Sunteți pe pagina 1din 36

https://t.

me/abcdelectrical
https://t.me/abcdelectrical

Contents

Manual for K-Notes ................................................................................. 2


Transmission Lines .................................................................................. 3
Underground Cables ............................................................................. 14
Overhead Insulators .............................................................................. 16
Distribution Systems ............................................................................. 16
Per Unit System .................................................................................... 17
Load Flow Study .................................................................................... 18
Economic Power Generation ................................................................ 20
Fault Analysis ........................................................................................ 21
Power System Stability.......................................................................... 29
Power System Protection ...................................................................... 33

© 2014 Kreatryx. All Rights Reserved.

1
https://t.me/abcdelectrical

Manual for K-Notes

Why K-Notes?

Towards the end of preparation, a student has lost the time to revise all the chapters from his /
her class notes / standard text books. This is the reason why K-Notes is specifically intended for
Quick Revision and should not be considered as comprehensive study material.

What are K-Notes?

A 40 page or less notebook for each subject which contains all concepts covered in GATE
Curriculum in a concise manner to aid a student in final stages of his/her preparation. It is highly
useful for both the students as well as working professionals who are preparing for GATE as it
comes handy while traveling long distances.

When do I start using K-Notes?

It is highly recommended to use K-Notes in the last 2 months before GATE Exam
(November end onwards).

How do I use K-Notes?

Once you finish the entire K-Notes for a particular subject, you should practice the respective
Subject Test / Mixed Question Bag containing questions from all the Chapters to make best use
of it.

© 2014 Kreatryx. All Rights Reserved.

2
https://t.me/abcdelectrical

Transmission Lines
Skin Effect

It is tendency of AC current to be concentrated on the surface of conductor.


Cause: Non-uniform distribution of magnitude flux linkages Due to skin effect, the effective
area of cross section of conductor decrease and hence resistances increases.
In case of DC, There is no skin effect so
RDC  R AC
 With increase in frequency, skin effect increases.
 With increase in r , skin effect increases.
Inductance of a Transmission line

 Single Conductor
 0 r
Internal inductance
8
External inductance from distance ‘ d1 ’ to ‘ d2 ’
0r  d2 
Lex  ln  
2  d1 
0 r 0 r  d2 
Total inductance   ln  
8 2  r 
   d     d
 0 r ln  1   0 r ln  
2  re 4  2  r  
r  0.7788r = Geometric mean radius (GMR)

 Single phase 2 – wire line


 0 rd
Inductance of single wire  ln  
2  r  
Total inductance = L1  L2
0  d 
Lsys  ln  
  r 
If radius of both wire is not same, assume radius of 1st wire ra & that of second wire is rb

0  d 

Lsys  ln
  r r 
 a b 
ra  0.7788ra & rb  0.7788rb

If instead of a single conductor per phase we use multiple conductor, then GMR is
replaced by self GND (Geometric Mean Distance) and ‘d’ by mutual GMD.

3
https://t.me/abcdelectrical

Self GMD

1
self GMDfwd  D11 D12 ........D1n D21 D22 .........D2n  ....... Dn1 Dn2 ........Dnn  n2

Where Dii  ri  0.7788ri


1
Self GMDbwd  Di 1 ' '  
Di' 2' ........Di'm' .............. Dml' ' ................Dmm 
' '
 m2

Where Dii  ri  0.7788ri

Mutual GMD
1
Mutual GMD  D11' D12' ...........D1m'  ................. Dn1' Dn2' .................Dnm'  
mn

Now, with these terms all the inductance expressions change to


0  d 
Single wire : ln  
2  self GMD 

0  mutual GMD 
1  , 2 wire: ln  
2  Self GMD 

Three – phase Transmission line

Symmetrical configuration

0r  D 
Lph  ln  
2  r 

r  0.7788r

4
https://t.me/abcdelectrical

Asymmetrical configurations

If conductors are placed horizontally or vertically.


1
Deq  Dab  Dbc  Dca  3

0r  Deq 
Lph  ln  
2  r 

In case of bundled conductor, more than one conductor per phase


We replace Dab  Dabeq = mutual GMD between a phase & b phase

Similarly, Dbc  Dbceq

Dca  Dcaeq

In place of GMR, Self GMD is used


1

  Self GMD Self GMD 


Self GMD=  Self GMD
3
a b c

Example: Calculate inductance per phase of following circuit?

Between successive conductors, distance = 3m , Radius of each conductor = 1m


Solution
1
Dab eq  Da1b1 . Da1b2 . Da2b1 . Da2b2  4

1
 3  12  12  3 4
 6m
1
Dbc eq  3  6  6  3 4  4.24m
1
Dca eq   6  9  9  6  4  7.348m

Deq = mutual GMD


1
 Dab.eq  Dbc.eq  Dca.eq  3

= 5.71m

5
https://t.me/abcdelectrical

1
Self GMD   r  D
a a1a2
 Da2a1  r   4

0.7788  0.012  152 


1
4

= 0.341m
1
Self GMD   r  D
b b1b2
 Db2b1  r   4

= 0.2467m
1
Self GMD  r  D
c c1c2
 Dc2c1  r  4

= 0.1528m
1
Self GMD   Self GMD a Self GMD b Self GMD  c  3

= 0.2398m
0  GMD 
L ln  
2  GMD Self 

 5.71 
 2  10 7 ln    0.634mH / km
 0.2398 
Remember, Inductance calculated using these formulas is per unit length.

Transposition of Transmission line

The position of different lines are changed after regular intervals to reduce radio interference in
neighboring communication lines.

Capacitance
Single Phase 2 – Wire System
0 r
Cab 
 D 
ln  
 rr 
 12 
Line to neutral capacitance

6
https://t.me/abcdelectrical

20 r 20 r
Can  , Cbn 
D  D 
ln   ln  
 r1   r2 
Three phase single conductor system
20 r
Cph 
 GMD 
ln  
 r 
For bundled conductors
20 0
Cph 
 GMD 
ln  
 Self GMD 
In capacitance calculations, it must always be remembered that there is no concept of r, we
simply use radius in calculating self GMD.
Performance of Transmission line
Classification of lines based on length

1) Short Line
l < 80 km or l*f < 4000 , Where f = frequency

2) Medium Line
80 km < l < 200 km
4000 < l*f < 10000

3) Long Line
l > 200 km
l*f > 10000

Modeling of transmission lines

Transmission lines are modeled as 2 – port network


Vs  AVR  BIR
Is  CVR  DIR

Under no load
Vs
IR  0 , Vs  AVR , VR 
A

7
https://t.me/abcdelectrical

Vs
No Load Voltage  and IR  0 , Is  CVR
A

Vs
 VR
A
Voltage Regulation   100%
VR
This current is called as line charging current and is responsible for as effect is called as “Ferranti
Effect”.

Ferranti Effect
Under no-load or light load conditions receiving end voltage becomes more than sending end
voltage due to presence of line charging current.

Short transmission line

Vs  VR  IR R  jwL 

 VR  IR Z

 Vs  1 z   VR 
 I   0 1   I 
 s   R 

A = D (symmetrical)

AD – BC = 1 (reciprocal)

Approximate Voltage Regulation


For lagging pf
IR
VR=
VR
R cos  R
 X sin R 

load pf=cosR

For leading pf
IR
VR  R cos R  X sin R 
VR

8
https://t.me/abcdelectrical

Medium Transmission Line

Normal – T – Model

 YZ   YZ  
 1   Z 1  
 Vs   2   4    VR 
   
 Is    YZ    IR 
Y 1   
  2  

Here all problems are in actual values & not per unit length.

Nominal-π-Model

 YZ 
1 Z 
 Vs   2 V 
    R
 Is   Y  1  YZ  1  YZ   IR 
 4  2 
 

Long transmission Line

Vx  VR cosh X  IR Z c sinh x
VR
IR  IR cosh x  sinh x
Zc
Where Vx & I x are voltage and current at distance ‘x’ from receiving end.

R  jL
Zc  = surge impedance
G  jC

In case of long transmission line, we use all promoters’ per-unit length.


For loss less line, R=G=0
L
Zc 
C
For distribution less line, RC = LG
For sending end, x = l
Vs  VR cosh l  IR Z c sinh l

VR
Is  IR coshl+ sinh l
Zc

9
https://t.me/abcdelectrical

cosh l Z c sinh l


 Vs     VR 
  1  
 Is   Z cosh l   IR 
 c


A = D (symmetric)
AD - BC = 1 (reciprocal)
Power Transfer Equation

Vs Vr A
cos      Vr cos    
2
Pr 
B B

Vs Vr A
sin      Vr sin    
2
Qr 
B B

For Short TL

B  Z   B  Z ; 

A  10  A   A  1, =0
2
Vs Vr Vr
Pr  cos       cos 
Z Z
2
Vs Vr Vr
Qr  sin       sin 
Z Z

If resistance of line is neglected

Z  jX  X and   900

2
Vs Vr Vs Vr Vr
Pr  sin ; QR = cos  
X X X

Remember, the last expression can be applied between any two bases in a power system as long
as transmission line connecting them is loss less.

Wave Propagation

Due to continuous energy transfer between L & C elements of a transmission line we consider
energy propagation from sending to receiving end & hence wave propagation.
Z c = Surge impedance or characteristic impedance.

10
https://t.me/abcdelectrical

γ = Propagation constant.

 R  jL G  jC 


For loss less line
R=G=O

  j LC
    j

 = attenuation constant
 = phase constant

In case of loss less line   0 (no attenuation)

   LC
1
Velocity of wave  , Where L & C are per unit length
LC
2 2
Wavelength   
  LC

Surge Impedance Loading

When load impedance = surge impedance

Vr(L
2
L)
PL  = Surge Impedance Loading
ZC

If ZL  ZC
VR  IR Z C

According to long line

VX  VR coshx+VR sinhx  2VRex


So no term containing e yx & hence no reflected wave & hence whenever surge impedance is
connected at load, there is no reflection.

11
https://t.me/abcdelectrical

Surge Traversal

Theremin equivalent circuit

When surge voltage ‘ V ’ is induced on the line & line can be represented as Theremin
equivalent circuit shown.
ZC = Characteristic impedance of line

ZL = load impedance or characteristics impedance of second

line connected in series to first.


 ZL 
Transmitted voltage V2  2V   potential divider 
 ZL  Z C 
Incident Voltage V1  V

Reflected voltage  V
V  V  V2 [Voltage continuity]

 Z  ZC 
V  V  L 
 ZL  Z C 
V V V
Reflected current   , Refracted current   2 , Incident current 
ZC ZL ZC

V  ZL  Z C
Reflection coefficient: 
V ZL  Z C

V2 2ZL
Refraction coefficient: 
V ZL  Z C

Voltage Control

 Usually in case of lagging loads, the voltage at receiving end falls below sending end voltage
and to boost the receiving end voltage we connect a shunt capacitor at receiving end.
 Similarly, in case of leading loads, receiving end voltage is higher than sending end voltage
so we connect a shunt reactor to avoid over-voltage.
Usually in GATE, we need to calculate rating of capacitor for voltage control & it is illustrated
through a question shown below:

12
https://t.me/abcdelectrical

Example: A three phase overhead lines has a resistance & reactance of 5 & 20 respectively.
The load at receiving end is 30MW, 0.85 pf lagging at 33kv & we connect a compensating
equipment at receiving end to maintain voltage at each end equal to 33 Kv. Find rating of
compensating equipment?
Solution:
Assuming base (MVA) = 30 MVA
Base voltage = 33 kv
30Mw
pu power =  1pu
30MVA
V2
Base impedance =  36.3
S
5  j20
pu impedance =   0.56875.960
36.3
2
VS VR VR
PR 
Z
cos      
Z
cos   Z  0.568 ; =75.96 0 
11 12
1 cos  75.96     cos75.96  cos  75.96     0.81
0.568 0.568

  40.110

VS VR VR 1 1 12
QR  sin       sin   sin  75.96  40.11   sin75.96
Z Z 0.568 0.568

QR = - 0.645 pu

QL  PL tan   1  tan  cos1 0.85 

QL = 0.6197 pu

QR  QL  QC  QC  1.2647pu

QC  1.2647  30 = 37.9 MVAR

So, we can observe the steps involved


Step – 1 : Calculate  from PL as capacitor does not consume any real power.

Step-2 : Calculate QR using  calculated above

Step-3 : QR  QL  QC than Calculate QC

13
https://t.me/abcdelectrical

Power Factor Correction

Usually, to improve the supply side power factor we connect a capacitor device like capacitor
bank or synchronous condenser (synchronous motor under over excited condition).
Suppose, initially a load of real power P1 & lagging pf cos 1 is connected & we want to
improve pf to cos 2 lagging  2  1  & we connect a capacitive device which consumes real
power PC  & thus net real power after connection.

P2  P1  PC

Q2  P2 tan 2 ; Q1  P1 tan 1

QC  P1 tan 1  P2 tan 2

In case of capacitor bank, PC  0  P1  P2

If we wish to calculate capacitance per phase


(in both voltage control & pf correction )
QC
QC  3CVph
2
 C
3Vph
2

Underground Cables
Insulation resistance
 R 
R ln   
2l  r 

L = length of cable
R = Outer radius (sheath radius)
R = conductor radius

Capacitance Model

CC : Core capacitance
CS : Core to sheath capacitance

14
https://t.me/abcdelectrical

Capacitance per phase


Cph  CS  3CC

Calculating CS & CC

1) Any of two cores or conductors are connected to


sheath & capacitance is measured between remaining
core & sheath.

C1  CS  2CC

2) All three cores are connected together & capacitance is


measured between any core & sheath.
C2  3CS
C2
CS 
3
C2
2CC  C1 
3
C C 
CC   1  2 
 2 6 

3C1 C2
Cph  CS  3CC  
2 6

3) Any one of core is connected to sheath & capacitance is


measured between remaining 2 cores.

3CC CS
C3  
2 2

Cph  2C3

15
https://t.me/abcdelectrical

Dielectric loss in a UG cable

P  3Cph Vph
2
tan 

where tan   loss tangent

1
tan  
cphR

R = Insulation resistance

Overhead Insulators
For suspension type string insulator, the model for 3-discs looks like as shown.
C
Let m  m
CS
V2  V1 1  m
V3  V1 1  m2  3m
The voltage of disc nearest to the conductor is highest.
string voltage
String efficiency 
No. of discs  voltage across bottom disc


V
1
 V2  V3   100%
3  V3

Distribution Systems
 Sources fed from both ends
1) Assume I A from VA
2) Calculate I A from
VA  VB   I A  I1  r1   I A  I1  I2  r2   I A  I1  I2  I3  r3
3) Substitute I A in  I A  I1  ,  I A  I1  I2  &  I A  I1  I2  I3  & check for sign change.
4) Node for minimum potential = Node for sign change
5) Calculate minimum potential by KVL
Example: Refer Kuestion power systems for that.

16
https://t.me/abcdelectrical

Per Unit System


In pu system, energy quantity is expressed as a ratio of some based value.

Absolute value or Actual value


pu value=
Base value
Percentage value = pu value x 100%
Base value
1 -  System
 Sbase , Vbase , Ibase , Zbase
 Out of these, 2 value must be known, to convert entire system into pu system.
 Sbase  Vbase  Ibase
Sbase Vbase Vbase
2

Ibase  , Z base  
Vbase Ibase Sbase
 Usually, we assume Sbase & Vbase as known.

3 -  System

 Sbase & Vbase are assumed


Sbase
 Ibase 
3  Vbase
Vbase = line to line voltage
Sbase = 3 – phase power
 For start connection
V ph Vbase / 3 Vbase 2
Z base  base  
Ibase ph Ibase Sbase
 For delta connection
V ph Vbase 3V 2
Z base  base   base
Ibase ph Ibase / 3 Sbase

In per unit system, equivalent impedance of transformer referred to primary or


secondary in same.

17
https://t.me/abcdelectrical

Change of base

If base of system is changed from Vbase  old , Sbase  old  to Vbase new  ,Sbase new 

2
 V  old   Sbase new  
Zpu new   Zpu  old    base   
 Vbase new    Sbase  old  

Load Flow Study


Power System Matrices

 YBUS matrix

 y10  y12  y12 0 


YBUS    y12 y 20  y12  y 23  y 23 
 0  y 23 y 23  y 30 

OBSERVATIONS

1) The diagonal elements are sum of all admittance connected to that particular bus.
2) The off-diagonal elements are negative of admittance connected between two buses.
3) If two buses are not connected to each other than that elements is zero.
4) YBUS Matrix is a symmetrical matrix.
5) Most of the elements are zero & hence it is a sparse matrix.
Total number of zero elements
% sparsity =
Total number of elements

 ZBUS matrix

ZBUS   YBUS 
1

 ZBUS matrix used in fault analysis.


 Suppose a 3 – phase SC fault occurs on bus ‘k’ then fault current
Vprefault ,k
If 
Zkk  Z f
Vprefault , k  Pr e  fault voltage at bus 'k'
Zkk = elements of ZBUS matrix.
Z f = fault impedance
 Due to fault voltage at other buses are also affected.

18
https://t.me/abcdelectrical

 V1   I1 
    0
.  .   
.  .  0
    . 
 Vk   Ik   
.
.    Z  .   V    ZBUS   
   BUS    BUS I
.  .   f
    . 
 Vn   In   
    . 
     0 
   

Vk  If Zkk


Vf
If   Z  0
Zkk f
 
Vj  Z jk I"f
Z jk
Vj  Vf
Zkk

 Post – fault voltage at bus j


Z jk
Vjf  Vj  V
Zkk f
If there is generator connected to bus ‘ j ’ then current supplied by generator.
Eg  Vjf
I
jX"d

Classification of buses
At each bus, there are 4 parameter: V , ,P,Q .
At any bus, out of these 4 quantities any 2 are specified.

1) Slack Bus / Swing Bus/Reference Bus

V ,  are know quantities.


P, Q are unknown quantities.
Any extra power needed by the system is supplied by slack bus.
2) Generator Bus / PV Bus
P, V is specified
Q,  are unspecified

19
https://t.me/abcdelectrical

3) Load Bus / PQ Bus


P & Q are constant as specified
V &  are unknown
Generally, newton – Raphson method is used for load flow solution and we form Jacobian
matrix, & the order of Jacobian matrix is
2n  m  2  2n  m  2
N = no. of total buses
M = no. of pv buses

Economic Power Generation


 Incremental cost
If is cost required to generate an additional unit of energy.
 IC i = Incremental cost of ith generator
Ci
 IC i 
PGi
PGi = Power generated by ith generator
Ci = cost of ith generator

 Transmission Loss
m m
PL    PP
i jBij
i 1 j 1

Pi , Pj : Real power injection at i & j buses


th th

B ij = loss coefficient
m : no. of generator units

Penalty Factor

1
Li 
 P 
 1  L 
 PGi 

For economic power sharing


 IC i Li  cons tant
 Constant is called as incremental cost of system.
  IC i = incremental cost ith unit
 L i = penalty factor of ith unit

20
https://t.me/abcdelectrical

 From this expression, for m generator we get ( m – 1) equation and mth equation is
m

P
i 1
Gi  PD  PLOSS

PD = total power demand


For example, refer kuestions on Power systems.

Fault Analysis
Symmetrical Components

For an unbalanced 3 – phase system, the analysis is done better by means of symmetrical
components.
Va0  Zero sequence components

Va1  Positive sequence components

Va2  Negative sequence components

 Va0  1 1 1   Va 
  1   0

 Va1   3 1  2   Vb  ; Where   e j120


V  1 2    Vc 
 a2  
Vs   A Vp 
1

Vp = phase voltage
Vs = Symmetrical component
1 1 1
 
A  1  2 
1   2 

Power in terms of symmetrical components
P  3  Va1 Ia1  Va2 Ia2

 Va3 Ia0



Remember, same transformation exist for current also.


Sequence Network

Alternators

 Positive Sequence Network

Z1 positive sequence impedance


Z1  jX"d

21
https://t.me/abcdelectrical

 Negative Sequence Network

Va2  Ia2 Z2
Z 2 : Negative sequence impedance
 X d " X q " 
Z2  j  
 2 

 Zero Sequence Network

Va0  Ia0  Z0  3Zn 


Z 0 = Zero sequence impedance
Z n =Neutral impedance (  in case of delta)
Z0  jXl
X l = leakage reactance

Transformers

 Positive Sequence Network

Z1 = Positive sequence impedance

Z1  jXl

 Negative Sequence Network

Z 2 = Negative sequence impedance

Z2  jXl

 Zero sequence network

Depending upon scheme of connection, we close series or shunt connection & method
of grounding.

22
https://t.me/abcdelectrical

Shunt connection are closed for delta connection & series connection are closed for star
connection with grounded neutral. If primary & secondary are inter changed then circuit
becomes mirror image.

 Case – 1

If neutral is grounded through an impedance Z n

Z 0  Z T0  3Zn

 Case – 2

 Case – 3

 Case – 4

23
https://t.me/abcdelectrical

 Case – 5

Transmission Lines

 Positive Sequence Network

 Negative Sequence Network

 Zero Sequence Network

Z1  Z2  Zs  Zm

Z0  Zs  2Zm

Z s = Self impedance

Zm = mutual impedance

Remembers, all sequence networks are always drawn in per unit & never in actual values.

Fault Analysis
The following short circuit faults are considered
1. LG (Single Line to ground fault)
2. LL (Line to line fault)
3. LLG (Line to Line to Ground fault)
4. 3-phase short circuit fault.

24
https://t.me/abcdelectrical

3-phase short circuit fault comes under the category of symmetrical SC fault whereas other 3
faults are called as unsymmetrical SC fault.

Order of severity
LG < LL < LLG < 3 -  SC

But if faults occur at terminal of alternator then LG fault is most severe.

Occurrence of SC fault

LG > LL > LLG > 3 -  SC

Transient on a Transmission line

Equivalent Circuit

i  t   it  iss

Vm Rt
V
sin      e L  m sin  wt     


Z Z

 L 
 
2
  tan1   ; Z  R  L
2

 R 

Maximum momentary current

2Vm
imm  sin     
Z

If resistance is neglected,   900

2Vm
imm  cos 
Z

Short circuit model of a synchronous machine

During initial SC period for 1-2 cycles, current are induced in field & damper winding of machine
so reactance at least & called as sub transient reactance  X d "

After initial sub-transient period, current in damper winding in reduced to zero, and this period
is called as transient period & reactance of machine is called as Transient Reactance  X d "

25
https://t.me/abcdelectrical

Finally, when current in field winding is also reduced to zero, we enter steady state period &
reactance is called as steady state reactance  Xd  .

Xd "  X d '  X d

Symmetrical Fault Analysis

 We replace alternators by an emf source in series with sub transient reactance and emf
source under no-load is usually 100 pu or terminal voltage in pu.
V 00
Ef  t pu
Vbase
 Transformer & Transmission lines are replaced by reactance.
 The equivalent circuit can be solved either by finding thevenin equivalent across fault or
by simple network analysis & fault in SC is calculated.

Ef
If 
Z eq  Z f

Z f = fault impedance.

 In symmetrical fault analysis, we only consider positive sequence impedance.


1
 SC MVA   pu
Zeq  Z f

 SC MVA  
MVA base MVA
Zeq  Z f

For example, refer to kuestion on power systems.

Selection of Circuit Breakers

 Usually, circuit breakers are selected on the basis of most severe fault which is 3 – phase
SC fault.
 Three ratings of circuit Breakers are important.

1) Rated momentary current


Momentary current ( rms ) = 1.6  Isc
Isc is symmetrical SC current which we calculated in previous section.

2) Making current
Making current = 2.54  Isc

26
https://t.me/abcdelectrical

3) Symmetrical Interrupting Current


We need to recalculate Isc by using sub-transient reactance for alternators & transient
reactance for synchronous motors. Induction motors & other loads are neglected.

Then, we multiply it by a factor to calculate symmetrical interrupting current. This factor


depends on speed of circuit breakers which is measured in terms of numbers of cycles it takes to
operate.

Speed Factor
8 Cycles or slower 1.0
5 Cycles 1.1
3 Cycles 1.2
2 Cycles 1.3

Unsymmetrical Faults Analysis

 Line to Ground Fault

We first draw equivalent positive, negative & zero sequence networks & calculate thevenin
impedance across fault terminals from each network.

Assuming equivalent positive, negative & zero sequence reactance are Z1 , Z 2 & Z 0
respectively.

Here all sequence currents are equal.

Ia1  Ia2  Ia0

Ea
Ia1 
Z1  Z 2  Z 0  3Z f

Fault current I a

Ia  3Ia1

3  Ea
Ia 
Z1  Z 2  Z 0  3Z f

Short Circuit MVA

SC MVA   3Ea1 , I a1 *

27
https://t.me/abcdelectrical

3 Ea1 I2

Z1  Z 2  Z 0  3Z f

3
In pu SC MVA   pu
Z1  Z 2  Z 0  3Z f

3 MVA base
 MVA
Z1  Z 2  Z 0  3Z f

 Line to Line Fault

Here, we calculate equivalent positive & negative sequence impedance Z1 & Z 2 respectively.

Ea
Ia1 
Z1  Z 2  Z f

Fault current

 j 3  Ea
Ib 
Z1  Z 2  Z f

Short Circuit MVA

3
SC MVA   pu
Z1  Z 2  Z f

3 MVA base
 MVA
Z1  Z 2  Z f

 Line to Line to Ground Fault

Ea
Ia1 
Z1  Z 2  Z 0  3Z f  
I  Z2
Ia0  a1
 Z2  Z0 
Fault Current = 3  Iao

28
https://t.me/abcdelectrical

Short Circuit MVA

3
SC MVA   pu
Z1   Z 2  1 3Z f  Z 0  

3 MVA base
 MVA
Z1   Z 2  Z 0  3Z f 
Remember, all fault analysis will be done in pu system.

Power System Stability


Two types of stability are studied:

1) Steady State Stability


2) Transient Stability

Steady State Stability

For Steady State Stability


dP
0
d
And for this condition to be true.
Pe  Pmax
If power demand is greater than maximum demand than machine goes out of synchronous.
E V
For a loss less machine, Pmax 
XS
Transient Stability
Swing Equation

Md2 
 Pm  Pe 
dt2
M = inertia constant ( MJ-S / elect - rad)
Pm= mechanical input (MW)
Pe = electrical output (MW)
 = rotor angle
Another Form

H d2 
 Pm  Pe 
f dt2
H = inertia constant ( MJ / MVA)
Pm & Pe both are in pu

29
https://t.me/abcdelectrical

GH
M (MJ – S / elect - deg)
180f
GH
M (MJ – S / elect - rad)
f
G = machine rating (MVA)
 If two alternators are swinging coherently. Then they can be replaced by a single
alternator having
Meq  M1  M2
But “ H “ cannot be added directly, they must first be on same base.
 If machines are not swinging coherently, then
M1M2
Meq 
M1  M2

 Accelerating Power,
Pa  Pm  Pe 
In steady state Pm  Pe
In transient, Pm  Pe so rotor accelerate or decelerate.

Equal area criterion

For system to possess transient stability


 Pad  0
There are basically 3 stages in stability analysis

 Before Fault
We say maximum power transferrable is Pmax,1
& Pe  Pmax,1 sin 

 During fault
We say maximum power transferrable is Pmax,2
Pe  Pmax,2 sin 

 After Fault
We say maximum power transferrable is Pmax,3
Pe  Pmax,3 sin 

30
https://t.me/abcdelectrical

Critical clearing angle

It is the maximum value of  beyond which if the fault is cleared system will be unstable. The
time instant corresponding to this angle is called as critical clearing time assuming fault occurs
at t = 0.

Case-1 : Fault occurs on TL near to bus

Pmax,2  0
Pmax,3  Pmax,1
Cr  clearing angle
By equal area criteria
2

 Pm  Pmax,1 sin  d  0


0

 P 
0  sin1  m 
 Pmax,1 
For critical clearing 2  max

max    0

2H  Cr  0 
tCr  = Critical Clearing Time
f Pm

Case-2 : Fault occurs on one of parallel lines close to bus

Before Fault

E V
Pmax,1 
Xg   X1 X2 

During Fault

E V
Pmax,2  0
Xeq

After Fault

E V
Pmax,3 
Xg  X1

31
https://t.me/abcdelectrical

 P 
0  sin1  m

 Pmax,1 
 

 P 
max    sin1  m

 Pmax,3 
 

For transient stability


2

 Pad  0
0

c 2

 Pm  0  d   Pm  Pmax,3 sin   d  0


0 c

For critical Clearing

2  max

2H  Cr  0 
tCr 
f Pm

Case-3 : Fault occurs in middle of one of parallel lines

The equivalent reactance during the fault is highest and thus Pmax,2 is lowest

Pmax,1  Pmax,3  Pmax,2

2

 Pad  0
0

c 2

 Pm  Pmax,2 sin d   Pmax,3 sin  Pm  d


0 c

For critical clearing,

 P 
2  max    sin1  m 
 Pmax,3 
 

32
https://t.me/abcdelectrical

cr  cos 1 
P
m  max  0   Pmax,3 cos max  Pmax2 cos 0 
 Pmax3  Pmax2 
 

 This is a generic formula and can be applied to other two cases as well after substituting
value of Pmax,1 , Pmax,2 & Pmax,3 .
 But tcr can only be calculated from cr in previous two cases using expression written
before.

Power System Protection


 In our current protection, normally a current transformer is connected between
protected elements and the relay.
Plug setting multiplier (PSM)
Fault current

 T ratio  Pick  up current 
Usually pick up current = Relay setting x Rated secondary current of CT
Pick-up current is minimum current above which a relay operates.

 Differential Relays

The current through operating coil  k  I1  I2 


If this current is greater than pick-up current then
it operates, else it does not operates.
K I1  I2  Ipick up  Trip 
K I1  I2  Ipick up Block 

 We usually provide a restraining coil to avoid relay mal-operation.

Relay operates if
 Nr I1  I2 
K I1  I2  K   Ipu
 N0 2 

Ipu = pick up current


Nr = Number of turns in restraining coil
N0 = Number of turns in operating coil
The ratio operating coil current & restraining coil current is called as bias of differential
relay.

33
https://t.me/abcdelectrical

Protection of Transmission line

1) Mho relay is at least affected by power surges& thus it is used for protection of long
transmission lines. It is inherently directional.
2) Impedance relay is used for protection of medium transmission lines.
3) Reactance relay is unaffected by ground resistance & hence used for earth fault
protection & also for short transmission Lines.
 These relays are collectively called as distance relays.

Protection of Transformers

 Differential relays are used for protection of large transformers and CT are always
connected in configuration opposite to power transformer.
Example: 1) If power transformer is   Y then CT is Y  
: 2) If power transformer is    then CT is Y  Y
 Buccholz relay used to prevent any incipient fault below oil level in a transformer of small
KVA.

34
https://t.me/abcdelectrical

S-ar putea să vă placă și