRI S. D. JOSHI ( .-lhrrrafc )
S~JRI D. K. SEIJGAL Leader Engineering Works, Jalandhar
SIJR I B. B. SIKKA ( Altcrnutc )
SENIOR CIVIL ENGINEER ( WATT-R SUPPLY ) Railway Board ( Ministry of Railways ), New Delhi
SIIRI R. C. SFJARMA Directorate General of Supplies and Disposals, New Delhi
SHRI R. K. SOMANY Hindustan Sanitaryware and lndustrics Limited, Bahadurgarh
SI~I<I SANDIP SOMANY ( AItmatc )
SHRI SUIXSH KUMAR SHARMA Central Building Research Instit utc, Roorkee
SIIKI SUR~SH KUMAR SHAR,MA ( Altermte )
SHRI S. S~JNDARAM Glass Fibre Technology Ccntre ( R and D ) CEAT Limited,
Secunderabad
SUPTDG ENGINEER ( QUALITY CONTROL ) Uttar Pradesh Jal Nigam, Lucknow
MANAGER ( MATERIALS ) ( Altar.riuf~ )
Director General, HIS ( E.x-ofliciu Mmbcr )
Srcwtar:,
SHRI S. S. SETllI
Director ( Civ Engg ). BIS
19
IS 8931 : 1993
C’rrrtl~ E&INI:ER Tamil Nadu Water Supply and Drainage Board, Madras
SHRI S. B. DANGYAc1-r All India Plastic Manufacturer’s .4ssociation, Bombay
HON QCRCTARY ( Aflernalc )
SHRI A. W. DI-SIIPAND~ National Environmental Engineering Research Institute, Nagpllr
SlIRI K. c. l)lXlT ( ffl?CVxate )
DIRECTVK Maharashtra Engixcring Research Institute, Nasik
20
Standard Mark
The use of the Standard Mark is governed by the provisions of the Br~eau Q/” Ztuliurl
Stmtlurtls Act, lY86 and the Rules and Regulations made thereunder. The Standard Mark on
products covered by an Indian Standard conveys the assurance that they have been produced
to comply with the requirements of that standard under a well defined system of inspection,
testing and quality control which is devised and supervised by RIS and operated by the
producer. Standard marked products are also continuously checked by BIS for conformity
to that standard as a further safeguard. Details of conditions under which a licence for the
use of the Standard Mark may be granted to manufacturers or producers may be obtained
from the Bureau of Indian Standards.
Bweao of Indinn Standards
BIS is a statutory institution established under the Bureau of Indian Standards Act, 1986 to
promote harmonious development of the activities of standardization, marking and quality
certification of goods and attending to connected matters in the country.
Copyright
BIS has the copyright of all its publications. No part of these publications may be reproduced
in any form without the prior permission in writing of BIS. This does not preclude the free use,
in the course of implementing the standard, of necessary details, such as symbols and sizes, type
or grade designations. Enquiries relating to copyright be addressed to the Director
( Publications ), BIS.
1
..
,-;. ..I p_ _. -
--i
,’ 2
6.3.2.1 From the physical test sample obtained in 6.3.1 one tumbler
test sample of about 100 kg shall be prepared. The rest of the sample shall
be preserved for other physical tests.
6.3.2.2 The tumbler test sample shall be dried at 105 f 5°C till free
from moisture and cooled to the room temperature and then divided
( preferably by riffle division method ) so as to obtain 2 tumbler test samples
of about 25 kg each for each sub-lot or 4 final tumbler test samples of about
25 kg each for the whole lot. The tumbler test shall be carried out in
accordance with IS : 6495-1972*.
6.3.3 Preparation of Final Crushing Test Samprd- From the reserved
sample for other physical tests obtained after preparing tumbler test
sample as in 6.3.2, a crushing test sample of abaut 5 kg shall be prepared
*Method of tumbler test for pellets, sinters and sized iron ores.
Amend No. 1, to IS 8931 : 1993
( Png~ 13, Annr \’ A) - Delete the wonf ‘IS 4694 : 1968’. ‘IS 4827 : 1983’,
‘IS 4X28 : lwu’, ‘I ; 7008 (Parts 1,2,3 and 4 ) : 1988 awl IS 7450 : 1974’ and
H&l ‘IS 1MR : lQ’0 Specification for elcrlr~~plrtcd coating of niclrcl plus
~+~romium and c0pri.r plus nirkrl plus chromium’.
1Pq,v 14,Amwr l3,clmue R-4.1(i) and (iii) 1 .-‘-.lLklcte the word ‘tap’.
1 PnRe I4,Annr~ R, cfuu.w H-U(iv) 1-..- T)clctetheword ‘lap and’.
1 Prq~ 14,Annc\ R, r/mire B&!(i) and (iii) j klek the word ‘tap’.
[ Prrqr 14, Annc~ H, c/au.se H-4.2(v), lint I 1 -- K)rlcle the word ‘tapl and’.
( I’qy 16, Annc~rc‘, &rrse C-2, line 2 ) -~~ I’Jcirle the words ‘and dynamic’
( ?‘tr~r 16, ~nrt~x C, C-4. ffadinx ) Srrh<fitute the following for IIW
c.Yl&g:
‘KmrJve the txlnnei aswmhly and cltae the txjnrrrt end and the outlet with a
plug. Apply for 60 s a sIatic water pnssure of 2.5 MPa, this pressure being
utr;1surd at the juncfion of the valve and the pipe. Thcrp should not he any
deformation or lcakrgr in the body.’