Fathi M. Shaqour
Assistant Professor, Department of Applied Geology and the Environment,
University of Jordan, Amman, Jordan
e-mail: Shaqourf@yahoo.com, f.shaqour@ju.edu.jo
ABSTRACT
Compaction of backfill materials is normally carried out by mechanical
means, to achieve a specified percentage of compactivity. In some cases,
hydro-compaction is used for the same purpose.
INTRODUCTION
Soil compaction is a process where soil particles are packed more closely by reduction of
volume voids, resulting from the momentary application of loads such as rolling, tamping
or vibration. This process involves the expulsion of air from the voids without the
moisture content being changed significantly (Bell, 1993). It also involves the reduction
of volume leading to increase of density and shear strength of the soil (Duncan, 1990).
Effective compaction is normally achieved by compacting constituent particles of in-situ
soil or borrowed fill to a denser configuration that can reach maximum at optimum
moisture content. Well compacted materials display engineering properties that are
substantially superior to the same materials in a loose state (Watson and Burnett, 1995).
Soil compaction is common in civil engineering practice mainly in highway and rail road
works, run ways, earth dams, sanitary landfills and backfilling of excavations for
substructures and retaining walls. The quality of compacted fill is controlled by
interrelated factors such as soil type, thickness of compacted layer and the compaction
effort. Soil type including; grain size, gradation and clay or fine content, play an
important role in soil behavior under compaction. Coarse-grained soils exist in inter-
granular contact and their compaction involves particle rearrangement. The way in which
these particles are arranged within the soil mass, and the distribution of particle size
throughout, will ultimately determine the degree of compaction and hence the density,
stability and the bearing capacity of the soil. Therefore the maximum compaction can be
achieved by the best packing of well-graded soil where the fine grains fill the spaces
between the large grains. However surplus of fines can be detrimental by preventing
inter-granular contact between course particles.
Moisture content is a major controlling factor for soil compaction specially the fine-
grained soils. Increasing the water content of soil under compaction effectively increases
the workability of the soil and enables higher density to be achieved. However, further
increase of the percentage of water content beyond a certain critical value will result in
fall of density due to trap air and excess water in soil pores. This critical value of water
content, known as the optimum moisture content can be determined by the Proctor or
standard compaction test (Anon., 1976). Field tests are needed to assess the actual density
achieved by compaction on site (Parsons, 1987). The interaction between density and
moisture content of compacted soil is well documented in soil mechanic literature.
R.R.Proctor first introduced it in early 1930s, where he developed a procedure to
determine the maximum dry density and the optimum moisture content, which then
became known as Proctor Density Test, and adopted by ASTM as Test method D-698
that was then modified in ASTM D-1557 (Figure 1).
Figure 1. Typical curve for the change of dry density
with moisture content (Proctor compaction test)
Backfilled materials are commonly compacted by mechanical means using hand operated
vibratory compactors in case of small confined areas and machine driven vibratory
compactors such as smooth and paddle foot rollers, for large open areas.
Hydro-compaction is also used by flooding or jetting the granular fill material with water
in which super saturation produce degree of compaction (National Clay Pipe Institution,
1990). This method of compaction has been used for foundations with small loads.
However its use is frequently held back by many shortcomings such as; risks for adjacent
existing buildings, slow process, oversetting of the soils and possible cause of water table
rise, and insufficient compaction to the top layers (Bagasarov et al. 1992). There are
limitations and certain conditions for the success of this method such as uniformity of
sand, fines content and free draining in addition to the time factor.
The present study investigates this method of hydro-compaction and discusses the
limiting factors insight of results from field and laboratory tests carried out by flooding
sand with water. Field experiments were conducted on sand layers of 600 and 1000 mm
thickness laid in trenches of 1.0 meter width and about 30 meters length. Also laboratory
experiments on smaller samples using a 200 liters size drum have been carried out.
The maximum dry density and optimum moisture content of the material were
determined by running Standard Proctor compaction test following ASTM D698. The
average maximum dry density of three samples representing the natural sand and other
three samples representing the washed sand was found to be 2.1 MG/m3 at optimum
moisture content of 10.5%, and 1.95 MG/m3 at optimum moisture content of 10%
respectively. Figure 3 presents the dry density-soil moisture curve of the fill material for
both washed and unwashed samples.
Figure 3. Dry density vs. moisture content of the fill material (a: washed sand, b: Natural
sand)
TEST PROCEDURE
Two series of tests were carried out. The first series, involved field experiments on
natural sand used for backfilling of excavated trenches for laying pipes of sewer lines.
Two trenches with dimensions of about 30 m length, 1m width and about 1.5 m depth,
have been selected for the experiments. The first one was tested after backfilled with a
sand layer of 1m thickness, while the second was tested after backfilled with a sand layer
of 0.6 m thickness. The second series of tests involved laboratory experiments on smaller
samples of the same sand material, where 200-liter cylindrical samples (0.6 m diameter
and 1m depth) have been used. Tests were conducted on samples similar to those used for
trench tests, as well as on washed samples to discard the fines. This series of tests aimed
at investigating the efficiency of hydro-compaction under more controlled conditions as
well as to detect the role of fines content on the compactivity of natural sands.
Field Experiments
A normal practice of sewer line construction is to lay pipes at certain depth between
manholes over a granular bedding layer, which is then covered, gently by sand layers of
150 and 200 mm thickness. This is to protect the pipe from the following mechanical
compaction of the overlying successive sand layers of 200-300 mm thickness. This
process takes a long time and costly effort; however it is the commonly followed
procedure in engineering practice to achieve the required results of compaction. In some
cases, especially when excavations are located in open areas, contractors recommend to
use the procedure of compaction by watering, i.e. flooding the fill material in the trench
with water or simply hydro-compaction. They claim it is easier and can achieve the result
in less total time and effort. Generally and as per contract, it is the responsibility of the
contractor to select the method of compaction provided he achieves the required specified
degree of compaction. In the present case the contractor proposed to use hydro-
compaction for the pipe trenches being easier and faster. The debate was whether the
method is reliable and able to achieve the required compaction, with an acceptable degree
of uniformity. It was agreed with the contractor to carry out experiments on the method
of hydro-compaction before it can be approved as an acceptable procedure. Accordingly
a set of field experiments was designed by the author to test the effectiveness of such a
method using the same natural sand. Two trenches have been selected for experiments
where moist fill sand was placed to a thickness of 1000 mm in the first one and 600 mm
in the second, and then water was applied at the top of the fill sand until the trench is
flooded by water to a height of about 200 mm. Field density tests have been carried out
using the sand cone test method, after 2 duration periods of 2 and 18 hours since flooding
the trench with water, in order to test the effect of time factor (Figure 4). The density tests
were carried out at different lateral and vertical positions of the trench in order to test the
homogeneity of compaction throughout the trench. Figure 5 shows a schematic diagram
of the tested trenches indicating the position of density tests for both 2 hours and 18 hours
test series.
Laboratory experiments
In order to study the effect of the fines content on the efficiency of hydro-compaction
under more controlled conditions than in the case of field testing, laboratory experiments
were designed and executed on the same natural sand that was used in the field
experiments, however in those tests washed sand on sieve No.50 to get rid of the fines,
have been used in addition to the normal natural sand. A 200-liter drum was used for the
laboratory experiments.
Figure 4. Photographs for density testing on site, (a) near surface test, (b) deep test
Figure 5. Schematic diagram of the test trenches and the test locations
The drum was perforated from the bottom and the sides and then fixed on a gravel layer
to allow good drainage of the sand, and then wrapped with a membrane to prevent the
migration of sand particles during inundation with water (Figure 6). The drum was filled
with known weight of sand in three layers to help getting homogenous samples of density
of 1.6 MG/m3. Then water was applied to the drum and kept at a constant head of about
150 mm over the sand surface, for a period of an hour, during which draining water was
observed from the sides and bottom of the drum. The amount of settlement of the sand
surface as a result of inundation by water was recorded and therefore the consequent
change of density was calculated. Also sand cone tests were carried out at two different
depths (200 and 600 mm) from the surface of the drum both before and after inundation.
Figure 6. Photographs for drum testing, (a) during watering; (b) after watering
TEST RESULTS
Laboratory Experiments
Laboratory tests on the natural sand gave relative compaction results in the range of 88%
to 93%, which shows slightly better compaction than in the trenches. This could be
attributed to the smaller size of the samples, which allowed better circulation and
drainage of water through the sand and therefore better packing by rearrangement of the
sand particles. This further explains why the washed samples gave even better results,
where the relative compaction ranged from 90% to 95%. These results confirm the effect
of the fines content, even small percentages in the range of 5%, on the compactivity of
the sand following hydro-compaction, although they have positive influence in case of
the common practice procedures of compaction in which the fines fill the spaces between
the larger particles. It seems that such an effect is masked by the role of drainage in case
of hydro-compaction.
Figure 7. Relative compaction vs. moisture content in the test locations of the trenches
Density tests have been conducted after two soaking durations, 2 hours and 18 hours for
the trench tests and 1 hour for the laboratory tests. Test results indicate that a certain
degree of compaction up to 91.5% can be achieved by watering the sand, however not to
the required degree for a structural fill. Figure 8 shows the frequency distribution of the
test results, indicating that 3 test results were between 90% and 95% which the range of
non-structural fills, 3 results were abnormal. About 40% of the results were in the range
between 85% and 90%, which for certain conditions can be accepted for non-structural
fill material. However, it is worth mentioning that the results are very inconsistent; as the
measured relative compaction values are random both laterally and vertically (Figure 9).
The figure also indicates that the range between near-surface and deep test results vary
along the trench.
Figure 8. Frequency distribution of the field density test results
A main factor is the moisture content, which was found high, and this has prevented
successful and accurate density measurements due to potential slumping of the density
hole walls and this was evident by the abnormal results of higher than 100%. Another
problem is the random distribution of moisture content as measured both laterally and
vertically throughout the trench (Figure 10), ranging between 9.8% and 15%, with
measured high moisture contents even after drainage period of 18 hours. This is a
reflection of the water flow through the soil, which normally follow the paths relative to
soil permeability that is directly influenced by the distribution of fines within the sand
grains, though the percentage of fines is small.
The results generally indicate that the quantity of water added to the sand, the duration of
soaking and the method of water application are controlling factors in this method of
hydro-compaction, in addition to the existence of even small quantities of fines, which
could exist in concentrations within the sand layer, and therefore cause zones of low
permeability that divert the flow of water within the sand layer. This could explain the
variations in moisture contents both laterally and vertically. Variations in water quantity
and time can lead to random results as the trials have demonstrated. In some cases high
moisture contents were recorded long after watering (about 18 hours) and this indicates
that the drainage is not uniform through the trench and such non-uniformity is
responsible for the heterogeneity of the density results.
(a) Trench 1
(b) Trench 2
However, among the random distribution of test results, there are indications that the
longer drainage period, the more chance to get higher relative compaction (Figure 9),
with the tendency of the near surface tests to generally give higher relative compaction
than the deep tests of the same drainage period, which could also be related to the
possibility of better and relatively faster draining of the top part of the layer.
Laboratory tests indicate a slight improvement of compaction over the trench tests,
though not very distinctive. This could be attributed to the smaller size of the samples
allowed better circulation and drainage of water through the sand and therefore better
packing by rearrangement of the sand particles. This further explains why the washed
samples gave even better results, where the relative compaction ranged from 90% to 93%
(Table 2). These results confirm the possible effect of the fines content, even small
percentages in the range of 5%, on the compactivity of the sand following hydro-
compaction, although they have positive influence in case of the common practice
procedures of compaction in which the fines fill the spaces between the larger particles. It
seems that such an effect is masked by the role of drainage in case of hydro-compaction.
Figure 10. Distribution of moisture contents in the test trenches (a) Trench 1 and (b)
Trench 2
CONCLUSIONS
1. Measured moisture content and density values of hydro-compacted sand were random
both laterally and vertically, and no pattern was detected in the spread of results.
Therefore hydro-compaction is considered inadequate to give uniform compaction to
high relative densities of greater than 95%, that is required for structural fills.
2. The random results demonstrate beyond doubt that one positive result does not indicate
consistently good compaction. Therefore quality control is very difficult and
consequently there is great risk of settlement of the fill.
3. Hydro-compaction is more efficient on washed sand with less or no fines content that
can be better drained, however its not practical and costy to use washed sand for
backfilling.
6. The percentage of failures was high, 35% in 600 nun layers and 75% in the 800 mm
layers. Also inaccurate results were obtained from inadequate density test procedure and
high moisture content.
REFERENCES
1. Anon. (1976) Methods of Tests for Soils for Civil Engineering Purposes, BS
1377, British Standards Institution, London.
2. ASTM (1990) American Society for Testing and Materials. Standard D - 1557:
Test Method for moisture - density relations of soils and soil - aggregate mixtures
using 10 lb (40.54 kg) rammer and 18 in (457 mm) drop. Annual Book of ASTM
Standard, Vol. 04.08.
3. Bagdasarov, Yu. A, Rabinovich, I. G., Epaneshnikov, L. O. and Khanzhin N. A.
(1992) Compaction of collapsible soils by soaking with tamping during the
collapse process. Soil Mechanic and Foundation Engineering, Vol. 28 No. 4, P
159 - 164.
4. Bell, F. G (1993) Engineering treatment of soils. E & IN Spon, an imprint of
Chapman & Hall, London, PP 302.
5. BS 1377 (1975) British Standards Institution. Methods of test for soils for civil
engineering purposes. Test No. 15 (B).
6. National Clay Pipe Institution (1990) Clay Pipe Engineering Manual. Santafi
Springs, California, USA, PP 114.
7. Parsons, A. W. (1987) Shallow compaction, in Ground Engineer's Reference
Book (ed. F. G. Bell), Butterworths, London, P. 37/13 - 37/17.
8. ASTM (1990) American Society for Testing and Materials. Standard D-698: Test
Methods for Moisture - Density Relations of soils and soil aggregate mixtures
using 5.5 lb (20.4 kg) rammer and 12 in (304.8 mm) drop. Annual Book of
ASTM standards, Vol. 04.08.
9. Duncan, J. (1992) Soils and foundations for architects and engineers. Van
Nostrand Reinhold, PP 361.
10. Watson, I and Burnett, A. D. (1995) Hydrology An Environmental approach. Ft.
Lauderdale: Buchanan Books, Cambridge, PP 702
© 2004 ejge