Q. 1

A generating station has a connected load of 43 MW and a maximum demand of 20 MW, the units generated
being 61.5 × 106 per annum. The laod factor is
FAQ Have any Doubt ?

A
0.35
Correct Option

Solution :
(a)

B
0.75

C
0.25

D
0.56

QUESTION ANALYTICS

https://onlinetestseriesmadeeasy.in/madeeasy/index.php?pageName=timeManagementReport&testid=141&t=a&testType=2 1/14
2/13/2018 MADE EASY ONLINE TEST SERIES

Q. 2

A transmission line has A = D = 0.8, B = 200∠90° Ω, C = 0.5 × 10–6 S and sending end voltage is 400 kV at no load.
The sending end current in the line is
FAQ Have any Doubt ?

A
0.121 A

B
0.1443 A
Correct Option

Solution :
(b)

C
0.324 A
Your answer is Wrong

D
0.414 A

QUESTION ANALYTICS

Q. 3

A 2 wire dc ring distributor is 300 m long and is fed at 240 V at point A. At point B, 150 m from A, a load of 120 A
is taken and at C, 100 m in the opposite direction, a load of 80 A is taken. If resistance per 100 m of single
conductor is 0.03 Ω, then the current in the section AB of feeder is
FAQ Have any Doubt ?

A
41.2 A
https://onlinetestseriesmadeeasy.in/madeeasy/index.php?pageName=timeManagementReport&testid=141&t=a&testType=2 2/14
2/13/2018 MADE EASY ONLINE TEST SERIES
41.2 A

B
102.4 A

C
52.3 A

D
86.67 A
Correct Option

Solution :
(d)

QUESTION ANALYTICS

Q. 4

A string insulator has 5 units. The voltage across the bottom most unit is 25% of the total voltage. The string
efficiency is
FAQ Have any Doubt ?

A
25%

B
50%

https://onlinetestseriesmadeeasy.in/madeeasy/index.php?pageName=timeManagementReport&testid=141&t=a&testType=2 3/14
2/13/2018 MADE EASY ONLINE TEST SERIES

C
80%
Your answer is Correct

Solution :
(c)

D
75%

QUESTION ANALYTICS

Q. 5

A transmission line operating at 11 kV is delivering 20 MW of power. If the line voltage is changed to 33 kV, then
the power transfer capability is increased to _______ MW.
FAQ Have any Doubt ?

180 (178 - 182)


Your answer is Correct180

Solution :
180 (178 - 182)

QUESTION ANALYTICS

https://onlinetestseriesmadeeasy.in/madeeasy/index.php?pageName=timeManagementReport&testid=141&t=a&testType=2 4/14
2/13/2018 MADE EASY ONLINE TEST SERIES

Q. 6

In a 3-Φ, 3 wire system, the conductors are arranged in a horizontal plane with spacing D13 = 4 m, D12 = D23 = 2 m.
Conductors are transposed having diameter of 2.5 cm. The ratio of mutual GMD to self GMD is _________ .
FAQ Have any Doubt ?

258.83 (258.50 - 259.00)


Your answer is Correct258.84

Solution :
258.83 (258.50 - 259.00)

QUESTION ANALYTICS

Q. 7

The insulation resistance of a single core cable is 200 MΩ/km. The insulation resistance for 5 km length is
________ MΩ.
FAQ Have any Doubt ?

40 40
Your answer is Correct

Solution :
40

https://onlinetestseriesmadeeasy.in/madeeasy/index.php?pageName=timeManagementReport&testid=141&t=a&testType=2 5/14
2/13/2018 MADE EASY ONLINE TEST SERIES

QUESTION ANALYTICS

Q. 8

Two generator rated 200 MW and 400 MW are operating in parallel. The droop characteristics of their governors
are 4% and 5%, respectively from no load to full load. Assuming that the generators are operating at 50 Hz at no
load, if 600 MW load is to be shared between both the generators, the system frequency at this load is (assume
free governor operation)
FAQ Have any Doubt ?

A
47.69 Hz
Your answer is Correct

Solution :
(a)

B
46.55 Hz

C
48.50 Hz

D
46.90 Hz

QUESTION ANALYTICS

https://onlinetestseriesmadeeasy.in/madeeasy/index.php?pageName=timeManagementReport&testid=141&t=a&testType=2 6/14
2/13/2018 MADE EASY ONLINE TEST SERIES

Q. 9

A 275 kV transmission line has the following line constants:

The power at unity power factor that can be received if the voltage profile at each end is to be maintained at 275
kV is
FAQ Have any Doubt ?

A
112.63 MW

B
175.75 MW

C
117.63 MW
Correct Option

Solution :
(c)

D
160.00 MW

QUESTION ANALYTICS

https://onlinetestseriesmadeeasy.in/madeeasy/index.php?pageName=timeManagementReport&testid=141&t=a&testType=2 7/14
2/13/2018 MADE EASY ONLINE TEST SERIES

Q. 10

An 11 kV, 50 Hz, single phase cable has a diameter of 20 mm, an internal sheath radius of 15 mm. If the dielectric
has a relative permittivity of 2.4 and a loss angle of 0.031 radian, the dielectric loss for 2.5 km length of the cable
is
FAQ Have any Doubt ?

A
2910 watt

B
1938 watt

C
969 watt
Your answer is Correct

Solution :
(c)

D
484.5 watt

QUESTION ANALYTICS

Q. 11

A 3-Φ, 50 Hz line consists of three conductors each of diameter 21 mm. The spacing between the conductors are
as follows:
A–B=3m
B – C = 5 m,
C – A = 3.6 m,
The inductive reactance per phase per km of the line is
https://onlinetestseriesmadeeasy.in/madeeasy/index.php?pageName=timeManagementReport&testid=141&t=a&testType=2 8/14
2/13/2018 MADE EASY ONLINE TEST SERIES

FAQ Have any Doubt ?

A
0.38 Ω/km
Your answer is Correct

Solution :
(a)

B
0.68 Ω/km

C
1.20 Ω/km

D
1.40 Ω/km

QUESTION ANALYTICS

Q. 12

A 3-phase transmission line is supported by a 3 unit suspension insulator stirng. The voltage across the unit
nearest to the line is 20 kV and that across the adjacent unit is 15 kV. The ratio of mutual to ground capacitance is
FAQ Have any Doubt ?

A
0.12

B
01
https://onlinetestseriesmadeeasy.in/madeeasy/index.php?pageName=timeManagementReport&testid=141&t=a&testType=2 9/14
2/13/2018 MADE EASY ONLINE TEST SERIES
0.14

C
0.16

D
0.18
Correct Option

Solution :
(d)

QUESTION ANALYTICS

Q. 13

Given a single area with two generating units.

FAQ Have any Doubt ?

49.75 (49.40 - 49.90)


Correct Option

Solution :
49.75 (49.40 - 49.90)

https://onlinetestseriesmadeeasy.in/madeeasy/index.php?pageName=timeManagementReport&testid=141&t=a&testType=2 10/14
2/13/2018 MADE EASY ONLINE TEST SERIES

QUESTION ANALYTICS

Q. 14

An interconnected cable links generating stations 1 and 2 is as shown below.

FAQ Have any Doubt ?

0.96 (0.80 - 1.20)


Your answer is Correct.962

Solution :
0.96 (0.80 - 1.20)

https://onlinetestseriesmadeeasy.in/madeeasy/index.php?pageName=timeManagementReport&testid=141&t=a&testType=2 11/14
2/13/2018 MADE EASY ONLINE TEST SERIES

QUESTION ANALYTICS

Q. 15

A 3-phase, 3 core, metal sheathed cable gave the following test for capacitance.
1. Capacitance between two conductor bunched with the sheath and the third conductor is 0.4 μF per km.
2. Capacitance between bunched conductors and sheath is 0.625 μF/km.
The value of capacitance per phase is ________ μF/km.
FAQ Have any Doubt ?

0.4957 (0.35 - 0.60)


Your answer is Correct0.496

Solution :
0.4957 (0.35 - 0.60)

https://onlinetestseriesmadeeasy.in/madeeasy/index.php?pageName=timeManagementReport&testid=141&t=a&testType=2 12/14
2/13/2018 MADE EASY ONLINE TEST SERIES

QUESTION ANALYTICS

Q. 16

An isolated generator connected to a turbine with its continuous maximum power of 20 MW, 50 Hz. Generator
connected with two loads of 8 MW, each operate at 50 Hz. Generator has 5% drop characteristic. One of these
loads are programmed to trip if frequency full belows 48 Hz. If an additional load of 6 MW added then frequency
of generator is _________ Hz.
FAQ Have any Doubt ?

50.25 (50.10 - 50.30)


Correct Option

Solution :
50.25 (50.10 - 50.30)

https://onlinetestseriesmadeeasy.in/madeeasy/index.php?pageName=timeManagementReport&testid=141&t=a&testType=2 13/14
2/13/2018 MADE EASY ONLINE TEST SERIES

Your Answer is 49.25

QUESTION ANALYTICS

https://onlinetestseriesmadeeasy.in/madeeasy/index.php?pageName=timeManagementReport&testid=141&t=a&testType=2 14/14