Sunteți pe pagina 1din 73

Operation and Maintenance Manual

Bently Nevada* Asset Condition Monitoring

3500/61E and /67E Temperature Monitor


Part Number 287547-01
Rev. F (08/15)
3500/61E and /67E Temperature Monitor

© 2011- 2015 Bently Nevada, Inc.


All rights reserved.

The information contained in this document is subject to change without notice.

* Denotes a trademark of Bently Nevada, Inc., a wholly owned subsidiary of General Electric
Company.

Keyphasor, System 1

The following are trademarks of the legal entities cited:

Modbus is a registered trademark of Schneider Electric USA, Inc.

Printed in USA. Uncontrolled when transmitted electronically.

Contact Information
The following contact information is provided for those times when you cannot contact your
local representative:

1631 Bently Parkway South

Mailing Address Minden, Nevada USA  89423

USA
1.775.782.3611
Telephone
1.800.227.5514
Fax 1.775.215.2873
Internet www.GEmeasurement.com

ii
Additional Information
NOTE
This manual does not contain all the information required to operate and maintain the monitoring system. The
following is a complete list of the 3500 ENCORE manuals. Refer to these manuals for other required information.

3500 ENCORE Rack Installation Manual (part number 100M3415-01 )


3300 System Upgrade Manual (part number 287550-01)
3500/10E Power Supply Manual (part number 100M3339-01)
3500/15E Power Supply Manual (part number 287549-01)
3500/23E System Monitor Manual (part number 287545-01
3500/33E Relay 16-Channel Relay Module Manual (part number 100M3283-01)
3500/61E & 67E Temperature Monitor Manual (part number 287547-01)
3500/42E Vibration Monitor Manual (part number 287546-01)
3500/45E Position Monitor Manual (part number 288619-01)
3500/50E Tachometer Monitor Manual (part number 287548-01)
3500 Acceleration Measurement Manual (part number 287552-01)
3500 Case Expansion Measurement Manual (part number 288621-01)
3500 Complementary Input Differential Expansion Measurement Manual (part number 288623-01)

3500 Eccentricity Measurement Manual (part number 287555-01)


3500 Radial Vibration Manual (part number 287558-01)
3500 Ramp Differential Expression Measurement Manual (part number 288620-01)
3500 Shaft Absolute Measurement Manual (part number 287554-01)
3500 Thrust & Diff Expansion Measurement Manual (part number 287553-01)
3500 Valve Position Measurement Manual (part number 288622-01)
3500 Velocity Measurement Manual (part number 287551-01)

iii
3500/61E and /67E Temperature Monitor
Product Disposal Statement
Customers and third parties, who are not member states of the European Union, who are in
control of the product at the end of its life or at the end of its use, are solely responsible for the
proper disposal of the product. No person, firm, corporation, association or agency that is in
control of product shall dispose of it in a manner that is in violation of any applicable federal,
state, local or international law. Bently Nevada, Inc. is not responsible for the disposal of the
product at the end of its life or at the end of its use.

iv
Contents

1.0 Receiving and Handling Instructions 1


2.0 3500 ENCORE Compatibility Requirements 3
2.1 3500 Rack Upgrade 3
2.2 3500 ENCORE System 3
2.3 ENCORE Nomenclature 4
3.0 General Information 5
3.1 Available Data 6
3.1.1 Monitor Statuses 6
3.1.2 Channel Statuses 7
3.1.3 Static Values 12
3.2 Display Control Buttons 13
4.0 I/O Module Descriptions 15
4.1 Typical 6 Channel TC Inputs (3300) 16
4.2 Typical 6 Channel TC Inputs (ENCORE System) 17
4.3 Typical 6 Channel RTD Inputs (3300) 18
4.4 Typical 6 Channel RTD Inputs (ENCORE System) 19
4.5 Typical 2 Channel TC Inputs 19
4.6 Typical 2 Channel RTD Inputs 20
5.0 Configuration Information 23
5.1 Hardware Considerations 23
5.2 Monitor Options 23
5.2.1 Reference Information 24
5.2.2 Slot Input/Output Module Type 24
5.2.3 Monitor Relay Selection 25
5.2.4 Monitor Danger Relay Voting (3500 Rack Upgrade ) 25
5.2.5 Channel Types 26
5.2.6 Line Noise Rejection 26
5.2.7 General Parameters and Buttons 26
5.3 Temperature Channel Configuration Options 26

v
3500/61E and /67E Temperature Monitor

5.3.1 Direct Static Variable 27


5.3.2 Temperature Offset Adjustment 30
5.3.3 OK Mode 30
5.3.4 Transducer Selection 31
5.3.5 Barriers 31
5.3.6 Transducer Orientation 31
5.3.7 Delay 32
5.3.8 Alarm Mode 33
5.4 Alarm Setpoints 33
5.4.1 Available Setpoints 34
5.5 Software Switches 34
5.5.1 Monitor Switches 35
5.5.2 Channel Switches 36
6.0 Maintenance 39
6.1 Choosing a Maintenance Interval 39
6.2 Performing Firmware Upgrades 39
6.2.1 Print Extended Information 41
7.0 Verification 43
7.1 Required Test Equipment 43
7.2 Using the 3500 Rack Configuration Software 43
7.2.1 Verification Screen Setup 44
7.2.2 Verification Screen 44
7.2.3 Cold Junction Compensation (CJC) Value 45
7.3 Verifying RTD Temperature Channels 45
7.3.1 Test Equipment Setup - RTD Temperature 45
7.3.2 Test RTD Alarms 47
7.3.3 Verify RTD Channel Values 49
7.3.4 Test OK Limits 50
7.4 Verifying Thermocouple Temperature Channels 53
7.4.1 Test Equipment Setup 53

vi
7.4.2 Test Alarms 54
7.4.3 Verify TC Channel Values 56
7.4.4 Test OK Limits 58
7.5 Verify Recorder Outputs 60
7.6 If a Channel Fails a Verification Test 61
8.0 Troubleshooting 63
8.1 Alarm Event List Messages 63
8.2 Self-Test 63
8.3 System Event List Messages 64
8.3.1 Example of a System Event List Message 64
8.4 Advanced Diagnostics 65

vii
Section 1.0 Receiving and Handling Instructions

1.0 Receiving and Handling Instructions


Visually inspect the module for obvious shipping damage. If you detect shipping damage, file a
claim with the carrier and submit a copy to Bently Nevada, Inc.

WARNING
Verify the position of the PIM switch is the same on all PIMs being installed. If
the switches are not in the same position the rack may not be properly
grounded and cause a false trip.

Circuit boards contain devices that are susceptible to damage when exposed to electrostatic
charges. Damage caused by obvious mishandling of the board will void the warranty. To avoid
damage, observe the following precautions in the order given.

WARNING
Machinery protection may be lost when you remove this module from the
rack.

l Do not discharge static electricity onto the circuit board. Avoid tools or procedures that
would subject the circuit board to static damage. Some possible causes of static damage
include ungrounded soldering irons, nonconductive plastics, and similar materials.

l Use a suitable grounding strap (such as 3M Velostat® No. 2060) before handling or
performing maintenance on a printed circuit board.

l Transport and store circuit boards in electrically conductive bags or foil.

l Use extra caution during dry weather. Relative humidity less than 30% tends to multiply the
accumulation of static charges on any surface.

When performed properly, you may install this module into or remove this module from the rack
while power is applied to the rack. Refer to the Rack Installation and Maintenance Manual (part
number 129766-01) for the proper procedure.

1
3500/61E and /67E Temperature Monitor

2
Section 2.0 3500 ENCORE Compatibility Requirements

2.0 3500 ENCORE Compatibility Requirements


The following software and firmware versions listed are the minimum versions needed.

2.1 3500 Rack Upgrade


Table 2-1: Firmware and Software Versions required by the ENCORE Monitors and System
3500 Rack System 1* Conversion Utility Monitor System Monitor
Configuration Software Software Software Firmware Firmware

Upgrade Rack 4.0 6.75 1.0 5.29 or Rev C 1.96

3500/67E 4.3 SP1 6.80 1.1 5.3 or Rev D 1.96

3500/61E 4.0 6.75 1.0 5.29 1.96

3500/42E
Shaft Absolute, 4.3 SP1 6.80 1.1 5.3 or Rev D 1.97
Phase Alarming

3500/50E
4.3 SP1 6.80 1.1 5.3 or Rev D 1.96
Reverse Rotation

3500/23E
Keyphasor*
4.3 SP1 6.80 1.1 5.3 or Rev D 1.96
channels 3 & 4,
Event Ratio

3500/45E 4.4 6.80 1.1 5.36 Rev H 1.98

2.2 3500 ENCORE System


Table 2-2: Firmware and Software Versions required by the ENCORE Monitors and System
3500 Rack System 1 Conversion Utility Monitor System Monitor
Configuration Software Software Software Firmware Firmware

ENCORE Rack 4.7 6.85 1.1 6.2 2.09

3500/61E 4.7 6.85 1.1 6.2 2.09

3500/42E 4.7 6.85 1.1 6.2 2.09

3500/50E 4.7 6.85 1.1 6.2 2.09

3500/23E 4.7 6.85 1.1 2.09 2.09

3
3500/61E and /67E Temperature Monitor
3500 Rack System 1 Conversion Utility Monitor System Monitor
Configuration Software Software Software Firmware Firmware

3500/45E 4.7 6.85 1.1 6.2 2.09

3500/33E 4.7 6.85 1.1 5.0 2.09

2.3 ENCORE Nomenclature


3500 ENCORE Rack Upgrade

A 3300 Monitoring System Rack that has been upgraded to contain 3500 ENCORE modules. The
original 3300 I/O modules are retained. 3500/45E and 3500/42E monitors installed in a 3500
ENCORE Rack Upgrade are limited to two measurement channels.

3500 ENCORE System

A 3500 ENCORE Monitoring System rack designed to contain 3500 ENCORE modules including
3500 ENCORE I/O modules. 3500/45E and 3500/42E monitors installed in a 3500 ENCORE System
have four measurement channels.

4
Section 3.0 General Information

3.0 General Information


The 3500/61E and 3500/67E Temperature Monitors are designed for temperature measurement
applications. They accept input from either resistance temperature detectors (RTD) or
thermocouples (TC) and use these inputs to drive alarms. These monitors can be programmed
using the 3500 Rack Configuration Software.

3500/61E Temperature Monitor

The /61E is a 6 channel monitor. It requires a vacant slot to its right in the 3300 chassis. For
example, if you insert the /61E into slot 5 of the rack, you must leave slot 6 vacant.

Note
When using a 3300 Rack, two slots are required because the 3500/61E monitor replaces the 3300/30 and 3300/35
Temperature monitors which occupied two slots.

3500/67E Temperature Monitor

The /67E is a 2 channel monitor. It requires only one slot in the 3300 Chassis.

Note
The 3500/61E and 3500/67E monitors have similar functionality. For simplicity, this manual refers only to the
3500/61E except when the functionality differs between the two monitors.

The primary purposes of the monitors are to provide:

1. Machinery protection by continuously comparing current machine temperature against


configured alarm setpoints to drive alarms and relays, and
2. Essential machine temperature information to both operator and maintenance personnel.

Note
The /67E is not compatible with the 3500 ENCORE rack.

Alarm setpoints are configured using the 3500 Rack Configuration Software. Alarm and danger
setpoints can be configured for the active static value.

The monitors ship from the factory unconfigured. Spare monitors can be re-configured for
different applications as needed.

To configure a monitor install the monitor in a 3500 ENCORE rack and follow the instructions in
the Configuration Section.

5
3500/61E and /67E Temperature Monitor
3.1 Available Data
The Temperature Monitor returns specific static values that depend upon the type of channel
that is configured. This monitor also returns both monitor and channel statuses which are
common to all types of channels.

3.1.1 Monitor Statuses


This section describes the monitor statuses. Table "Location of Monitor Statuses" summarizes
where you can find the monitor statuses.

Table 3-1: Location of Monitor Statuses


Statuses Monitor Front Via Modbus Protocol Rack Configuration Software

Monitor Not OK X X X

Monitor Alert/Alarm 1 X X X

Monitor Danger/Alarm 2 X X X

Monitor Bypass X X

3.1.1.1 Not OK Status

This indicates whether the monitor is functioning correctly. The monitor returns a Not OK status
under any of the following conditions:

l Module Hardware Failure

l Node Voltage Failure

l Configuration Failure

l Transducer Failure

l Slot ID Failure

l Channel Not OK

If the Monitor goes to a Not OK state, the system OK Relay on the Power Input Module goes to Not
OK (de-energized).

3.1.1.2 Alert/Alarm 1 Status

This indicates whether the monitor has entered Alert/Alarm 1. A monitor will enter the Alert/Alarm
1 state when any static value provided by the monitor exceeds its configured Alert/Alarm 1

6
Section 3.0 General Information
setpoint.

3.1.1.3 Danger/Alarm 2 Status

This indicates whether the monitor has entered Danger/Alarm 2. A monitor will enter the
Danger/Alarm 2 state when any static value provided by the monitor exceeds its configured
Danger/Alarm 2 setpoint.

3.1.1.4 Bypass Status

This indicates when the monitor has bypassed alarming for 1 or more static values on a channel.
A condition that sets the channel bypass status will also set this monitor bypass status.

3.1.1.5 LED Descriptions

The LEDs on the front panel of the Monitor indicate the operating status of the module. Refer to
the channel type configuration sections in the appropriate channel type manual for all of the
available LED conditions.

OK

l Green - The monitor has not detected an error in its operation or the operation of its I/O
module.

l Flashing - Previously a fault existed but now the fault condition does not exist.

l 0ff - No power or a fatal error has occurred.

Alert (Amber) - An Alert condition exists and the Alert relay is in the alarm state.

Danger (Red - A Danger condition exists and the Danger relay is in the alarm state.1

Bypass (Red) - A channel is configured for alarming and a channel is bypassed.


13500 Rack Upgrade; If Monitor Danger Alarm AND voting is configured and the monitor has a

Dual Relay I/O Module, both channels must be in Danger mode for the relay to enter Danger.

3.1.2 Channel Statuses


This section describes the channel statuses that the monitor provides. Table "Location of Channel
Statuses" summarizes where you can find the channel statuses.

7
3500/61E and /67E Temperature Monitor
Table 3-2: Location of Channel Statuses
Statuses Monitor Front Via Modbus Protocol Rack Configuration Software

Channel OK X X X

Channel Alert/Alarm 1 X X X

Channel Danger/Alarm 2 X X X

Channel Bypass X X X

Channel Off X X X

Channel Not Monitoring X X

3.1.2.1 Monitor Display

Note
/61E Monitors with 6 channels are shown. The /67E Monitors are similar but have 2 channels.

1. Channel Number and Name


2. Value
3. Centigrade or Fahrenheit
4. Alarm Indicator yellow = Alert orange = Danger

Figure 3 - 1: Monitor Display

8
Section 3.0 General Information

Figure 3 - 2: Point Names Display


3.1.2.2 Not OK Status

A fault has been detected by the associated monitor channel.

The Monitor Not OK LED is on.

1. Color = yellow

Figure 3 - 3: Temperature Channel NOT OK status


3.1.2.3 Alert/Alarm 1 Status

This indicates whether the associated monitor channel has entered Alert/Alarm 1. A channel will
enter the Alert/Alarm 1 state when any static value provided by the channel exceeds its
configured Alert/Alarm 1 setpoint.

The Monitor Alert LED is on.

9
3500/61E and /67E Temperature Monitor

1. Color = yellow

Figure 3 - 4: Temperature Alert Display


3.1.2.4 Danger/Alarm 2 Status

This indicates whether the associated monitor channel has entered Danger/Alarm 2. A channel
will enter the Danger/Alarm 2 state when any static value provided by the channel exceeds its
configured Danger/Alarm 2 setpoint.

The Monitor Danger LED is on.

1. Color = red/orange

Figure 3 - 5: Temperature Alarm Display


3.1.2.5 Channel Alarm Bypass

This indicates that a setpoint alarm is in Bypass.

10
Section 3.0 General Information

1. Alert/Alarm Bypass (yellow)


2. Danger/Alarm Bypass (red)
3. Both Alert and Danger Alarm Bypass

Figure 3 - 6: Alarm Bypass Display


3.1.2.6 Bypass Status

This indicates that the channel is bypassed. The following conditions may cause a channel
bypass status:

l Monitor has never been configured.

l Monitor is in configuration mode.

l Monitor is in power up self-test.

l Channel has an invalid configuration.

l Fatal error found during self-test.

l Rack alarm Inhibit is enabled.

l A software switch is bypassing any channel alarming function.

The Monitor Bypass LED is on.

11
3500/61E and /67E Temperature Monitor

1. Color is blue

Figure 3 - 7: Bypass Display


3.1.2.7 Off Status

This indicates whether the channel has been turned off. You may use the 3500 Rack
Configuration Software to turn off the monitor channels.

3.1.3 Static Values


The monitor returns a temperature value for TC and RTD channels.

The monitor also returns a Cold Junction Compensation (CJC) value for TC channels.

Figure 3 - 8: CJC Display

12
Section 3.0 General Information
3.2 Display Control Buttons
The buttons allow you to move forward (down) and backward (up) through the pages of the
monitor display.

Figure 3 - 9: Control Buttons

13
3500/61E and /67E Temperature Monitor

14
Section 4.0 I/O Module Descriptions

4.0 I/O Module Descriptions


The Temperature I/O Module receives and conditions signals from either resistance temperature
detectors (RTD) or thermocouple (TC) transducers. These signals are then sent to the Temperature
Monitor for additional signal processing.

The 3500/67E Temperature Monitor uses one I/O module. The 3500/61E Temperature Monitor
requires an I/O Module and a Recorder Outputs Module in a 3500 Rack Upgrade .

Note
The field wiring of TC inputs must be placed in conduit to meet CE requirements.

15
3500/61E and /67E Temperature Monitor
4.1 Typical 6 Channel TC Inputs (3300)

1. Typical Ungrounded Thermocouple Tip


2. Typical Grounded Thermocouple Tip
3. Recorder Output Terminals
4. Alarm Relay Contacts

Figure 4 - 1: Thermocouple Input and Recorder Outputs

For more information, please refer to 3300 Six Channel Temperature Monitor 3300/30
Thermocouple & 3300/35 RTD Operation Manual (Part Number 80182-01).

16
Section 4.0 I/O Module Descriptions
4.2 Typical 6 Channel TC Inputs (ENCORE System)

Figure 4 - 2: Thermocouple Input and Recorder Outputs


1. Typical Ungrounded Thermocouple Tip
2. Typical Grounded Thermocouple Tip
3. Recorder Output Terminals

17
3500/61E and /67E Temperature Monitor
4.3 Typical 6 Channel RTD Inputs (3300)

1. 3-wire RTD
2. 4-wire RTD
3. Recorder Output Terminals

Figure 4 - 3: Signal Input Relay

For more information, refer to 3300/30 Six Channel Temperature Monitor, 3300/30 Thermocouple &
3300/35 RTD Operation Manual (Part Number 80182-01).

18
Section 4.0 I/O Module Descriptions
4.4 Typical 6 Channel RTD Inputs (ENCORE System)

1. 3-wire RTD
2. 4-wire RTD
3. Recorder Output Terminals

Figure 4 - 4: Signal Input Relay

4.5 Typical 2 Channel TC Inputs


The information in this section applies only to the 67E, which is not supported in the ENCORE
System.

19
3500/61E and /67E Temperature Monitor

1. Typical Grounded Tip Thermocouple


2. Channel A Recorder Output
3. Alarm 1 Relay Contacts
4. Typical Ungrounded Tip Thermocouple
5. Channel B Recorder Output
6. Alarm 2 Relay Contacts

Figure 4 - 5: Signal Input Relay

For more information, please refer to 3300/36 Dual Temperature Monitor (Part Number 122275-01).

4.6 Typical 2 Channel RTD Inputs


The information in this section applies only to the 67E, which is not supported in the ENCORE
System.

20
Section 4.0 I/O Module Descriptions

1. Typical 4-wire RTD


2. Channel A Recorder Output
3. Alarm 1 Relay Contacts
4. Typical 3-wire RTD
5. Channel B Recorder Output
6. Alarm 2 Relay Contacts

Figure 4 - 6: Signal Input Relay

Note
For more information, please refer to:
3300 Six Channel Temperature Monitor 3300/30 Thermocouple & 3300/35 RTD Operation Manual (Part Number
80182-01)

21
3500/61E and /67E Temperature Monitor

22
Section 5.0 Configuration Information

5.0 Configuration Information


To configure the Temperature Module, use this section to gather the configuration information
and then use the Rack Configuration software to set options and download the configuration to
the module. Refer to 3300 System Upgrade Manual (part number 287550-01) for information on
installing and running the Rack Configuration software.

5.1 Hardware Considerations


The slots in the rack are numbered, counting from left to right. Slot 0 is reserved for the power
supply. Slot 1 is reserved for the 3500/23E System module. The remaining slots are called
"monitoring positions." The 3500/61E Temperature Monitor requires two slots in a 3500 Rack
Upgrade and can be installed into any of the monitoring positions as long as there is a vacant
slot to its right. The 3500/67E Temperature Monitor requires only one slot.

5.2 Monitor Options

Figure 5 - 1: 3500/61E Configuration Screen

23
3500/61E and /67E Temperature Monitor

Figure 5 - 2: 3500/67E Configuration Screen

5.2.1 Reference Information


These fields contain information that indicates which module you are configuring.

Slot

Indicates the slot monitoring position of the monitor in the Rack.

Rack Type

Indicates the type of Rack Interface Module that is installed in the rack

Configuration ID

Displays an optional identifier of up to six characters, which, if present, was entered upon last
configuration download to the module.

5.2.2 Slot Input/Output Module Type


This field lets you identify the I/O configuration of the monitor. The option that you select must
agree with the factory settings on the monitor.

24
Section 5.0 Configuration Information
l 3500 Rack Upgrade

l Legacy 3300 I/O RTD

l Legacy 3300 I/O RTD with Internal Barriers

l Legacy 3300 I/O Isolated TC

l Legacy 3300 I/O Isolated TC with Internal Barriers

l 3500 ENCORE I/O

l 3500 ENCORE rack

l 3500 ENCORE RTD/TC temperature

5.2.3 Monitor Relay Selection


The options are:

l None/Dual

l Quad (/67E Monitor only)

Verify which option is correct by examining the I/O module located behind the monitor on the
back of the rack. For more information see the section "Input/Output Module Descriptions".

Warning
For safety critical applications where the machine must not be operated without a functioning protection system,
the relays should be setup to de-energize to trip.

Plant operation requirements need to be taken into consideration when making this decision.

5.2.4 Monitor Danger Relay Voting


(3500 Rack Upgrade )
This option allows you to add logic processing to channel alarming.

l OR - if either channel of a channel pair is in danger alarm, the danger alarm relay is
activated.

l AND - if both channels of a channel pair are in danger alarm, the danger alarm relay is
activated.

Relay Voting is available when the Dual Relay option is selected.

25
3500/61E and /67E Temperature Monitor
5.2.5 Channel Types
l Temperature

This channel type offers a simple configuration where only basic temperature
measurements are required.

5.2.6 Line Noise Rejection


This field allows selection of 50Hz or 60 Hz line noise rejection. Depending on the system power
source being used, this option should be selected to match the line frequency. If the incorrect
option is set, the line noise from the system power source may couple into the input signals.

5.2.7 General Parameters and Buttons

Note
Please refer to the 3500 Rack Configuration Software Online Help for more information on these items.

5.2.7.1 Set Defaults Button

Returns all settings on the current configuration screen and on the screens at levels below the
current screen to the default settings.

Note
Clicking on Set Defaults returns the settings on all screens at levels below the current screen to their default
settings even if the changes at lower levels were confirmed by clicking on the OK button at the lower level screen.

5.2.7.2 Point Names Button

Click this button to assign a custom name to a channel of data. Custom names allow an operator
easily to identify which machine point is being examined. Default names are displayed as
RxxSxxCxx to denote the rack, slot, and channel source of the data.

5.2.7.3 Print Form Button

Click this button to send a copy of the current configuration screen to the printer.

5.3 Temperature Channel Configuration Options


This section describes the options available on the Temperature Channel configuration screen.

26
Section 5.0 Configuration Information

Figure 5 - 3: Temperature Channel Configuration Screen

5.3.1 Direct Static Variable


The Enable field contains the units, full scale range and clamp value for the Temperature Direct
static variable.

5.3.1.1 Range Options


Table 5-1: Thermocouple Full Scale Ranges
Type of Thermocouple Full Scale Range (°C) Full Scale Range (°F) Custom Temperature Range

0 to 100
0 to 200
0 to 150
0 to 300
0 to 200
0 to 400 -18 to 760° C
Type J 0 to 250
0 to 500 (0 to 1400° F)
0 to 500
0 to 1000
0 to 750
Custom
Custom

27
3500/61E and /67E Temperature Monitor
Type of Thermocouple Full Scale Range (°C) Full Scale Range (°F) Custom Temperature Range

0 to 100 0 to 200
0 to 150 0 to 300
0 to 200 0 to 400
0 to 250 0 to 500 -18 to 1370° C
Type K
0 to 500 0 to 1000 (0 to 2498° F)
0 to 750 0 to 1500
0 to 1000 0 to 2000
Custom Custom

-100 to 100
-100 to 100
0 to 100
0 to 200
0 to 150
0 to 300
0 to 200
0 to 400 -100 to 1000° C
Type E 0 to 250
0 to 500 (-148 to 1832° F)
0 to 500
0 to 1000
0 to 750
0 to 1500
0 to 1000
Custom
Custom

-100 to 100 -100 to 100


0 to 100 0 to 200
0 to 150 0 to 300 -160 to 400° C
Type T
0 to 200 0 to 400 (-256 to 752° F)
0 to 250 0 to 500
Custom Custom

Table 5-2: RTD Full Scale Ranges


Type of RTD Full Scale Range (°C) Full Scale Range (°F) Custom Temperature Range

-200 to 200
-200 to 200
-100 to 100
-122 to 2001
-50 to 2001
-100 to100
-50 to 1001 -200 to 700° C
0 to 200
100 ohm Platinum 0 to 100 (-328 to 1292° F)
0 to 300
(0.00392) 0 to 150 -50 to 700° C1
0 to 400
0 to 200 (-122 to 1292° F)1
0 to 500
0 to 250
0 to 1000
0 to 500
Custom
Custom

28
Section 5.0 Configuration Information
Type of RTD Full Scale Range (°C) Full Scale Range (°F) Custom Temperature Range

-200 to 200
-200 to 200
-100 to 100
-122 to 2001
-50 to 2001
-100 to 100
-50 to 1001
0 to 200 -200 to 850° C
0 to 100
100 ohm Platinum 0 to 300 (-328 to 1562° F)
0 to 150
(0.00385) 0 to 400 -50 to 850° C1
0 to 200
0 to 500 (-122 to 1562° F)1
0 to 250
0 to 1000
0 to 500
0 to 1500
0 to 750
Custom
Custom

-100 to 100
-100 to 100
-50 to 1001
0 to 200 -100 to 260° C
0 to 100
0 to 300 (-148 to 500° F)
10 ohm Copper 0 to 150
0 to 400 -50 to 260° C1
0 to 200
0 to 500 (-122 to 500° F)1
0 to 250
Custom
Custom

0 to 100 0 to 200
0 to 150 0 to 300
-80 to 260° C
120 ohm Nickel 0 to 200 0 to 400
(-112 to 500° F)
0 to 250 0 to 500
Custom Custom

1 External barriers are configured.

5.3.1.2 Custom Full Scale Ranges

When you select Custom Range Options, the following items are displayed:

Minimum

Enter the lower limit.

Maximum

Enter the upper limit.

Units

Select Centigrade or Fahrenheit.

The allowed limits are in the tables above.

29
3500/61E and /67E Temperature Monitor
5.3.1.3 Clamp Value

The value sent to the Recorder Outputs and Modbus when the monitor receives invalid input.
Invalid input can be caused by:

l Channel Not OK status

l Monitor Not OK status

The clamp value is not shown in the 3500 Rack Configuration software.

5.3.2 Temperature Offset Adjustment


Press the Adjust button to enter the Adjust - Zero Temp Reference Screen.

The screen lets you make a minor offset correction to the current reading of a temperature
sensor that is installed and measuring a known reference value. It is intended to be used with a
standard ice bath test to establish a 0 degree C reference.

The data display portion of the screen lets you observe the effect of the adjustment on the Direct
static value for the channel.

The new configuration must be downloaded in order for it to take effect.

5.3.3 OK Mode
Latching

If you configure a channel for Latching OK, then once the channel has gone Not OK the status
will stay Not OK until you use one of the following methods to issue a reset:

l Pressing the reset switch on the front of the System Module

l Closing the contact on the Power Input Module (PIM)

l Issuing the reset command over Modbus

l Issuing the reset command through the 3500 Display Interface Module

l Issuing the reset command in the 3500 Rack Configuration Software

Non-latching

If you configure a channel for Non-latching OK, the OK status of that channel will track the
defined OK status of the transducer.

30
Section 5.0 Configuration Information
5.3.4 Transducer Selection
l Type J

l Type K

l Type E

l Type T

l 3 Wire 100 Ohm Platinum (0.00392) RTD

l 3 Wire 100 Ohm Platinum (0.00385) RTD

l 3 Wire 10 Ohm Copper RTD

l 3 Wire 120 Ohm Nickel RTD

l 4 Wire 100 Ohm Platinum (0.00392) RTD

l 4 Wire 100 Ohm Platinum (0.00385) RTD

l 4 Wire 10 Ohm Copper RTD

l 4 Wire 120 Ohm Nickel RTD

Note
The 3500 Rack Upgrade limits the selection based on the I/O type.

5.3.5 Barriers
Select External or Galvanic Isolator if there are external barriers connected between the monitor
and the transducer. Barriers are used to restrict the amount of energy that can flow into a
hazardous area. When selecting external barriers, the lower full-scale range value is -50° C for
some RTDs. Refer to the tables in section 5.3.1.1 for more information.

5.3.6 Transducer Orientation


The Degrees value specifies the location of the transducer on the machine. The range for
orientation angle is 0 to 180 degrees left or right as observed from the driver to the driven end of
the machine train. Refer to the figure below.

31
3500/61E and /67E Temperature Monitor

1. Shaft
2. Driver end
3. Driven end
4. 0°
5. 90° right
6. 180°
7. 90° left

Figure 5 - 4: Shaft Orientation for Horizontal Shafts

5.3.7 Delay
Delay is the time for which a static value must remain at or above an over alarm level, or below an
under alarm level, before the monitor declares an alarm as active.

5.3.7.1 Alert Delay

You can set the Alert time delay in 1 second increments (from 1 to 60 seconds) for all available
static values. Alert is the first level alarm that occurs when the transducer signal level exceeds the
selected Alert/Alarm 1 setpoint. You can set this setpoint on the Setpoint screen.

5.3.7.2 Danger Delay

You can set the Danger Time Delay at 500 millisecond increments from 1 to 60 seconds. Danger is
the second level alarm that occurs when the transducer signal level exceeds the selected
Danger/Alarm 2 setpoint. You can set this setpoint on the Setpoint screen.

5.3.7.3 810 ms Delay

It is possible to set the Danger time delay at a millisecond interval that varies from 380 to 810
milliseconds, depending on the number of active channels. The millisecond danger interval is
determined as follows:

270ms minimum time + (90ms x number of active channels)

32
Section 5.0 Configuration Information
5.3.8 Alarm Mode
The options for Alarm Mode are Latching and Non-latching. You can set the Alarm Mode option
for both the Alert and Danger alarms.

5.3.8.1 Latching

Once a latching alarm is active it will remain active even after the static value drops below the
configured setpoint level. The channel will remain in alarm until you use one of the following
methods to reset it:

l Pressing the RESET switch on the System Monitor

l Closing the contact on the Power Input Module (PIM)

l Clicking the Reset button in the Operator Display software

l Issuing the reset command over Modbus

l Issuing the reset commend in the 3500 Rack Configuration Software

5.3.8.2 Non-latching

When a non-latching alarm is active, it changes to inactive as soon as the static value drops
below the configured setpoint level.

5.4 Alarm Setpoints


This section specifies the available setpoints for the Temperature channel. A setpoint is the level
within the full-scale range that determines when an alarm occurs.

The 3500 ENCORE Monitoring System allows two Alert/Alarm 1 setpoints (one over setpoint and
one under setpoint) to be set on each Temperature static value. The channel will drive an
Alert/Alarm 1 indication if the channel's static value exceeds its setpoints.

The 3500 ENCORE Monitoring System also allows two Danger/Alarm 2 setpoints (one over
setpoint and one under setpoint) to be set for each Temperature channel. The channel will drive a
Danger/Alarm 2 indication if the channel's static value exceeds its setpoints.

Note
You can place the setpoint over and under limits only within the OK limits of the specified transducer.

Use the following screen in the Rack Configuration Software to adjust Alert/Alarm 1 and
Danger/Alarm 2 setpoints.

33
3500/61E and /67E Temperature Monitor

Figure 5 - 5: Setpoint Configuration Screen

5.4.1 Available Setpoints


The table below lists the Alert/Alarm 1 and Danger/Alarm 2 setpoints that are available for the
Temperature channel. Modbus uses the setpoint number.

Setpoint Number Temperature Setpoint

1 Over Alert/Alarm 1

2 Under Alert/Alarm 1

3 Over Danger/Alarm 2

4 Under Danger/Alarm 2

5.5 Software Switches


The Temperature Monitor supports 2 module software switches and 3 channel software
switches. These switches let you temporarily bypass or inhibit monitor and channel functions. Set
these switches on the Software Switches screen under the Utilities Option on the main screen of
the 3500 Rack Configuration Software.

34
Section 5.0 Configuration Information
No changes will take effect until you press the Set button.

5.5.1 Monitor Switches

Figure 5 - 6: Module Switches Dialog

Configuration Mode

This switch allows you to configure the monitor. To configure the monitor, enable this switch and
set the key switch on the front of the System Monitor in the PROGRAM position. When the 3500
Rack Configuration Software downloads a configuration, it will automatically enable and disable
this switch. If the software loses its connection to the rack during the configuration process, use
this switch to remove the module from Configuration Mode.

Monitor Alarm Bypass

When you enable this switch the monitor does not perform alarming functions but will still
provide all static values.

35
3500/61E and /67E Temperature Monitor
5.5.2 Channel Switches

Figure 5 - 7: Channel Switch Dialog


Alert Bypass

When you enable this switch, all alert alarms are disabled. A Bypass status is indicated and the
module Bypass LED is illuminated.

Danger Bypass

When you enable this switch, all danger alarms are disabled. A Bypass status is indicated and the
module Bypass LED is illuminated.

Channel Bypass

When you enable this switch, the channel is disabled. A Bypass status is indicated and the
module Bypass LED is illuminated. Use this option to disable the channel temporarily.

Note
The cold junction temperature is always displayed for the Temperature 2 channels on the Verification Screen.

36
Section 5.0 Configuration Information
The channel switch number is used in Modbus communication.

Table 5-3: Channel Switches


Channel Switch Number Switch Name

1 Alert Bypass

2 Danger Bypass

4 Bypass

37
3500/61E and /67E Temperature Monitor

38
Section 6.0 Maintenance

6.0 Maintenance
The boards and components inside the modules cannot be repaired in the field. Rack
maintenance consists of testing module channels to verify that they are operating correctly. You
should use a spare to replace modules that are not operating correctly.

The 42E monitor can be hot-swapped but its supporting I/Os cannot. Refer to the following
manuals for the proper procedure:

3300 System Upgrade Manual (part number 287550-01)

3500 ENCORE Rack Installation Manual (part number 100M3415-01 ).

6.1 Choosing a Maintenance Interval


Use the following approach to choose a maintenance interval:

1. Start with an interval of one year and then shorten the interval if either of the following
conditions apply:

l The monitored machine is classified as critical.

l The rack operates in a harsh environment, such as in extreme temperature, high


humidity, or a corrosive atmosphere.

2. At each interval, use the results of the previous verifications and ISO Procedure 10012-1 to
adjust the interval.

6.2 Performing Firmware Upgrades


The following instructions describe how to use the 3500 Rack Configuration Software to upgrade
a monitor's existing firmware. You must use the 3500 Rack Configuration Software to reconfigure
the monitor after upgrading its firmware.

Alert
During the following procedure you must not interrupt power to the rack or remove the monitor you are upgrading
from the rack. If either of these occurs the monitor may become inoperable.

39
3500/61E and /67E Temperature Monitor
1. Start the 3500 Rack Configuration Software and connect to the rack.

2. Upload and save the current configuration of the monitor, as the upgrade process will
erase all configuration information in the monitor.

3. Under the Utilities menu option, select Update Firmware.

Figure 6 - 1: Update Firmware Screen

4. Select the module that you wish to update and click on the OK button.

5. The software will request you to select the file that you wish to download. Select the file and
click on the Open button. The software will now download the file.

6. After the download completes, reload the configuration to the monitor. If the process fails
then the monitor will revert to its old code. Under no circumstances should you remove the
monitor until the update process finishes.

Warning

Firmware upgrade 2.04 cannot be used to upgrade version 1.20.

Note
A 3500/91 EGD Communication Gateway module with version 1.20 or lower firmware has a 2 Mbyte flash.

40
Section 6.0 Maintenance

Note
A 3500/91 Multi-Protocol Gateway module with version 2.04 or greater firmware has a 4 Mbyte flash.

6.2.1 Print Extended Information


Click this button to display extended information about a selected module(s):

l The module type, firmware version, and the slot it occupies in the rack
l Monitor Serial Number
l PWA Part Number and Revision
l PWA Modification Part Number and Revision (if any)
l Firmware Part Number and Revision
l I/O Serial Number
l I/O Part Number and Revision
l I/O Modification Part Number and Revision (if any)

The information can be printed from within the text editor.

Note
The software checks the monitor serial number for validity. If considered invalid, the software substitutes the word
"unknown" for the normal hardware part number and revision number. You must make a physical inspection of the
board to determine those attributes.

41
3500/61E and /67E Temperature Monitor

42
Section 7.0 Verification

7.0 Verification
7.1 Required Test Equipment
The verification procedures in this section require the following test equipment.

RTD list

l Decade resistance (with an accuracy of 0.01 Ohm)

Thermocouple list

l Precision millivolt source

l Multimeter (with an accuracy of 0.001 mV)

l A temperature meter with sensor (with an accuracy of 0.1°C)

7.2 Using the 3500 Rack Configuration Software


The laptop computer that is part of the test setup uses the 3500 Rack Configuration Software to
display output from the rack and to reset certain operating parameters in the rack. To perform
the test procedures in this section you must be familiar with the following operations of the 3500
Rack Configuration Software:

l Uploading, downloading, and saving configuration files

l Enabling and disabling channels and alarms

l Bypassing channels and alarms

l Displaying the Verification screen

The 3500 Rack Configuration and Utilities Guide (part number 129777-01) explains how to perform
these operations.

Note
It is important to save the original rack configuration before doing any maintenance or troubleshooting procedures.
It may be necessary during these procedures to change some of the configuration settings which must be restored
to their original values at the conclusion of the procedures. At that time the original configuration should be
downloaded to the rack.

43
3500/61E and /67E Temperature Monitor
7.2.1 Verification Screen Setup
1. Run the 3500 Rack Configuration Software on the test computer.

2. Choose Verification from the Utilities menu.

3. Choose the proper Slot number and Channel number.

4. Click the Verify button.

7.2.2 Verification Screen


Figure "Verification Screen" shows how the Verification screen displays output from a 3500
ENCORE rack:

Figure 7 - 1: Verification Screen

Any channel bar graph value that enters Alert/Alarm 1 or Danger/Alarm 2 will cause the alarm
lines in the Channel Status box to indicate an alarm. Any channel that enters alarm will cause the
alarm lines in the Module Status box to indicate an alarm.

The bar graph display uses specific lines to indicate the following Setpoints:

44
Section 7.0 Verification
l Danger/Alarm 2 Over = Solid red line

l Alert/Alarm 1 Over = Solid yellow line

l Alert/Alarm 1 Under = Dashed yellow line

l Danger/Alarm 2 Under = Dashed red line

7.2.3 Cold Junction Compensation (CJC) Value


The cold junction temperataure is always displayed for the Temperature 2 channels on the
Verification Screen.

Alarm setpoints are not available on this static value.

7.3 Verifying RTD Temperature Channels


The following sections describe how to test alarms, verify channels, and test OK limits for
channels configured as RTD Temperature. The output values and alarm setpoints are verified by
varying the input temperature signal level and observing that the correct results are reported in
the Verification screen on the test computer.

7.3.1 Test Equipment Setup - RTD Temperature


The following test equipment setup can be used as the initial setup needed for all the verification
procedures (test alarms, verify channel static values, verify OK status, and test OK limits).

Caution
High voltage present. Contact could cause shock, burns or death.

Alert
Tests will exceed alarm setpoint levels causing alarms to activate. This could result in a relay contact state change.

Disconnecting the field wiring will cause a Not OK condition.

The monitor supports two RTD configurations, 3-Wire and 4-Wire. To simulate a RTD signal
connect the decade resistor to channel 1 as shown in the following figure.

45
3500/61E and /67E Temperature Monitor

1. Decade Resistor

Figure 7 - 2: RTD Temperature Setup

46
Section 7.0 Verification

1. Decade Resistor

Figure 7 - 3: ENCORE System RTD Temperature Setup

The Test Equipment outputs should be floating relative to earth ground. For external termination
I/O modules, the test setup is identical except that the test equipment outputs connect to the
external termination block. Make the lead length between the decade resistor and the I/O module
as short as possible.

7.3.2 Test RTD Alarms


Simulate the temperature signal with a decade resistor. Test the alarm levels by varying the
output from the test equipment and observing the results in the Verification screen on the test
computer. It is only necessary to test those alarm parameters that are configured and being
used. To test alarms adjust the test signal to:

47
3500/61E and /67E Temperature Monitor
1. Exceed the over Alert/Alarm 1 and Danger/Alarm 2 Setpoints

2. Drop below any under Alert/Alarm 1 and Danger/Alarm 2 Setpoints

3. Produce a non-alarm condition.

When varying the signal from an alarm condition to a non-alarm condition, alarm hysteresis
must be considered. Adjust the signal well within the alarm setpoint for the alarm to clear.

1. Disconnect all field wiring from the channel terminals on the Temperature I/O Module.

2. Connect the test equipment and run the software as described in the section, "Test
Equipment and Software Setup."

3. Adjust the decade resistor to produce a reading that is within the setpoint levels on the bar
graph display of the Verification screen.

4. Press the RESET switch on the System Monitor. Verify that the OK LED is on, the color of the
bar graph indicator is green, and the Current Value field contains no alarm indication.

5. Adjust the voltage/current source such that the signal just exceeds the Over Alert/Alarm 1
setpoint level. Wait for 2 or 3 seconds after the alarm time delay expires and verify that the
bar graph indicator changes color from green to yellow and that the Current Value Field
indicates an Alarm.

6. Press the RESET switch. Verify that the color of the bar graph indicator remains yellow and
that the Current Value Field still indicates an alarm.

7. Adjust the voltage/current source such that the signal just exceeds the Over Danger/Alarm
2 setpoint level. Wait for 2 or 3 seconds after the alarm time delay expires and verify that the
bar graph indicator changes color from yellow to red and that the Current Value Field
indicates an Alarm.

8. Press the RESET switch. Verify that the color of the bar graph indicator remains red and that
the Current Value Field still indicates an alarm.

9. Adjust the voltage/current source such that the signal reads within the Alarm setpoint
levels. If the nonlatching option is configured, observe that the bar graph indicator
changes color to green and that the Current Value Field contains no indication of alarms.
Press the RESET switch to reset latching alarms.

48
Section 7.0 Verification
10. Adjust the voltage/current source such that the signal just exceeds the Under Alert/Alarm 1
setpoint level. Wait for 2 or 3 seconds after the alarm time delay expires and verify that the
bar graph indicator changes color from green to yellow and that the Current Value Field
indicates an Alarm.

11. Press the RESET switch. Verify that the color of the bar graph indicator remains yellow and
that the Current Value Field still indicates an alarm.

12. Adjust the voltage/current source such that the signal just exceeds the Under
Danger/Alarm 2 setpoint level. Wait for 2 or 3 seconds after the alarm time delay expires
and verify that the bar graph indicator changes color from yellow to red and that the
Current Value Field indicates an Alarm.

13. Press the RESET switch. Verify that the color of the bar graph indicator remains red and that
the Current Value Field still indicates an alarm.

14. Adjust the current/voltage source such that the signal reads within the Alarm setpoint
levels. If the nonlatching option is configured, observe that the bar graph indicator
changes color to green and that the Current Value Field contains no indication of alarms.
Press the RESET switch on the Rack Interface Module (RIM) to reset latching alarms.

15. If you cannot verify any configured alarm, check the configured setpoints again. If the
monitor still does not alarm properly or fails any other part of this test, you must replace the
monitor. Refer to "If a Channel Fails a Verification Test" in your monitor hardware manual.

16. Disconnect the test equipment and reconnect the field wiring to the channel terminals on
the Temperature I/O Module. Verify that the OK LED comes on. Press the RESET switch to
reset the OK LED.

17. Repeat steps 1 through 16 for all configured channels.

7.3.3 Verify RTD Channel Values


Simulate the Temperature input signal with a voltage/current source. To verify the channel
values, vary the output from the test equipment and observe that the correct results are reported
in the Verification screen on the test computer.
Note
See the "3500/61E & 3500/67E Temperature Monitor" Specification (part number 287825-01) for the rated accuracy
for each transducer type.

49
3500/61E and /67E Temperature Monitor
1. Disconnect all field wiring from the channel terminals on the Temperature I/O Module.

2. Connect the test equipment and run the software as described in the section, "Test
Equipment and Software Setup."

3. Select a minimum of three verification resistance values that are within the selected full-
scale range and that correspond to the NIST standard value, such as the tables in the
MINCO's Bulletin TS-102 (G), "Temperature Sensors & Transmitters".

4. Adjust the decade resistor to the first verification value that was selected from the tables.

5. Verify that the bar graph display and the Current Value Box is the specified accuracy for
that type of RTD of the verification values shown in the tables. If the recorder output is
configured, refer to Section "Verify Recorder Outputs" for the steps to verify the recorder
output.

6. Repeat the procedure in step 4 and 5 until all of the verification points have been tested.

7. If the readings do not meet specifications, verify that the input signal is correct. If the
monitor still does not meet specifications or fails any other part of this test, you must
replace the monitor. See the section "If a Channel Fails a Verification Test" in your hardware
manual.

8. Disconnect the test equipment and reconnect the field wiring to the channel terminals on
the Temperature I/O Module. Verify that the OK LED comes on. Press the RESET switch to
reset the OK LED.

9. Repeat steps 1 through 8 for all configured channels.

Example:

Some values for Platinum (a=0.00392) have the following resistance values:

Verification value 1: T1= 0° C Resistance = 100.0 W

Verification value 2: T1= 90° C Resistance = 135.3 W

Verification value 3: T1= 150° C Resistance = 158.3 W

7.3.4 Test OK Limits

Note
All other channels in the rack must be OK or Bypassed for the OK relay to be energized.

50
Section 7.0 Verification
To test OK limits, input a simulated RTD signal (resistance value) and adjust it above the Upper OK
limit and below the Lower OK limit. This resistance value will cause a not OK condition and the OK
Relay to change state (de-energize). The Upper and Lower OK limits are displayed in the
Verification screen on the test computer.

1. Disconnect all field wiring from the channel terminals on the Temperature I/O Module.

2. Connect the test equipment and run the software as described in the section, "Test
Equipment Setup."

3. Bypass all other configured channels.

4. Adjust the decade box to a value in the middle of the OK Limits listed in "RTD Transducer OK
Limits".

5. Press the RESET switch. Verify that the monitor OK LED is on and that the Channel OK State
line in the Channel Status section of the Verification screen reads OK.

6. Verify that the OK relay on the System Monitor indicates OK (is energized). (See the
appropriate System Monitor manual for more information.)

7. Increase the decade resistor (large value) until the OK LED just goes off (upper limit). Verify
that the Channel OK State line in the Channel Status section reads not OK and that the OK
Relay indicates not OK.

Verify that the Channel OK State line in the Channel Status section reads not OK and that
the OK Relay indicates not OK.

Verify that the Upper OK limit displayed on the Verification screen is equal to or less positive
than the input signal.

8. Adjust the decade resistor to some value in the middle of the OK limits as listed in Table "RTD
Transducer OK Limits".

9. Press the RESET switch. Verify that the OK LED comes back on and that the OK relay
energizes. Verify that the Channel OK State line in the Channel Status section reads OK.

51
3500/61E and /67E Temperature Monitor
10. Gradually decrease the decade resistor (small value) until the OK LED just goes off (lower
limit).

Verify that the Channel OK State line in the Channel Status section reads not OK and that
the OK Relay indicates not OK.

Verify that the Lower OK limit displayed on the Verification screen is equal to or less
negative than the input voltage.

11. Adjust the decade resistor to some value in the middle of the OK limits as listed in Table "RTD
Transducer OK Limits".

12. Press the RESET switch. Verify that the OK LED comes back on and that the OK relay
energizes. Verify that the Channel OK State line in the Channel Status section reads OK.

13. Disconnect the test equipment and reconnect the field wiring to the channel terminals on
the Temperature I/O Module. Verify that the OK LED comes on and that the OK relay
energizes. Press the RESET switch to reset the OK LED.

14. If you cannot verify any configured OK limit, you must replace the monitor. Refer to "If a
Channel Fails a Verification Test" in your monitor hardware manual.

15. Repeat steps 1 through 14 for all configured channels.

16. Return the bypass switches for all configured channels back to their original settings.

Table 7-1: RTD Transducer OK Limits


Lower OK Limit Lower OK Limit Upper OK Limit Upper OK Limit
RTD Type
(Ohms) (Degrees) (Ohms) (Degrees)

Pt (a=0.00392) 17.00 -200° C 350.17 +700° C

Pt (a=0.00392)-
79.961 -50° C 350.17 +700° C
1

Pt (a=0.00385) 18.40 -200° C 390.38 +850° C

Pt (a=0.00385)-
80.311 -50° C 390.38 +850° C
1

Ni (a=0.00672) 66.60 -80° C 380.31 +260° C

Ni (a=0.00672)-
86.161 -50° C 380.31 +260° C
1

52
Section 7.0 Verification
Lower OK Limit Lower OK Limit Upper OK Limit Upper OK Limit
RTD Type
(Ohms) (Degrees) (Ohms) (Degrees)

Cu (a=0.00427) 5.13 -100° C 19.12 +260° C

Cu (a=0.00427)-
7.1041 -50° C 19.12 +260° C
1

7.4 Verifying Thermocouple Temperature Channels


The following sections describe how to test alarms, verify channels, and test OK limits for
channels configured as Thermocouple Temperature. The output values and alarm setpoints are
verified by varying the input temperature signal level and observing that the correct results are
reported in the Verification screen on the test computer.

7.4.1 Test Equipment Setup


Use the following test equipment setup for all the verification procedures (Test Alarms, Verify
Channels, and Test OK Limits).

Warning
High voltage present. Contact could cause shock, burns or death. Do not touch exposed wires or terminals.

Alert
Tests will exceed alarm setpoint levels causing alarms to activate. This may result in a relay contact state change.

Disconnecting the field wiring will cause a Not OK condition.

Simulate the transducer signal by connecting the precision millivolt source to the input terminal
for channel 1 with polarity as shown in the following figure.

53
3500/61E and /67E Temperature Monitor

1. Precision millivolt source


2. Multimeter

Figure 7 - 4: Thermocouple Equipment Setup

The Test Equipment outputs should be floating relative to earth ground. For external termination
I/O modules, the test setup is identical except that the test equipment outputs connect to the
external termination block.

7.4.2 Test Alarms


Simulate the temperature signal with a precision millivolt source. To test the alarm levels vary the
output from the precision millivolt source and observe the Verification screen on the test
computer. It is only necessary to test those alarm parameters that are configured and being
used. Adjust the test signal to:

1. Exceed the over Alert/Alarm 1 and Danger/Alarm 2 Setpoints

2. Drop below any under Alert/Alarm 1 and Danger/Alarm 2 Setpoints

3. Produce a non-alarm condition.

When varying the signal from an alarm condition to a non-alarm condition, alarm hysteresis
must be considered. Adjust the signal well within the alarm setpoint for the alarm to clear.

54
Section 7.0 Verification
1. Disconnect all field wiring from the channel terminals on the Temperature I/O Module.

2. Connect the test equipment and run the software as described in the section, "Test
Equipment Setup."

3. Adjust the precision millivolt source to produce a reading that is within the setpoint levels
on the bar graph display of the Verification screen.

4. Press the RESET switch on the System Monitor. Verify that the OK LED is on, the color of the
bar graph indicator is green, and the Current Value field contains no alarm indication.

5. Adjust the precision millivolt source such that the signal just exceeds the Over Alert/Alarm 1
setpoint level. Wait for 2 or 3 seconds after the alarm time delay expires and verify that the
bar graph indicator changes color from green to yellow and that the Current Value Field
indicates an Alarm.

6. Press the RESET switch. Verify that the color of the bar graph indicator remains yellow and
that the Current Value Field still indicates an alarm.

7. Adjust the precision millivolt source such that the signal just exceeds the Over
Danger/Alarm 2 setpoint level. Wait for 2 or 3 seconds after the alarm time delay expires
and verify that the bar graph indicator changes color from yellow to red and that the
Current Value Field indicates an Alarm.

8. Press the RESET switch. Verify that the color of the bar graph indicator remains red and that
the Current Value Field still indicates an alarm.

9. Adjust the precision millivolt source such that the signal reads within the Alarm setpoint
levels. If the nonlatching option is configured, observe that the bar graph indicator
changes color to green and that the Current Value Field contains no indication of alarms.
Press the RESET switch to reset latching alarms.

10. Adjust the precision millivolt source such that the signal just exceeds the Under Alert/Alarm
1 setpoint level. Wait for 2 or 3 seconds after the alarm time delay expires and verify that the
bar graph indicator changes color from green to yellow and that the Current Value Field
indicates an Alarm.

11. Press the RESET switch. Verify that the color of the bar graph indicator remains yellow and
that the Current Value Field still indicates an alarm.

55
3500/61E and /67E Temperature Monitor
12. Adjust the precision millivolt source such that the signal just exceeds the Under
Danger/Alarm 2 setpoint level. Wait for 2 or 3 seconds after the alarm time delay expires
and verify that the bar graph indicator changes color from yellow to red and that the
Current Value Field indicates an Alarm.

13. Press the RESET switch. Verify that the color of the bar graph indicator remains red and that
the Current Value Field still indicates an alarm.

14. Adjust the precision millivolt source such that the signal reads within the Alarm setpoint
levels. If the nonlatching option is configured, observe that the bar graph indicator
changes color to green and that the Current Value Field contains no indication of alarms.
Press the RESET switch on the Rack Interface Module (RIM) to reset latching alarms.

15. If you cannot verify any configured alarm, check the configured setpoints again. If the
monitor still does not alarm properly or fails any other part of this test, you must replace the
monitor. Refer to "If a Channel Fails a Verification Test" in your monitor hardware manual.

16. Disconnect the test equipment and reconnect the field wiring to the channel terminals on
the Temperature I/O Module. Verify that the OK LED comes on. Press the RESET switch to
reset the OK LED.

17. Repeat steps 1 through 16 for all configured channels.

7.4.3 Verify TC Channel Values


Simulate the Temperature signal with a precision millivolt source. To verify channel values vary
the output from the test equipment and observe the Verification screen on the test computer.

Note
These parameters have an accuracy specification that is dependent on the physical configuration of the system.

1. Disconnect all field wiring from the channel terminals on the Temperature I/O Module.

2. Connect the test equipment and run the software as described in the section, "Test
Equipment and Software Setup."

3. On the Verification screen, record the current value of the CJC bar graph. This value is the
CJC temperature at the input terminal of the monitor at the start of the test.

56
Section 7.0 Verification
4. Select a minimum of three verification voltage values (Vtable) that are within the selected
full-scale range and that corresponds to the NIST standard value, such as the tables in
Omega's "The Temperature Handbook Vol. 28" .

5. Using a Thermocouple Table, convert the CJC temperature value recorded above to the
CJC voltage. (Vcjc).

6. Adjust the value for the verification value listed in the Thermocouple Table to the voltage
that is applied in the test configuration (Vtest).

7. Adjust the precision millivolt source to the first verification value that has been adjusted
(Vtest). Adjust the verification value using Equation "Verification Temperature Value" below.
Record the current value of the Direct Value bar graph.

8. Verify that the bar graph display and the current value are within ±0.5° C (±0.9° F) of the
expected value. If the recorder output is configured, refer to Section - Verify Recorder
Outputs for the steps to verify the recorder output.

9. Repeat the steps 6 and 7 for the remaining verification values.

10. Record the value of the CJC bar graph. This value is the CJC temperature at the input
terminal of the monitor at the end of the test. This temperature and the temperature
recorded in step 3 cannot vary by more the 1° C (1.8° F). If it does vary, repeat steps 3
through 9.

11. If the readings do not meet specifications, verify that the input signal is correct. If the
monitor still does not meet specifications or fails any other part of this test, you must
replace the monitor. See the section "If a Channel Fails a Verification Test" in your hardware
manual.

12. Disconnect the test equipment and reconnect the field wiring to the channel terminals on
the Temperature I/O Module. Verify that the OK LED comes on. Press the RESET switch to
reset the OK LED.

13. Repeat steps 1 through 14 for all configured channels.

Equation: Verification Temperature Value

Vtest = Vtable -Vcjc

Example 1:

Some values for Type-J have the following resistance values:

57
3500/61E and /67E Temperature Monitor
Verification value 1: T1= 0° C Voltage = 0.000 mV

Verification value 2: T1= 90° C Voltage = 4.725 mV

Verification value 3: T1= 150° C Voltage = 8.008 mV

Example 2:

Assume that the CJC temperature measured in step 3 is 29 °C, the monitor is configured for the
type-J TC, and the desired test verification value is 100 °C.

For the CJC temperature of 29 °C the Thermocouple Table indicates this corresponds to a CJC
voltage (Vcjc) of 1.484 mV.

From the same table, the test temperature of 100° C corresponds to a voltage (Vtable) of 5.268 mV.

Adjusted Verification Input Voltage Value is: Vtest = 5.268 mV - 1.484 mV

Vtest = 3.784 mV

7.4.4 Test OK Limits

Note
All other channels in the rack must be OK or Bypassed for the OK relay to be energized.

To test OK limits input a precision millivolt DC voltage and adjust it above the Upper OK limit and
below the Lower OK limit. This voltage will cause a not OK condition and the OK Relay to change
state (de-energize). The Upper and Lower OK limits are displayed in the Verification screen on the
test computer.

1. Disconnect all field wiring from the channel terminals on the Temperature I/O Module.

2. Connect the test equipment and run the software as described in the section, "Test
Equipment and Software Setup."

3. Bypass all other configured channels.

4. Adjust the precision millivolt source to some value in the middle of the OK limits as listed in
the Table "Thermocouple Transducer OK Limit".

5. Press the RESET switch. Verify that the monitor OK LED is on and that the Channel OK State
line in the Channel Status section of the Verification screen reads OK.

58
Section 7.0 Verification
6. Verify that the OK relay on the System Monitor indicates OK (is energized). (See the
appropriate System Monitor manual for more information.)

7. Increase the precision millivolt source (more positive) until the OK LED just goes off (upper
limit).

Verify the contents of the library item

Verify that the Upper OK limit voltage displayed on the Verification screen is equal to or less
positive than the input voltage.

8. Adjust the precision millivolt source to some value in the middle of the OK limits as listed in
the Table "Thermocouple Transducer OK Limit".

9. Press the RESET switch. Verify that the OK LED comes back on and that the OK relay
energizes. Verify that the Channel OK State line in the Channel Status section reads OK.

10. Gradually decrease the precision millivolt source (more negative) until the OK LED just goes
off (lower limit).

Contents of the library item

Verify that the Lower OK limit voltage displayed on the Verification screen is equal to or less
negative than the input voltage.

11. Adjust the precision millivolt source to some value in the middle of the OK limits as listed in
the Table "Thermocouple Transducer OK Limit".

12. Press the RESET switch. Verify that the OK LED comes back on and that the OK relay
energizes. Verify that the Channel OK State line in the Channel Status section reads OK.

13. Disconnect the test equipment and reconnect all field wiring to the channel terminals on
the Temperature I/O Module. Verify that the OK LED comes on and that the OK relay
energizes. Press the RESET switch on the Rack Interface Module (RIM) to reset the OK LED.

14. If you cannot verify any configured OK limit, you must replace the monitor. Refer to "If a
Channel Fails a Verification Test" in your monitor hardware manual.

15. Repeat steps 1 through 14 for all configured channels.

16. Return the bypass switches for all configured channels back to their original settings.

59
3500/61E and /67E Temperature Monitor
Table 7-2: Thermocouple Transducer OK Limit
Lower OK Limit Lower OK Limit Upper OK Limit Upper OK Limit
Thermocouple
(millivolts) (Degrees) (millivolts) (Degrees)

Type-J -0.896 -18° C 42.922 +760° C

Type-K -0.701 -18° C 54.807 +1370° C

Type-E -5.237 -100° C 76.358 +1000° C

Type-T -4.865 -160° C 20.869 +400° C

7.5 Verify Recorder Outputs


Recorder outputs for the 3500/61E Temperature Monitor Module are 4 to 20 mA.

1. Disconnect all field wiring from the channel terminals on the Temperature I/O Module.

2. Connect a multimeter to the COM and REC channel terminals of the I/O module. The
multimeter should be able to measure 4 mA to 20 mA.

3. Set the static value for which the recorder is configured to full-scale (refer to the static value
of the channel type you are testing). Verify that the recorder output is reading 20 mA ± 1%.

4. Set the static value for which the recorder is configured to mid-scale (refer to the static
value of the channel type you are testing). Verify that the recorder output is reading 12 mA ±
1%.

5. Set the static value for which the recorder is configured to bottom-scale (refer to the static
value of the channel type you are testing). Verify that the recorder output is reading 4 mA ±
1%.

6. Set the static value so that the recorder is outside its full-scale range. Verify that the
recorder output is reading at the clamped value, as set in the software, ±1%.

7. If you cannot verify the recorder output, you should check the recorder configuration and
connections. If the monitor recorder output still does not verify properly, you will need to
replace the monitor. Go to Section "If a Channel Fails a Verification Test."

8. Disconnect the test equipment and reconnect the field wiring to the channel terminals on
the Temperature I/O Module. Verify that the OK LED comes on. Press the RESET switch to
reset the OK LED.

9. Repeat steps 1 through 8 for all configured recorder channels.

60
Section 7.0 Verification
7.6 If a Channel Fails a Verification Test
When handling or replacing circuit boards, always be sure to adequately guard against damage
from Electrostatic Discharge (ESD). Always wear a proper wrist strap and work on a grounded
conductive work surface.

1. Use the 3500 Rack Configuration Software to save the configuration for the module.

2. Replace the module with a spare. Refer to the installation section in the following
documents:

3500 Monitoring System Installation and Maintenance Manual (part number 129766-01)
3300 System Upgrade Manual (part number 287550-01)
3500 ENCORE Rack Installation Manual (part number 100M3415-01)

3. Return the faulty board to Bently Nevada, Inc. for repair.

4. Use the 3500 Rack Configuration Software to download the configuration for the spare
module.

5. Verify the operation of the spare.

61
3500/61E and /67E Temperature Monitor

62
Section 8.0 Troubleshooting

8.0 Troubleshooting
This section describes how to use the information provided by the self-test, the LEDs, the System
Event List, and the Alarm Event List to troubleshoot a problem.

8.1 Alarm Event List Messages


Table "Alarm Event List Messages" summarizes the Alarm Event List Messages that the module
returns.

Table 8-1: Alarm Event List Messages


Alarm Even List Message When the Message will occur

A static value in the channel has entered Alert / Alarm 1 and changed the
Entered Alert/ Alarm 1
channel Alert / Alarm 1 status

A static value in the channel has left Alert / Alarm 1 and changed the
Left Alert/ Alarm 1
channel Alert / Alarm 1 status

A static value in the channel has entered Danger / Alarm 2 and changed
Entered Danger/ Alarm 2
the channel Danger / Alarm 2 status

A static value in the channel has entered Danger / Alarm 2 and changed
Left Danger/ Alarm 2
the channel Danger / Alarm 2 status

Entered Not OK Module went Not OK

Left Not OK Module returned to the OK state

8.2 Self-Test
To perform the monitor self-test:

1. Connect a computer running the 3500 Rack Configuration Software to the 3500 rack (if
required).

2. Select Utilities from the main screen of the 3500 Rack Configuration Software.

3. Select System Events/Module Self-test from the Utilities menu.

63
3500/61E and /67E Temperature Monitor
4. Press the Module Self-test button on the System Events screen.

Advisory
The system will lose machinery protection while the monitor is performing its self-test.

5. Select the slot that contains the monitor and press the OK button. The monitor will perform
a full self-test and the software will display the System Events screen. The list will not
contain the results of the self-test.

6. Wait 30 seconds for the module to run a full self-test.

7. Press the Latest Events button. Software will update the System Events screen to include
the results of the monitor self-test.

8. Verify that the monitor passed the self-test. If the monitor failed the self-test, refer to

3300 System Upgrade Manual (part number 287550-01)

the System Event List to determine possible actions. See " List of 3500 and 3500 ENCORE
Messages" on page 1.

8.3 System Event List Messages


This section describes the messages that the module enters into the System Event List Messages
and gives an example of one message.

For a complete list of the 3500 ENCORE System Event Messages, please refer to 3500/23E System
Monitor Manual (part number 287545-01.

8.3.1 Example of a System Event List Message


Table 8-2: Sample System Event List Message
Sequence Event Event Date Event
Event Information Class Event Time Slot
Number Number DD/MM/YY Specific

Device Not
0000000123 32 1 02/01/90 12:24:31:99 5L
Communicating

Sequence Number: This is the number of the event in the System Event List (for example 123).
Event Information: This provides the name of the event (for example Device Not Communicating).
Event Number: This identifies the specific event that occurred.
Class: This indicates the severity of the event. The following classes are available:

64
Section 8.0 Troubleshooting
Table 8-3: System Event List Classes
Class Value Classification

0 Severe/Fatal Event

1 Potential Problem Event

2 Typical Logged Event

3 Reserved

Event Date: This specifies the date that the event occurred.
Event Time: This specifies the time that the event occurred.
Event Specific: This provides additional information for the events that use this field.
Slot: This identifies the module with which the event is associated. If a half-height module is installed
in the upper slot or a full-height module is installed, the field will be 0 to 15. If a half-height
module is installed in the lower slot, then the field will be 0L to 15L. For example, a module
installed in the lower position in slot 5 would be 5L.

8.4 Advanced Diagnostics


If you examine a number of events together, you can obtain a better picture of the reason for the
fault. The following list contains recommended action for the following scenarios.
Although the recommendations in this section provide the most probable solutions, other faults
may exist. When troubleshooting a temperature monitor, carefully review all possible problems.

Condition Details Action

Replace the temperature module


All Active
Transducers are If the external termination I/O module is being used, check
not OK the cable between the I/O monitor and the External
Termination Block.

If the I/O module supports both RTD & TC, check the I/O
Two Adjacent module and the temperature module.
Adjacent channels are defined
Channels are not
as 1-2, 3-4, or 5-6. If the I/O module supports TC only (isolated), the problem is
OK
probably in the main monitor.

Adjacent channels are defined


Three Adjacent
as 1-3 or 4-6. This scenario Check that the green connector is correctly installed into the
Channels are not
applies only to I/O modules I/O module.
OK
with internal termination.

65
3500/61E and /67E Temperature Monitor
Condition Details Action

One or more
Transducer for a particular
channels are Not
channel(s) shown as Not OK
OK on the Internal
(Wiring Open)
Barrier I/O Module

One of the Transducer Not OK (Wiring


Following Events Shorted)
Occur After Check the backplane for a bent or otherwise damaged pin.
Installing a Module Transducer Not Ok (Wiring
in the Rack Open)

Check to make sure that there are no ground loops. A


The display shows
ground loop is when the transducer is grounded at the
excessive noise on
sensor, and either a non-isolated I/O module is used or an
the input signal
isolated I/O module is grounded at the rack.

Replace main module.


All of the recorder
output signals are Check that the connectors are correctly installed into the I/O
incorrect or are not module and External Termination Block (if available) and
available inspect to make sure that the cable and field wiring are not
damaged.

66

S-ar putea să vă placă și