Sunteți pe pagina 1din 6

.

.::

K-Factor Transformers and Non-linear Loads


Kiran Deshpande*, Prof.Rajesh Holmukhe*, Prof.Yogesh Angal**

Abstract-Harmonic currents generated by non-linear loads can cause problems in the power systems and particularly the
distribution transformers as they are vulnerable to overheating and premature failure. Normally designers recommend an oversized
transformer to protect transformer from overheating. K-factor transformers are specifically designed to accommodate harmonic
currents. K-transformers are preferred because they have additional thermal capacity of known limits, design features that minimize
harmonic current losses, and neutral and terminal connections sized at 200% of normal. K-factor transformers allow operation up to
nameplate capacity without derating.

Index Terms- Additional thermal capacity, Derating, Distribution transformers, Harmonic currents, K- Factor, Nameplate capacity,
Neutral and Terminal connections, Non-linear loads, Overheating.

I. INTRODUCTION
Today's modem offices and plants are dominated by nonlinear
loads, desktop computers, solid state ballasts, PID lighting,
programmable controllers, and variable speed drives to name a
few. Due to these electronic loads, significant harmonic loads
have been added to the building's distribution systems. The
result is premature failure ofthe transformer due to
overheating. Till recent times, the only solution to this problem
was to derate the transformer. This solution is no longer
acceptable.

II. A review of Nonlinear Loads

The effect of nonlinear loads on the electrical power systems


has become matter of concern since past few years. Nonlinear
loads draw currents which are not sinusoidal. They include
equipments such as solid state motor drives, arc furnaces, Fig. 1. Voltage and current waveform for nonlinear load.
battery chargers, UPS systems, and the increasing electronic
power supplies. The increased use of these nonlinear loads is III. Effects of Harmonic Currents on Power System
the cause of concern as larger percentage of power systems
tend to become nonlinear. The nonlinear loads were thought to Harmonic currents adversely affect every component of the
be matter of concern for industrial power systems where large power system. These currents create additional dielectric,
static power converters were being used. But now larger thermally, and/or mechanical stresses. Harmonic currents
application of electronics to practically every electrical load, flowing through the power system impedances result in
nonlinear loads are present in commercial and even residential harmonic voltage drops which are observed as harmonic
power system. Nonlinear loads produce harmonic currents
voltage distortion. The voltage distortions could become very
which flow from the load towards the power source following
severe when the power systems inductive and capacitive
the path of least impedances. Harmonic currents are the
impedances become equal, a condition of parallel resonance.
currents which have frequencies that are whole number
This condition could appear at one of the nonlinear load's
multiples of fundamental frequency. The harmonic currents
superimposed on the fundamental currents result in the non-
significant harmonic current frequencies (typically the 5th, r.
II th or 13th harmonic). Harmonic currents can cause losses in
sinusoidal waveform associated with the nonlinear loads.Fig.l
show the voltages and current waveforms for nonlinear loads. normal power components even when resonance conditions do
It can be seen that voltage waveform is sinusoidal but current not prevail. Due to skin and proximity effects, wiring
waveform is not. experience additional heating. If normal wiring sizing methods
are employed, then the derating for wiring for harmonics is
minimal and can be ignored.
• Dept.of Electrical Engineering, College of Engineering, Bharati Vidyapeeth
University, Pune,
E-mail: irkin85@hotmail.com IV. Methods to Derate Transformer as suggested by ANSI!
•• Dept.of Instrumentation Engineering, Dr.D. Y.Patil Institute of Engineering IEEE Standards .
and Technology, Pimpri, Pune: 411 018. Harmonic currents cause additional heating in the form of
additional winding eddy current losses in transformers.ANSI / Typical tr.m fo mer dtrall
IEEE C 57.110 provides methods to derate a transformer for
any given load profile. This standard considers the winding
eddy current losses to be proportional to the harmonic number
required. This relationship has been found to be accurate for
lower power frequency harmonics, but result in an
overestimation of losses for higher harmonics (generally
greater than II th). A typical derating curve is shown in fig.2.
Transformers directly supplying single phase power supplies
may require derating of 30% to 40% to avoid overheating.
'Underwriters Laboratories' (UL) recognize the potential
safety hazards associated with nonlinear loads and developed
a rating system to indicate the capability of transformer to
handle harmonic loads. The ratings are described in UL-I56I
and are known as K-Factors. K-Factors are a weighing of the
harmonic load currents according to their effects on
transformer heating, as derived from ANSIIIEEE C57.II O. A
K-Factor of 1.0 indicates a linear load (no harmonics).The
higher the K-Factor, the greater the effect of harmonic
heating (I].

U) 1! ~
(1)
Load K~acto'
Where Ih is the load current at the harmonic h, expressed in a
per-unit basis such that the total RMS current equals one Fig. 2.Typical Transformer derating for
ampere, i.e. Nonlinear loads

(2) measurements are not available. K-Factor transformers are


designed to be operated fully loaded with any harmonic load
The problem associated with calculating K- Factor is selecting having K-Factor equal to or less than its K-rating. For
the range of harmonic frequencies that should be included. example, a K-13 transformer can be fully loaded with any
Some use up to 15th harmonic, others up to 25 th harmonic, and harmonic load having a K-Factor up to K-13. If the load has a
still others include up to 50th harmonic. For the same load, K-Factor greater than 13, then the transformer cannot be
each of these calculations can yield significantly different safely operated at full load and would require derating.
K-Factors, because even very small current levels associated
with higher harmonics, when multiplied by the harmonic v. How do K-Factor Transformers differ from
number squared, can yield significantly to the K-Factor. Based Standard Transformers?
on the underlying assumptions of C57.II0, it seems
reasonable to limit the K-Factor calculation to harmonic K-Factor transformers have additional thermal capacity to
currents less than 25 th harmonic. Sample calculations are tolerate the heating effects of the harmonic currents. A well
given in Table No.l.ln establishing standard transformer K- designed K-Transformer will also minimize the winding eddy-
Factor rating; UL chose ratings of 1, 4, 9, 13, 20, 30, 40 and current losses through the use of parallel conductors and other
50. From a practical viewpoint individual loads with K- winding techniques. The K-factor indicates the multiples of
Factors greater than 20 are infrequent. At best office areas the 60 Hz winding eddy current losses that the transformer can
with some nonlinear loads and large computer rooms normally safely dissipate. Transformer load losses consist of winding
have observed K-Factors of 4 to 9. Areas with high 12R losses plus stray losses. Using UL best methods, stray
concentrations of single phase computers and terminals have losses are assumed to be primarily winding eddy current
observed K- Factors of 13 to 17. When multiple nonlinear losses for transformers 300 KVA and smaller.
loads are powered from the same source, lower harmonic
current levels may be expected due to phase shifts and For example, a transformer having winding 12Rlosses of2000
cancellations. In one study of commercial buildings, single watts and 60 Hz stray losses of 1000 watts would, with a K-20
phase loads with current distortion of 104%, THD (Total rating, is required to dissipate the 2000 watts ofeR losses plus
Harmonic Distortion) resulted in only a 7% THD at the 20 times the 60Hz stray losses of 1000 watts for a total load
service entrance, when added with other loads in the building. loss of 4000 watts without exceeding the maximum winding
Additional studies of typical loads are beginning to provide temperature rise. The result is a larger, more expensive
information which could aid in the development of transformer.
additional rules of thumb to use when direct load
For K-Factor transformers, UL also requires that the neutral
terminal and connections to be sized to accommodate twice
the rated phase conductor size (double the minimum neutral Development of
capacity) of standard transformers.
Triplen Harmonic Current
Instantaneous 3.phase 60 Hz currents = 0 at any instant
There are several areas where designs are changed to AmPS
C
accommodate the effects of harmonics.

1. Secondary Windings: The secondary windings,


instead of working with a pure sine wave and
producing normal values and stray losses have to
cope up with non-sinusoidal waveforms containing
multiple harmonics, which raise the stray losses
significantly. To compensate for these increased
Instantaneous triplen 3rd harmonic currents (180
losses, a multiple of small, individually insulated Hz )where neutral current = 3 x phase currents
conductors are used. Transposition is used wherever
necessary.
2. Neutral: Since harmonic currents are additive in
neutral, neutral currents in excess of two times phase
currents can be measured. To compensate for this,
double sized neutral lugs and lug pads is furnished.
3. Primary winding: The primary winding has some
lower order harmonics circulating within the delta,
producing losses and additional heating. This is
compensated for by using a heavier conductor.
4. Core: The core is affected by voltage harmonic
distortion. This voltage distortion increases the core
flux density, creating higher core loss, higher
Fig.3. Development of Triplen Harmonic current.
magnetizing currents, higher audible noise and
heating problems. To reduce flux density, alloy
the input current. Therefore a transformer can be overloaded
induction designed core is used.
without the primary over-current protection ever tripping.
Adding secondary over-current protection helps, but it
VI. About Standard Transformers not marked with still does not protect the transformer from the heating effects
K-Factor ratings: of harmonic currents. The use of supplemental protection in
the form of winding temperature sensors can be used to
Standard transformers, i.e. transformers not marked with a K- provide alarm and/or system shutdown in the event of
Factor rating, may have some tolerance to nonlinear loading, overload, excessive harmonic current, high ambient
but their capability is unknown to the user and is not certified temperature, or inadequate cooling
by a third party such as UL. Currently marking transformer
with a K-Factor rating is not required by UL. Due to VIII. More on Triplen Harmonic currents.
conservative design application, some unmarked transformer
may therefore have enough extra thermal capacity to tolerate Triplen harmonic currents are phase currents which flow from
additional harmonic load heating. This is particularly true for each of the phases into the fourth wire neutral and have
80° C or 115°C rise transformers built with 220°C insulation frequencies in integer multiples of three times the 60 Hz base
material which can safely withstand a 150°C winding frequency (180 Hz, 360Hz, 540Hz etc). At each of these third
temperature rise. multiple triplen frequencies, these triplen phase currents are in
phase with each other and when flowing in the neutral as zero
VII. Consideration of additional Over Current sequence currents are equal to three times their RMS phase
Protection for Transformers supplying values. The development of triplen harmonic current is shown
Nonlinear Loads. in fig.3.
Additional over current protection should be considered for all
transformers supplying nonlinear loads. The National Electric In a 3 phase, 4 wire system, single phase line to neutral
Code allows primary-only over current protection at 125°C of currents flow in each phase conductor and return in common
the transformer's primary full load amperes. With three-phase neutral. Since the three 60 Hz currents are separated by 120°,
transformers, the triplen harmonics are cancelled in the delta when balanced they cancel each other. The measured resultant
winding and do not appear in the input current. The output current is equal to zero.
currents and transformer loading greater than is apparent from
Theory also states that for even harmonics, starting with the
second order, when balanced, the even harmonic will cancel in
the common neutral. Other odd harmonics add in the common Shielde~Transformer UnshieldedTransformer
neutral, but their magnitude is considerably less than triplens. sn~l~

t-
The RMS value of the total current is the square root of the
RMS value of the individual currents squared.

I Total -- IJoHz + liaoHz + liooHz + IJzoHz + ... (3)


&
~I
~1t~~
J I
~l1t-
T ~I'"
~
II ~i!
~l ~
',.r.
~. :..
·.1.

Where I = RMS value of current. ~ ~ \ '-----''j

At any given instant, the 60 Hz currents on the three phase


legs have a vector resultant of zero and cancel in the neutral.
But, the third (and other odd triplen harmonics) on the phase
legs are in phase and become additive in the neutral. Fig. 4. Shielded and unshielded Transformers.

IX. The UL Approach to Transformers Relatively small DC components (up to the RMS magnitude
of the transformer excitation current at rated voltage) are
A. A transformer intended for use with loads drawing expected to have no significant effects on the load carrying
non-sinusoidal currents shall be marked "Suitable for of the transformer excitation current at rated voltage) are
non-sinusoidal current load with K-Factor not to expected to have no significant effect on the load carrying
exceed x. (x= 4, 9, 13, 20, 30, 40 or 50). capability of a transformer determined by this recommended
B. Formulas to determine eddy losses and total losses practice. Higher DC load components may adversely affect
where the transformer load losses (PLL) are to be transformer capability and must be corrected by the user.
determined as follows:
Harmonic currents flowing through transformer leakage
PLL = PDC(l + K(PEC)) (4) Impedance and through system impedance may also produce
some small harmonic distortion in the voltage waveform at the
Where, PDC = Total 12Rlosses transformer terminals. Such voltage harmonics may cause
extra harmonic losses in the transformer core. However,
K = the K-Factor rating at the transformer (4, 9, 13, 20, 30, operating experience has indicated that core temperature rise
40 or 50). usually will not be the limiting parameter for determination of
safe magnitudes of non-sinusoidal load currents.
PEC = assumed eddy current losses calculated as follows:
The Noise Isolation Transformer suppresses common mode
For Transformers rated 300 KVA or less, and for transformers noise by introducing a ground shield between its primary and
Rated 300 KVA and above, in which; secondary windings. The ground shield provides a low
impedance path to ground by capacitive coupling which
PAC = Impedance loss prevents unwanted high frequency signals contained in the
source voltage from reaching the transformer secondary.
C= 0.7 for transformers having a turn ratio greater than 4:1
and having one or more winding with a current rating greater The grounded shield between primary and secondary windings
than 1000 amperes., or C= 0.6 for all other transformers. is called an electrostatic shield. This shield does not perform
any function with regard to harmonic current or voltage
PDC-I = the fR losses for the inner winding. distortion wave forms. However this shield is extremely
valuable in protecting sensitive equipments from common
The impedance losses and the fR losses shall be determined mode electrical noise and transients generated on the line side
in accordance with the test code for Dry Type Distribution and of the transformer. The shielded and unshielded transformers
Power Transformers, ANSI/IEEE C57.12.91-1979. [4] are shown in fig, 4.

As stated in ANSI/IEEE C57.1 10-1986, harmonic load The ratio of common mode noise attenuation (CMA) on the
currents may be accompanied by DC components in the load input to that of the output of the transformer is expressed in
current which are frequently caused by the loss of a diode in a decibels as shown in equation shown here below:
rectifier circuit. A DC component of load current will increase
the transformer core loss slightly, and may increase the CMA = 20 10glo [Vin]
Vout
dB (5)
magnetizing current and audible sound level. [3].
Table No.1.Calculations for a typical nonlinear load Table No.2. K- Factors for various types of Loads

h In (In)2 InlL (In)2) (In)2 Load K- Factor ILK


(harmonic h2 Incandescent
(nonlinear K-I 0.00
number) Load Lighting
Current) Electric Resistance
K-I 0.00
Heating
I 100.0% 1.000 0.792 0.626 0.626 Motors (without
K-I 0.00
solid state drives)
3 65.7 0.432 0.520 0.270 2.434
Control
K-I 0.00
5 37.7 0.142 0.296 0.089 2.226 Transformers
Motor-Generators K-I 0.00
7 12.7 0.016 0.101 0.010 0.495 Distribution
K-I 0.00
Transformers
9 4.4 0.002 0.035 0.001 0.098 Electric Discharge
K-4 25.82
5.3 Lighting
II 0.003 0.042 0.002 0.213
UPS K-4 25.82
13 2.5 0.001 0.020 0.000 0.066 Welders K-4 25.82
Induction Heating
15 1.9 0.000 0.015 0.000 0.051 K-4 25.82
Equipment
1.8 PLCs and solid
17 0.000 0.014 0.000 0.059 K-4 25.82
state controls
19 1.1 0.000 0.009 0.000 0.027 Telecommunication
Equipment (e.g. K-13 57.74
21 0.6 0.000 0.005 0.000 0.010 PBX)
UPS without input
23 0.8 0.000 0.006 0.000 0.021 K-13 57.74
filtering
25 0.4 0.000 0.003 0.000 0.006 Multiwire
receptable circuits
Total 1.596 1.00 6.33 in general care K-13 57.74
areas of health care
facilities
Main frame
An isolation transformer with an electrostatic shield can have K-20 80.94
a ratio of input noise voltage (VIN) to output noise voltage computer loads
(VOUT) within the range of 10:1 to 1000:1 or even higher. Solid State Motor
K-20 80.94
The calculations for K-Factor loads can be carried out with the Drives
help of information available in the Table No.2 and 3. Multiwire
receptable circuits
in Industrial,
X. Disadvantage of using Derated Transformers K-30 123.54
Medical and
instead ofK-Factor Transformer
Educational
Laboratories
The use of derated standard transformers instead of K-Factor
Small Main Frames
Transformers carries some disadvantage as under: K-30 123.54
(Mini and Micro)
Other loads
I. First is the issue of managing the derating when the
identified as
transformer nameplate indicates greater capacity.
producing very high K-40 208.17
Initially, the transformer may be operated at reduced
amounts of
loading. But in the future, the loading may be
harmonics
increased without considering the intended derating.

2. If smaller overcurrent protection is used intentionally Table No.3. Index of K-rating


to limit the overloading, nuisance tripping may occur
due to the transformer inrush current. Larger over- K- K-I K-4 K-9 K-13 K-20 K-30 K-40
current protection may be required for the oversized Factor
ILK 0.0 25.82 44.72 57.74 80.94 123.54 208.17
(derated) standard transformer resulting in larger
conductor requirements with the associated higher
.:

feeder costs. power systems increasing as more electronic loads are added.
3. The transformers designed specifically for nonlinear Whether this will provide sufficient impetus for new rating
loads minimize losses due to harmonic currents. They system for other power system components is problematical.
operate with the nonlinear loads more efficiently and One thing is sure, though, until the day that harmonic currents
generate less heat that need to be dissipated. actually diminish, K-Factor Transformers will play an
important role in coping with the problems harmonics create.
Xl. Using a K-Factor Transformer
References
Once the harmonic current of the total load is known, and a K-
Factor is specified (K4, K13 etc.), the appropriate type K- [I] The Institute of Electrical & Electronic Engineers,
Factor transformer can be fully loaded up to 100% or "Recommended Practice for establishing Transformer
nameplate KVA. All other optional feature that the industry is capabilities when supplying Non-sinusoidal Load
accustomed to can be specified. Currents", ANSIIIEEE C57.110-1986, New York, 1986.

I. Copper or Aluminum. [2] Gruzs, T.M. "A survey of Neutral Currents in Three-
2. 80° C, 115°C, 150°C. phase Computer Power Systems", IEEE Transactions on
3. Electro-static shield. Industry Application, Vo1.26, No.4, July/August 1990.

XII. What should be remembered when using a [3] IEEE P-l100 Working Group. Recommended Practice
K-Factor Transformer? for Powering and Grounding Sensitive Electronic
Equipments. Draft 1992.
I). Harmonic loads do cause premature failure when
standard transformers are used. [4] Underwriters Laboratory. Proposed Requirements and
Proposed Effective Dates for the First Edition of the
2) Average reading RMS meters do not measure Standard for Dry Type General Purpose and Power
harmonic currents. True reading RMS meters should Transformers, UL 156. Santa Clara CA, 1991.
be used.
[5] Computer Business Equipment Association (CBEMA).
3) Insist on a K-Factor transformer that has been 3rd Three Phase Power Source Overloading Caused by Small
party tested. Accept no verbal claims. The proof must Computers and Electronic Office Equipment. ESC-3
be on the label. Information Letter, 1987.

[6] McGranaghan et al. "Analysis of Harmonic Distortion


Conclusions:
Levels in Commercial Buildings." PQA 91,Paris, France,
October 1991.
Because transformers are the power system components most
affected by nonlinear loads, they are the first to receive a
[7] ANSI/IEEE Standard 519-1981. IEEE Guide to Harmonic
harmonic rating system. K-Factor ratings are based on heating
Control and Reactive Compensation of Static Power
effects of harmonics and are not necessarily applicable to
Converters.
other power system components. If harmonic rating systems
for other components are needed, they will have to be
[8] McPartland Brian J.: "Use K-Factor Transformers?
developed by other methods, e.g., THD, crest factor, or some
Definitely! But Which K-Factor?" EDI, June 1991, Vo\.2
new and component-specific weighing of harmonic currents.
No.6.
What is the likelihood that additional rating systems will
actually be developed? That's hard to predict. The best
solution to the problem caused by harmonic currents would be
preventive, i.e. the use of components does not generate
harmonics. Impending standards such as lEC 555 and IEEE
519 encourage the development of such devices.

Indeed, low harmonic current power supplies and electronic


ballasts are already available. As such new designs are
implemented, they should gradually displace existing
electronic loads (and their greater harmonics), serving to
reduce the prevalence of harmonic currents over the long term.

Short term, however, projection show harmonic levels in

S-ar putea să vă placă și