Function Block Library ILS_CEM
Function Description Edition 09/13
Annunciation 8 C_ANNUN8
Safety Guidelines
This manual contains notices you have to observe in order to ensure your personal safety, as well as to prevent damage
to property. The notices referring to your personal safety are highlighted in the manual by a safety alert symbol, notices
referring to property damage only have no safety alert symbol. The notices shown below are graded according to the
degree of danger.
Danger
! indicates that death or severe personal injury will result if proper precautions are not taken.
Warning
! indicates that death or severe personal injury may result if proper precautions are not taken.
Caution
! with a safety alert symbol indicates that minor personal injury can result if proper precautions are not
taken.
Caution
without a safety alert symbol indicates that property damage can result if proper precautions are not
taken.
Attention
indicates that an unintended result or situation can occur if the corresponding notice is not taken into
account.
If more than one degree of danger is present, the warning notice representing the highest degree of danger will be used.
A notice warning of injury to persons with a safety alert symbol may also include a warning relating to property damage.
Qualified Personnel
The device/system may only be set up and used in conjunction with this documentation. Commissioning and operation
of a device/system may only be performed by qualified personnel. Within the context of the safety notices in this
documentation qualified persons are defined as persons who are authorized to commission, ground and label devices,
systems and circuits in accordance with established safety practices and standards.
Prescribed Usage
Note the following:
Warning
! This device and its components may only be used for the applications described in the catalog or the
technical description, and only in connection with devices or components from other manufacturers
which have been approved or recommended by Siemens.
Correct, reliable operation of the product requires proper transport, storage, positioning and assembly
as well as careful operation and maintenance.
Trademarks
All names identified by ® are registered trademarks of the Siemens AG.
The remaining trademarks in this publication may be trademarks whose use by third parties for their own purposes
could violate the rights of the owner.
Siemens AG
Automation and Drives Siemens AG 2005
Postfach 4848, 90327 Nuremberg, Germany Technical data subject to change.
Siemens Aktiengesellschaft
Reference Manual Objects Annunciation 8 C_ANNUN8
ANNUNCIATION 8 C_ANNUN8 1
Description of C_ANNUN8 4
Type/Number 4
Calling OBs 4
Function 4
Operating principle 5
Input interfaces 5
Group and Object links 8
Process values 14
Output interfaces 15
Time characteristics 16
Message characteristics 16
Module states 17
Commands 17
I/O-bar of C_ANNUN8 18
OS-Variable table 22
Variable details 24
N:\Cemat\DOKU\V80_SP1\English\Reference\Objekte\000_Normal\C_ANNUN8_009.doc
Annunciation 8 C_ANNUN8 Reference Manual Objects
Description of C_ANNUN8
Type/Number
Module name: C_ANNUN8
Module no.: FB1005
Calling OBs
C_ANNUN8 must be called in OB1 (MAIN_TASK).
Function
th
Block Type C_ANNUN8 can generate 7 individual alarms. The 8 alarm is used for alarm
repetition. With annunciation modules, binary signals can be displayed on the screen as an
alarm message.
N:\Cemat\DOKU\V80_SP1\English\Reference\Objekte\000_Normal\C_ANNUN8_009.doc
Reference Manual Objects Annunciation 8 C_ANNUN8
Operating principle
Input interfaces
FLS1 – FLS7 Fault Basic state 0-signal
Format BOOL
When a signal changes its state from 0 to 1 at one of these interfaces, an alarm is generated. If
a signal delay (e.g. TFLS1) is set for response, the output signal F1 and the alarm are delayed
by this time. Corresponds to MST0 of the C_ANNUNC.
N:\Cemat\DOKU\V80_SP1\English\Reference\Objekte\000_Normal\C_ANNUN8_009.doc
Annunciation 8 C_ANNUN8 Reference Manual Objects
Typical application:
In the case of a control supply voltage failure for MCC or field signals, one alarm message
would be triggered for each sensor signal. To avoid this, one should connect the control voltage
signal to the annunciation release interface at the appropriate modules. This results in no alarm
being produced. The cause of the “control voltage failure“ is reported by an annunciation
module configured for this.
Caution: If MMFR has 0-Signal the annunciation fault is not shown in the summarizing
! indication of group and route and not listed in the status call.
Caution: Using QUIT for individual acknowledgement, the acknowledgement interface at the
! C_PUSHBT must not be connected.
For group-wise acknowledgement connect the output ACK of the corresponding group to
interface QUIT of the annunciation block. See Engineering Manual, chapter AS-Engineering.
N:\Cemat\DOKU\V80_SP1\English\Reference\Objekte\000_Normal\C_ANNUN8_009.doc
Reference Manual Objects Annunciation 8 C_ANNUN8
N:\Cemat\DOKU\V80_SP1\English\Reference\Objekte\000_Normal\C_ANNUN8_009.doc
Annunciation 8 C_ANNUN8 Reference Manual Objects
An annunciation block can be linked to two groups or routes via GR_LINK1 and GR_LINK2. If
an annunciation block belongs to more than two groups or routes the additional block C_MUX
must be inserted, which provides 5 additional link interfaces.
Caution: The main group (or main route) should be connected to GR_LINK1! This is the one
! which is opened with a click on button "Main group" in the faceplate of the annunciation block.
An Annunciation block which belongs to a drive can be connected to the drive via interface
O_LINK instead of the connection to the group or route vie GR_LINK1 and GR_LINK2 or via
C_MUX. The main group (or main route) information is not available in this case.
Caution: It is not allowed to use the Object link and the Group/Route link at the same time:
! If O_LINK is used, GR_LINK1 and GR_LINK2 or C_MUX must not be connected!
N:\Cemat\DOKU\V80_SP1\English\Reference\Objekte\000_Normal\C_ANNUN8_009.doc
Reference Manual Objects Annunciation 8 C_ANNUN8
Caution: If a C_MUX block is used, the programming order is very important. The C_MUX
! must be called before the annunciation block!
The MUX_IN interface can under no circumstances be used for connection with a
group or route. It is used exclusively for connection with another MUX module.
Structure variables:
MUX_LINK.Point_GRL Pointer Default: 0
Format INTEGER
MUX_LINK.Command Group / Route Command Default: 16#00
Format WORD
N:\Cemat\DOKU\V80_SP1\English\Reference\Objekte\000_Normal\C_ANNUN8_009.doc
Annunciation 8 C_ANNUN8 Reference Manual Objects
Example of a circuit:
G_LINK ST R_LINK ST
ST G_LINK
Route2
C_Route MAIN_TASK
1/4
Group2 R_LINK ST
1/6
ST GR_LINK1
G_LINK ST ST GR_LINK2
ST MUX_LINK
Group3
C_Group MAIN_TASK
1/7 MUX1
C_MUX MAIN_TASK
G_LINK ST 1/1
BO EN ENO BO
ST MUX_IN MUX_OUT ST
Group4 ST GR_LINK1
1/8 ST GR_LINK3
ST GR_LINK4
G_LINK ST ST GR_LINK5
! Caution: Observe the processing sequence! The C_MUX module must be called before the
annunciation module. For the other modules, the run sequence is as follows: First the
annunciations, measured values and drives, then the associated routes and finally the
associated groups.
Caution: Some people use one C_MUX block and connect its output to a number of
! drives/devices, annunciations and measurements.
If you do so, make sure that the C_MUX is called before all the other objects and
that no other C_MUX call comes in between.
We don't recommend using the same C_MUX if the blocks are located in different
runtime groups.
N:\Cemat\DOKU\V80_SP1\English\Reference\Objekte\000_Normal\C_ANNUN8_009.doc
Reference Manual Objects Annunciation 8 C_ANNUN8
NO_OF_I
FT1
R08 MAINTASK
FT2 C_ANNUN8 1/3
FT3
.... O_LINK
FT20
The drive block collects the information and forwards it to the group (or route). The result is as
follows:
- All objects, linked to the drive are listed in the drive object list and in the group (or route)
object list (one level below the drive).
- All objects, linked to the drive are highlighted in the process picture with button "Show
related objects".
- The faults of all objects, linked to the drive are included in the summarizing fault indication
of the group (or route).
- The warnings of all objects, linked to the drive are included in the summarizing warning
indication of the group (or route).
- In case of a dynamic fault during the startup of the group, the group start will be interrupted.
N:\Cemat\DOKU\V80_SP1\English\Reference\Objekte\000_Normal\C_ANNUN8_009.doc
Annunciation 8 C_ANNUN8 Reference Manual Objects
Caution: C_RECV_G can only be linked to a C_GROUP module. Linking to routes is not
! permitted and will not work!
In the AS of the Cemat Objects the output O_LINKQ of block C_SEND_G is connected to input
O_LINK of the drives/devices, annunciations, measurements and process feedback blocks.
NO_OF_FT
FT1
FT2
NO_OF_I
FT3
FT1
....
FT2
FT30
FT3
....
AS02
LSEND04 MAINTASK R01 MAINTASK
C_SEND_G 1/5 C_ANNUN8 1/2
LINK
O_LINK
O_LINKQ
M01 MAINTASK
NO_OF_I C_DRV_1D 1/3
FT1
O_LINK O_LINKQ
FT2
FT3
M02 MAINTASK
C_DAMPER 1/4
....
FT50
O_LINK O_LINKQ
N:\Cemat\DOKU\V80_SP1\English\Reference\Objekte\000_Normal\C_ANNUN8_009.doc
Reference Manual Objects Annunciation 8 C_ANNUN8
Structure variables:
O_LINK.iDB Instance DB master object Default: 0
Format INTEGER
O_LINK.iDW DW number NO_OF_FT in master object Default: 0
Format INTEGER
O_LINK.Command Group / Route Command Default: 16#00
Format BYTE
O_LINK.Status Status master object Default: 16#00
Format BYTE
N:\Cemat\DOKU\V80_SP1\English\Reference\Objekte\000_Normal\C_ANNUN8_009.doc
Annunciation 8 C_ANNUN8 Reference Manual Objects
Process values
The process values can be set during configuration and they can be changed online from the
OS. To permit the modification of the process values from the faceplates, they must not be
connected in the CFC.
N:\Cemat\DOKU\V80_SP1\English\Reference\Objekte\000_Normal\C_ANNUN8_009.doc
Reference Manual Objects Annunciation 8 C_ANNUN8
Output interfaces
F1 – F7 Output signals, fault
Format BOOL
Always use one of these signals for the control so that delays that have been configured can
take effect.
SIM_ON Simulation ON
Format BOOL
This output has to be connected to input SIM_ON of the driver block. This enables to switch
on/off the simulation from the faceplate. Refer to Release functions.
N:\Cemat\DOKU\V80_SP1\English\Reference\Objekte\000_Normal\C_ANNUN8_009.doc
Annunciation 8 C_ANNUN8 Reference Manual Objects
Time characteristics
The module must be called before the associated route or group.
Any called C_MUX modules must run before this module.
Message characteristics
The module uses the ALARM_8 module to generate annunciations.
A plausibility and priority logic at the process level analyses all object faults
Only one fault annunciation is issued for each fault
Secondary annunciations are suppressed automatically
The fault source is recorded in detail and uniquely.
The current operational state of the plant objects is automatically taken into consideration during
the fault analysis, e.g. all fault annunciations are suppressed automatically for a stationary
group
No superfluous fault annunciations are created
The operator does not need to manually disable/suppress any annunciations.
Refer to the Variable details for the assignment of the annunciation text and annunciation class
to the module parameters.
N:\Cemat\DOKU\V80_SP1\English\Reference\Objekte\000_Normal\C_ANNUN8_009.doc
Reference Manual Objects Annunciation 8 C_ANNUN8
Module states
Variable STATUS:
Commands
Refer to the Variable details for the assignment of the command word.
N:\Cemat\DOKU\V80_SP1\English\Reference\Objekte\000_Normal\C_ANNUN8_009.doc
Annunciation 8 C_ANNUN8 Reference Manual Objects
I/O-bar of C_ANNUN8
C_ANNUN8
Permitted
Element Meaning Format Default Type Attr. HMI
Values
N:\Cemat\DOKU\V80_SP1\English\Reference\Objekte\000_Normal\C_ANNUN8_009.doc
Reference Manual Objects Annunciation 8 C_ANNUN8
Permitted
Element Meaning Format Default Type Attr. HMI
Values
N:\Cemat\DOKU\V80_SP1\English\Reference\Objekte\000_Normal\C_ANNUN8_009.doc
Annunciation 8 C_ANNUN8 Reference Manual Objects
Permitted
Element Meaning Format Default Type Attr. HMI
Values
GR_LINK1.
Link INT 0 I U
Link
GR_LINK1.
Group/ route command WORD 16#00 I U
Command
GR_LINK2.
Link INT 0 I U
Link
GR_LINK2.
Group/ route command WORD 16#00 I U
Command
MUX_LINK.
Pointer INT 0 I U
Point_GRL
MUX_LINK.
Group/ route command WORD 16#00 I U
Command
O_LINK.
Instance DB master object INT 0 I U
iDB
O_LINK DW number NO_OF_FT in
INT 0 I U
iDW master object
O_LINK.
Group/ route command BYTE 16#00 I U
Command
O_LINK.
Status master object BYTE 16#00 I U
Status
N:\Cemat\DOKU\V80_SP1\English\Reference\Objekte\000_Normal\C_ANNUN8_009.doc
Reference Manual Objects Annunciation 8 C_ANNUN8
Permitted
Element Meaning Format Default Type Attr. HMI
Values
N:\Cemat\DOKU\V80_SP1\English\Reference\Objekte\000_Normal\C_ANNUN8_009.doc
Annunciation 8 C_ANNUN8 Reference Manual Objects
OS-Variable table
C_ANNUN8
PLC Data
OS Variable Description OS Data Type
Type
N:\Cemat\DOKU\V80_SP1\English\Reference\Objekte\000_Normal\C_ANNUN8_009.doc
Reference Manual Objects Annunciation 8 C_ANNUN8
PLC Data
OS Variable Description OS Data Type
Type
N:\Cemat\DOKU\V80_SP1\English\Reference\Objekte\000_Normal\C_ANNUN8_009.doc
Annunciation 8 C_ANNUN8 Reference Manual Objects
Variable details
Internal structure of the Commands, Alarms, Visualization status and Interface word:
COM_B10 8
COM_B11 SACK 9 einzel quittieren single acknowledge
COM_B12 10
COM_B13 11
COM_B14 12
COM_B15 13
COM_B16 14
COM_B17 15
N:\Cemat\DOKU\V80_SP1\English\Reference\Objekte\000_Normal\C_ANNUN8_009.doc
Reference Manual Objects Annunciation 8 C_ANNUN8
N:\Cemat\DOKU\V80_SP1\English\Reference\Objekte\000_Normal\C_ANNUN8_009.doc
Annunciation 8 C_ANNUN8 Reference Manual Objects
Objekt markieren
STA_B10 MARK 24 Highlight object (group command)
(Gruppenkommando)
STA_B11 WARN1 25 Signal 1 ist eine Warnung Signal No. 1 is a warning
STA_B12 WARN2 26 Signal 2 ist eine Warnung Signal No. 2 is a warning
STA_B13 WARN3 27 Signal 3 ist eine Warnung Signal No. 3 is a warning
STA_B14 WARN4 28 Signal 4 ist eine Warnung Signal No. 4 is a warning
STA_B15 WARN5 29 Signal 5 ist eine Warnung Signal No. 5 is a warning
STA_B16 WARN6 30 Signal 6 ist eine Warnung Signal No. 6 is a warning
STA_B17 WARN7 31 Signal 7 ist eine Warnung Signal No. 7 is a warning
N:\Cemat\DOKU\V80_SP1\English\Reference\Objekte\000_Normal\C_ANNUN8_009.doc