McDonnell & Miller

Installation & Maintenance


Instructions
MM-248(C)
Conductance Actuated
Level Controls
Series 750B
(Panel Mount)
Series 750BM
(Plug-In Module)
Series 750B

Typical Applications:
– LWCO for steam or hot water boilers
– Differential level control
Features:
– 24 VAC and 120 VAC models
– Panel mount or plug-in module
– Automatic or manual reset
– CSD-1 Code Compliant
The Series 750B controllers provide reliable control of burner
circuits, motor starters, electric valves or pumps in boilers, cooling
towers or other liquid level applications. Designed for use with the
750-C chamber, Series RS sensors or other remote probes to Series 750BM
create a complete operating system.

! WARNING
• All work must be performed by qualified personnel trained in the proper application, instal-
lation, and maintenance of plumbing, steam, and electrical equipment and/or systems in
accordance with all applicable codes and ordinances.
WARN
ING
CAUT
ION
• Read and understand these instructions prior to installation and save this document for
future reference.
• To prevent electrical shock, turn off system power before making electrical connections.
• If used as a LWCO, the control must be installed in series with all other limit and operating
controls.
• We recommend that secondary (redundant) Low Water Cut-Off controls be installed on all
steam boilers with heat input greater than 400,000 BTU/hour or operating above 15 psi of
steam pressure. At least two controls should be connected in series with the burner control
circuit to provide safety redundancy protection should the boiler experience a low water
condition. Moreover, at each annual outage, the low water cut-offs should be dismantled,
inspected, cleaned, and checked for proper calibration and performance.
• Probe wire distance MUST NOT EXCEED 500 ft. Use MTW or THHN #14 or #16 AWG wire
and MUST BE separate from high voltage wire runs.
• Reset switch wire length MUST NOT EXCEED 50 ft. Use same type of wire designated for
probe wires and MUST BE separate from high voltage wire runs.
Failure to follow this warning could cause property damage, personal injury or death.
LWCO Models Pump Control Models
750 xx - x - xxx - x - xx 750 xx - x - xxx - xx - xx xx

LWCO Delay LP Delay


01-60 01-60

Sensitivity (Kilo-ohms) HP Delay


C 26K 00
01-60
Voltage
24 24 VAC Power Input Level Delay
120 120 VAC Power Input I Inverse (pump up)

Function Sensitivity
L Low Water Cut-Off C 26K

Design Voltage
B Panel Mount 120 120 VAC Power Input
BM Plug-In Module
Function
P Differential Level Control
Specifications
Design
NEMA Rating: None B Panel Mount
Temperature: BM Plug-In Module
Storage: -40 to 150 deg. F (-40˚ to 65˚C)
Ambient: 0 to 150 deg. F (-17˚ to 65˚C)
Humidity: 85% (non-condensing)
Contact Rating: 7.2A, 1/3 HP, 120VAC
Power Consumption: 1.5VA

INSTALLATION CSD-1 Code Compliance


750BM Octal Socket: On Manual Reset units, if the control is in a low-
1. Install socket in appropriate enclosure using water condition (water off probe) when there is an
two (2) #6 or #8 sheet metal screws. interruption of power, the control will remain in a
2. For rail mount Octal socket - Install socket on low-water condition when power is restored. The
appropriate rail (DIN mount) in enclosure. reset button will need to be pressed when the
water level is restored to a level above the probe.
3. Wire socket per 750BM wiring diagram, following
NEC and local codes.
4. Install 750BM control module in socket.
750B Panel Mount Circuit Board:
1. Install circuit board in an appropriate enclosure. MAINTENANCE
2. Drill (3) 3/16” (5mm) diameter holes per provided
dimensional template on page 3. Standard SCHEDULE:
stand-offs (provided) are designed for back
• Inspect probe annually for scale build-up and
plates of 1/8” (3mm) nominal thickness.
clean if necessary. Make certain there is no
3. Install circuit board being careful that the three scale or build-up on the probe or its white
stand-offs align with the appropriate drilled holes. insulator.
Gently push down on the circuit board at the
• Replace probe every 10 years. More frequent
outer edges of all four corners. CAUTION: Do
replacement of the probe is required if it is used
not overflex the circuit board during installa-
in locales where significant water treatment is
tion. Do not push down on the transformer
required, where more frequent cleaning is
or relays during installation.
necessary, or in applications with high make-up
4. Wire control per 750B wiring diagram, following water requirements.
NEC and local codes. Use approporiate sized
spade connectors. • Replace the low water cut-off every 15 years.

2
Dimensions
750BM-L-24 750B-L-24
750BM-L-120 750B-L-120
750BM-P-120 750B-P-120
Dimensional Template
1 3/4" (44)

2 3/16" (55)
1 3/4" (44)
7/32" (5)
2 13/16" (71)

2 3/32"
(17)
TRANSFORMER
3 15/16" (100)

2 1/2" (63)
1 5/8" (41)
(19)
3/4"

1" (25)

750BM-11PS 750BM-8PS
2 11/32" (68)
2 1/16" (52) 2" (50)
1" (25)
1 1/32"(26)

1 5/16" (33)
1 9/16" (39)
2 1/32" (51)

The Series 750B is an open circuit board design


which needs to be mounted in an appropriate
enclosure. The following items are available for
mounting the board.

Mounting Plate 750B-PL (176320) 750B-PL Mounting Plate


This is a plate which can be mounted in an existing
enclosure to which any of the Series 750B circuit
boards can be mounted.
McDonnell & Miller
Liquid Level Control
Enclosure 750B-ENC (176345)
Any of the 750B circuit boards can be installed in
this enclosure which is a NEMA 1 General
Purpose UL recognized component. A mounting
plate and standoffs are included. 750B-ENC Enclosure

3
McDonnell & Miller
750BM-L-24 and 750BM-L-120 750B-L-24 and 750B-L-120
AC SUPPLY
NOTE N H
CONTACT COMMON LOAD
AC SUPPLY INTERNALLY WIRED TO L1
N H TANK CAN BE USED AS GROUND
LOAD PROBE IF IT IS METALLIC

L1(1)
TANK CAN BE USED AS GROUND

NC (11)

COM

NO (10)
N.C. PROBE IF IT IS METALLIC
L1
11 N.O.

TRANSFORMER
1 10
N.C. RESET
OPTIONAL
2 9

N.C. RESET (7)


3 8 RESET
L2 OPTIONAL RESET (8)

4 7 LOW (6)

L2(2)
GND (5)
5 6

GND PROBE GROUND PROBE IS


LONGEST PROBE
GROUND PROBE IS
LONGEST PROBE

FOR METAL TANK


Automatic Reset Manual Reset
When liquid is on the probe connected to terminal #6, the With a normally closed pushbutton switch (supplied by
relay is energized (LED will be lit). When there is no others) connected to terminals #7 and #8, and after a low
water on the probe, the relay is de-energized (LED will water condition, the relay will remain de-energized until
not be lit). the pushbutton is pressed and the liquid rises to the level
of the probe connected to terminal #6 .

750BM-P-120 750B-P-120
AC SUPPLY
AC SUPPLY N H
N H
LOAD
LOAD TANK CAN BE USED AS GROUND
PROBE IF IT IS METALLIC
N.C. TANK CAN BE USED AS GROUND
L1(1)

PROBE IF IT IS METALLIC
NC (7)

COM (8)

NO (6)

L1 COMMON
1 8
N.C. CONT.
L2
TRANSFORMER

2 7
HIGH N.O. CONT.
PROBE
3 6
LOW (4)

LOW 4 5 GND HIGH (3)


PROBE
L2(2)

GND (5)

GROUND PROBE IS
LONGEST PROBE
GROUND PROBE IS
LONGEST PROBE

Differential Service Single Level Service


When liquid rises to the high probe (Terminal #3), the When the liquid rises to the probe connected to terminal
relay will de-energize opening contacts on terminals #8 #3, the relay will energize closing contacts on terminals
and #6. The relay will remain de-energized until the liquid #8 and #6. The relay will remain energized until the
falls below the low probe (Terminal #4) when it will ener- liquid falls below the probe when it will de-energize and
gize, closing the contacts on terminals #8 and #6. open contacts on terminals #8 and #6. Note that for
Single Level Service there is no probe connected to
terminal
ITT ©2007 ITT Corporation
8200 N. Austin Ave. Printed in U.S.A. 2-07 210059
Morton Grove, IL 60053
tel: 847-966-3700
fax: 847-966-9052
www.mcdonnellmiller.com