Documente Academic
Documente Profesional
Documente Cultură
T HE capacity of renewable energy generation has continued control methods for converter cells such as zero-sequence AC
to grow in the last decade, and it will become 2.5 TW in voltage injection method for SSBC [10], [11] and
zero-sequence AC current injection method for SDBC [12].
2020 [1]. In accordance with constructions of large-scale
However, in order to avoid the voltage saturation and over
renewable energy generation systems such as solar PV and
junction temperature, these voltage-balancing methods could
result in increased voltage and current stress of the converters
Manuscript received Apr. 11, 2018; revised Jun. 23, 2018; accepted Aug. 6, and thereby they may compromise the reactive power
2018. delivering capability of the MMCCs when they are practically
Takaaki Tanaka is with Corporate R&D Headquarters, Fuji Electric Co., Ltd, designed for wind farms.
1910064 Tokyo, Japan (e-mail: tanaka-takaaki@fujielectric.com).
Ke Ma is with the Department of Electrical Engineering, Shanghai Jiao
MMCC solutions with Double Star Chopper Cells (DSCC)
Tong University, 200240 Shanghai, China (e-mail: kema@sjtu.edu.cn). and Double Star Bridge cells (DSBC) have been reported to be
Huai Wang, and Frede Blaabjerg are with the Department of Energy used for Back-to-Back converters such as Medium Voltage
Technology, Aalborg University, 9220 Aalborg, Denmark (e-mail: motor drive and High Voltage Direct Current (HVDC)
hwa@et.aau.dk, fbl@et.aau.dk).
Color versions of one or more of the figures in this paper are available online
transmission applications typically, but they can also be used
at http://ieeexplore.ieee.org.. for a STATCOM application. They can keep operating under
(b) SDBC
TABLE II
SEQUENCE VOLTAGE AMPLITUDE DEFINITION OF DIFFERENT GRID FAULTS vS,u, vS,v, vS,w
SCENARIOS ON BUS C (THE VS IS THE RATED VOLTAGE ON BUS C) Bus C (33kV) M: Virtual neutral point at Bus C (grid side)
Fault types Each sequence voltage vector i Lac iul u phase lower arm
iuu u phase upper arm S,u
uu ul
𝐷 2 Cell uu1 Cell uux Cell ul1 Cell ulx
+
𝑉𝑑𝑞 +
(b) 3 3 vPU vUN
− iS,v
Single-phase- [𝑉𝑑𝑞 ] = 𝑉𝑆 𝐷 1 𝐷 1 i v phase upper arm ivl v phase lower arm
to-ground fault − +𝑗( − ) P vu N
𝑉0 6 6 2√3 2√3 vu vl
[ 0 ] Cell vu1 Cell vux Cell vl1 Cell vlx
𝐷 1 vPV vVN
+
𝑉𝑑𝑞 + iwuw phase upper arm iS,w iwl w phase lower arm
(c) 2 2 wu
− wl
Phase-to-phase [𝑉𝑑𝑞 ] = 𝑉𝑆 𝐷 1 √3𝐷 √3 Cell wu1 Cell wux Cell wl1 Cell wlx
short-circuit fault − + + 𝑗 (− − )
𝑉0 4 4 4 4 vPW vWN
[ 0 ]
Da_wlx Da_wlx Dc_wlx
2 1 Sa_wlx Sa_wlx
+
𝑉𝑑𝑞 𝐷+ Sc_wlx
(d)
−
3 3
Cwlx or vCwlx Cwlx vwlx
Two-phase- [𝑉𝑑𝑞 ] = 𝑉𝑆 𝐷 1 𝐷 1 vCwlx Sd_wlx
to-ground fault − + + 𝑗 (− + ) Sb_wlx vwlx Sb_wlx
𝑉0 6 6 2√3 2√3
[ 0 ] Db_wlx Db_wlx Dd_wlx
※x is total cell counts in a arm
39 69 156 78
Number of total cells Ncell
( 13 cells/cluster ) ( 23 cells/cluster ) (26 series/arm) (13 series/arm)
Rated output current of each cell Ir 1400 Arms 808 Arms 700 Arms 700 Arms
is seen by the STATCOM due to the used delta-wye nominal output AC voltage each converter cell in the DSCC
transformer TR2. Table II shows the asymmetrical grid fault becomes AC 725 Vrms with the nominal modulation factor for
scenarios on Bus C corresponding with each grid fault. The AC component n = 0.8.
̇ + , 𝑉𝑑𝑞
𝑉𝑑𝑞 ̇ − and 𝑉̇ 0 are positive-, negative and zero-sequence The cell converter counts Ncell of the MMCC solutions with
component of the voltage, respectively, which are defined as SSBC, SDBC, DSCC, and DSBC are expressed by the
scenarios used in this paper. equations in Table IV, respectively. Total number of switching
devices Nsw for each MMCC topology is derived by each cell
circuit type and Ncell.
III. SPECIFICATIONS OF THE MMCC-STATCOMS FOR STUDY
Rated output currents Ir in each cell among the MMCC
An 80 MVar / 33 kV case study for a practical STATCOM solutions are also expressed by the equations in Table IV,
application is chosen in this paper. Fig. 3 shows circuit respectively. The current ratings of the IGBT modules in each
configurations of the STATCOM based on MMCC with SSBC, of the cell converter among the MMCC solutions are selected
SDBC, DSCC, and DSBC, respectively. Table III shows the depending on the Ir. It is worth to note that the Nsw and Ncell
specifications, the cell numbers, and key components. The among the MMCC solutions are different. However, the
design procedure is given below. equivalent total power semiconductor chip area calculated by
the total IGBT module counts, the current capacity of each
A. Basic structure and power semiconductor device IGBT module and the rated voltage of each IGBT module,
The rated DC-link voltage VC,dc of each converter cell in the which strongly influence the total cost of the STATCOM,
four types of the MMCC solutions are designed to be the same become same values approximately.
at 2600 Vdc where widely used 4.5 kV IGBT modules are
selected for each converter cell in this case study. The nominal B. Modulation type and frequencies for PWM
output AC voltage each converter cell in the SSBC, SDBC and Phase-shift PWM modulation is chosen because of the
DSBC is designed at 1450 Vrms with the nominal modulation advantage that the electro-thermal stresses of the IGBT
factor n = 0.8. The margin of the modulation factor (0.2) is modules and capacitors are equally distributed among the cells
determined by the voltage drop of the output impedance, in the same cluster (or arm). The equivalent switching
current control dynamics, pulse width limitation due to dead frequency of the MMCC feq_sw is designed to be the same at 10
time, and modular redundancy. However, the circuit kHz. In this result, the carrier frequency fc of the MMCC
configuration of the converter cell for the DSCC is chopper solutions with SSBC and SDBC are 380 Hz and 215 Hz,
converter, which cannot output minus voltage. Because +/- respectively. The carrier frequency fc of the MMCC solutions
output voltage is also required for the DSCC based STATCOM, with DSCC and DSBC are the same 190 Hz. It is noted that fc of
the output voltage in each chopper converter cell is each MMCC solution should not be an integer multiple of the
superimposed with the half value of the rated DC-voltage ( i.e. fundamental frequency in order to avoid diverging the
1300 Vdc ). When the above design guideline is followed, the
TABLE IV
THE KEY EQUATIONS FOR THE DESIGN OF THE MMCC SOLUTIONS
SSBC SDBC DSCC DSBC
capacitor voltages among the cells when fc is below several IV. THEORETICAL OPERATION OF MMCC FAMILY UNDER
hundred Hz [25], [26]. ASYMMETRICAL REACTIVE POWER COMPENSATION
C. Interconnection inductance In this section, the theoretical operation of each MMCC
In this case study, the Lac is designed as 6 % of the solution is solved by a mathematical formula, focusing on the
normalized impedance Zpu based on 33 kV and 80 MVar asymmetrical reactive power compensation. This analysis
operating condition of the converter. In this design rule, the Lac contributes to understanding the limitation of the asymmetrical
of the MMCC solutions with SSBC, SDBC, DSCC, and DSBC compensation capability of the MMCC solutions. The
is calculated by equations in Table IV, respectively. The total asymmetrical three-phase systems are solved by using vector
energy stored in the whole interconnection inductor EL has the representation, where the method seems the simplest way to do
same value among the MMCC solutions in this designed case, it according to previous works [27-29].
which will strongly influence the total volume of the
A. The definition of the grid fault voltage and current on Bus C
STATCOM.
The grid voltages and currents on Bus C are defined as
D. DC-link capacitance 𝑣𝑆,𝑢 = 𝑉𝑆+ sin(𝜔𝑆 𝑡) + 𝑉𝑆− sin(𝜔𝑆 𝑡 + 𝜙𝑣𝑛 )
The DC-link capacitance of each cell Cx is designed as 𝑣𝑆,𝑣 = 𝑉𝑆+ sin (𝜔𝑆 𝑡 −
2𝜋
) + 𝑉𝑆− sin (𝜔𝑆 𝑡 + 𝜙𝑣𝑛 +
2𝜋
)
capacitor voltage ripple scaled by the rated DC-link voltage 3 3 (2)
2𝜋 2𝜋
Vc,dc (2600V). The voltage ripple Vc,pu is designed to be 10% 𝑣𝑆,𝑤 = 𝑉𝑆+ sin (𝜔𝑆 𝑡 + ) + 𝑉𝑆− sin (𝜔𝑆 𝑡 + 𝜙𝑣𝑛 − )
{ 3 3
below nominal rated operation. The relationship between the
voltage ripple and the capacitance Cx of the MMCC solutions 𝑖𝑆,𝑢 = 𝐼𝑆+ sin(𝜔𝑆 𝑡 + 𝜙𝑖𝑝 ) + 𝐼𝑆− sin(𝜔𝑆 𝑡 + 𝜙𝑖𝑛 )
with SSBC, SDBC, DSCC, and DSBC are also expressed by 2𝜋 2𝜋
equations in Table IV based on an averaging model, 𝑖𝑆,𝑣 = 𝐼𝑆+ sin (𝜔𝑆 𝑡 + 𝜙𝑖𝑝 − ) + 𝐼𝑆− sin (𝜔𝑆 𝑡 + 𝜙𝑖𝑛 + ) (3)
3 3
respectively [12], [32]. Here, is a modulation factor of a cell, 𝑖 = 𝐼𝑆+ sin (𝜔𝑆 𝑡 + 𝜙𝑖𝑝 +
2𝜋
) + 𝐼𝑆− sin (𝜔𝑆 𝑡 + 𝜙𝑖𝑛 −
2𝜋
)
{ 𝑆,𝑤 3 3
which is set to be =1 and assuming the largest voltage ripple
in this case study. The total energy stored in all dc-link
where 𝑉𝑆+ is the amplitude of positive-sequence voltage, 𝑉−𝑆
capacitors EC among the MMCC solutions can be expressed as
𝑁 2 and 𝜙𝑣𝑛 are the amplitude and phase angle of
𝐸𝐶 = 𝑐𝑒𝑙𝑙 𝐶𝑥 𝑉𝐶,𝑑𝑐 (1)
2
negative-sequence voltage, 𝐼𝑆+ and 𝜙𝑖𝑝 are the amplitude and
After the Ncell, Cx, and Ir as shown in Table IV are substituted phase angle of positive-sequence current, 𝐼− 𝑆 and 𝜙𝑖𝑛 are the
for (1), the EC among the MMCC solutions is updated to the amplitude and phase angle of negative-sequence current,
formulation as shown in Table IV. It is noted that the EC for respectively. After a dq transformation of (2) and (3), the grid
+ −
SSBC, SDBC, and DSBC is the same. However, the Ec of the voltage 𝑉̇ 𝑆,𝑑𝑞 , 𝑉̇ 𝑆,𝑑𝑞 can be expressed as
DSCC is 4 times larger than the others because of the used ̇ + = 𝑉𝑆,𝑑
𝑉𝑆,𝑑𝑞 + +
+ 𝑗𝑉𝑆,𝑞
chopper cells. As an example, where the EC of the DSCC is {
̇ − − −
(4)
𝑉𝑆,𝑑𝑞 = 𝑉𝑆,𝑑 + 𝑗𝑉𝑆,𝑞
compared with the DSBC, both the Ncell and the Cx of the DSCC
become twice higher than DSBC because of the used chopper
+
cells with the output voltage including superimposed the half The 𝑉𝑆,𝑑 , 𝑉+ − −
𝑆,𝑞 , 𝑉𝑆,𝑑 and 𝑉𝑆,𝑞 are detected by dual-frame dq
value of the rated dc-voltage VC,dc. It should be noted that the EC transformation scheme in an actual current controller [30]. It is
+
depends greatly on the total volume of the STATCOM. noted that the 𝑉𝑆,𝑞 has a zero value because the standard phase
is set at the d-axis of the positive-sequence grid voltage by the
PLL.
+ − ̇ , 𝐼𝑆,𝑣
̇ , 𝐼𝑆,𝑤
̇ at Bus C can be expressed as
Similarly, the grid current 𝐼̇ 𝑆,𝑑𝑞 , 𝐼̇ 𝑆,𝑑𝑞 on Bus C can be The grid currents 𝐼𝑆,𝑢
expressed as ̇
𝐼𝑆,𝑢 ̇
+
𝐼𝑆,𝑑𝑞 ̇
−
+ 𝐼𝑆,𝑑𝑞
̇
+
𝐼𝑆,𝑑𝑞 = +
𝐼𝑆,𝑑 + +
𝑗𝐼𝑆,𝑞 ̇ ̇
+
[ 𝐼𝑆,𝑣 ] = [𝐼𝑆,𝑑𝑞 𝑒 −𝑗2𝜋 ⁄3 ̇ 𝑒 𝑗2𝜋 ⁄3 ]
−
+ 𝐼𝑆,𝑑𝑞
{ −
̇ − −
(5)
𝐼𝑆,𝑑𝑞 = 𝐼𝑆,𝑑 + 𝑗𝐼𝑆,𝑞 ̇
𝐼𝑆,𝑤 + ̇ 𝑒
𝐼𝑆,𝑑𝑞 𝑗2𝜋 ⁄ 3 ̇ 𝑒 −𝑗2𝜋 ⁄3
−
+ 𝐼𝑆,𝑑𝑞
− + −
(𝐼𝑆,𝑑 ) + 𝑗(𝐼𝑆,𝑞 + 𝐼𝑆,𝑞 )
+
The 𝐼𝑆,𝑑 , 𝐼+ − −
𝑆,𝑞 , 𝐼𝑆,𝑑 and 𝐼𝑆,𝑞 are supplied by the STATCOM. √3 + 1 − √3 − 1 + √3 − 1 −
+ + − − = ( 𝐼𝑆,𝑞 − 𝐼𝑆,𝑑 − 𝐼𝑆,𝑞 ) + 𝑗 (− 𝐼𝑆,𝑞 + 𝐼𝑆,𝑑 − 𝐼𝑆,𝑞 ) (10)
2 2 2 2 2 2
These reference values 𝐼𝑆,𝑑,𝑟𝑒𝑓 , 𝐼𝑆,𝑞,𝑟𝑒𝑓 , 𝐼𝑆,𝑑,𝑟𝑒𝑓 and 𝐼𝑆,𝑞,𝑟𝑒𝑓 can
√3 + 1 − √3 − 1 + √3 − 1 −
be defined as [(− 2 𝐼𝑆,𝑞 − 2 𝐼𝑆,𝑑 + 2 𝐼𝑆,𝑞 ) + 𝑗 (− 2 𝐼𝑆,𝑞 − 2 𝐼𝑆,𝑑 − 2 𝐼𝑆,𝑞 )]
+ +
𝐼𝑆,𝑑 = 𝐼𝑆,𝑑,𝑟𝑒𝑓 ≡0 The instantaneous active powers pu, pv, pw of each
+ +
𝐼𝑆,𝑞 = 𝐼𝑆,𝑞,𝑟𝑒𝑓 phase-cluster of the MMCC-SSBC including the Lac can be
− − (6)
𝐼𝑆,𝑑 = 𝐼𝑆,𝑑,𝑟𝑒𝑓 expressed as
− − 1
{𝐼𝑆,𝑞 = 𝐼𝑆,𝑞,𝑟𝑒𝑓 ̇ ∗ ∙ 𝐼𝑆,𝑢
ℜ[𝑉𝑆,𝑢𝑛 ̇ ]
𝑝𝑢 2
1
[ 𝑝𝑣 ] = ̇ ∗ ∙ 𝐼𝑆,𝑣
ℜ[𝑉𝑆,𝑣𝑛 ̇ ] (11)
+ 2
where 𝐼𝑆,𝑑,𝑟𝑒𝑓 is set to be zero value because of reactive power 𝑝𝑤 1
+ ̇∗
[2 ℜ[𝑉𝑆,𝑤𝑛 ̇ ]]
∙ 𝐼𝑆,𝑤
compensation operation. The 𝐼𝑆,𝑞,𝑟𝑒𝑓 is given from the central
̇ ∗ is the complex conjugate of the 𝑉𝑆,𝑢𝑛
where 𝑉𝑆,𝑢𝑛 ̇ . By using
control of the wind power plant under normal operation. In this
result, the STATCOM has two operating modes which are (11), the 𝑉 0̇ in order to make pu = pv = pw, can be solved by
inductive operation in case of 𝐼+ 𝑆,𝑞,𝑟𝑒𝑓 < 0 and capacitive 𝑉 0̇ =
+ − − − − + − − + + − − + −
operation in case of 𝐼+ > 0. When a grid fault happens, the 𝑉𝑆,𝑑 (𝐼𝑆,𝑑 𝐼𝑆,𝑑 − 𝐼𝑆,𝑞 𝐼𝑆,𝑞 − 𝐼𝑆,𝑞 𝐼𝑆,𝑞 ) + 𝑉𝑆,𝑑 𝐼𝑆,𝑞 (𝐼𝑆,𝑞 + 𝐼𝑆,𝑞 ) + 𝑉𝑆,𝑞 𝐼𝑆,𝑞 𝐼𝑆,𝑑
𝑆,𝑞,𝑟𝑒𝑓
+ + − − − −
+
additional amount of 𝐼𝑆,𝑞,𝑟𝑒𝑓 may be required due to a recent (𝐼𝑆,𝑞 𝐼𝑆,𝑞 − 𝐼𝑆,𝑑 𝐼𝑆,𝑑 − 𝐼𝑆,𝑞 𝐼𝑆,𝑞 )
+ − − − − + − − + − + − + −
published grid code of Transmission System Operators (TSOs). 𝑉𝑆,𝑑 (𝐼𝑆,𝑑 𝐼𝑆,𝑞 + 𝐼𝑆,𝑑 𝐼𝑆,𝑞 − 𝐼𝑆,𝑞 𝐼𝑆,𝑑 ) + 𝑉𝑆,𝑞 𝐼𝑆,𝑞 (𝐼𝑆,𝑞 − 𝐼𝑆,𝑞 ) − 𝑉𝑆,𝑑 𝐼𝑆,𝑞 𝐼𝑆,𝑑
− − +𝑗 + + − − − −
The 𝐼𝑆,𝑑,𝑟𝑒𝑓 and 𝐼𝑆,𝑞,𝑟𝑒𝑓 are set to be zero value according to the (𝐼𝑆,𝑞 𝐼𝑆,𝑞 − 𝐼𝑆,𝑑 𝐼𝑆,𝑑 − 𝐼𝑆,𝑞 𝐼𝑆,𝑞 )
mentioned recent grid codes. (12)
̇ ̇ ̇
Each phase-cluster converter output voltage 𝑉𝑢𝑛 , 𝑉𝑣𝑛 , 𝑉𝑤𝑛 can
B. The MMCC-SSBC with zero-sequence AC voltage
be expressed as
Where the zero-sequence AC voltage with the same ̇
𝑉𝑢𝑛̇ 𝑉𝑆,𝑢𝑛 𝑉̇𝐿,𝑢
frequency as the phase-cluster current is injected, the
[ 𝑉𝑣𝑛 ̇
̇ ] = [ 𝑉𝑆,𝑣𝑛 ] − [ 𝑉̇𝐿,𝑣 ] (13)
zero-sequence voltage and the cluster current formulate the
̇
𝑉𝑤𝑛 ̇𝑉𝑆,𝑤𝑛 𝑉̇𝐿,𝑤
different active power between the clusters in the
MMCC-SSBC. This phenomenon is used for the dc-link ̇ , 𝑉𝐿,𝑣
where the 𝑉𝐿,𝑢 ̇ 𝑎𝑛𝑑 𝑉𝐿,𝑤
̇ are the BEFs of the Lac. The
capacitor voltage balancing control between the phase-clusters ̇ , 𝑉𝐿,𝑣
𝑉𝐿,𝑢 ̇ and 𝑉𝐿,𝑤
̇ can be expressed as
under asymmetrical grid fault conditions, which value is solved 𝑉̇𝐿,𝑢 ̇
𝐼𝑆,𝑢
as follows. [ 𝑉̇𝐿,𝑣 ] = 𝑗𝜔𝑆 𝐿𝑎𝑐 [ 𝐼𝑆,𝑣 ̇ ]
Each phase-cluster voltage of the MMCC-SSBC including 𝑉̇𝐿,𝑤 ̇
𝐼𝑆,𝑤
the Back Electromotive Forces (BEFs) of the interconnection +
𝐼𝑆,𝑞 −
+ 𝐼𝑆,𝑞 −
− 𝑗𝐼𝑆,𝑑
inductor Lac can be expressed as
1 + √3 − 1 √3 + 1 √3 −
̇
𝑉𝑆,𝑢𝑛 ̇
𝑉𝑆,𝑢 (− 𝐼𝑆,𝑞 + 𝐼 − 𝐼 − ) + 𝑗 (− 𝐼 + 𝐼− + 𝐼 )
= −𝜔𝑆 𝐿𝑎𝑐 2 2 𝑆,𝑑 2 𝑆,𝑞 2 𝑆,𝑞 2 𝑆,𝑑 2 𝑆,𝑞
[ 𝑉𝑆,𝑣𝑛̇ ] = [ 𝑉𝑆,𝑣 ̇ ] + 𝑉̇ 0 (7)
̇ ̇ 1 + √3 − 1 √3 + 1 − √3 −
𝑉𝑆,𝑤𝑛 𝑉𝑆,𝑤 (− 𝐼𝑆,𝑞 − 𝐼 − 𝐼− ) + 𝑗 ( 𝐼𝑆,𝑞 + 𝐼𝑆,𝑑 − 𝐼 )
[ 2 2 𝑆,𝑑 2 𝑆,𝑞 2 2 2 𝑆,𝑞 ]
where 𝑉𝑆,𝑢̇ , 𝑉𝑆,𝑣
̇ and 𝑉𝑆,𝑤
̇ are the grid voltage on Bus C, 𝑉̇ 0 is
where the resistance of the Lac is neglected because the
the zero-sequence voltage of the MMCC-SSBC, which is resistance is much smaller than the total impedance given by
voltage difference between the point n and M as shown the inductance. Then maximum phase-cluster peak voltage
mentioned Fig. 3 (a). The 𝑉̇ 0 is defined as Vmax_pu between the three-phases standardized by peak rated
𝑉̇ 0 = 𝑥𝑆𝑆𝐵𝐶 + 𝑗𝑦𝑆𝑆𝐵𝐶 (8)
phase grid voltage √2/3𝑉𝑆 can be expressed as
where the xSSBC is real part of the 𝑉̇ 0 , the ySSBC is imaginary part ̇ |,|𝑉𝑣𝑛
max(|𝑉𝑢𝑛 ̇ |,|𝑉𝑤𝑛
̇ |)
𝑉max _𝑝𝑢 = (15)
of the 𝑉̇ 0 . The 𝑉𝑆,𝑢
̇ , 𝑉𝑆,𝑣
̇ and 𝑉𝑆,𝑤̇ can be expressed as 2
√ 𝑉𝑠
3
̇
𝑉𝑆,𝑢 ̇ + + 𝑉𝑆,𝑑𝑞
𝑉𝑆,𝑑𝑞 ̇−
The maximum phase-cluster r.m.s current Imax_pu between the
[ 𝑉𝑆,𝑣 ̇ 𝑒
̇ ] = [𝑉𝑆,𝑑𝑞
+ −𝑗2𝜋 ⁄ 3 ̇ − 𝑒 𝑗2𝜋 ⁄3 ]
+ 𝑉𝑆,𝑑𝑞 three-phases normalized by the rated phase current √2𝐼𝑟 of the
̇
𝑉𝑆,𝑤 ̇ + 𝑒 𝑗2𝜋 ⁄3 + 𝑉𝑆,𝑑𝑞
𝑉𝑆,𝑑𝑞 ̇ − 𝑒 −𝑗2𝜋 ⁄3 STATCOM can be expressed as
+ − − max(|𝐼𝑢̇ |,|𝐼𝑣̇ |,|𝐼𝑤
̇ |)
(𝑉𝑆,𝑑 + 𝑉𝑆,𝑑 ) + 𝑗(𝑉𝑆,𝑞 ) 𝐼max _𝑝𝑢 = (16)
√2𝐼𝑟
1 + 1 − √3 − √3 + √3 − 1
(− 𝑉𝑆,𝑑 − 𝑉𝑆,𝑑 − 𝑉 ) + 𝑗 (− 𝑉 + 𝑉 − 𝑉− ) Fig. 4 with line graphs show calculated result of the
= 2 2 2 𝑆,𝑞 2 𝑆,𝑑 2 𝑆,𝑑 2 𝑆,𝑞 (9)
normalized maximum phase-cluster peak voltage and r.m.s
1 + 1 − √3 − √3 + √3 − 1 current of the MMCC-SSBC under the different types of the
(− 𝑉𝑆,𝑑 − 𝑉𝑆,𝑑 + 𝑉 ) + 𝑗 ( 𝑉𝑆,𝑑 − 𝑉 − 𝑉− )
[ 2 2 2 𝑆,𝑞 2 2 𝑆,𝑑 2 𝑆,𝑞 ]
grid fault scenarios as a function of the voltage dip severity D 2.0
2.0
using (15) and (16). The Iq+ is set to be the rated phase 1.8
1.8
Maximumphase-cluster
phase-cluster
current value as √2𝐼𝑟 . The grid voltage is given by the 1.6 Single-phase
1.6 fault
Single-phase fault
[p.u]
1.4
1.4 Voltage
Voltage saturation
saturation level(1.25
level (1.25p.u.)
p.u.)
[p.u.]
mentioned Table II. The normalized inductance of the Lac is set 1.2
1.2
voltage
at 6% with reference to the model mentioned in Table III. In the 1.0 Phase-to-phase
1.0 Phase-to-phase fault
voltage
fault
case of a single-phase fault, the maximum-phase-cluster peak 0.8
0.8
Maximum
peak
0.6 Two-phase-to-ground
0.6 Two-phase-to-ground faultfault Note: The zero-sequence
voltage reaches the voltage saturated level of the designed ac voltage for the capacitor
0.4 Line: Mathematical modelLine:voltage
0.4 Equation
balancing control
STATCOM when D = 0.45. On the other hand, the 0.2 Mark: PLECS model
0.2 Mark: PLECS simulation
is considered in this graph.
maximum-phase-cluster r.m.s. current does not increase as a 0.0
0.0
0.0
0 0.1 0.2 0.3 0.3 0.4 0.5 0.5 0.6
0.6 0.7 0.8 0.9 0.9 1
function of grid fault conditions. The marks in Fig. 4 indicate Voltage
Voltagedip
dipseverity: D[p.u.]
severity: D [p.u.]
simulation results using PLECS software, which conditions are
shown in the next chapter. The calculation values correspond (a) Maximum-phase-cluster peak voltage
reasonably well with the PLECS simulations based on the given
2.0
2.0
STATCOM configurations.
phase-cluster
1.8
1.8
Single-phase
Single-phasefault
fault
cluster
fault
current [p.u.]
1.4
1.4
Two-phase-to-ground
Two-phase-to-groundfault
fault
Where the zero-sequence AC current with the same 1.2
1.2
Maximum
frequency as the cluster output voltage is injected, the 1.0
1.0
Maximum
0.8
0.8
zero-sequence current and the cluster output voltage formulate 0.6
0.6
Note: The zero-sequence ac
voltage for the capacitor
the different active power between the clusters in the 0.4
0.4 Line: Mathematical model
Line: Equation
voltage balancing control is
MMCC-SDBC. This phenomenon is used for the dc-link 0.2
0.2 Mark: PLECS model Mark:considered in this graph.
PLECS simulation
capacitor voltage balancing control among the phase-clusters 0.0
0.0
0.0
0 0.1
0.1 0.2
0.2 0.3
0.3 0.4 0.5 0.6
0.4 0.5 0.6 0.7
0.7 0.8
0.8 0.9
0.9 11
under asymmetrical grid fault conditions, which value is solved Voltage
Voltagedip
dipseverity: D[p.u.]
severity: D [p.u.]
as follows.
For the configuration of MMCC-SDBC, the phase-cluster (b) Maximum-phase-cluster r.m.s. current
̇ , 𝐼𝑣𝑤
current 𝐼𝑢𝑣 ̇ , 𝐼𝑤𝑢
̇ can be expressed as Fig. 4. Maximum-phase-cluster output of the MMCC-SSBC corresponding
to various grid fault scenario
𝐼𝑢𝑣 ̇ ̇ 𝑒 𝑗𝜋⁄6 + 𝐼𝑆,𝑑𝑞
+
𝐼𝑆,𝑑𝑞 ̇ 𝑒 −𝑗𝜋 ⁄6
−
1 +
𝐼𝑆,𝑞 − −
(𝑉𝑆,𝑑 − +
𝑉𝑆,𝑑 − 𝑉𝑆,𝑑 − −
𝑉𝑆,𝑑 − 𝑉𝑆,𝑞 −
𝑉𝑆,𝑞 ) + 𝐼𝑆,𝑞 +
𝑉𝑆,𝑑 +
(𝑉𝑆,𝑑 −
− 𝑉𝑆,𝑑 −
) − 𝐼𝑆,𝑑 + −
𝑉𝑆,𝑑 𝑉𝑆,𝑞
[𝐼𝑣𝑤 ̇ ]= +̇ 𝑒 −𝑗𝜋 2 + 𝐼𝑆,𝑑𝑞
[ 𝐼𝑆,𝑑𝑞 ⁄ ̇ 𝑒 𝑗𝜋⁄2 ] + 𝐼 0̇
−
𝐼 ̇0 =
̇ √3 − −
√3(𝑉𝑆,𝑑 + +
𝑉𝑆,𝑑 − 𝑉𝑆,𝑑 − −
𝑉𝑆,𝑑 + 𝑉𝑆,𝑞 𝑉𝑆,𝑞 )
𝐼𝑤𝑢 ̇ 𝑒 𝑗5𝜋 ⁄6 + 𝐼𝑆,𝑑𝑞
+
𝐼𝑆,𝑑𝑞 −̇ 𝑒 −𝑗5𝜋 ⁄6
+ − − − − + − − + + − − + −
+
𝐼𝑆,𝑞 𝐼 −
𝐼 − +
𝐼𝑆,𝑞 𝐼− 𝐼−
𝐼𝑆,𝑞 (𝑉𝑆,𝑑 𝑉𝑆,𝑞 + 𝑉𝑆,𝑑 𝑉𝑆,𝑞
+ 𝑉𝑆,𝑑 𝑉𝑆,𝑞 ) + 𝐼𝑆,𝑑 𝑉𝑆,𝑑 (𝑉𝑆,𝑑 + 𝑉𝑆,𝑑 ) − 𝐼𝑆,𝑞 𝑉𝑆,𝑑 𝑉𝑆,𝑞
(𝑥𝑆𝐷𝐵𝐶 − + 𝑆,𝑞 + 𝑆,𝑑 ) + 𝑗 (𝑦𝑆𝐷𝐵𝐶 + + 𝑆,𝑞 − 𝑆,𝑑 ) +𝑗 − − + + − −
2√3 2√3 2 2 2 2√3 √3(𝑉𝑆,𝑑 𝑉𝑆,𝑑 − 𝑉𝑆,𝑑 𝑉𝑆,𝑑 + 𝑉𝑆,𝑞 𝑉𝑆,𝑞 )
=
+
√3𝐼𝑆,𝑞 −
𝐼𝑆,𝑞 −
√3𝐼𝑆,𝑑
(17) (20)
(𝑥𝑆𝐷𝐵𝐶 + − ) + 𝑗 (𝑦𝑆𝐷𝐵𝐶 + )
3 3 3 ̇ , 𝑉𝑣𝑤
Each phase-cluster converter output voltage 𝑉𝑢𝑣 ̇ , 𝑉𝑤𝑢
̇ of
+ +
𝐼𝑆,𝑞 𝐼− −
𝐼𝑆,𝑑 𝐼𝑆,𝑞 −
𝐼𝑆,𝑞 −
𝐼𝑆,𝑑
𝑆,𝑞
the MMCC-SDBC can be expressed as
[(𝑥𝑆𝐷𝐵𝐶 − 2√3 + 2√3 − 2
) + 𝑗 (𝑦𝑆𝐷𝐵𝐶 −
2
−
2
−
2√3
)]
𝑉𝑢𝑣 ̇ 𝑉𝑆,𝑢𝑣̇ 𝑉̇𝐿,𝑢𝑣
̇
0
where 𝐼 is the zero-sequence current circulated in the
[ 𝑉𝑣𝑤 ̇
̇ ] = [ 𝑉𝑆,𝑣𝑤 ] − [ 𝑉̇𝐿,𝑣𝑤 ] (21)
MMCC-SDBC. The 𝐼 0̇ can be expressed as
̇
𝑉𝑤𝑢 ̇
𝑉𝑆,𝑤𝑢 𝑉̇𝐿,𝑤𝑢
𝐼 0̇ = 𝑥𝑆𝐷𝐵𝐶 + 𝑗𝑦𝑆𝐷𝐵𝐶 (18)
̇
0
where the xSDBC is real part of the 𝐼 , the ySDBC is imaginary part ̇ , 𝑉𝐿,𝑣𝑤
where the 𝑉𝐿,𝑢𝑣 ̇ ̇
and 𝑉𝐿,𝑤𝑢 are the BEFs of the Lac. The
of the 𝐼 0̇ . Each line-to-line voltage 𝑉𝑆,𝑢𝑣
̇ , 𝑉𝑆,𝑣𝑤
̇ ̇
, 𝑉𝑆,𝑤𝑢 of the ̇ , 𝑉𝐿,𝑣𝑤
𝑉𝐿,𝑢𝑣 ̇ ̇
and 𝑉𝐿,𝑤𝑢 can be expressed as
MMCC-SDBC including the BEFs of the Lac can be expressed 𝑉̇𝐿,𝑢𝑣 𝐼𝑆,𝑢𝑣̇
as ̇
[ 𝑉𝐿,𝑣𝑤 ̇
] = 𝑗𝜔𝑆 𝐿𝑎𝑐 [ 𝐼𝑆,𝑣𝑤 ]
𝑉𝑆,𝑢𝑣̇ ̇ + 𝑒 𝑗𝜋⁄6 + 𝑉𝑆,𝑑𝑞
𝑉𝑆,𝑑𝑞 ̇ − 𝑒 −𝑗𝜋⁄6 𝑉̇𝐿,𝑤𝑢 ̇
𝐼𝑆,𝑤𝑢
+ − − + − −
̇
[𝑉𝑆,𝑣𝑤 ̇ + 𝑒 −𝑗𝜋⁄2 + 𝑉𝑆,𝑑𝑞
] = √3 [ 𝑉𝑆,𝑑𝑞 ̇ − 𝑒 𝑗𝜋⁄2 ] (𝑦𝑆𝐷𝐵𝐶 +
𝐼𝑆,𝑞
+
𝐼𝑆,𝑞
−
𝐼𝑆,𝑑
) + 𝑗 (−𝑥𝑆𝐷𝐵𝐶 +
𝐼𝑆,𝑞
−
𝐼𝑆,𝑞
−
𝐼𝑆,𝑑
)
2 2 2√3 2√3 2√3 2
̇
𝑉𝑆,𝑤𝑢 𝑉̇ + 𝑒 𝑗5𝜋 ⁄6 + 𝑉̇ − 𝑒 −𝑗5𝜋⁄6 −
√3𝐼𝑆,𝑑
+
√3𝐼𝑆,𝑞 −
𝐼𝑆,𝑞
𝑆,𝑑𝑞 𝑆,𝑑𝑞
= −𝜔𝑆 𝐿𝑎𝑐 (𝑦𝑆𝐷𝐵𝐶 +
3
) + 𝑗 (−𝑥𝑆𝐷𝐵𝐶 −
3
+
3
) (22)
√3 + − − + − −
{(√3𝑉𝑆,𝑑 + √3𝑉𝑆,𝑑 + √3𝑉𝑆,𝑞 ) + 𝑗(𝑉𝑆,𝑑 − 𝑉𝑆,𝑑 + √3𝑉𝑆,𝑞 )} +
𝐼𝑆,𝑞 −
𝐼𝑆,𝑞 −
𝐼𝑆,𝑑 +
𝐼𝑆,𝑞 −
𝐼𝑆,𝑞 −
𝐼𝑆,𝑑
2 [(𝑦𝑆𝐷𝐵𝐶 − 2
−
2
−
2√3
) + 𝑗 (−𝑥𝑆𝐷𝐵𝐶 +
2√3
−
2√3
+
2
)]
− + −
= √3{−𝑉𝑆,𝑞 + 𝑗(−𝑉𝑆,𝑑 + 𝑉𝑆,𝑑 )} where the resistance of the Lac is neglected. The
√3 − + − + − −
maximum-phase-cluster peak voltage and r.m.s. current of the
[ {(𝑉𝑆,𝑞 − √3𝑉𝑆,𝑑 − √3𝑉𝑆,𝑑 ) + 𝑗(𝑉𝑆,𝑑 − 𝑉𝑆,𝑑 − √3𝑉𝑆,𝑞 )} ] MMCC-SDBC can be calculated in the same way as the
2
(19) MMCC-SSBC.
The 𝐼 ̇0 in order to make the instantaneous active powers Fig. 5 with line graphs show the normalized
between the phase-clusters to have the same value can be maximum-phase-cluster peak voltage and r.m.s. current of the
expressed as follows [24]: MMCC-SDBC under the different types of the grid fault
scenarios in respect to the voltage dip severity D. The Iq+ is set
to be the rated phase current value as √2𝐼𝑟 . The grid voltage is
given by the mentioned Table II. The normalized inductance of
Lac is set at 6% with reference to the model mentioned in Table 2.0
2.0
1.8 Line: Mathematical model
Line: Equation
1.8
phase-cluster
III. It is noted that the maximum-phase-cluster peak voltage 1.6
1.6
Mark: PLECS
Mark: PLECSsimulation
model
Maximu cluster
1.4
1.4
voltage [p.u.]
maximum-phase-cluster r.m.s. current increases rapidly when 1.2
1.2 Phase-to-phase fault
Phase-to-phase fault
D < 0.5 below under the phase-to-phase short-circuit fault and 1.0
1.0
0.8
Maximum
0.8
two-phase-to-ground fault, and reach the over current level 0.6
0.6 Single-phase fault
Single-phase fault Note: The zero-sequence
(1.25) decided by over junction temperature of the IGBT model, 0.4
0.4 Two-phase-to-ground
Two-phase-to-ground
ac current for the capacitor
faultfault voltage balancing control
which will be discussed in the next chapter. When D 0.2
0.2 is considered in this graph.
0.0
0.0
approaches 0 under these faults, the current approaches to 0.0
0 0.1
0.1 0.2
0.2 0.3
0.3 0.4 0.5 0.6
0.4 0.5 0.6 0.7
0.7 0.8
0.8 0.9
0.9 11
infinity value while the denominator of the (20) is close to zero. Voltage
Voltagedip
dipseverity: D[p.u.]
severity: D [p.u.]
When D is zero under these fault voltages, there is no solution
(a) Maximum-phase-cluster peak voltage
of the zero-sequence current, and it is claimed to be the major
problem of the MMCC-SDBC for the STATCOM application 2.0
2.0
[9], [29]. The marks in Fig. 5 indicate simulation results using Infinity Phase-to-phase fault
Phase-to-phase fault
1.8
1.8
Maximumphase-cluster
phase-cluster
PLECS software and the condition is shown next chapter. The 1.6
1.6
Maximum cluster
1.4
1.4
[p.u.]
calculation values correspond reasonably well with the PLECS Over current level (1.25p.u.)
(1.25 p.u.)
current
1.2
1.2
simulation values based on the practical scaled STATCOM 1.0
1.0 Two-phase-to-groundfault
fault
current
Two-phase-to-ground
model. 0.8
0.8
Maximum
Single-phasefault
fault
r.m.s.
Single-phase
0.6
0.6 Note: The zero-sequence
D. The MMCC-DSCC with circulating DC current and DC 0.4
0.4 Line:acEquation
Line: Mathematical model current for the capacitor
voltage balancing control
voltage between terminal P and N 0.2
0.2 Mark: PLECS model Mark:is PLECS simulation
considered in this graph.
0.0
0.0
The DSCC has two neutral points P and N in each single star 0.0
0 0.1 0.2 0.3
0.3 0.4 0.50.5 0.6 0.7 0.8 0.8 0.9
0.9 11
connection. The differential voltage VPN between P and N is Voltage
Voltagedip
dipseverity: D[p.u.]
severity: D [p.u.]
normally 50 % of the rated dc-link voltage each converter cell
in the DSCC in order to output AC voltage using the chopper (b) Maximum-phase-cluster r.m.s. current
converter cells. Where the circulating dc current is injected in Fig. 5. Maximum-phase-cluster output of the MMCC-SDBC corresponding
each leg of the DSCC, the circulating current and the VPN to various grid fault scenario
formulate the independent active power between the legs in the
MMCC-DSCC. This phenomenon is used for the dc-link 𝑖𝑧,𝑢 𝑖𝑢𝑢 + 𝑖𝑢𝑙
1
capacitor voltage balancing control among the legs under [ 𝑖𝑧,𝑣 ] = [ 𝑖𝑣𝑢 + 𝑖𝑣𝑙 ] (25)
2
asymmetrical grid fault conditions, which value is solved as 𝑖𝑧,𝑤 𝑖𝑤𝑢 + 𝑖𝑤𝑙
follows. Based on (23) and (24), the circulating currents to cancel out
The instantaneous active power on frame pS,, pS,, pS,0 the instantaneous active power imbalance among the phases
of the MMCC-DSCC arising from asymmetrical reactive arising by the asymmetrical reactive power output operation
power supply can be expressed as can be expressed as
1 1 1 1 0
1 − − ̇ ∗ ∙ 𝐼𝑆,𝑢
ℜ[𝑉𝑆,𝑢 ̇ ] 𝑖𝑧,𝑢
𝑝𝑆,𝛼 2 2 2
1 −
1 √3 𝑃𝑆,𝛼
2
[𝑝𝑆,𝛽 ] = 0 √3
−
√3 1
̇ ∗ ∙ 𝐼𝑆,𝑣
ℜ[𝑉𝑆,𝑣 ̇ ] (23) [ 𝑖𝑧,𝑣 ] = 2 2 [ ] (26)
3 2 2 2 𝑉𝑃𝑁 𝑃𝑆,𝛽
𝑝𝑆,0 𝑖𝑧,𝑤 1 √3
1 1 1 1
̇∗ ̇ [− 2 − 2 ]
[√2 √2 √2 ] [2 ℜ[𝑉𝑆,𝑤 ∙ 𝐼𝑆,𝑤 ]] ̇
̇ , 𝑉𝑆,𝑣
̇ and 𝑉𝑆,𝑤
̇ , are the same as The AC component of each arm output voltages 𝑉𝑃𝑈,𝑎𝑐 ,
where the 𝑉𝑆,𝑢 ̇ ̇ ̇ ̇ ̇
̇ ̇ ̇ 𝑉𝑃𝑉,𝑎𝑐 , 𝑉𝑃𝑊,𝑎𝑐 , 𝑉𝑁𝑈,𝑎𝑐 , 𝑉𝑁𝑉,𝑎𝑐 and 𝑉𝑁𝑊.𝑎𝑐 can be expressed as
(9), the 𝐼𝑆,𝑢 , 𝐼𝑆,𝑣 and 𝐼𝑆,𝑤 are the same as (10). It is noted that
𝑉̇𝑃𝑈,𝑎𝑐 −𝑉𝑆,𝑢 ̇ 𝑉̇𝐿,𝑢𝑢
the 𝑝𝑆,𝛼 and 𝑝𝑆,𝛽 are the instantaneous active power imbalances
𝑉̇𝑃𝑉,𝑎𝑐 −𝑉𝑆,𝑣 ̇ 𝑉̇𝐿,𝑣𝑢
among the phases. The 𝑝𝑆,0 shows the instantaneous active ̇𝑉𝑃𝑊,𝑎𝑐 ̇
−𝑉𝑆,𝑤 𝑉̇𝐿,𝑤𝑢
power of the three-phase MMCC-DSCC. Normally, each = − (27)
converter cell of the MMCC-DSCC has injected dc-bias 𝑉̇𝑈𝑁,𝑎𝑐 ̇
𝑉𝑆,𝑢 𝑉̇𝐿,𝑢𝑙
voltage with 50% of modulation factor in order to output AC 𝑉̇𝑉𝑁,𝑎𝑐 𝑉𝑆,𝑣 ̇ 𝑉̇𝐿,𝑣𝑙
(+/-) voltage using chopper cells which dc-bias voltage appears [𝑉𝑊𝑁,𝑎𝑐 ] [ 𝑉𝑆,𝑤 ] [ 𝑉̇𝐿,𝑤𝑙 ]
̇ ̇
to be the differential voltage VPN between P and N terminal. The ̇
where the 𝑉𝐿,𝑢𝑢 ̇ , 𝑉𝐿,𝑤𝑢
, 𝑉𝐿,𝑣𝑢 ̇ ̇ , 𝑉𝐿,𝑣𝑙
, 𝑉𝐿,𝑢𝑙 ̇ 𝑎𝑛𝑑 𝑉𝐿,𝑤𝑙̇ are BEFs of
VPN can be expressed as ̇
the Lac. The 𝑉𝐿,𝑢𝑢 ̇
, 𝑉𝐿,𝑣𝑢 ̇
, 𝑉𝐿,𝑤𝑢 ̇ , 𝑉𝐿,𝑣𝑙
, , 𝑉𝐿,𝑢𝑙 ̇ ̇
and 𝑉𝐿,𝑤𝑙 can be
2
𝑉𝑃𝑁 = 2√ 𝑉𝑠 𝛼𝑚𝑔𝑛 (24) expressed as
3
𝑉̇𝐿,𝑢𝑙 𝑉̇𝐿,𝑢𝑢 ̇
𝐼𝑆,𝑢 𝑉̇𝐿,𝑢
where mgn is the ratio between maximum converter output ̇ ̇ 𝜔𝑆 𝐿𝑎𝑐 1
[ 𝑉𝐿,𝑣𝑙 ] = − [ 𝑉𝐿,𝑣𝑢 ] = 𝑗 [ 𝐼𝑆,𝑣 ] = [ 𝑉̇𝐿,𝑣 ]
̇ (28)
voltage and rated grid voltage and as a used design margin. The 2 2
circulating currents of each of the leg iz,u, iz,v and iz,w can be 𝑉̇𝐿,𝑤𝑙 𝑉̇𝐿,𝑤𝑢 ̇
𝐼𝑆,𝑤 𝑉̇𝐿,𝑤
expressed as
where the resistance of the Lac is neglected. The
̇ , 𝑉𝐿,𝑣
𝑉𝐿,𝑢 ̇ and 𝑉𝐿,𝑤
̇ were given in (14). The maximum arm 2.0 Single-phase
2.0 Single-phase fault
fault
1.8
1.8
output peak voltage Vmax_pu between the arm-converters
output
phase-cluster
1.6 Phase-to-phase fault
1.6
[p.u.]
fault
̇
𝑉𝑃𝑁 +max(|𝑉𝑃𝑈,𝑎𝑐 ̇
|,|𝑉𝑃𝑉,𝑎𝑐 ̇
|,|𝑉𝑃𝑊,𝑎𝑐 ̇
|,|𝑉𝑈𝑁,𝑎𝑐 ̇
|,|𝑉𝑉𝑁,𝑎𝑐 ̇
|,|𝑉𝑊𝑁,𝑎𝑐 |) 1.2 Two-phase-to-ground fault
1.2
Maximum
voltage
𝑉max _𝑝𝑢 = (29) 1.0
1.0
voltage
2
√ 𝑉𝑠
Maximum
Maximum
3 0.8
0.8 Note: The circulating dc
peak
Each arm output r.m.s. current iuu,rms, ivu,rms, iwu,rms, iul,rms, ivl,rms 0.6
0.6 current and Vpn as dc value
Line: Equation
0.4 Line:
0.4 Mathematical model for the capacitor voltage
and iwl,rms can be expressed as balancing control is
0.2 Mark:
0.2 Mark: PLECS
PLECS simulation
model
̇ 2 2 considered in this graph.
√(|𝐼𝑆,𝑢 |) + (𝑖𝑧,𝑢 ) 0.0
0.0
√2 2 0.0
0 0.1 0.2 0.2 0.3
0.3 0.40.4 0.50.5 0.6
0.6 0.70.7 0.8 0.9 0.9 11
𝑖𝑢𝑢,𝑟𝑚𝑠 𝑖𝑢𝑙,𝑟𝑚𝑠 Voltage
̇ | 2 2 Voltagedipdipseverity: D [p.u.]
severity: D [p.u.]
[ 𝑖𝑣𝑢,𝑟𝑚𝑠 ] = [ 𝑖𝑣𝑙,𝑟𝑚𝑠 ] = √(|𝐼𝑆,𝑣 𝑖
) + ( 𝑧,𝑣) (30)
√2 2 (a) Maximum arm output peak voltage
𝑖𝑤𝑢,𝑟𝑚𝑠 𝑖𝑤𝑙,𝑟𝑚𝑠
2
̇ 𝑖𝑧,𝑤 2
√ |𝐼𝑆,𝑤| 2.0
2.0
[ ( √2 ) + ( 2 ) ] 1.8
1.8 Single-phase fault
armoutput
phase-cluster
The maximum arm output r.m.s current Imax_pu normalized by 1.6
1.6 Phase-to-phase
Phase-to-phasefault
fault
[p.u.]
the rated arm current of the STATCOM 1/2𝐼𝑟 can be expressed Two-phase-to-ground
Two-phase-to-groundfault
[p.u.]
[p.u.]
1.4
1.4 fault
as
arm
voltage
1.2
1.2
current
Maximum
current
max(𝑖𝑢𝑢,𝑟𝑚𝑠 ,𝑖𝑣𝑢,𝑟𝑚𝑠 ,𝑖𝑤𝑢,𝑟𝑚𝑠) 1.0
1.0
𝐼max _𝑝𝑢 = (31)
Maximum
Maximum
𝐼𝑟 /2 0.8
0.8
peak
Note: The circulating dc
Fig. 6 with line graphs show the calculated result of the
r.m.s.
0.6
0.6 current and Vpn as dc value
normalized maximum arm output peak voltage and r.m.s. 0.4
0.4 Line:Equation
Line: Mathematical model for the capacitor voltage
Mark: PLECS
PLECSsimulation
model balancing control is
current of the MMCC-DSCC under the different types of the 0.2
0.2 Mark: considered in this graph.
grid fault scenarios regarding of the voltage dip severity D by 0.0
0.0
0.0
0 0.1
0.1 0.2
0.2 0.3
0.3 0.4
0.4 0.5
0.5 0.6
0.6 0.7
0.7 0.8
0.8 0.9
0.9 11
using (29) and (31). The Iq+ is set to be the rated phase Voltage
Voltagedip
dipseverity:
severity: DD[p.u.]
[p.u.]
current value as √2𝐼𝑟 . The grid voltage is given by the
(b) Maximum arm output r.m.s. current
mentioned Table II. The normalized inductance of Lac is set to
Fig. 6. Maximum arm output of the MMCC-DSCC corresponding to various
be 6%, the mgn is set at 1.127 with reference to the practical grid fault scenario
scale model in mentioned Table III. It is noted that the
maximum arm output peak voltage and r.m.s current do not
increase significantly under different grid fault conditions. The 2.0
2.0
1.8
1.8 Single-phase fault
marks in Fig. 6 plot the simulation result using the PLECS Single-phase fault
output
phase-cluster
1.6
1.6 Phase-to-phase fault
Phase-to-phase fault
[p.u.]
1.4
[p.u.]
0.6
0.6 current and Vpn as dc value
E. The MMCC-DSBC with circulating DC current and DC 0.4
0.4 Line: Mathematical model for the capacitor voltage
Line:Equation
balancing control is
0.2
0.2 Mark:
Mark:PLECS
PLECS simulation
model
voltage between terminal P and N considered in this graph.
0.0
0.0
The operation principle of the MMCC-DSBC is almost the 0.0
0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.7 0.8 0.9 11
same as the MMCC-DSCC. The only difference is the Voltage
Voltagedip
dip severity:
severity: DD[p.u.]
[p.u.]
amplitude of the VPN. In the case of the MMCC-DSBC, each of (a) Maximum arm output peak voltage
the arms is able to supply AC (+/-) voltage without the VPN
2.0
2.0
because of the used H-Bridge converter cells. However, due to
1.8
1.8
output
phase-cluster
the voltage balancing control, the V’PN is required, which can be 1.6
1.6 Single-phase
Single-phase fault
fault
[p.u.]
[p.u.]
expressed as
[p.u.]
arm
1.4
1.4 Over
Overcurrent
current level
level
arm
′
𝑉𝑃𝑁 = 𝛼𝐷𝑆𝐵𝐶 𝑉𝑃𝑁 (32)
voltage
current
1.2 Phase-to-phase
1.2 Phase-to-phase fault
fault (1.07 p.u.)
(1.07 p.u.)
Maximum
current
Two-phase-to-ground fault
Two-phase-to-ground fault
between terminal P and N of the DSCC to the DSBC. The
peak
0.8
0.8
r.m.s.
Power module 2
Power module 3
Power module 4
tD(j-c1)
Iq+ is set to be the rated phase current value as √2𝐼𝑟 . The grid
voltage is given by the mentioned Table II. The normalized tD(j-c4)
inductance of Lac is set to 6%, the mgn is set at 1.127 with tS(j-c4)
reference to the practical scale model given in Table III. The
marks are the practical scaled simulation results, which test RS(j-c4) RD(j-c4)
conditions will be shown next chapter. It is noted that the Tc
maximum arm peak voltage tracks 1 p.u. by the injected V’PN as IGBT chip to case R(c-h) Diode chip to case
the designed maximum value. The maximum arm r.m.s. current thermal impedance thermal impedance
increases moderate in respect to the D, but reach the over
current level (1.07) which is decided by the over junction +
Th
temperature of the IGBT module, which is shown next chapter. -
The arm current becomes larger than the DSCC because of
lower the V’PN. The over current level becomes lower than the Fig. 8. Thermal network between power semiconductor chip and heat
SDBC because the current distribution between the IGBT sink on each cell converter.
modules in a converter cell increases by injected dc voltage and
current for the capacitor voltage balancing method. The marks the Diodes, and recovery loss of the Diodes in the power
in Fig. 7 show the simulation result using PLECS software, modules. The electrical loss parameters depending on the
which conditions are given in the next chapter. The calculated flowing currents, applied voltages, and junction temperatures
values correspond reasonably well with the PLECS simulation are selected from the datasheets for the power modules in
values based on practical scale STATCOM model. mentioned Table III [31]. The thermal network between the
power semiconductor chip and heatsink for power module are
V. PERFORMANCE BENCHMARK OF MMCC SOLUTIONS constructed by Foster RC network as shown in Fig. 8. Here, pS
is power loss of IGBT chip; pD is power loss of Diode chip; TS_j
A. Electrical and thermal simulation modeling is junction temperature of IGBT; TD_j is junction temperature of
In this paper, the LVRT capability of a STATCOM which is Diode; Tc is the case temperature in the power semiconductor
based on the MMCC with SSBC, SDBC, DSCC, and DSBC is module; Th is heat sink temperature; RS(j-cn), tD(j-cn), RS(j-cn)
simulated by using the software PLECS. The three types of grid and tD(j-cn) are thermal parameters for the Foster RC network
fault voltage are given by the mentioned voltage vector as of the power semiconductor module (n:1-4). The thermal
shown in Table II. The voltage is applied at the Bus B side of impedances of the power modules are also selected from the
the TR2 as shown in mentioned Fig. 2, as discussed in section II. datasheets. The heat sink temperature based on liquid cooling
In order to fix the standard voltage vectors applied to the system is considered as a constant value at 60 ℃ in this
MMCC, the impedance of the TR2 is neglected. The simulation model because the temperature of the heatsink is
specifications of the MMCC with SSBC, SDBC, and DSCC are normally much lower and more stable compared with the
assembled based on the parameter in Table III. The reactive junction temperature in a properly designed converter system.
current reference is set to rated 1 p.u. of the positive-sequence
only as recent grid codes do not require negative sequence B. Electrical and thermal simulation of the MMCC-SSBC
current to compensate for the asymmetrical grid voltage. Fig. 9 shows the key waveforms of the MMCC-SSBC under
The modulation scheme for the MMCC with SSBC, SDBC, the single-phase-to-ground fault with the dip severity D of 0.5
DSCC, and DSBC are selected widely-used Phase Shift PWM p.u.. It can be seen that the peak value of the voltage reference
as mentioned in sub-section III-B. The output current is increases by 22% maximum on w phase cluster under the
controlled by a dual-frame control scheme with sequence single-phase-to-ground fault in order to inject zero-sequence
decoupling using a notch filter [30]. The capacitor voltage voltage vzero to balance the DC-link capacitor voltages of the
control method for SSBC is selected [11] with a zero-sequence converter cells. Here, the injected zero-sequence voltage is
AC voltage injection. The capacitor voltage control method for expressed by (34) when all capacitor voltages are balanced.
SDBC is selected [12] with a zero-sequence AC current v *u1 v * v1 v * w1
injection. The capacitor voltage control method for DSCC is v *zero (34)
3
selected [13] with a circulating DC currents injection method. Fig. 10 shows the junction temperatures of four IGBTs and
The capacitor voltage control method for DSBC is selected [15] diodes in each cell of u1, v1 and w1 under the same simulation
using a circulating DC current injection method. conditions. The peak junction temperature of the IGBT and
The electrical losses and junction temperatures on each Diode are the same, 115℃ and 109℃ respectively among the
power semiconductor module are simulated by thermal
different cluster cells. The temperatures are below the limit of
simulation function on the PLECS. The electrical losses of the
128 ℃ by considering a 15 % margin for the IGBT modules
power semiconductor modules consist of the conduction loss of
the IGBTs, turn on / off loss of the IGBTs, conduction loss of
200k v-phase w-phase 1.0
u-phase
(on Bus B) (V)
0.9
Test voltage
[p.u]
command[p.u.]
0 0.8
voltagecommand
0.7
-200k 0.6
0.5
40k 0.4
Peakvoltage
vun vvn
vwn
PWM voltage
Peak
-20k 0.1 Two-phase-to-ground fault
40k
0.0
0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1
Voltage dip severity:
Dip severity on PCC DB[p.u.]
[p.u.]
Output current
2k
iS,u iS,v iS,w
(a) Peak voltage command
(A)
0
130
-2k
[°C]
Temperature limitation Tmax: 128℃ (=150℃×0.85)
temperature[℃]
120
junctiontemperature
1
v*u1 v*v1 110
Voltage command
v*w1
IGBT
value (p.u.)
100 Diode
0
*
v zero 90
Peakjunction
-1 80 Phase-to-phase fault
Two-phase-to-ground fault
DC-link capacitor
vcw1-13 70
Peak
2.8k
vcu1-13 vcv1-13 Single-phase fault
voltage (V)
2.6k 60
0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1
2.4k 10 ms Voltage
Dip dip on
severity severity:
PCC DD B [p.u.]
130
Temperature limitation: 128℃ (150℃×0.85) voltages of the converter cells. Here, the injected zero-sequence
120 IGBT: 114℃ peak IGBT: 115℃ peak IGBT: 114℃ peak current is expressed by (35).
Junction temperature [℃]
[p.u.]
command[p.u]
0 0.8
0.7
voltagecommand
-200k 0.6
0.5
vuv vvw vwu 0.4
Peakvoltage
50k
PWM voltage
0
0.2 Phase-to-phase fault
Peak
-50k 0.1 Two-phase-to-ground fault
0.0
0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1
Output current
[°C]
temperature[℃]
ivw iwu 120 Temperature limitation Tmax:
Diode
Cluster current
1k
106℃ (=125℃×0.85)
iuv
junctiontemperature
110
(A)
0
100
-1k
izero IGBT
90
Peakjunction
1 * *
Voltage command
v u1 v v1 v *
w1
80
Phase-to-phase fault
value (p.u.)
70 Two-phase-to-ground fault
0
Peak
Single-phase fault
60
-1
0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1
Voltage
Dip dip on
severity severity:
PCC DDB [p.u.]
vcu1-23 vcv1-23 vcw1-23
DC-link capacitor
2.8k
(b) Peak junction temperature
voltage (V)
2.6k
Fig. 14. Electrical-thermal simulations of the MMCC-SDBC at different dip
severities
2.4k 10 ms
Fig. 17 shows the maximum peak voltage command value
Fig. 12 Key waveforms of the MMCC-SDBC under phase-to-phase fault
with a dip severity D of 0.4 p.u.
and peak junction temperature among the arms regarding the
voltage dip severity D under the various grid fault scenarios. It
Temperature limitation: 106℃ (125℃×0.85) can be noted that the peak voltage command does not saturate
130
in the various grid fault scenarios. The peak junction
120
temperature does not reach the temperature limitation in the
Junction temperature [℃]
80
Diode: 67℃ peak Diode: 121℃ peak Diode: 121℃ peak Fig. 18 shows the simulated key waveforms of the
IGBT: 114℃ peak IGBT: 114℃ peak
IGBT: 66℃ peak
MMCC-DSBC under the single-phase-to-ground fault with dip
70
severity D = 0.4 p.u.. It can be noted that the arm currents and
60
2.8 2.9 3.0 2.8 2.9 3.0 2.8 2.9 3.0 PWM output voltage of each arm contain the dc component as
Time[sec] Time[sec] Time[sec]
(a) u1-cell (b) v1-cell (c) w1-cell
well as the DSCC. However, the amplitude of the PWM output
Fig. 13. Thermal distribution of the MMCC-SDBC under phase-to-phase voltage with dc-component is smaller than the DSCC because
fault with the dip severity D of 0.4 p.u. of avoiding the voltage saturation of each cell output voltage
command. In this result, the circulating DC current increases
It is noted that the r.m.s. value of the arm current increases by for the capacitor voltage balancing control.
only a few % under the phase-to-phase fault. Fig. 19 shows the junction temperatures of IGBTs and diodes
Fig. 16 shows the junction temperatures of IGBTs and diodes in the chopper converter cells uu1, vu1, wu1, ul1, vl1 and wl1
in the chopper converter cells uu1, vu1, wu1, ul1, vl1 and wl1 under the same conditions. The junction temperatures are
under the same condition. The junction temperatures are widely widely distributed among the arms compared with the
distributed among the arms compared with the other MMCC MMCC-SDBC because injected dc-component with different
types because the chopper converter cells are used with modulation factor among the arms. The peak junction
different modulation factor among the arms. The peak junction temperature increases to maximum 104 ℃ at the diodes of uu1
temperature increases to maximum 104 ℃ at the diodes of u1 cells. This temperature is below the limit of 106 ℃ by
cells. This temperature is below the limit of 106 ℃ by considering a 15 % margin for the IGBT modules with the
considering a 15 % margin for the IGBT modules with the absolute maximum rating of junction temperature which is
absolute maximum rating of junction temperature defined by defined by the manufacturer.
the manufacturer.
200k u-phase v-phase Temperature limitation: 106℃ (125℃×0.85)
130
vUN vVN 90
50k
PWM voltage
80
vWN
(V)
2k
iS,u iS,v iS,w
(A)
1k
100
0 90
-1k 80
ivl ivu iZu iZv iZw
Saul1 Daul1 Savl1 Davl1 Sawl1 Dawl1
70
Sbul1 Dbul1 Sbvl1 Dbvl1 Sbwl1 Dbwl1
1 * *
Voltage command
v uu1 v vl1 60
2.9 3.0 2.8 3.0
2.8 2.9 3.0 2.8 2.9
value (p.u.)
2.8k
1.0
voltage (V)
[p.u.]
command[p.u.]
2.6k
vcul1-26 0.9
2.4k vcvl1-26 vcwl1-26 10 ms
voltagecommand
Fig. 15. Key waveforms of the MMCC-DSCC under phase-to-phase fault 0.8
with a dip severity D of 0 p.u.
Peakvoltage
0.7
Fig. 20 shows the maximum peak voltage command value Single-phase fault
and peak junction temperature among the arms regarding dip 0.6 Phase-to-phase fault
Peak
severity D under the various grid fault scenarios. It can be noted Two-phase-to-ground fault
0.5
that the peak voltage command keeps same value under the 0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1
various grid fault conditions with the different voltage dip Voltage
Dip dipon
severity severity:
Bus B: DDB[p.u.]
[p.u.]
severity because the VPN is injected maximum value to
(a) Peak voltage command
minimize the amplitude of the circulating DC current. The peak
130
junction temperatures exceed the limitation value when D is
[℃]
tempelature[°C]
lower than 0.6. However, the slope is moderate compared with 120
Temperature limitation Tmax:
junctiontemperature
100 Diode
F. Performance Comparison between the MMCC family
90
Fig. 21 (a) shows the reactive current compensation IGBT
junction
capability for the MMCC solutions with SSBC, SDBC, DSCC 80 Phase-to-phase fault
70
Peak
Single-phase fault
different dip severity D with various grid faults. The
60
compensation capability limits of MMCC family are 0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1
determined by the modulation saturation point and maximum Voltage dip severity:
Dip severity on PCC DA[p.u.]
[p.u.]
junction temperature. The (b) and (c) plot the peak voltage (b) Peak junction temperature
command and peak junction temperature of the IGBT modules Fig. 17. Electrical-thermal simulations of the MMCC-DSCC at different dip
in the whole converter cells corresponding to the operating severities
conditions on the (a). The peak voltage command and junction current when the dip severity of the grid voltage is higher than
temperature are normalized by instantaneous dc-link voltage 0.7 p.u., but the reactive current compensation capability shows
each cell converter and temperature limitation value decided by different characteristics for the dip severity lower than 0.7 p.u.
the manufacturer as mentioned in the sub-section V-B, C, and as discussed below.
D. The MMCC family can continue to supply the rated reactive
Temperature limitation: 106℃ (125℃×0.85)
200k v-phase w-phase 130
(on Bus B) (V)
Test voltage
u-phase IGBT: 92℃ peak
120 Diode: 95℃ peak
-200k 100
IGBT: 118℃ peak IGBT: 119℃ peak
90 Diode: 119℃ peak Diode: 117℃ peak
50k vUN vVN vWN
PWM voltage
80
(V)
0 70
60
-50k -vPU -vPV -vPW 2.8 2.9 3.0 2.8 2.9 3.0 2.8 2.9 3.0
Time[sec] Time[sec] Time[sec]
(a) uu1-cell (b) vu1-cell (c) wu1-cell
Output current
100
IGBT: 117℃ peak IGBT: 119℃ peak
iul iuu
Arm current (A)
70
-2k iwu ivl iwl ivu iZu iZv iZw
60
2.8 2.9 3.0 2.8 2.9 3.0 2.8 2.9 3.0
1 Time[sec] Time[sec] Time[sec]
Voltage command
0.8
voltage (V)
2.5 k
0.7
0.6
vcuu1-26 vcul1-26 10 ms 0.5
2.0 k
0.4
Fig. 18. Key waveforms of the MMCC-DSBC under single-phase-to-ground Single-phase fault
0.3
fault with a dip severity D of 0.4 p.u. Phase-to-phase fault
0.2
1) The MMCC-SSBC: It reveals that the SSBC can supply 0.1 Two-phase-to-ground fault
the rated reactive current under phase-to-phase fault and 0.0
two-phase-to-ground fault condition regardless of the dip 0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1
Voltage Dip severity: D [p.u.]
severity. However, the reactive current capability decreases
(a) Peak voltage command
steeply at a voltage dip severity of 0.4 p.u. under
130
single-phase-to-ground fault and it cannot operate anymore
Peak junction tempelature [℃]
[p.u.]
1 D-1
The practical designed SSBC and SDBC have unavailable
[p.u.]
D-3 D-2
0.9
factor
Low Voltage Ride Through operating conditions under some of C-3
index
0.8
the grid fault condition because of the dc-link capacitor voltage A-2
modulation
Modulation
control. The DSCC can keep the operation in all grid fault 0.7 B-1 C-1 B-2 C-2
scenarios for the whole voltage dip severity without any current
0.6
derating. However, the total volume of the MMCC-DSCC
Peak
A-3
seems larger than other MMCC solutions because the total 0.5
B-3
energy stored in the capacitors becomes larger for using 0.4
chopper converter cells. The DSBC can keep the operation in 0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1
Voltage dip severity: D [p.u.]
all grid fault scenarios for the whole dip severity with Voltage dip severity: D [p.u.]
maximum 35% current derating in this case study. The total (b) Voltage command according to the reactive current
cost and volume of the DSBC seem similar to SSBC and SDBC
because of similar total power semiconductor chip area and 1.1
Limitation level D-3 D-1 D-2
total energy stored of the passive components. The present
[p.u.]
1
B-1 B-3
[p.u.]
result suggests that the DSBC becomes the most attractive B-2
temperature
0.9
solution for the STATCOM application on the MMCC family.
temperature
A-2, A-3
As a future work, asymmetrical faulty grid voltage 0.8 C-1, C-3 C-3
0.5
0.4
REFERENCES 0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1
Voltage dip severity: D [p.u.]
[1] IEA, Renewable Energy Medium-Term Market Rport 2015. IEA Voltage dip severity: D [p.u.]
Publications, 2015.
[2] F. Blaabjerg and J. M. Guerrero, ”Smart grid and renewable energy (c) Junction temperature according to the reactive current
systems,” in Proc. Electrical Machines and Systems (ICEMS), 2011, pp. Fig. 21. Reactive current compensation capability of the MMCCs for
1-10. different dip severities.
[3] T. Ackermann, Wind Power in Power Systems 2nd Edition. John Wiley &
Sons Ltd., 2012. [9] E. Behrouzian, M. Bongiorno, “Investigation of Negative-Sequence
[4] H. Akagi, ”Multilevel Converters: Fundamental Circuits and Systems,” Injection Capability of Cascaded H-Bridge Converters in Star and Delta
Proceedings of the IEEE, vol. 105, No. 11, pp. 2048-2065, Nov. 2017 Configuration,” IEEE Trans. on Power Electron., vol. 32, pp. 1675-1683,
[5] M. Pereira, D. Retzmann, M. Wiesinger, and G. Wong, ”SVC PLUS: An Feb. 2017.
MMC STATCOM for Network and Grid Access Applications,” in Proc. [10] T. Kikuma, M. Takasaki, ”A Method Unbalance Compensation on
IEEE Trondheim PowerTech, 2011, pp. 1-5. Y-connection Modular Multilevel Converter,” IEEJ Trans. on Industry
[6] B. Ronner, P. Maibach and T. Thurnherr, “Operational experiences of Applications, vol.132, no.12, pp.1159-1166, 2012.(Japanese)
STATCOMs for wind parks,” IET Renewable Power Generation, Vol. 3, [11] Y. Ota, Y. Shibano, N. Niimura, H. Akagi, ”A Phase-Shifted PWM
Iss. 3, pp. 349-357, 2009. D-STATCOM Using a Modular Multilevel Cascade Converter
[7] M. Claus, S. Mcdonald, P. Cahill, D. Retzmann, M. Pereira and K. (SSBC)—Part II: Zero-Voltage-Ride-Through Capability ,” IEEE Trans.
Uecker, “Innovative VSC Technology for Integration of "Green Energy" on Ind. Appl., Vol. 51, no. 1, pp. 289-296, Jan-Feb. 2015.
- without Impact on System Protection and Power Quality,” in Proc. [12] M. Hagiwara, R. Maeda, H.Akagi, “Negative-Sequence Reactive-Power
CIRED 21st International Conference on Electricity Distribution, Jun. Control by a PWM STATCOM Based on a Modular Multilevel Cascade
2011, pp. 1-4. Converter (MMCC-SDBC),” IEEE Trans. on Ind. Appl., vol. 48, no. 2, pp.
[8] R.E. Betz, T. Summers, T. Furney, “Symmetry Compensation using a 720-729, MAR.-APR. 2012.
H-Bridge Multilevel STATCOM with Zero Sequence Injection,” in Proc. [13] M. Hagiwara, R. Maeda, and H. Akagi, ”Negative-Sequence
IEEE IAS Annual Meeting, Oct. 2006, pp. 1724–1731. Reactive-Power Control by the Modular Multilevel Cascade Converter
Based on Double-Star Chopper-Cells (MMCC-DSCC),” in Proc. of Takaaki Tanaka (M'18) received the B.E.
ECCE, 2010, pp. 3949-3954.
degree in electrical engineering from
[14] M. Guan, Z. Xu, ”Modeling and Control of a Modular Multilevel
Converter-Based HVDC System Under Unbalanced Grid Conditions,” National Institute of Technology, Maizuru
IEEE Trans. on Power Electron., vol. 27, no. 12, pp. 4858-4867, Dec. College, Kyoto, Japan, in 2010 and the M.E.
2012. degree in electrical engineering from
[15] J. Jung, S. Cui, Y. Lee and S. Sul, “A Cell Capacitor Energy Balancing
Nagaoka University of Technology, Niigata,
Control of MMC-HVDC under the AC Grid Faults,” in Proc.
International Conference on Power Electronics 2015 (ECCE-Asia 2015), Japan, in 2012. He is currently a researcher
2015, pp. 1-8. at the Corporate R&D Headquarters, Fuji
[16] T. Tanaka, H. Wang, K. Ma, F. Blaabjerg, “Reactive Power Electric, Co., Ltd., Tokyo, Japan.
Compensation Capability of a STATCOM based on Two Types of
Mr. Tanaka was a Visiting Researcher with the Center of
Modular Multilevel Cascade Converters for Offshore Wind Application,”
in Proc. International Future Energy Electoronics Conference 2017 Reliable Power Electronics (CORPE), Aalborg University,
(ECCE-Asia 2017), 2017, pp. 1-6. Aalborg, Denmark from Dec. 2015 to Nov. 2017. His research
[17] T. Tanaka, H. Wang, K. Ma, F. Blaabjerg, “Low voltage ride through interests include power electronics and its applications such as
performance of a STATCOM based on modular multilevel cascade
in renewable energy, transportation, reliability, power density,
converters for offshore wind application,” in Proc. of ECCE, 2017, pp.
1-8. WBG devices and circuit architecture.
[18] K. Ma, M. Liserre, F. Blaabjerg, “Operating and Loading Conditions of a
Three-Level Neutral-Point-Clamped Wind Power Converter Under Ke Ma (S’09-M’11-SM’18) received the
Various Grid Faults,” IEEE Trans. Ind. Appl., vol. 50, pp. 520-530,
B.Sc. and M.Sc. degrees in electrical
Jan./Feb. 2014.
[19] F. Blaabjerg, D. M. Ionel, Renewable Energy Devices and Systems with engineering from the Zhejiang
Simulations in MATLAB® and ANSYS® 1st Edition. CRC Press, 2017. University, China in 2007 and 2010
[20] T. Neumann, T. Wijnhoven, G. Deconinck, and I. Erlich, “Enhanced respectively. He received the Ph.D.
Dynamic Voltage Control of Type 4 Wind Turbines During Unbalanced
degree from the Aalborg University,
Grid Faults,” IEEE Trans. on Energy Conversion, vol. 30, no. 4, pp.
1650-1659, Dec. 2015 Denmark in 2013, where he became an
[21] IEC 61000-4-34, Electromagnetic compatibility (EMC) - Part 4-34: Assistant Professor in 2014. He was
Testing and measurement techniques - Voltage dips, short interruptions part-time consultant with Vestas Wind
and voltage variations immunity tests for equipment with input current
Systems A/S, Denmark in 2015. In 2016 he joined the faculty
more than 16 A per phase. IEC, 2009.
[22] CIGRE/CIRED/UIE Joint Working Group C4.110, Voltage Dip of Shanghai Jiao Tong University, China as a tenure-track
Immunity of Equipment and Installations, CIGRE, 2010 Research Professor. His current research interests include the
[23] M. H. Bollen, Understanding Power Quality Problems. New York, US: power electronics and its reliability in the application of HVDC,
John Wiley & Sons Ltd., 2000.
renewable energy and motor drive systems.
[24] R. Teodorescu, M. Liserre and P. Rodriguez, Grid Converters for
Photovoltaic and Wind Power Systems, John Wiley & Sons, Ltd, 2011 He is now serving as Associate Editor for two IEEE journals.
[25] K. Ilves, L. Harnefors, S. Norrga, Hans-Peter Nee, “Analysis and In 2016 He was awarded with the “1000 Talents Plan Program
Operation of Modular Multilevel Converters With Phase-Shifted Carrier for Young Professionals” of China. He was the receiver of
PWM,” IEEE Trans. on Power Electron., vol. 30, no. 1, pp. 268-283, Jan.
“Excellent Young Wind Doctor Award 2014” by European
2015
[26] E. Behrouzian, M. Bongiorno, and R. Teodorescu, “Impact of Switching Academy of Wind Energy, and several prized paper awards by
Harmonics on Capacitor Cells Balancing in Phase-Shifted PWM-Based IEEE.
Cascade H-Bridge STATCOM,” IEEE Trans. on Power Electron., vol.
32, no. 1, pp. 815-824, Jan 2017
Huai Wang (M'12, SM’17) received the
[27] Z. He, F. Ma, Q. Xu, Y. Chen, C. Li, M. Li, J. M. Guerrero, A.
Luo, ”Reactive Power Strategy of Cascaded Delta-Connected B.E. degree in electrical engineering, from
STATCOM Under Asymmetrical Voltage Conditions,” IEEE Jour. of Huazhong University of Science and
Emerging and Selected Topics in Power Electron., vol. 5, no. 2, Jun. Technology, Wuhan, China, in 2007 and
2017.
the Ph.D. degree in power electronics,
[28] P. Sochor, H. Akagi, N. M. L. Tan, “Low-Voltage-Ride-Through Control
of a Modular Multilevel SDBC Inverter for Utility-Scale Photovoltaic from the City University of Hong Kong,
Systems,” in Proc. of ECCE, 2017, pp. 1-8. Hong Kong, in 2012. He is currently an
[29] P. Wu, Y. Chen, and P. Cheng, “The Delta-Connected Cascaded Associate Professor at the Center of
H-Bridge Converter Application in Distributed Energy Resources and
Reliable Power Electronics (CORPE),
Fault Ride Through Capability Analysis,” IEEE Trans. Ind. Appl., vol. 53,
no. 2, pp. 4665-4672, Sep./Oct. 2017. Aalborg University, Aalborg, Denmark. He was a Visiting
[30] H. Song, K. Nam, “Dual Current Control Scheme for PWM Converter Scientist with the ETH Zurich, Switzerland, from Aug. to Sep.
Under Unbalanced Input Voltage Condition,” IEEE Trans. Ind. Electro., 2014, and with the Massachusetts Institute of Technology
vol. 46, no. 5, pp. 953-959, Oct. 1999.
(MIT), USA, from Sep. to Nov. 2013. He was with the ABB
[31] Website of Hitachi Power Semiconductor Device, Ltd., Product Lineup
of 4500V-IGBT module. [Online]. Available: Corporate Research Center, Switzerland, in 2009. His research
http://www.hitachi-power-semiconductor-device.co.jp/en/product/igbt/li addresses the fundamental challenges in modelling and
st/4500v.html validation of power electronic component failure mechanisms,
[32] A. Marzoughi, R. Burgos, D. Boroyevich and Y. Xue, “Analysis of
and application issues in system-level predictability, condition
capacitor voltage ripple minimization in modular multilevel converter
based on average model,” in Proc. Control and Modeling for Power monitoring, circuit architecture, and robustness design.
Electronics (COMPEL), Jul. 2015, pp. 1-7. Dr. Wang received the Richard M. Bass Outstanding Young
Power Electronics Engineer Award from the IEEE Power
Electronics Society in 2016, and the Green Talents Award from
the German Federal Ministry of Education and Research in
2014. He is currently the Award Chair of the Technical
Committee of the High Performance and Emerging
Technologies, IEEE Power Electronics Society, and the Chair
of IEEE PELS/IAS/IE Chapter in Denmark. He serves as an
Associate Editor of IET POWER ELECTRONICS, IEEE
JOURNAL OF EMERGING AND SELECTED TOPICS IN
POWER ELECTRONICS, and IEEE TRANSACTIONS ON
POWER ELECTRONICS.