Design of Plinth Beam & Tie Beam

Spacing of columns 4 m
Height of brick in Compound wall = H= 3.05 m
Width of compound wall = 0.23 m
Wt of Brick wall above plinth beam = 1.333 T/m

Design Moment = 1.5 X 2.67 Tm


4.00 Tm
Shear 1.5 x 2.67 T
4.00 T
Factored Bending moment M = 40.0 KNm

Width of beam B= 230.0 mm


Depth of beam D= 300.0 mm
Dia of reinf. Bar 12.0 mm in 1 layers
Fck 25 N/mm2
Steel fy 500 N/mm2
depth reqd. 224.5 mm As per IS 456
depth provided 300.0 mm
cover 30.0 mm
bar dia 16.0 mm
d eff 262 mm
Ast reqd 361 mm2
Ast Provd 402 mm2 0.58% OK min reqd 0.17% as per IS 456
bar area 201.1 mm2
Nos required 1.8
Nos provided 2.0

Shear at Junction of beam with column


width of the beam 230 mm
Effective Depth of beam d= 262 mm
Net factored shear force = = 40 KN
Net Shear Stress = 40.0 /( 0.23 x 0.262 )
= 0.664 MPa
100.As/Bv.d = 40212.39 /( 230.0 x 262 )= 0.667
Design concrete shear stress = 0.614 MPa From Table 61 of SP 16 FOR IS 456.
vc = 0.614 < vu = 0.664 Shear reinf reqd.
vc max = 3.750 MPa Hence SAFE From Table 61 of SP 16 FOR IS 456.

Considerstirrups at spacing of 200 mm


Asv reqd = 57.2952 mm2
Hence Provide 2 legged 8 mm dia stirrups=> 100.531 mm2 Hence OK

Design of RCC Wall for retaining the filled earth.


Height of Earth to be retained = 0.4 m RCC wall Will be spaning between 2 Columns
Earth pressure = Ka. g.h =0.33 x 1.9 x 0.399999999999977span = 4m
= 0.25 T/sqm
Assuming the slab to be simply supported between 2 columns
the design moment = w.l.l/8 = 0.25 x4^2/8 = 0.502 Tm / m width
Design moment for RC wall = 1.5 X 0.502
= 0.752 Tm / m

Factored Bending moment M = 7.5 KNm

Width of beam B= 1000.0 mm


Depth of beam D= 230.0 mm
Dia of reinf. Bar 10.0 mm in 1 layers
Fck 25N/mm2
Steel fy 500N/mm2
depth reqd. 46.7mm As per IS 456
depth provided 230.0mm
cover 30.0mm
bar dia 10.0mm
d eff 195mm
Ast reqd 90mm2
Ast Provd 393mm2 0.17% OK min reqd 0.15% as per IS 456
bar area 78.5mm2
Nos required 1.1
Nos provided 5.0
Spacing 200 C/C Provide 10 @ 200C/C