Sunteți pe pagina 1din 2

WATER SUPPLY PUMPS SPECS

-The pump set shall be supplied by a BS EN ISO 9001 registered company for the design and
manufacture of packaged water booster sets.
- Pumps and motors
- the pumps will be of vertical multistage, inline construction with
direct-coupled motors and formal WRAS approval for use on potable water systems.
- The pumps will have stainless steel bodies with stainless steel shaft and impellers, and fitted
with tungsten carbide faced mechanical seals
-The accumulator shall have a working pressure suitable for the expected maximum system
pressure. The test pressure will be 1.5 times the maximum working pressure of the vessel
-The pumps will be controlled by duplex pressure transducers in conjunction with a dedicated
programmable electronic pump controller. The pressure transducers will be directly mounted
to the delivery pipework via individual isolating ball valves.
-The control panel enclosure shall be of 1.2mm thick (minimum) mild steel construction with
powder coat finish and galvanised steel mounting plate. A removable gland plate shall also be
provided. Standard 3mm DIN locks are to be used on all enclosures unless otherwise
specified by the project engineer
-Adjustable minimum run timers are provided nominally set to 3
minutes, to prevent hunting and to ensure the storage volume within the accumulator
maximised.
-The pumps will stop immediately under low level conditions
-After a power failure, low level condition or other system shut down the pump set will enter a
reduced start mode whereby only one pump will be permitted to run for an adjustable period
of time until normal working pressure has been achieved. Once normal pressure has been
reached the pumps will revert to normal operation. If normal pressure is not achieved within
the set time an alarm is raised and the pump set switched off.
-LED indications are provided for power on and common fault plus individual pump run and
fault.
-The equipment is to be supplied with suitably rated flexible pipe couplings for both suction
and delivery manifolds and baseplate mounted set of anti-vibration mountings.
-The equipment is to be delivered to site with adequate protect to limit the ingress of dirt, dust
and water under normal site storage conditions
-The original equipment manufacture is to commission the booster set to the satisfaction of the
project engineer and issue completed, comprehensive checklists and commissioning
certificates accordingly.
-At least 4 copies of the operating and maintenance manuals pertaining to the booster sets
are to issued for the project contain the following section and/or such information as required
by the Employer:
● Contents
● Description of operation;
● Equipment data sheet;
● Installation guidelines;
● Commissioning guidelines;
● General information on pumps, panel, accumulator, pressure switches etc…
● Recommended spares list;
● Maintenance guidelines;
● General assembly drawings, wiring diagram and PCU information.
-The equipment shall be complete with manufacturer’s guarantee effective for 12 months after
Commissioning

SUBMERSIBLE SUMP PUMPS(HEAVY DUTY)


-Pump Casing: Cast iron, with strainer inlet, legs that elevate pump to permit flow into
impeller, and vertical discharge for piping connection.
- Impeller: Statically and dynamically balanced, ASTM A 48/A 48M, Class No. 25 A
cast iron design for clear wastewater handling, and keyed and secured to shaft.
-Pump and Motor Shaft: Stainless steel, with factory-sealed, grease-lubricated ball
bearings.
- Seal: Mechanical
-Motor: Hermetically sealed, capacitor-start type; with built-in overload protection;
lifting eye or lug; and three-conductor, waterproof power cable of length required and
with grounding plug and cable-sealing assembly for connection at pump
Controls:
- Enclosure: NEMA 250, Type 1.
- Switch Type: Pedestal-mounted float switch with float rods and rod buttons.
- Automatic Alternator: Start pumps on successive cycles and start multiple
pumps if one cannot handle load.
- Float Guides: Pipe or other restraint for floats and rods in basins of depth
greater than 60 inches (1500 mm).
- High-Water Alarm: Cover-mounted, compression-probe alarm, with electric
bell; 120-V ac, with transformer and contacts for remote alarm bell.
-WATER TIGHT CABLE FROM CORROSION AND DAMADE
-Moisture-Sensing Probe: Internal moisture sensor and moisture
Alarm
-installation on auto coupling