GENERAL NOTES

The work of any design professionals and or contractor which are or should be
involved in this project shall follow good construction practices.

The contractor is responsible to check the plans and is to notify the designer
of any errors or omissions prior to start of construction.

Written dimensions have precedence over scaled dimensions.

All manufactured materials, components, fasteners, assemblies, etc., shall be


handled and installed in accordance with manufacturer's instructions.

Contractor shall complete work in accordance with National Building Regulations. Finish
work is to be in a professional

Door openings are to be set 150mm from intersecting walls unless otherwise
stated. Window openings are to be set 100mm from intersecting walls unless
otherwise stated.

See structural engineering drawings for structural connection techniques,

instructions for construction and tie down details. Contact Mechanical, electrical

and plumbing engineering drawings for required services and installation

specifications

Showers shall be ceramic tile wall to 7 ft. above finished floor level and shall be
provided with a water resistant backing. All
shower doors shall be tempered or laminated safety glass or shatter resistany plastic.

Specifications and drawings indicate finished structure. Builder shall be responsible


for construction methods, procedures, and conditions (including safety) except as
specfcally indicated in the contract documents.

All fire resisting doors shall have a fire rating of not less than 1 hour and fitted with an
automatic self-closing device
actuated by a fusible link.
GENERAL NOTES
1. All dimensions are in millimeter (mm)
1. Do not scale from the drawing

IC

ft)
( 40
mm

00
3.6 46

15
19 13 ea
12 ar
IC d
ve
Pa

ft)
IC

80
IC

m(
.3m
00

87
15

3
24
IC

46
13

46
13
IC

a
a re

37
d

00
ve

91
Pa

20

nk
ta
ic t
ep
ea

S
ar contact :
n
Law
e-mail :
45
49
ea tranc
e
ar en
wn
La
PROPOSED FOUR (4) BEDROOM RESIDENTIAL
ea ea
00

ar ar BUILDING LOCATED AT EAST LEGON HILLS..


35

wn ve
d
0 0 La Pa
25

ea DANIEL PROVENCAL
ar
d
00

ve
12

Pa

AS SHOWN
00
50

00
15

EAST LEGON HILLS

1 : 100
OCTOBER, 2018
PKO.
SIAW
BLOCK PLAN ING.CYPRIAN K. WENYONU

45 A-001 01
GENERAL NOTES
1. All dimensions are in millimeter (mm)
1. Do not scale from the drawing

A B C D E
9500

4400 1700 2250 1150

806 2000 1744 352 900 298 347 765 2439

2860

exit

600
1 W1 D1 1

875
1100

1100
1625
2 D1
BEDROOM 2
2

2000
2
11.21m

W1
2500

2500
KITCHEN AREA

2000
2

W1
21.04m
STORE
2
3.64 m

875
3 D2 3

900
W3
1500

1500
WC/BATH
2075 4.39m
2

850
4 4
1200

1200
LOBBY
8.53m2
WC/BATH

D2
900

W2
2.21m
DINING AREA
5 5

2000
2

W1
29.75m
13750

13750
1200

1200
1486

UP
6 6

850
WC/BATH
1750

1750
900

2
W2

5.20 m

900
W3
7 LIVING AREA
D1
D2
7 contact :

1325
2
29.75m
e-mail :
3414
3000

3000
BEDROOM 1
2
21.53m

2000
W1
PROPOSED FOUR (4) BEDROOM RESIDENTIAL
BUILDING LOCATED AT EAST LEGON HILLS..
8 W1 D1
8
1500

1500
1325
9 W4
9
DANIEL PROVENCAL

entrance

AS SHOWN
806 2000 430 900 173 3100 2000 150

4405 1695 2250 1150


9500
EAST LEGON HILLS

A B C D E
1 : 100
OCTOBER, 2018

GROUND FLOOR PLAN PKO.


SIAW
SCALE 1:100 ING.CYPRIAN K. WENYONU

45 A-002 02
GENERAL NOTES
1. All dimensions are in millimeter (mm)
1. Do not scale from the drawing

A B C D E F
9500

3131 1269 1700 2250 1150

806 2000 3219 2000 1625

1 W1 W1 1

1635

2850
3600
WALK-IN CLOSET

3600
2
11.48 m MASTER BEDROOM
2
21.96m

2000
W1
2 D2 2

750
3 3
D1
900

W3
WC/BATH
1500

1500
8.93 m

1865
1200

4 4
1200

1200
LOBBY
900

W3

8.67 m
2
DOWN
5 5

2000
WC/BATH

W1
2
6.71m
1200

1200
14341

14341
1486

6 6
D2
D1

850
1750

1750
900

W2

900
W2
7 7 contact :

900
BEDROOM 3 FAMILY AREA
2 2
19.55m 18.81m
e-mail :

900
3414

W2
3000

3000
8 D3
8 PROPOSED FOUR (4) BEDROOM RESIDENTIAL
BUILDING LOCATED AT EAST LEGON HILLS..
9 W1
9

3366
TERRACE
2091

2091
2
2016

13.94m

DANIEL PROVENCAL
10 10
AS SHOWN

806 2000 1594 347 2347 2903


4405 1695 2250 1150
9500
EAST LEGON HILLS

A B C D E F 1 : 100
OCTOBER, 2018
FIRST FLOOR PLAN PKO.
SIAW
SCALE 1:100
ING.CYPRIAN K. WENYONU

45 A-003 03
GENERAL NOTES
1. All dimensions are in millimeter (mm)
1. Do not scale from the drawing

NORTH ELEVATION SOUTH ELEVATION


SCALE 1:100 SCALE 1:100

contact :

e-mail :

PROPOSED FOUR (4) BEDROOM RESIDENTIAL


BUILDING LOCATED AT EAST LEGON HILLS..

DANIEL PROVENCAL

WEST ELEVATION EAST ELEVATION


SCALE 1:100 SCALE 1:100
AS SHOWN

EAST LEGON HILLS

1 : 100
OCTOBER, 2018
PKO.
SIAW
ING.CYPRIAN K. WENYONU

ELEVATION

45 A-004 04
GENERAL NOTES
1. All dimensions are in millimeter (mm)
1. Do not scale from the drawing

3 LAYER FLINTKOTE
WATERPROOF
A B C F
MEMBRANE LAID ON
250 REINFORCED CONC.
CONCRETE SLAB
COPING 50 50
150

SOFFIT

1000
1000
RENDERED
AND PAINTED

BLOCKWORK
`A`

350
REINFORCED CONCRETE
BEAM

DETAIL `A`

2800

3150

7300
450
900

3150
1350
450 150
earth filling

hardcore filling hardcore filling


hardcore filling

contact :

e-mail :

PROPOSED FOUR (4) BEDROOM RESIDENTIAL


BUILDING LOCATED AT EAST LEGON HILLS..

DANIEL PROVENCAL

AS SHOWN

EAST LEGON HILLS

1 : 100
OCTOBER, 2018
PKO.
SIAW
ING.CYPRIAN K. WENYONU

45 A-005 05
GENERAL NOTES
1. All dimensions are in millimeter (mm)
1. Do not scale from the drawing

900 750
2000

50 450 50 450 50 450 50 450 50

DARK GRAY POWDER COATED ALUMINUM


FRAME WITH CLEAR GLASS SLIDING WINDOW

2000 900 900 2000

50 925 50 925 50 50 800 50 50 800 50 50 1900 50 contact :

e-mail :

PROPOSED FOUR (4) BEDROOM RESIDENTIAL


BUILDING LOCATED AT EAST LEGON HILLS..

DANIEL PROVENCAL

AS SHOWN
DARK GRAY POWDER COATED ALUMINUM DARK GRAY POWDER COATED ALUMINUM DARK GRAY POWDER COATED ALUMINUM DARK GRAY POWDER COATED ALUMINUM
FRAME WITH CLEAR GLASS SLIDING WINDOW FRAME WITH CLEAR GLASS SLIDING WINDOW FRAME WITH CLEAR GLASS SLIDING WINDOW FRAME WITH CLEAR GLASS SLIDING WINDOW

EAST LEGON HILLS

1 : 100
OCTOBER, 2018
PKO.
SIAW
ING.CYPRIAN K. WENYONU

45 A-006 06
GENERAL NOTES
1. All dimensions are in millimeter (mm)
1. Do not scale from the drawing
LEGEND
1. F = FLOOR
1. granite (450x900x19)mm polished in - situ
9500
2. ceramic tile (600x600x12)mm matte finish
4400 1700 2250 1150 ceramic tile (450x450x12)mm matte finish
3.
4. granolitic paving

5. in -situ Terazzo
6. pigmented floor paint on sand cement screed
2860
2. S = SKIRTING
1. 20X100mm chamfered edge timber "Emire" skirting

2. 20X100mm granite skirting

3. 10X100mm ceramic tile matte finish

4. 8X100mm ceramic tile polished


BEDROOM 2
11.21m
2 5. 10X100mm ceramic tile polished

F S W C F S W C 6. 20X100mm granolitic (polished)


KITCHEN AREA 2 3 2 3 2 3 2 10
21.04m
2

STORE
7. 10X100mm guarry tiles
F S W C
2 3 2 3
3.64 m
2
8. 8X100mm ceramic tile

WC/BATH
3. W = WALL
2
4.39m

emulsion paint on fair faced application


1.
of gypsum to rendered surface

DINING AREA
WC/BATH
2.21m
2 2. matte acrylic paint on fair faced application
2
29.75m of gypsum to rendered surface
F S W C
2 3 2 10
3. emulsion paint on tyrolean

4. matte acrylic paint on tyrolean

F S WC WC/BATH
5.20 m
2
5. glazed ceramic tile to ceilling (200x300x10mm)
2 3 2 10 6. glazed ceramic tile to door hight with matt acrylic
paint above to ceilling.(tiles to flush with render)
LIVING AREA
29.75m
2 7. designed timber board cladding
contact :
8. timber "Asamfona" T&G strip cladding
e-mail :
BEDROOM 1

4. C = CEILING
2
21.53m

F S W C
2 3 2 10
1. mineral fibre board (1200x2400x12)mm/(600x600x12) PROPOSED FOUR (4) BEDROOM RESIDENTIAL
as corner battens BUILDING LOCATED AT EAST LEGON HILLS..
2. gypsum board (1200x2400x12)mm on
proprietary suspension system

3. gypsum board (600x600x12)mm on proprietary


DANIEL PROVENCAL
4. mineral fibre board (600x600x19)mm, Acoustic on
proprietary suspension system

5. smooth emulsion paint on rendered conc. soffit AS SHOWN


6. oil paint on rendered conc. soffit
4405 1695 2250 1150
7. textured paint on rendered conc. soffit
9500
8. lacquered " Emire T&G strips
9. acrylic paint on 9mm ordinary plywood
EAST LEGON HILLS
10.emulsion paint on plaster board
11.perforated chipboard (600x600x12mm)-smooth finish
1 : 100
12.Exterior quality gypsum board (600x600x12mm) on OCTOBER, 2018
proprietary suspension system
PKO.
SIAW
ING.CYPRIAN K. WENYONU

FINISHES LAYOUT ON GROUND FLOOR


45 A-007 07
GENERAL NOTES
1. All dimensions are in millimeter (mm)
1. Do not scale from the drawing
LEGEND
1. F = FLOOR
granite (450x900x19)mm polished in - situ
9500 1.
2. ceramic tile (600x600x12)mm matte finish
3131 1269 1700 2250 1150 ceramic tile (450x450x12)mm matte finish
3.
4. granolitic paving

5. in -situ Terazzo
6. pigmented floor paint on sand cement screed

2. S = SKIRTING
1. 20X100mm chamfered edge timber "Emire" skirting

2. 20X100mm granite skirting

3. 10X100mm ceramic tile matte finish

F S W C 4. 8X100mm ceramic tile polished


2 3 2 10
5. 10X100mm ceramic tile polished
WALK-IN CLOSET
11.48 m
2
MASTER BEDROOM
2
6. 20X100mm granolitic (polished)
21.96m

F S W C
7. 10X100mm guarry tiles
2 3 2 10 8. 8X100mm ceramic tile

F S WC
2 3 2 3 3. W = WALL
WC/BATH
2
8.93 m

1. emulsion paint on fair faced application


of gypsum to rendered surface

F S W C 2. matte acrylic paint on fair faced application


LOBBY
2 3 2 3 2 of gypsum to rendered surface
8.67 m
WC/BATH
F S W C
3. emulsion paint on tyrolean
2
6.71m
2 3 2 10
4. matte acrylic paint on tyrolean

5. glazed ceramic tile to ceilling (200x300x10mm)

6. glazed ceramic tile to door hight with matt acrylic


paint above to ceilling.(tiles to flush with render)

7. designed timber board cladding contact :


BEDROOM 3
19.55m
2
FAMILY AREA
2
18.81m 8. timber "Asamfona" T&G strip cladding
e-mail :
F S W C
F S W C
2 3 2 10
2 3 2 10 4. C = CEILING
1. mineral fibre board (1200x2400x12)mm/(600x600x12) PROPOSED FOUR (4) BEDROOM RESIDENTIAL
as corner battens BUILDING LOCATED AT EAST LEGON HILLS..
F S W C
2 3 1 1 2. gypsum board (1200x2400x12)mm on
TERRACE proprietary suspension system
2
13.94m

3. gypsum board (600x600x12)mm on proprietary


DANIEL PROVENCAL
4. mineral fibre board (600x600x19)mm, Acoustic on
proprietary suspension system

5. smooth emulsion paint on rendered conc. soffit AS SHOWN


6. oil paint on rendered conc. soffit
7. textured paint on rendered conc. soffit
4405 1695 2250 1150 8. lacquered " Emire T&G strips
9500
9. acrylic paint on 9mm ordinary plywood EAST LEGON HILLS
10.emulsion paint on plaster board
11.perforated chipboard (600x600x12mm)-smooth finish 1 : 100

12.Exterior quality gypsum board (600x600x12mm) on OCTOBER, 2018


proprietary suspension system PKO.
SIAW
ING.CYPRIAN K. WENYONU

FINISHES LAYOUT ON FIRST FLOOR 45 A-008 08


GENERAL NOTES
1. All dimensions are in millimeter (mm)
1. Do not scale from the drawing

LEGEND

18w, compact luminaire with corrosion resistant diffuser


NOTES
1. Do not scale from the layout drawings. Work according to architectural or electricall
2x36w, corrosion resistant fluorescent luminaire
details unless otherwise authorised.
1x36w, surface mounted fluorescent luminaire with acrylic diffuser
2. All lighting and fan points bearing the same number and/or switched from the same single
18w, cfl luminaire with die cast aluminium and wall mounted prismatic diffuser
pole switch shall be wired and connected to the same circuit on the distribution board.
16w, wall mounted white polycarbonate square luminaire with opal diffuser and
lamp 3. Ganged lighting switches shall be of the phase barrier model
16w, white polycarbonate sqaure luminaire with opal diffuser and lamp 4. All 13-A switched socket outlets bearing the same number shall be ring circuit wired and
connected to the same circuit on the distribution board.
9w, surface mounted luminaire with acrylic diffuser
5. The circuit protective conductor of every ring final sub-circuit shall also be run in the form
13w, cfl ceiling mounted luminaire with tubular satin glass diffuser
of a ring having both ends connected to the earthing terminal at the origin of the circuit.
16w, white polycarbonate circular luminaire with opal diffuser and lamp
6. All wiring shall be of the concealed pvc condiut system unless otherwise indicated.
18w, 600mm fluorescent luminaire with shaver unit 7. Cable sizes for all circuits shall be as indicated in the schematic distribution diagrams.
36w, 1200mm fluorescent luminaire installed under first floor stairway Cable specifications in the schematic distribution diagrams are for 3x1c, pvc insulated
copper cables unless otherwise indicated.
E 8w non-maintain emergency lighting of 3hour duration
8. The size of all conduits shall be selected in accordance with regulations and as a function
1400mm crompton type ceiling mounted fan complete with regulator of the number and sizes of the indicated conductors. The minimum size of conduit for all
150mm dia wall mounted extractor fan applications shall be 20mm.

1 gang 1way 6A sp plate switch 9. The electrical contractor shall use the schematic diagram for the wiring for effective balance
of the system. He shall ensure that the connected load at the time of testing is properly
2 gang 1way 6A sp plate switch balanced.
10. All manual fire alatm call points,automatic fire alarm call points and fire alarm sounders
1 gang 2way 6A sp plate switch shall be sited as indicated on the drawings and shall be wired with 3c, 2.5mm FP 200
fire resistant cables.
13A 1 gang flush mounted switched socket outlet
11. Any connection of the fire alarm system to an a/c mains supply shall be taken directly
13A 2 gang flush mounted switched socket outlet from the mains power intake to the building and arranged in such a way that it cannot
be switched off in error or confused with lighting or other power circuits. A separate fused
13A 2 gang flush mounted switch socket outlet mounted at 1200mm above isolation switch suitably labelled shall be provided and connected as power supply to the
finished floor level fire alarm supervisory control panel (FAP) and fire alarm repeater panels (FRP).
13A 1 gang flush mounted switch socket outlet mounted at 1200mm above
finished floor level 12. All metal parts other than current carrying parts shall be effectively earthed.
Flush mounted telephone socket outlet 2
13. The highest point of the lightning preventor air terminal shall not be less than
20A dp control switch with neon and marked for Air-conditioner 3000mm above the highest salient point of the building.
14. In fixing the lightning preventor down tapes, there shall be no sharp bends and absulutely contact :
TV Single TV coaxial socket outlet no up turns.
CU e-mail :
Consumer unit 15. Loud speaker outlet points shall be wired with 3c, 2.5mm stranded double sheated stranded
DB copper cables.
Distribution board
MDB 16. The entire installation shall comply with the current edition of the IEE regulations.
Main distribution panel board
PROPOSED FOUR (4) BEDROOM RESIDENTIAL
Main earthing system BUILDING LOCATED AT EAST LEGON HILLS..
Early streamer emmission Air terminal
w 20A dp control switch and marked water heater
Bell and bell push DANIEL PROVENCAL

BT Telephone terminal box (100 x 100 x 50mm)


45A, 240V cooker control unit mounted 1200mm above finish floor level AS SHOWN
20A, 240V control switch for pump
13A dp fused connection unit with neon indicator
Indoor video/audio display unit
EAST LEGON HILLS
Manual change over switch
16A, 240V industrial switch for Generator
1 : 100
Manual change over switch
OCTOBER, 2018
m E . C . G Pre-paid meter PKO.
SIAW
ING.CYPRIAN K. WENYONU

45 MEP-001 09
GENERAL NOTES
1. All dimensions are in millimeter (mm)
1. Do not scale from the drawing

9500

4400 1700 2250 1150

BEDROOM 2

S
KITCHEN AREA S

S STORE
tv

WC/BATH
S2
tv S

S2 WC/BATH

DINING AREA

WC/BATH S

contact :
LIVING AREA
tv e-mail :

S BEDROOM 1

PROPOSED FOUR (4) BEDROOM RESIDENTIAL


S
BUILDING LOCATED AT EAST LEGON HILLS..

tv

DANIEL PROVENCAL

AS SHOWN

4405 1695 2250 1150


EAST LEGON HILLS
9500

1 : 100
OCTOBER, 2018
PKO.
SIAW
ING.CYPRIAN K. WENYONU

ELECTRICAL LAYOUT ON GROUND FLOOR-(POWER)


45 MEP-002 10
GENERAL NOTES
1. All dimensions are in millimeter (mm)
1. Do not scale from the drawing

9500

3131 1269 1700 2250 1150

S
WALK-IN CLOSET
MASTER BEDROOM

WC/BATH

tv

LOBBY

WC/BATH

S
contact :
BEDROOM 3 FAMILY AREA

e-mail :
S

tv

PROPOSED FOUR (4) BEDROOM RESIDENTIAL


BUILDING LOCATED AT EAST LEGON HILLS..

TERRACE

DANIEL PROVENCAL

AS SHOWN

4405 1695 2250 1150


9500 EAST LEGON HILLS

1 : 100
OCTOBER, 2018
PKO.
SIAW
ING.CYPRIAN K. WENYONU

ELECTRICAL LAYOUT ON FIRST FLOOR-(POWER)


45 MEP-003 11
GENERAL NOTES
1. All dimensions are in millimeter (mm)
1. Do not scale from the drawing

9500

4400 1700 2250 1150

L1

L1 BEDROOM 2

L1 L1
L1
KITCHEN AREA

STORE
L1

L1 L1
WC/BATH

L1 WC/BATH

DINING AREA

L1 L1

WC/BATH L1

L1
contact :
LIVING AREA
e-mail :
L1

BEDROOM 1

PROPOSED FOUR (4) BEDROOM RESIDENTIAL


L1 L1
BUILDING LOCATED AT EAST LEGON HILLS..

DANIEL PROVENCAL

AS SHOWN

4405 1695 2250 1150


9500
EAST LEGON HILLS

1 : 100
OCTOBER, 2018
PKO.
SIAW
ING.CYPRIAN K. WENYONU

ELECTRICAL LAYOUT ON GROUND FLOOR-(LIGHTING) 45 MEP-004 12


GENERAL NOTES
1. All dimensions are in millimeter (mm)
1. Do not scale from the drawing

9500

3131 1269 1700 2250 1150

L3

L1 L1

WALK-IN CLOSET
MASTER BEDROOM

L1

WC/BATH L1
L1

L1 LOBBY

WC/BATH
L1

L1

contact :
L1 L1 L1
BEDROOM 3 FAMILY AREA
e-mail :
L1

L1

PROPOSED FOUR (4) BEDROOM RESIDENTIAL


BUILDING LOCATED AT EAST LEGON HILLS..
L3

TERRACE

DANIEL PROVENCAL

AS SHOWN

4405 1695 2250 1150


EAST LEGON HILLS
9500

1 : 100
OCTOBER, 2018
PKO.
SIAW
ING.CYPRIAN K. WENYONU

ELECTRICAL LAYOUT ON FIRST FLOOR-(LIGHTING)


45 MEP-005 13
GENERAL NOTES
LEGEND 1. All dimensions are in millimeter (mm)
1. Do not scale from the drawing
SYMBOL DESCRIPTION

S Addressable Smoke Detector


( ceiling mounted )

Addressable Heat Detector


H
9500 ( ceiling mounted )

4400 1700 2250 1150 Addressable Manual Call Point


( wall mounted )
Addressable Electronic Sound
Flasher ( wall mounted )

Dry Powder Fire Extinguisher

Carbon Dioxide Fire Extinguisher


Co2

Fire Alarm Control Panel


FACP ( wall mounted )

BEDROOM 2

S S

KITCHEN AREA STORE

WC/BATH

WC/BATH

DINING AREA

WC/BATH
S

contact :
LIVING AREA

e-mail :

BEDROOM 1

S PROPOSED FOUR (4) BEDROOM RESIDENTIAL


BUILDING LOCATED AT EAST LEGON HILLS..

DANIEL PROVENCAL

AS SHOWN

4405 1695 2250 1150


9500
EAST LEGON HILLS

1 : 100
OCTOBER, 2018
PKO.
SIAW
ING.CYPRIAN K. WENYONU

FIRE SAFETY SYSTEM INSTALLATION ON GROUND FLOOR


45 MEP-006 14
GENERAL NOTES
1. All dimensions are in millimeter (mm)
LEGEND
1. Do not scale from the drawing

SYMBOL DESCRIPTION

S Addressable Smoke Detector


( ceiling mounted )
Addressable Heat Detector
9500 H
( ceiling mounted )
3131 1269 1700 2250 1150 Addressable Manual Call Point
( wall mounted )
Addressable Electronic Sound
Flasher ( wall mounted )

Dry Powder Fire Extinguisher

Carbon Dioxide Fire Extinguisher


Co2

Fire Alarm Control Panel


FACP ( wall mounted )

WALK-IN CLOSET
MASTER BEDROOM

S S

WC/BATH

LOBBY

WC/BATH

contact :
BEDROOM 3 FAMILY AREA
e-mail :
S S

PROPOSED FOUR (4) BEDROOM RESIDENTIAL


BUILDING LOCATED AT EAST LEGON HILLS..

TERRACE

DANIEL PROVENCAL

AS SHOWN

4405 1695 2250 1150


EAST LEGON HILLS
9500

1 : 100
OCTOBER, 2018
PKO.
SIAW
ING.CYPRIAN K. WENYONU

FIRE SAFETY SYSTEM INSTALLATION ON FIRST FLOOR 45 MEP-007 15


GENERAL NOTES
1. All dimensions are in millimeter (mm)
1. Do not scale from the drawing

LEGEND
NOTE.
COLD WATER PIPE THIS DRAWING SHALL BE READ IN CONJUNCTION WITH
ALL ARCHITECTURAL DRAWINGS.

WASTE PIPE 1. ALL WASTE WATER PIPES SHALL BE 50mm EXCEPT THE
OUTGOING FROM THE WASH HAND BASIN WHICH ARE
32mm CONNECTED TO A 50mm MAIN PIPE.
HOT WATER PIPE
2. ALL SANITARY APPLIANCES AND FLOOR DRAINS SHALL
BE FITTED WITH APPROPRIATE TRAPS.
SOIL PIPE
3. RODDING EYES SHALL BE FITTED AT ALL SUITABLE LOCATIONS
IN THE WASTE WATER SYSTEM.
STOP COCK

4. ALL DIMENSIONS ARE IN mm.

MANHOLE
5. WHERE COLD WATER PIPES AND SOIL PIPES CROSS EACH OTHER ,
THE COLD WATER PIPE SHALL BE ON TOP WITH A MINIMUM
INSPECTION CHAMBER
CLEARANCE OF 200mm.

STOP VALVE 6. ALL SANITARY APPLIANCES AND ENTRY POINTS SHALL BE FITTED
WITH APPROPRIATE STOP VALVES AND COUPLINGS.
KITCHEN SINK
7. NO WASTE PIPE SHALL JOIN ANOTHER (WASTE OR SOIL) PIPE AT
AN ANGLE OF 900 OR WITH A 'T' JOINT

8. POSITION OF COLD WATER INTAKE AND STORAGE EQUIPMENT contact :


W C BOWL
ARE ONLY SHOWN INDICATIVELY. EXACT POSITION OF THESE e-mail :
ITEMS SHALL SHOWN ON SITE BY THE CONSULTANTS.
PROPOSED FOUR (4) BEDROOM RESIDENTIAL
WASH HAND BASIN BUILDING LOCATED AT EAST LEGON HILLS..

BATH BOWL DANIEL PROVENCAL

WH AS SHOWN
15LIT. CAPACITY ELECTRIC WATER
w wh
s HEATER C/W SWITCH

EAST LEGON HILLS


F
1 : 100
OCTOBER, 2018
FHR PKO.
SIAW
ING.CYPRIAN K. WENYONU

45 MEP-008 16
GENERAL NOTES
1. All dimensions are in millimeter (mm)
1. Do not scale from the drawing

9500

4400 1700 2250 1150

ic 100mm dia. waste pipe ic ic 100mm dia. waste pipe ic

BEDROOM 2

ic
ic KITCHEN AREA

STORE

mh

WC/BATH

ic

WC/BATH

DINING AREA

ic
WC/BATH

mh
contact :
LIVING AREA
e-mail :
ic
BEDROOM 1

PROPOSED FOUR (4) BEDROOM RESIDENTIAL


BUILDING LOCATED AT EAST LEGON HILLS..

mh

DANIEL PROVENCAL

AS SHOWN

4405 1695 2250 1150


9500 EAST LEGON HILLS

1 : 100
OCTOBER, 2018
PKO.
SIAW
ING.CYPRIAN K. WENYONU

PLUMBING LAYOUT ON GROUND FLOOR(WASTEWATER DISPOSAL) 45 MEP-009 17


GENERAL NOTES
1. All dimensions are in millimeter (mm)
1. Do not scale from the drawing

9500

3131 1269 1700 2250 1150

WALK-IN CLOSET
MASTER BEDROOM

WC/BATH

LOBBY

WC/BATH

contact :
BEDROOM 3 FAMILY AREA
e-mail :

PROPOSED FOUR (4) BEDROOM RESIDENTIAL


BUILDING LOCATED AT EAST LEGON HILLS..

TERRACE

DANIEL PROVENCAL

AS SHOWN

4405 1695 2250 1150


9500 EAST LEGON HILLS

1 : 100
OCTOBER, 2018
PKO.
SIAW
ING.CYPRIAN K. WENYONU

PLUMBING LAYOUT ON FIRST FLOOR(WASTEWATER DISPOSAL) 45 MEP-010 18


GENERAL NOTES
1. All dimensions are in millimeter (mm)
1. Do not scale from the drawing

9500

4400 1700 2250 1150

BEDROOM 2

KITCHEN AREA

STORE

WC/BATH

WC/BATH

DINING AREA

WC/BATH

40mm dia.
contact :
LIVING AREA
e-mail :

BEDROOM 1 booster pump


PROPOSED FOUR (4) BEDROOM RESIDENTIAL
BUILDING LOCATED AT EAST LEGON HILLS..

(1no.) water storage tank


(7,000litres)
DANIEL PROVENCAL

stop valve AS SHOWN

water meter

50mm dia. cw pipe from mains EAST LEGON HILLS

1 : 100
OCTOBER, 2018
PKO.
SIAW
ING.CYPRIAN K. WENYONU

PLUMBING LAYOUT ON GROUND FLOOR(COLD WATER DISTRIBUTION) 45 MEP-011 19


GENERAL NOTES
1. All dimensions are in millimeter (mm)
1. Do not scale from the drawing

9500

3131 1269 1700 2250 1150

WALK-IN CLOSET
MASTER BEDROOM

WC/BATH

LOBBY

WC/BATH

contact :
FAMILY AREA
BEDROOM 3
e-mail :

PROPOSED FOUR (4) BEDROOM RESIDENTIAL


BUILDING LOCATED AT EAST LEGON HILLS..

TERRACE

DANIEL PROVENCAL

AS SHOWN

4405 1695 2250 1150


EAST LEGON HILLS
9500

1 : 100
OCTOBER, 2018
PKO.
SIAW
ING.CYPRIAN K. WENYONU

PLUMBING LAYOUT ON FIRST FLOOR(COLD WATER DISTRIBUTION) 45 MEP-012 20


GENERAL NOTES
1. All dimensions are in millimeter (mm)
Air should be excluded from s.t.l. to encourage the growth of amaaic bacteria to liquify sludge to facilitate the flow of the effluent accumated gasses are
1. Do not scale from the drawing
expected to be connected and expelled through f.a.o which should carried above eaves be protected against nestling of birds as in drawing.
septic tanks must be constructed in concrete and not sandcrete blocks top of septic tank to be not less than 150mm above finished ground level where
two or more water closets connected to the same soil pipe the trap on each water closet
other than the highest shall be ventilated to be an antisyphon pipe to the open air at a point 75mm above the weater seal in the highest water antisyphon
pipe and connections should be at 50mm intervals and shall be connected with the arm of
soil sipe at a point not less than 150mm and not more than 300mm from the highest point of the water seal which is nearest to the soil pipe
drains should be given sufficient falls and joints should be properly made to prevent blocking of the apperture and expedite the escape of accumulated
gasses.

contact :

e-mail :

PROPOSED FOUR (4) BEDROOM RESIDENTIAL


BUILDING LOCATED AT EAST LEGON HILLS...

DANIEL PROVENCAL

AS SHOWN

EAST LEGON HILLS

1 : 100
OCTOBER,2018
PKO.
SIAW
ING.CYPRIAN K. WENYONU

SEPTIC TANK DETAILS 45 MEP-013 21


GENERAL NOTES
1. All dimensions are in millimeter (mm)
1. Do not scale from the drawing

bending schedules
for r. c. septic tank

3000

750 2000 2000 2000


225 150 225 225
(06) 128- R12 @ 150 c\c
(07) 80 R12 @ 150 c\c

(03) 12- R12 @ 150 c\c


(04) 40- R12 @ 150 c\c

(05) 22- R12 @ 150 c\c


600

2400 600 600


600

600 600 2100


600

750 2175 2175


225 150 225

contact :
(08) 72- R12 @ 150 c\c
e-mail :
(09) 120 R12 @ 150 c\c

(02)14- R12 @ 150 c\c


PROPOSED FOUR (4) BEDROOM RESIDENTIAL
BUILDING LOCATED AT EAST LEGON HILLS...

(01) 41- R12 @ 125 c\c

DANIEL PROVENCAL

AS SHOWN

5100

EAST LEGON HILLS

1 : 100
OCTOBER,2018
PKO.

SEPTIC TANK DETAILS SIAW


ING.CYPRIAN K. WENYONU

45 MEP-014 22