Sunteți pe pagina 1din 31

FUNCTIONAL ESD LOGIC DIAGRAM

CLAUS REACTION FURNACE 086-F-001 (BMS)


UNIT – 086

This Document is the property of INDIAN OIL CORPORATION LTD and is lent without PARADIP REFINERY PROJECT
consideration other than the Borrower’s agreement that it shall not be reproduced, copied, Paradip, Orissa State, India
lent or disposed of directly or indirectly, nor used for any purpose other than that for which it
is specifically furnished. The apparatus shown in the document is covered by patents.
Information contained in this document may be proprietary to Indian Oil Corporation Ltd
and/or licensors, and is subject to obligations of confidentiality.
INDIAN OIL
CORPORATION LIMITED
F2 12/06/12 ISSUED FINAL VIAR CHIPA OPT
F1 14/02/12 ISSUED FINAL VIAR CHIPA OPT
FUNCTIONAL ESD LOGIC DIAGRAM
CLAUS REACTION FURNACE 086-F-001
A1 24/08/11 ISSUED FOR DESIGN VIAR CHIPA
OPT OPT
UNIT - 086
Rev Date Description By Chkd Appd
Class DSN Contract No. Scale Document No. Sheet Rev
xx xxxxxxx xxxxxxxxxxx NTS PDRP271-8550-64-086-0004 1 of 31 F2
INDEX

SR. NO. INTERLOCK DESCRIPTION SHT. REV REV REV SR. NO. INTERLOCK DESCRIPTION SHT. REV
NO. NO. A1 F1 F2 NO. NO.

01 - FRONT SHEET 1 24/08/2011 14/02/2012 12/06/2012

02 - INDEX 2 14/02/2012 12/06/2012


24/08/2011

03 - GENERAL NOTES 3 24/08/2011 14/02/2012 12/06/2012

04 - STANDARD LEGEND & SYMBOLS 4 24/08/2011 14/02/2012 12/06/2012

05 086-IZ-0900 CLAUS REACTION FURNACE 5-23 24/08/2011 14/02/2012 12/06/2012

This Document is the property of INDIAN OIL CORPORATION LTD and is lent without PARADIP REFINERY PROJECT
consideration other than the Borrower’s agreement that it shall not be reproduced, copied, Paradip, Orissa State, India
lent or disposed of directly or indirectly, nor used for any purpose other than that for which it
is specifically furnished. The apparatus shown in the document is covered by patents.
Information contained in this document may be proprietary to Indian Oil Corporation Ltd
and/or licensors, and is subject to obligations of confidentiality.
INDIAN OIL
CORPORATION LIMITED
F2 12/06/12 ISSUED FINAL VIAR CHIPA OPT

F1 14/02/12 ISSUED FINAL VIAR CHIPA OPT


FUNCTIONAL ESD LOGIC DIAGRAM
CLAUS REACTION FURNACE 086-F-001
A1 24/08/11 ISSUED FOR DESIGN VIAR CHIPA
OPT OPT
UNIT - 086
Rev Date Description By Chkd Appd
Class DSN Contract No. Scale Document No. Sheet Rev
xx xxxxxxx xxxxxxxxxxx NTS PDRP271-8550-64-086-0004 2 of 26 F2
GENERAL NOTES :

1. This document has been developed from P&ID and Control Narrative. Refer to reference documents below.

2. Logic Convention

a) Logic 0 : The OFF state; the negative state; the inactive state; the false state; the Alarm/Trip State.
b) Logic 1 : The ON state; the positive state; the active state; the true state; the Healthy/Normal Operating State.
c) All Reset / Acknowledge contact inputs or soft buttons shall be momentary True/Closed on Reset/Acknowledge and returns to False/Open in steady state condition.

3. Unless otherwise stated, configurable (Default value = 2 Seconds) time delay and dead band shall be provided for each analogue input signal to avoid nuisance trips.

4. All analogue inputs will be converted to corresponding engineering units.

5. The alarm and trip analogue set points shall be in engineering units.

REFERENCES :

1. Process Control and Operation Philosophy PDRP4200-8120-PH-1002

2. Instrument Symbols and Identification PDRP-8550-SP-0003

3. SmartPlant Instrumentation Loop Templates PDRP4200-8550-SP-1019

4. Instrument / Electrical Interface Standard PDRP-8550-SP-0012

5. P&ID Symbology PDRP4240-8110-25-600-0001 to 0008 & 0013

6. SRU & Tail Gas Treating Units 085, 086, 087 & 089 Control Narratives PDRP4220-271-8120-PD-085-0001

7. SRU & Tail Gas Treating Units 085, 086, 087 & 089 SIS Logic Narrative PDRP4200-271-8110-RP-085-0002

8. Cause & Effect Summary Units 085, 086, 087 & 089 PDRP4220-271-8110-24-085-0001

This Document is the property of INDIAN OIL CORPORATION LTD and is lent without PARADIP REFINERY PROJECT
consideration other than the Borrower’s agreement that it shall not be reproduced, copied, Paradip, Orissa State, India
lent or disposed of directly or indirectly, nor used for any purpose other than that for which it
is specifically furnished. The apparatus shown in the document is covered by patents.
Information contained in this document may be proprietary to Indian Oil Corporation Ltd
and/or licensors, and is subject to obligations of confidentiality.
INDIAN OIL
CORPORATION LIMITED
F2 12/06/12 ISSUED FINAL VIAR CHIPA OPT

F1 14/02/12 ISSUED FINAL VIAR CHIPA OPT


FUNCTIONAL ESD LOGIC DIAGRAM
CLAUS REACTION FURNACE 086-F-001
A1 24/08/11 ISSUED FOR DESIGN VIAR CHIPA
OPT OPT
UNIT - 086
Rev Date Description By Chkd Appd
Class DSN Contract No. Scale Document No. Sheet Rev
xx xxxxxxx xxxxxxxxxxx NTS PDRP271-8550-64-086-0004 3 of 31 F2
SL NO SYMBOL DESCRIPTION SL NO SYMBOL DESCRIPTION
LOGIC STATE LOGIC STATE
AND GATE E1 E2 A E1 COMPARATOR (XNOR GATE) E1 E2 A
E1
All Inputs E1…...En=1, Output A=1. 0 0 0 All Inputs E1…...En identical, Output A=1.
1 & Any One Input Ei = 0, Output A=0. 0 1 0 11 XNOR A
Otherwise, Output A=0.
0 0 1
A En 0 1 0
En 1 0 0 1 0 0
1 1 1 1 1 1

LOGIC STATE
E1 OR GATE E1 E2 A
>1 All Inputs E1…...En=0, Output A=0. 0 0 0
2 = A
Any One Input Ei = 1, OUTPUT A=1. 0 1 1 12 X SHXX Y
CONNECTOR BLOCK
En Connects the Logic between multiple sheet.
1 0 1
1 1 1

Line Symbol Line Symbol Description


LOGIC STATE
E A NOT GATE Hard Wired Signal
E A
3 Negation Of Input 0 1 13 Serial Interface Signal
E A E = 0, Output A=1, AND Vice Versa. 1 0
Internal Logic Signal

ON DELAY
The continuous existence of logic input E for time T causes Generates a short negative pulse of time period T whenever
T 0 logic output A to exist when T expires. A terminates when E INPUT E INPUT E
A 14 E A input E changes from low to high
4 E terminates. OUTPUT A
T SECS 2 secs OUTPUT A
T Time “T” to be indicated in the qualifying symbol.
Time “T” to be indicated in the qualifying symbol. T

OFF DELAY
The existence of logic input E causes logic output A to exist
0 T
immediately. A terminates when E has terminated and has not INPUT E
5 E A
again existed for time T.
T SECS
OUTPUT A
T
Time “T” to be indicated in the qualifying symbol.

LOGIC STATE
Storage Flip Flop (Set Dominant) E1 E2 A
E1 S Output remains in the state of last activation of I/Ps. 0 0 Unchanged
A Refer Table for Details.
6 E2 R
0 1 0
1 0 1
1 1 1

LOGIC STATE
Storage Flip Flop (Reset Dominant) E1 E2 A
E1 S
Output remains in the state of last activation of I/Ps. 0 0 Unchanged
7 A
Refer Table for Details. 0 1 0
E2 R
1 0 1
1 1 0

Generates a short positive pulse of time period T whenever


input E changes from low to high. INPUT E
E A
8
Time “T” to be indicated in the qualifying symbol. OUTPUT A
T secs T

E1
&

E1 E2
Logic output A exists if and only if any two of
9 E2 2oo3 A three logic inputs (E1, E2, E3) exists. & >1
= A

E3
E3
&

This Document is the property of INDIAN OIL CORPORATION LTD and is lent without PARADIP REFINERY PROJECT
consideration other than the Borrower’s agreement that it shall not be reproduced, copied, Paradip, Orissa State, India
lent or disposed of directly or indirectly, nor used for any purpose other than that for which it
is specifically furnished. The apparatus shown in the document is covered by patents.
Information contained in this document may be proprietary to Indian Oil Corporation Ltd
and/or licensors, and is subject to obligations of confidentiality.
INDIAN OIL
CORPORATION LIMITED
F2 12/06/12 ISSUED FINAL VIAR CHIPA OPT

F1 14/02/12 ISSUED FINAL VIAR CHIPA OPT


FUNCTIONAL ESD LOGIC DIAGRAM
CLAUS REACTION FURNACE 086-F-001
A1 24/08/11 ISSUED FOR DESIGN VIAR CHIPA
OPT OPT
UNIT - 086
Rev Date Description By Chkd Appd
Class DSN Contract No. Scale Document No. Sheet Rev
xx xxxxxxx xxxxxxxxxxx NTS PDRP271-8550-64-086-0004 4 of 31 F2
A B C D E F G H I J K L M

INPUT LOGIC OUTPUT


TAG NO. EQPT. NO.
LOCATION INTERNAL TAG INTERLOCK - 086-IZ-0900 TAG NO. LOCATION
SERVICE SERVICE

0 – CLOSE
086-XZV-0201
086-HZS-0201 ESD HMI 086-HZS-0201 086-XZY-0201 FIELD 086-F-001 NITROGEN PURGE
1
VALVE SHUTDOWN 1 SH25 1 0 & ON/OFF VALVE
SWITCH 0 0 &
0 0 0
2 SH24 1
0
2
2 SH25 1

086-HZS-0200 0 – CLOSE
VALVE SHUTDOWN 086-XZY-0200 FIELD 086-XZV-0200
ESD HMI 086-HZS-0200 086-F-001 NITROGEN PURGE
3 SWITCH 0 &
ON/OFF VALVE
0 0

4
2 SH25 2

086-HZS-0170 0 – CLOSE
5
ESD HMI 086-HZS-0170 086-XZV-0170
VALVE ESD SHUTDOWN 0 &
086-XZY-0170 FIELD REACTION FURNACE
0 ISOLATION VALVE
0

086-HZS-0228 0 – CLOSE
ESD HMI 086-HZS-0228
7 VALVE ESD SHUTDOWN 0 &
0
086-XZV-0228
086-XZY-0228 FIELD 086-F-002 NITROGEN PURGE
0
ON/OFF CONTROL
8

086-HZS-0229 0 – CLOSE
ESD HMI 086-HZS-0229
9 VALVE ESD SHUTDOWN
0 &
0
086-XZV-0229
10
0 086-XZY-0229 FIELD 086-F-002 NITROGEN PURGE
ON/OFF CONTROL

11

12

13

14

15

16

This Document is the property of INDIAN OIL CORPORATION LTD and is lent without PARADIP REFINERY PROJECT
NOTES: DESCRIPTION : (NITROGEN VALVES) consideration other than the Borrower’s agreement that it shall not be reproduced, copied,
lent or disposed of directly or indirectly, nor used for any purpose other than that for which it
Paradip, Orissa State, India
is specifically furnished. The apparatus shown in the document is covered by patents.
Information contained in this document may be proprietary to Indian Oil Corporation Ltd
and/or licensors, and is subject to obligations of confidentiality.
INDIAN OIL
REFERENCE DOCUMENTS : CORPORATION LIMITED
1. P&IDS : PDRP4220-271-8110-25-086 F2 12/06/12 ISSUED FINAL VIAR CHIPA OPT
2. SIS LOGIC NARRATIVE : PDRP4200-271-8110-RP-085-0002 F1 14/02/12 ISSUED FINAL VIAR CHIPA OPT
FUNCTIONAL ESD LOGIC DIAGRAM
3. CAUSE & EFFECT SUMMARY : PDRP4220-271-8110-24-085-0001 CLAUS REACTION FURNACE 086-F-001
A1 24/08/11 ISSUED FOR DESIGN VIAR CHIPA OPT
UNIT - 086
Rev Date Description By Chkd Appd
Class DSN Contract No. Scale Document No. Sheet Rev
xx xxxxxxx xxxxxxxxxxx NTS PDRP271-8550-64-086-0004 5 of 31 F2
A B C D E F G H I J K L M

INPUT LOGIC OUTPUT


TAG NO. EQPT. NO.
LOCATION INTERNAL TAG INTERLOCK - 086-IZ-0900 TAG NO. LOCATION
SERVICE SERVICE

0 – CLOSE 086-XZV-0191
1
086-HZS-0191B ESD HMI 086-HZS-0191B 0 & 2 SH27 1
086-XZY-0191 FIELD 086-F-001 PILOT FUEL GAS
VALVE SHUTDOWN S 0 – CLOSE
0 INLET ON/OFF VALVE
SWITCH 1 – OPEN

& 0 R
1 SH24 1 0

2 3 SH27 1 0

086-HZS-0193B 0 – OPEN 086-XZV-0193


VALVE SHUTDOWN 0 & 1 SH27 1 086-XZY-0193 FIELD 086-F-001 PILOT FUEL GAS
3
ESD HMI 086-HZS-0193B S 0 – OPEN
SWITCH 0 INLET VENT
1 – CLOSE
0 R

086-HZS-0192B 0 – CLOSE
&
ESD HMI 086-HZS-0192B 0 2 SH27 2 S
5
VALVE ESD SHUTDOWN 086-XZV-0192
0
086-XZY-0192 FIELD 086-F-001 PILOT FUEL GAS
0 R 0 – CLOSE INLET ON/OFF VALVE
1 – OPEN

086-HZS-0185B 0 – CLOSE
ESD HMI 086-HZS-0185B
7 VALVE ESD SHUTDOWN 0 & 1 SH27 2 S 086-XZV-0185
0
086-XZY-0185 FIELD 086-F-001 PILOT AIR INLET
0 R 0 – CLOSE
ON/OFF VALVE
8 1 – OPEN

086-HZS-0186B 0 – CLOSE
ESD HMI 086-HZS-0186B
9 VALVE ESD SHUTDOWN
0 & 1 SH27 3 S
0 086-XZV-0186
086-XZY-0186 FIELD 086-F-001 PILOT AIR INLET
10
0 R 0 – CLOSE ON/OFF VALVE
1 – OPEN

11

12

13

14

15

16

This Document is the property of INDIAN OIL CORPORATION LTD and is lent without PARADIP REFINERY PROJECT
NOTES: DESCRIPTION (PILOT VALVES) consideration other than the Borrower’s agreement that it shall not be reproduced, copied,
lent or disposed of directly or indirectly, nor used for any purpose other than that for which it
Paradip, Orissa State, India
is specifically furnished. The apparatus shown in the document is covered by patents.
Information contained in this document may be proprietary to Indian Oil Corporation Ltd
and/or licensors, and is subject to obligations of confidentiality. INDIAN OIL
REFERENCE DOCUMENTS : CORPORATION LIMITED
1. P&IDS : PDRP4220-271-8110-25-086 F2 12/06/12 ISSUED FINAL VIAR CHIPA OPT
2. SIS LOGIC NARRATIVE : PDRP4200-271-8110-RP-085-0002 F1 14/02/12 ISSUED FINAL VIAR CHIPA OPT
FUNCTIONAL ESD LOGIC DIAGRAM
3. CAUSE & EFFECT SUMMARY : PDRP4220-271-8110-24-085-0001 CLAUS REACTION FURNACE 086-F-001
A1 24/08/11 ISSUED FOR DESIGN VIAR CHIPA OPT
UNIT - 086
Rev Date Description By Chkd Appd
Class DSN Contract No. Scale Document No. Sheet Rev
xx xxxxxxx xxxxxxxxxxx NTS PDRP271-8550-64-086-0004 6 of 31 F2
A B C D E F G H I J K L M

INPUT LOGIC OUTPUT


TAG NO. EQPT. NO.
LOCATION INTERNAL TAG INTERLOCK - 086-IZ-0900 TAG NO. LOCATION
SERVICE SERVICE

0 – CLOSE
086-XZV-0188
1
086-HZS-0188 ESD HMI 086-HZS-0188 0 & 2 SH29 1
086-XZY-0188 FIELD 086-F-001 MAIN FUEL GAS
VALVE SHUTDOWN S 0 – CLOSE INLET ON/OFF VALVE
0 1 – OPEN
SWITCH
1 SH24 2 0 & 0 R
0

2 3 SH29 1 0

086-HZS-0190 0 – OPEN 086-XZV-0190


VALVE SHUTDOWN 0 & 1 SH29 1 086-XZY-0190 FIELD 086-F-001 MAIN FUEL GAS
ESD HMI 086-HZS-0190 S 0 – OPEN
3 SWITCH 0 VENT ON/OFF VALVE
1 – CLOSE
0 R

086-HZS-0189 0 – CLOSE
&
ESD HMI 086-HZS-0189 0 2 SH29 2 S 086-XZV-0189
5
VALVE ESD SHUTDOWN 0
086-XZY-0189 FIELD 086-F-001 MAIN FUEL GAS
INLET ON/OFF VALVE
0 R 0 – CLOSE
1 – OPEN

7 0 – MANUAL WITH 0% OP
1 – CONTROL RELEASE
086-FZF-0171 DCS 086-FIC-0171
086-FIC-0171 MODE CONTROL
8 FLAG

10

11

12

13

14

15

16

This Document is the property of INDIAN OIL CORPORATION LTD and is lent without PARADIP REFINERY PROJECT
NOTES: DESCRIPTION : (MAIN FUEL GAS VALVES) consideration other than the Borrower’s agreement that it shall not be reproduced, copied,
lent or disposed of directly or indirectly, nor used for any purpose other than that for which it
Paradip, Orissa State, India
is specifically furnished. The apparatus shown in the document is covered by patents.
Information contained in this document may be proprietary to Indian Oil Corporation Ltd
and/or licensors, and is subject to obligations of confidentiality. INDIAN OIL
REFERENCE DOCUMENTS : CORPORATION LIMITED
1. P&IDS : PDRP4220-271-8110-25-086 F2 12/06/12 ISSUED FINAL VIAR CHIPA OPT
2. SIS LOGIC NARRATIVE : PDRP4200-271-8110-RP-085-0002 F1 14/02/12 ISSUED FINAL VIAR CHIPA OPT
FUNCTIONAL ESD LOGIC DIAGRAM
3. CAUSE & EFFECT SUMMARY : PDRP4220-271-8110-24-085-0001 CLAUS REACTION FURNACE 086-F-001
A1 24/08/11 ISSUED FOR DESIGN VIAR CHIPA OPT
UNIT - 086
Rev Date Description By Chkd Appd
Class DSN Contract No. Scale Document No. Sheet Rev
xx xxxxxxx xxxxxxxxxxx NTS PDRP271-8550-64-086-0004 7 of 31 F2
A B C D E F G H I J K L M

INPUT LOGIC OUTPUT


TAG NO. EQPT. NO.
LOCATION INTERNAL TAG INTERLOCK - 086-IZ-0900 TAG NO. LOCATION
SERVICE SERVICE
0 – CLOSE 086-XZV-0202
086-HZS-0202B S 1 – OPEN
1 LOCAL MANUAL TRIP FIELD 086-HZS-0202B
0 – CLOSE 0 & 086-XZY-0202 FIELD 086-F-001 COMBUSTION
OUTLET
SWITCH 0 – CLOSE 0 0
R
0 0 – MANUAL WITH 0% OP
4 SH29 1 086-FIC-0175
1 – CONTROL RELEASE
086-HZS-0202C ESD HMI 086-HZS-0202C 0 & 086-FZF-0175 DCS 086-FIC-0175 MODE CONTROL
2 ESD TRIP 1 SH24 3 0 0 FLAG
0
0 – MANUAL WITH 0% OP
1 SH29 2 1 – CONTROL RELEASE 086-FIC-0176
086-HZS-0202A 086-FZF-0176 DCS 086-FIC-0176 MODE CONTROL
3 LOCAL MANUAL RESET FIELD 086-HZS-0202A FLAG
RESET
SWITCH

10

11

12

13

14

15

16

This Document is the property of INDIAN OIL CORPORATION LTD and is lent without PARADIP REFINERY PROJECT
NOTES: DESCRIPTION : COMBUSTION AIR consideration other than the Borrower’s agreement that it shall not be reproduced, copied,
lent or disposed of directly or indirectly, nor used for any purpose other than that for which it
Paradip, Orissa State, India
is specifically furnished. The apparatus shown in the document is covered by patents.
Information contained in this document may be proprietary to Indian Oil Corporation Ltd
and/or licensors, and is subject to obligations of confidentiality.
INDIAN OIL
REFERENCE DOCUMENTS : CORPORATION LIMITED
1. P&IDS : PDRP4220-271-8110-25-086 F2 12/06/12 ISSUED FINAL VIAR CHIPA OPT
2. SIS LOGIC NARRATIVE : PDRP4200-271-8110-RP-085-0002 F1 14/02/12 ISSUED FINAL VIAR CHIPA OPT
FUNCTIONAL ESD LOGIC DIAGRAM
3. CAUSE & EFFECT SUMMARY : PDRP4220-271-8110-24-085-0001 CLAUS REACTION FURNACE 086-F-001
A1 24/08/11 ISSUED FOR DESIGN VIAR CHIPA OPT
UNIT - 086
Rev Date Description By Chkd Appd
Class DSN Contract No. Scale Document No. Sheet Rev
xx xxxxxxx xxxxxxxxxxx NTS PDRP271-8550-64-086-0004 8 of 31 F2
A B C D E F G H I J K L M

INPUT LOGIC OUTPUT


TAG NO. EQPT. NO.
LOCATION INTERNAL TAG INTERLOCK - 086-IZ-0900 TAG NO. LOCATION
SERVICE SERVICE
0 – CLOSE
086-HZS-0181B S 1 – OPEN 086-XZV-0181
1 FIELD 0 – CLOSE 0 & 086-XZY-0181 FIELD 086-F-001 AMINE ACID GAS
LOCAL MANUAL TRIP 086-HZS-0181B 0 – CLOSE 0
0 INLET ON-OFF VALVE
SWITCH 0
R
0 0 – MANUAL WITH 0% OP
& 1 – CONTROL RELEASE 086-FIC-0146
086-HZS-0181C 1 SH24 4 0
086-FZF-0146 DCS
ESD HMI 086-HZS-0181C 0
086-FIC-0146 MODE CONTROL
2 ESD TRIP FLAG
1 SH31 1 0

0 – MANUAL WITH 0% OP
1 – CONTROL RELEASE 086-FIC-0147
086-HZS-0181A RESET 086-FZF-0147 DCS
FIELD 086-FIC-0147 MODE CONTROL
LOCAL MANUAL RESET 086-HZS-0181A FLAG
3
SWITCH

086-HZS-0126A
LCP 086-HZS-0126A 0 – CLOSE
5 STOP AMINE ACID GAS 1 SH30 3
1 SH10 1
1 SH11 2
6

10

11

12

13

14

15

16

This Document is the property of INDIAN OIL CORPORATION LTD and is lent without PARADIP REFINERY PROJECT
NOTES: DESCRIPTION : AMINE ACID GAS consideration other than the Borrower’s agreement that it shall not be reproduced, copied,
lent or disposed of directly or indirectly, nor used for any purpose other than that for which it
Paradip, Orissa State, India
is specifically furnished. The apparatus shown in the document is covered by patents.
Information contained in this document may be proprietary to Indian Oil Corporation Ltd
and/or licensors, and is subject to obligations of confidentiality. INDIAN OIL
REFERENCE DOCUMENTS : CORPORATION LIMITED
1. P&IDS : PDRP4220-271-8110-25-086 F2 12/06/12 ISSUED FINAL VIAR CHIPA OPT
2. SIS LOGIC NARRATIVE : PDRP4200-271-8110-RP-085-0002 F1 14/02/12 ISSUED FINAL VIAR CHIPA OPT
FUNCTIONAL ESD LOGIC DIAGRAM
3. CAUSE & EFFECT SUMMARY : PDRP4220-271-8110-24-085-0001 CLAUS REACTION FURNACE 086-F-001
A1 24/08/11 ISSUED FOR DESIGN VIAR CHIPA OPT
UNIT - 086
Rev Date Description By Chkd Appd
Class DSN Contract No. Scale Document No. Sheet Rev
xx xxxxxxx xxxxxxxxxxx NTS PDRP271-8550-64-086-0004 9 of 31 F2
A B C D E F G H I J K L M

INPUT LOGIC OUTPUT


TAG NO. EQPT. NO.
LOCATION INTERNAL TAG INTERLOCK - 086-IZ-0900 TAG NO. LOCATION
SERVICE SERVICE

0 – CLOSE 086-XZV-0183
086-HZS-0183 S
1 VALVE SHUTDOWN ESD HMI 086-HZS-0183
0 – CLOSE
0 & 1 – OPEN 086-XZY-0183 FIELD 086-F-001 SWS ACID GAS
0 INLET ON-OFF VALVE
SWITCH 0 0
0
R
1 SH31 3 0 0 – MANUAL WITH 0% OP
0 –STOP 1 – CONTROL RELEASE 086-FIC-0148
086-HZS-0127A LCP 086-HZS-0127A 1 SH09 1 086-FZF-0148 DCS
086-FIC-0148 MODE CONTROL
2
STOP SWS GAS SWITCH FLAG
1 SH24 5

086-HZS-0127B RESET
3 LCP 086-HZS-0127B
SWS GAS SOLENOIDS RESET

4 S
0 &
0
R
0
5

10

11

12

13

14

15

16

This Document is the property of INDIAN OIL CORPORATION LTD and is lent without PARADIP REFINERY PROJECT
NOTES: DESCRIPTION : SWS ACID GAS consideration other than the Borrower’s agreement that it shall not be reproduced, copied,
lent or disposed of directly or indirectly, nor used for any purpose other than that for which it
Paradip, Orissa State, India
is specifically furnished. The apparatus shown in the document is covered by patents.
Information contained in this document may be proprietary to Indian Oil Corporation Ltd
and/or licensors, and is subject to obligations of confidentiality. INDIAN OIL
REFERENCE DOCUMENTS : CORPORATION LIMITED
1. P&IDS : PDRP4220-271-8110-25-086 F2 12/06/12 ISSUED FINAL VIAR CHIPA OPT
2. SIS LOGIC NARRATIVE : PDRP4200-271-8110-RP-085-0002 F1 14/02/12 ISSUED FINAL VIAR CHIPA OPT
FUNCTIONAL ESD LOGIC DIAGRAM
3. CAUSE & EFFECT SUMMARY : PDRP4220-271-8110-24-085-0001 CLAUS REACTION FURNACE 086-F-001
A1 24/08/11 ISSUED FOR DESIGN VIAR CHIPA OPT
UNIT - 086
Rev Date Description By Chkd Appd
Class DSN Contract No. Scale Document No. Sheet Rev
xx xxxxxxx xxxxxxxxxxx NTS PDRP271-8550-64-086-0004 10 of 31 F2
A B C D E F G H I J K L M

INPUT LOGIC OUTPUT


TAG NO. EQPT. NO.
LOCATION INTERNAL TAG INTERLOCK - 086-IZ-0900 TAG NO. LOCATION
SERVICE SERVICE

0 – CLOSE 086-XZV-0180
086-HZS-0180B S 086-XZY-0180 FIELD
1
ESD HMI 086-HZS-0180B
0 –CLOSE 0 & 1 – OPEN FGD OUTLET SO2 GAS
VALVE SHUTDOWN SWITCH 0 FLOW CONTROL
0 0
0
R
1 SH11 4 0 0 – MANUAL WITH 0% OP
0 –STOP 1 – CONTROL RELEASE 086-FIC-0145
086-HZS-0128A 086-FZF-0145 DCS 086-FIC-0145 MODE CONTROL
2
LCP 086-HZS-0128A
STOP SO2 GAS SWITCH 1 SH09 2 FLAG

1 SH24 6
086-HZS-0128B RESET
3 SO2 GAS SOLENOIDS RESET
LCP 086-HZS-0128B

4 S
0 &
0
R
0
5

10

11

12

13

14

15

16

This Document is the property of INDIAN OIL CORPORATION LTD and is lent without PARADIP REFINERY PROJECT
NOTES: DESCRIPTION : SO2 GAS consideration other than the Borrower’s agreement that it shall not be reproduced, copied,
lent or disposed of directly or indirectly, nor used for any purpose other than that for which it
Paradip, Orissa State, India
is specifically furnished. The apparatus shown in the document is covered by patents.
Information contained in this document may be proprietary to Indian Oil Corporation Ltd
and/or licensors, and is subject to obligations of confidentiality. INDIAN OIL
REFERENCE DOCUMENTS : CORPORATION LIMITED
1. P&IDS : PDRP4220-271-8110-25-086 F2 12/06/12 ISSUED FINAL VIAR CHIPA OPT
2. SIS LOGIC NARRATIVE : PDRP4200-271-8110-RP-085-0002 F1 14/02/12 ISSUED FINAL VIAR CHIPA OPT
FUNCTIONAL ESD LOGIC DIAGRAM
3. CAUSE & EFFECT SUMMARY : PDRP4220-271-8110-24-085-0001 CLAUS REACTION FURNACE 086-F-001
A1 24/08/11 ISSUED FOR DESIGN VIAR CHIPA OPT
UNIT - 086
Rev Date Description By Chkd Appd
Class DSN Contract No. Scale Document No. Sheet Rev
xx xxxxxxx xxxxxxxxxxx NTS PDRP271-8550-64-086-0004 11 of 31 F2
A B C D E F G H I J K L M

INPUT LOGIC OUTPUT


TAG NO. EQPT. NO.
LOCATION INTERNAL TAG INTERLOCK - 086-IZ-0900 TAG NO. LOCATION
SERVICE SERVICE

086-HZS-0187B 086-XZV-0187
1 0 –CLOSE & 0 – CLOSE 086-XZY-0187 FIELD 086-F-001 TEMPERING
VALVE SHUTDOWN SWITCH
ESD HMI 086-HZS-0187B 0
0 – OPEN STEAM ON/OFF VALVE
0

0
1 SH24 7 086-FIC-0170
086-FZF-0170 DCS 086-FIC-0170 MODE CONTROL
2 0 – MANUAL WITH 0% OP
1 – CONTROL RELEASE
FLAG

086-FV-0170 0 – <5%
5 TEMPERING STEAM INLET DCS 086-FZIC-0170
FLOW CONTROL
1 – >5%

0 >=1
6
0
1 SH25 1
0
086-XZV-0187 0 –CLOSE
086-F-001 TEMPERING STEAM FIELD 086-XZSL-0187
7 ON/OFF VALVE

10

11

12

13

14

15

16

This Document is the property of INDIAN OIL CORPORATION LTD and is lent without PARADIP REFINERY PROJECT
NOTES: DESCRIPTION : STEAM consideration other than the Borrower’s agreement that it shall not be reproduced, copied,
lent or disposed of directly or indirectly, nor used for any purpose other than that for which it
Paradip, Orissa State, India
is specifically furnished. The apparatus shown in the document is covered by patents.
Information contained in this document may be proprietary to Indian Oil Corporation Ltd
and/or licensors, and is subject to obligations of confidentiality. INDIAN OIL
REFERENCE DOCUMENTS : CORPORATION LIMITED
1. P&IDS : PDRP4220-271-8110-25-086 F2 12/06/12 ISSUED FINAL VIAR CHIPA OPT
2. SIS LOGIC NARRATIVE : PDRP4200-271-8110-RP-085-0002 F1 14/02/12 ISSUED FINAL VIAR CHIPA OPT
FUNCTIONAL ESD LOGIC DIAGRAM
3. CAUSE & EFFECT SUMMARY : PDRP4220-271-8110-24-085-0001 CLAUS REACTION FURNACE 086-F-001
A1 24/08/11 ISSUED FOR DESIGN VIAR CHIPA OPT
UNIT - 086
Rev Date Description By Chkd Appd
Class DSN Contract No. Scale Document No. Sheet Rev
xx xxxxxxx xxxxxxxxxxx NTS PDRP271-8550-64-086-0004 12 of 31 F2
A B C D E F G H I J K L M

INPUT LOGIC OUTPUT


TAG NO. EQPT. NO.
LOCATION INTERNAL TAG INTERLOCK - 086-IZ-0900 TAG NO. LOCATION
SERVICE

4
0 >=1
0
0 0
0 –CLOSE
1 SH25 1
086-XZV-0193 0 –CLOSE 0
0
086-F-001 PILOT FUEL GAS FIELD 086-XZSL-0193 2 SH27 1 1 SH26 2
5
INLET VENT
1 SH26 3

086-XZV-0191 0 –CLOSE
086-F-001 PILOT FUEL GAS FIELD 086-XZSL-0191
6
INLET ON/OFF VALVE

086-XZV-0192 0 –CLOSE
086-F-001 PILOT FUEL GAS FIELD 086-XZSL-0192
7
INLET ON/OFF VALVE

086-XZV-0193 0 –OPEN
8 086-F-001 PILOT FUEL GAS FIELD 086-XZSH-0193
INLET VENT

086-XZV-0185 0 –CLOSE
086-F-001 PILOT AIR INLET FIELD 086-XZSL-0185
9
ON/OFF VALVE

086-XZV-0186 0 –CLOSE
10
086-F-001 PILOT AIR INLET FIELD 086-XZSL-0186
ON/OFF VALVE

11

12

13

14

15

16

This Document is the property of INDIAN OIL CORPORATION LTD and is lent without PARADIP REFINERY PROJECT
NOTES: DESCRIPTION : PILOT FEEDBACK consideration other than the Borrower’s agreement that it shall not be reproduced, copied,
lent or disposed of directly or indirectly, nor used for any purpose other than that for which it
Paradip, Orissa State, India
is specifically furnished. The apparatus shown in the document is covered by patents.
Information contained in this document may be proprietary to Indian Oil Corporation Ltd
and/or licensors, and is subject to obligations of confidentiality. INDIAN OIL
REFERENCE DOCUMENTS : CORPORATION LIMITED
1. P&IDS : PDRP4220-271-8110-25-086 F2 12/06/12 ISSUED FINAL VIAR CHIPA OPT
2. SIS LOGIC NARRATIVE : PDRP4200-271-8110-RP-085-0002 F1 14/02/12 ISSUED FINAL VIAR CHIPA OPT
FUNCTIONAL ESD LOGIC DIAGRAM
3. CAUSE & EFFECT SUMMARY : PDRP4220-271-8110-24-085-0001 CLAUS REACTION FURNACE 086-F-001
A1 24/08/11 ISSUED FOR DESIGN VIAR CHIPA OPT
UNIT - 086
Rev Date Description By Chkd Appd
Class DSN Contract No. Scale Document No. Sheet Rev
xx xxxxxxx xxxxxxxxxxx NTS PDRP271-8550-64-086-0004 13 of 31 F2
A B C D E F G H I J K L M

INPUT LOGIC OUTPUT


TAG NO. EQPT. NO.
LOCATION INTERNAL TAG INTERLOCK - 086-IZ-0900 TAG NO. LOCATION
SERVICE SERVICE

086-XZV-0201
1 086-F-001 NITROGEN PURGE FIELD 086-XZSH-0201 0 –OPEN 0 >=1
ON/OFF VALVE 0 0 >=1
0 0
2 SH25 1
086-XZV-0200 0 –OPEN 0
2 086-F-001 NITROGEN PURGE FIELD 086-XZSH-0200
ON/OFF VALVE

086-XZV-0170
SRU NITROGEN HEADER FIELD 086-XZSH-0170 0 –OPEN 0 >=1
3
LINE ON/OFF VALVE 0 –OPEN 0 0
4 SH26 1
0
086-XZV-0228
4 N2 TO SO2 GAS NOZZLE
FIELD 086-XZSH-0228

3 SH26 1
086-XZV-0229 0 –OPEN
5
FIELD 086-XZSH-0229 3 SH30 3
N2 TO AMINE ACID GAS
3 SH28 2
086-XZV-0201 0 –CLOSE 0 >=1
086-F-001 NITROGEN PURGE FIELD 086-XZSL-0201
6
ON/OFF VALVE 0 0 >=1
0 0
1 SH25 1
086-XZV-0200 0 –CLOSE 0
086-F-001 NITROGEN PURGE FIELD 086-XZSL-0200
7
ON/OFF VALVE

086-XZV-0170 0 –OPEN 0 >=1


8 SRU NITROGEN HEADER FIELD 086-XZSH-0170
0 0
LINE ON/OFF VALVE
0

086-XZV-0228 0 –CLOSE
FIELD 086-XZSL-0228
9 N2 TO SO2 GAS NOZZLE

086-XZV-0229 0 –OPEN
10 FIELD 086-XZSH-0229
N2 TO AMINE ACID GAS

11

12

13

14

15

16

This Document is the property of INDIAN OIL CORPORATION LTD and is lent without PARADIP REFINERY PROJECT
NOTES: DESCRIPTION : NITROGEN FEEDBACK consideration other than the Borrower’s agreement that it shall not be reproduced, copied,
lent or disposed of directly or indirectly, nor used for any purpose other than that for which it
Paradip, Orissa State, India
is specifically furnished. The apparatus shown in the document is covered by patents.
Information contained in this document may be proprietary to Indian Oil Corporation Ltd
and/or licensors, and is subject to obligations of confidentiality. INDIAN OIL
REFERENCE DOCUMENTS : CORPORATION LIMITED
1. P&IDS : PDRP4220-271-8110-25-086 F2 12/06/12 ISSUED FINAL VIAR CHIPA OPT
2. SIS LOGIC NARRATIVE : PDRP4200-271-8110-RP-085-0002 F1 14/02/12 ISSUED FINAL VIAR CHIPA OPT
FUNCTIONAL ESD LOGIC DIAGRAM
3. CAUSE & EFFECT SUMMARY : PDRP4220-271-8110-24-085-0001 CLAUS REACTION FURNACE 086-F-001
A1 24/08/11 ISSUED FOR DESIGN VIAR CHIPA OPT
UNIT - 086
Rev Date Description By Chkd Appd
Class DSN Contract No. Scale Document No. Sheet Rev
xx xxxxxxx xxxxxxxxxxx NTS PDRP271-8550-64-086-0004 14 of 31 F2
A B C D E F G H I J K L M

INPUT LOGIC OUTPUT


TAG NO. EQPT. NO.
LOCATION INTERNAL TAG INTERLOCK - 086-IZ-0900 TAG NO. LOCATION
SERVICE SERVICE

086-XZV-0188
1 086-F-001 MAIN FUEL GAS FIELD 086-XZSH-0188 0 –OPEN 0 &
0
INLET ON/OFF VALVE 0
0
1 SH22 1
0
086-XZV-0189 0 –OPEN
1 SH30 2
2 086-F-001 MAIN FUEL GAS FIELD 086-XZSH-0189
INLET ON/OFF VALVE

086-XZV-0190
0 –CLOSE
3
086-F-001 MAIN FUEL GAS FIELD 086-XZSL-0190
VENT ON/OFF VALVE
5 SH29 1

086-FV-0171 0 – <5%
4 TEMPERING STEAM INLET DCS 086-FZIC-0171
FLOW CONTROL 0 >=1
0
0
2 SH25 1
086-XZV-0188 0 –CLOSE 0
0
5 086-F-001 MAIN FUEL GAS FIELD 086-XZSL-0188 2 SH26 2
INLET ON/OFF VALVE
2 SH28 3
086-XZV-0190 0 –OPEN
086-F-001 MAIN FUEL GAS FIELD 086-XZSH-0190
6
VENT ON/OFF VALVE

086-XZV-0189 0 –CLOSE
086-F-001 MAIN FUEL GAS FIELD 086-XZSL-0189
7
INLET ON/OFF VALVE

086-PZT-0211 0 –LOW LOW


MAIN FUEL GAS TO REACTION FIELD 086-PZSLL-0211 3 SH26 1
8
FURNACE BURNER PRESSURE 3 SH29 2

086-PZT-0211 0 –HIGH HIGH


9 MAIN FUEL GAS TO REACTION FIELD 086-PZSHH-0211 4 SH26 1
FURNACE BURNER PRESSURE
4 SH29 2

10

11

12

13

14

15

16

This Document is the property of INDIAN OIL CORPORATION LTD and is lent without PARADIP REFINERY PROJECT
NOTES: DESCRIPTION : MAIN FUEL FEEDBACK consideration other than the Borrower’s agreement that it shall not be reproduced, copied,
lent or disposed of directly or indirectly, nor used for any purpose other than that for which it
Paradip, Orissa State, India
is specifically furnished. The apparatus shown in the document is covered by patents.
Information contained in this document may be proprietary to Indian Oil Corporation Ltd
and/or licensors, and is subject to obligations of confidentiality. INDIAN OIL
REFERENCE DOCUMENTS : CORPORATION LIMITED
1. P&IDS : PDRP4220-271-8110-25-086 F2 12/06/12 ISSUED FINAL VIAR CHIPA OPT
2. SIS LOGIC NARRATIVE : PDRP4200-271-8110-RP-085-0002 F1 14/02/12 ISSUED FINAL VIAR CHIPA OPT
FUNCTIONAL ESD LOGIC DIAGRAM
3. CAUSE & EFFECT SUMMARY : PDRP4220-271-8110-24-085-0001 CLAUS REACTION FURNACE 086-F-001
A1 24/08/11 ISSUED FOR DESIGN VIAR CHIPA OPT
UNIT - 086
Rev Date Description By Chkd Appd
Class DSN Contract No. Scale Document No. Sheet Rev
xx xxxxxxx xxxxxxxxxxx NTS PDRP271-8550-64-086-0004 15 of 31 F2
A B C D E F G H I J K L M

INPUT LOGIC OUTPUT


TAG NO. EQPT. NO.
LOCATION INTERNAL TAG INTERLOCK - 086-IZ-0900 TAG NO. LOCATION
SERVICE SERVICE

086-XZV-0202
1 086-F-001 COMBUSTION FIELD 086-XZSL-0202 0 –CLOSE 0 >=1
OUTLET 0 0 0 –CLOSE
1 SH25 1
0
086-FV-0175 0 – <5% 1 SH26 2
2 086-F-001 COMBUSTION AIR INLET DCS 086-FZIC-0175
1 – >5% 1 SH28 3
FLOW CONTROL VALVE

086-FV-0176 0 – <5%
3
086-F-001 COMBUSTION AIR INLET DCS 086-FZIC-0176
FLOW CONTROL VALVE 1 – >5%

086-XZV-0202 0 –OPEN
4 086-F-001 COMBUSTION FIELD 086-XZSH-0202
OUTLET
0 >=1
1 –OPEN
0 0
2 SH28 1
0
5

10

11

12

13

14

15

16

This Document is the property of INDIAN OIL CORPORATION LTD and is lent without PARADIP REFINERY PROJECT
NOTES: DESCRIPTION : COMBUSTION AIR FEEDBACK consideration other than the Borrower’s agreement that it shall not be reproduced, copied,
lent or disposed of directly or indirectly, nor used for any purpose other than that for which it
Paradip, Orissa State, India
is specifically furnished. The apparatus shown in the document is covered by patents.
Information contained in this document may be proprietary to Indian Oil Corporation Ltd
and/or licensors, and is subject to obligations of confidentiality. INDIAN OIL
REFERENCE DOCUMENTS : CORPORATION LIMITED
1. P&IDS : PDRP4220-271-8110-25-086 F2 12/06/12 ISSUED FINAL VIAR CHIPA OPT
2. SIS LOGIC NARRATIVE : PDRP4200-271-8110-RP-085-0002 F1 14/02/12 ISSUED FINAL VIAR CHIPA OPT
FUNCTIONAL ESD LOGIC DIAGRAM
3. CAUSE & EFFECT SUMMARY : PDRP4220-271-8110-24-085-0001 CLAUS REACTION FURNACE 086-F-001
A1 24/08/11 ISSUED FOR DESIGN VIAR CHIPA OPT
UNIT - 086
Rev Date Description By Chkd Appd
Class DSN Contract No. Scale Document No. Sheet Rev
xx xxxxxxx xxxxxxxxxxx NTS PDRP271-8550-64-086-0004 16 of 31 F2
A B C D E F G H I J K L M

INPUT LOGIC OUTPUT


TAG NO. EQPT. NO.
LOCATION INTERNAL TAG INTERLOCK - 086-IZ-0900 TAG NO. LOCATION
SERVICE SERVICE

086-XZV-0181
1 086-F-001 COMBUSTION FIELD 086-XZSL-0181 0 –CLOSE
0 >=1
OUTLET 0 0 1 SH25 1
0
086-FV-0146 0 – <5% 1 SH26 2
086-F-001 COMBUSTION AIR INLET DCS 086-FZIC-0146
2 1 – >5% 1 SH28 3
FLOW CONTROL VALVE
1 SH30 4
086-FV-0147 0 – <5%

3
086-F-001 COMBUSTION AIR INLET DCS 086-FZIC-0147
FLOW CONTROL VALVE 1 – >5%

086-XZV-0181 0 –OPEN
4 086-F-001 COMBUSTION FIELD 086-XZSH-0181
OUTLET
0 >=1
0 0
3 SH28 1
0
5

086-FZT-0146A 0 –LOW LOW


086-F-001 AMINE ACID GAS INLET FIELD 086-FZSLL-0146A 2 SH26 1
6
FLOW CONTROL

10

11

12

13

14

15

16

This Document is the property of INDIAN OIL CORPORATION LTD and is lent without PARADIP REFINERY PROJECT
NOTES: DESCRIPTION : AMINE ACID GAS FEEDBACK consideration other than the Borrower’s agreement that it shall not be reproduced, copied,
lent or disposed of directly or indirectly, nor used for any purpose other than that for which it
Paradip, Orissa State, India
is specifically furnished. The apparatus shown in the document is covered by patents.
Information contained in this document may be proprietary to Indian Oil Corporation Ltd
and/or licensors, and is subject to obligations of confidentiality. INDIAN OIL
REFERENCE DOCUMENTS : CORPORATION LIMITED
1. P&IDS : PDRP4220-271-8110-25-086 F2 12/06/12 ISSUED FINAL VIAR CHIPA OPT
2. SIS LOGIC NARRATIVE : PDRP4200-271-8110-RP-085-0002 F1 14/02/12 ISSUED FINAL VIAR CHIPA OPT
FUNCTIONAL ESD LOGIC DIAGRAM
3. CAUSE & EFFECT SUMMARY : PDRP4220-271-8110-24-085-0001 CLAUS REACTION FURNACE 086-F-001
A1 24/08/11 ISSUED FOR DESIGN VIAR CHIPA OPT
UNIT - 086
Rev Date Description By Chkd Appd
Class DSN Contract No. Scale Document No. Sheet Rev
xx xxxxxxx xxxxxxxxxxx NTS PDRP271-8550-64-086-0004 17 of 31 F2
A B C D E F G H I J K L M

INPUT LOGIC OUTPUT


TAG NO. EQPT. NO.
LOCATION INTERNAL TAG INTERLOCK - 086-IZ-0900 TAG NO. LOCATION
SERVICE SERVICE

086-XZV-0183
1 086-F-001 SWS ACID GAS FIELD 086-XZSL-0183
0 –CLOSE
0 >=1
INLET ON/OFF VALVE 0 1 SH25 1
0
086-FV-0148 0 – <5% 1 SH26 2
086-F-001 SWS ACID GAS INLET DCS 086-FZIC-0148
2
1 – >5% 1 SH28 3
FLOW CONTROL VALVE
1 SH30 4
1 SH31 5
3

10

11

12

13

14

15

16

This Document is the property of INDIAN OIL CORPORATION LTD and is lent without PARADIP REFINERY PROJECT
NOTES: DESCRIPTION : SWS ACID GAS FEEDBACK consideration other than the Borrower’s agreement that it shall not be reproduced, copied,
lent or disposed of directly or indirectly, nor used for any purpose other than that for which it
Paradip, Orissa State, India
is specifically furnished. The apparatus shown in the document is covered by patents.
Information contained in this document may be proprietary to Indian Oil Corporation Ltd
and/or licensors, and is subject to obligations of confidentiality. INDIAN OIL
REFERENCE DOCUMENTS : CORPORATION LIMITED
1. P&IDS : PDRP4220-271-8110-25-086 F2 12/06/12 ISSUED FINAL VIAR CHIPA OPT
2. SIS LOGIC NARRATIVE : PDRP4200-271-8110-RP-085-0002 F1 14/02/12 ISSUED FINAL VIAR CHIPA OPT
FUNCTIONAL ESD LOGIC DIAGRAM
3. CAUSE & EFFECT SUMMARY : PDRP4220-271-8110-24-085-0001 CLAUS REACTION FURNACE 086-F-001
A1 24/08/11 ISSUED FOR DESIGN VIAR CHIPA OPT
UNIT - 086
Rev Date Description By Chkd Appd
Class DSN Contract No. Scale Document No. Sheet Rev
xx xxxxxxx xxxxxxxxxxx NTS PDRP271-8550-64-086-0004 18 of 31 F2
A B C D E F G H I J K L M

INPUT LOGIC OUTPUT


TAG NO. EQPT. NO.
LOCATION INTERNAL TAG INTERLOCK - 086-IZ-0900 TAG NO. LOCATION
SERVICE SERVICE

086-XZV-0180
1 FGD OUTLET SO2 GAS FLOW ON/ FIELD 086-XZSL-0180 0 –CLOSE
0 >=1
OFF VALVE 0 1 SH25 1
0
086-FV-0145
0 – <5% 1 SH26 2
086-F-002 SO2 GAS INLET FLOW DCS 086-FZIC-0145
2 1 – >5% 1 SH28 3
CONTROL VALVE
1 SH30 4
1 SH31 5
3

10

11

12

13

14

15

16

This Document is the property of INDIAN OIL CORPORATION LTD and is lent without PARADIP REFINERY PROJECT
NOTES: DESCRIPTION : SO2 GAS FEEDBACK consideration other than the Borrower’s agreement that it shall not be reproduced, copied,
lent or disposed of directly or indirectly, nor used for any purpose other than that for which it
Paradip, Orissa State, India
is specifically furnished. The apparatus shown in the document is covered by patents.
Information contained in this document may be proprietary to Indian Oil Corporation Ltd
and/or licensors, and is subject to obligations of confidentiality. INDIAN OIL
REFERENCE DOCUMENTS : CORPORATION LIMITED
1. P&IDS : PDRP4220-271-8110-25-086 F2 12/06/12 ISSUED FINAL VIAR CHIPA OPT
2. SIS LOGIC NARRATIVE : PDRP4200-271-8110-RP-085-0002 F1 14/02/12 ISSUED FINAL VIAR CHIPA OPT
FUNCTIONAL ESD LOGIC DIAGRAM
3. CAUSE & EFFECT SUMMARY : PDRP4220-271-8110-24-085-0001 CLAUS REACTION FURNACE 086-F-001
A1 24/08/11 ISSUED FOR DESIGN VIAR CHIPA OPT
UNIT - 086
Rev Date Description By Chkd Appd
Class DSN Contract No. Scale Document No. Sheet Rev
xx xxxxxxx xxxxxxxxxxx NTS PDRP271-8550-64-086-0004 19 of 31 F2
A B C D E F G H I J K L M

INPUT LOGIC OUTPUT


TAG NO. EQPT. NO.
LOCATION INTERNAL TAG INTERLOCK - 086-IZ-0900 TAG NO. LOCATION
SERVICE SERVICE

086-PZT-0180A 0 – PRESS HI HI
1 086-F-002 PROCESS AIR FIELD 086-PZSHH-0180A
INLET PRESSURE
2 SH24 1

086-PZT-0180B 0 – PRESS HI HI
2 086-F-002 PROCESS AIR FIELD 086-PZSHH-0180B 2oo3
INLET PRESSURE

086-PZT-0180C 0 – PRESS HI HI
FIELD 086-PZSHH-0180C
3 086-F-002 PROCESS AIR
INLET PRESSURE

086-HZS-0120B 0 – TRIP
4
ESD MANUAL TRIP
ESD HMI 086-HZS-0120B

0 &
086-HZS-0120C 0 – TRIP 0 0
5 CONTROL ROOM MANUAL HWC 086-HZS-0120C
TRIP 0

086-HZS-0120A 0 – TRIP
6
FIELD MANUAL TRIP ON LCP 086-HZS-0120A
LCP

086-TZT-0124A 0 – TEMP HI HI
086-F-002 REACTION FIELD 086-TZSHH-0124A
7 FURNACE TEMPERATURE

0 &
0
086-TZT-0124B 0 – TEMP HI HI
0 0
8 086-F-002 REACTION FIELD 086-TZSHH-0124B 2oo3 0
1 SH24 1
0
FURNACE TEMPERATURE 0

086-TZT-0124C 0 – TEMP HI HI
9 086-F-002 REACTION FIELD 086-TZSHH-0124C
FURNACE TEMPERATURE

10
086-PDZT-0216A
AIR PREHEATER OUTLET FIELD 086-PDZSLL-0216A
COMBUSTION AIR D/P

086-PDZT-0216B
11
AIR PREHEATER OUTLET FIELD 086-PDZSLL-0216B 2oo3
COMBUSTION AIR D/P

086-PDZT-0216C
12 AIR PREHEATER OUTLET FIELD 086-PDZSLL-0216C
COMBUSTION AIR D/P

086-LZT-0120A 0 – LEVEL LO LO
13 086-V-004 WASTE HEAT FIELD 086-LZSLL-0120A
EXCHANGER STEAM DRUM LEVEL

086-LZT-0120B
0 – LEVEL LO LO
086-V-004 WASTE HEAT 2oo3
14 FIELD 086-LZSLL-0120B
EXCHANGER STEAM DRUM LEVEL

086-LZT-0120C 0 – LEVEL LO LO
15 FIELD
086-V-004 WASTE HEAT 086-LZSLL-0120C
EXCHANGER STEAM DRUM LEVEL

089-SIS-003 0 – TRIP
16 TGTU INCINERATOR ESD 089-SIS-003
RUNNING

This Document is the property of INDIAN OIL CORPORATION LTD and is lent without PARADIP REFINERY PROJECT
NOTES: DESCRIPTION : BMS SEQUENCE STEP 1.3.2 (SHUTDOWN) consideration other than the Borrower’s agreement that it shall not be reproduced, copied,
lent or disposed of directly or indirectly, nor used for any purpose other than that for which it
Paradip, Orissa State, India
is specifically furnished. The apparatus shown in the document is covered by patents.
Information contained in this document may be proprietary to Indian Oil Corporation Ltd
and/or licensors, and is subject to obligations of confidentiality. INDIAN OIL
REFERENCE DOCUMENTS : CORPORATION LIMITED
1. P&IDS : PDRP4220-271-8110-25-086 F2 12/06/12 ISSUED FINAL VIAR CHIPA OPT
2. SIS LOGIC NARRATIVE : PDRP4200-271-8110-RP-085-0002 F1 14/02/12 ISSUED FINAL VIAR CHIPA OPT
FUNCTIONAL ESD LOGIC DIAGRAM
3. CAUSE & EFFECT SUMMARY : PDRP4220-271-8110-24-085-0001 CLAUS REACTION FURNACE 086-F-001
A1 24/08/11 ISSUED FOR DESIGN VIAR CHIPA OPT
UNIT - 086
Rev Date Description By Chkd Appd
Class DSN Contract No. Scale Document No. Sheet Rev
xx xxxxxxx xxxxxxxxxxx NTS PDRP271-8550-64-086-0004 20 of 31 F2
A B C D E F G H I J K L M

INPUT LOGIC OUTPUT


TAG NO. EQPT. NO.
LOCATION INTERNAL TAG INTERLOCK - 086-IZ-0900 TAG NO. LOCATION
SERVICE SERVICE

086-FZT-0175A 0 – LOW LOW


1 086-F-001 COMBUSTION AIR INLET FIELD 086-FZSLL-0175A 2 SH26 3
FLOW CONTROL
3 SH28 4 2 SH25 1
0 &
086-FZT-0176A 0 – LOW LOW
3 SH26 3 2 SH26 2
2
086-F-001 COMBUSTION AIR INLET FIELD 086-FZSLL-0176A 0 0
1 SH23 1
FLOW CONTROL 0
2 SH28 4
3 SH25 1
3 SH26 2
086-BZSL-0102 1 – FLAME ON
086-F-002 REACTION FURNACE FIELD 086-BZSL-0102
3 MAIN FLAME SCANNER

2oo2
086-BZSL-0103 1 – FLAME ON
4 086-F-002 REACTION FURNACE FIELD 086-BZSL-0103
MAIN FLAME SCANNER

5
1oo2 5 SH26 1
5 SH30 2

0oo2 4 SH25 1
7
4 SH26 2
4 SH29 4
086-BZSL-0101 1 – FLAME ON
8 086-F-001 REACTION FURNACE FIELD 086-BZSL-0101 6 SH25 1 4 SH28 3
PILOT FLAME SCANNER
6 SH26 2
6 SH26 3
9
6 SH27 4
6 SH28 5
10

11

12

13

14

15

16

This Document is the property of INDIAN OIL CORPORATION LTD and is lent without PARADIP REFINERY PROJECT
NOTES: DESCRIPTION : BMS SEQUENCE STEP 1.3.2 (SHUTDOWN) consideration other than the Borrower’s agreement that it shall not be reproduced, copied,
lent or disposed of directly or indirectly, nor used for any purpose other than that for which it
Paradip, Orissa State, India
is specifically furnished. The apparatus shown in the document is covered by patents.
Information contained in this document may be proprietary to Indian Oil Corporation Ltd
and/or licensors, and is subject to obligations of confidentiality. INDIAN OIL
REFERENCE DOCUMENTS : CORPORATION LIMITED
1. P&IDS : PDRP4220-271-8110-25-086 F2 12/06/12 ISSUED FINAL VIAR CHIPA OPT
2. SIS LOGIC NARRATIVE : PDRP4200-271-8110-RP-085-0002 F1 14/02/12 ISSUED FINAL VIAR CHIPA OPT
FUNCTIONAL ESD LOGIC DIAGRAM
3. CAUSE & EFFECT SUMMARY : PDRP4220-271-8110-24-085-0001 CLAUS REACTION FURNACE 086-F-001
A1 24/08/11 ISSUED FOR DESIGN VIAR CHIPA OPT
UNIT - 086
Rev Date Description By Chkd Appd
Class DSN Contract No. Scale Document No. Sheet Rev
xx xxxxxxx xxxxxxxxxxx NTS PDRP271-8550-64-086-0004 21 of 31 F2
A B C D E F G H I J K L M

INPUT LOGIC OUTPUT


TAG NO. EQPT. NO.
LOCATION INTERNAL TAG INTERLOCK - 086-IZ-0900 TAG NO. LOCATION
SERVICE SERVICE

0 – FLOW LO LO
086-FZT-0146A 0 &
1
086-F-001 AMINE ACID GAS FIELD 086-FZSLL-0146A
2 SH28 1 0 0 >=1
INLET FLOW CONTROL
0 0
2 SH30 2 1 SH23 1
0

2 2 SH31 3

1 SH15 1
086-LZT-0111A 0 – LEVEL HI HI
086-V-001 ACID GAS KO DRUM FIELD 086-LZSLL-0111A
3
LEVEL 2oo3
0 – LEVEL HI HI 3 SH28 1
086-LZT-0111B FIELD 086-LZSLL-0111B
4 086-V-001 ACID GAS KO DRUM 3 SH30 2
LEVEL
3 SH31 3
0 – LEVEL HI HI
086-LZT-0111C
086-V-001 ACID GAS KO DRUM FIELD 086-LZSLL-0111C
5
LEVEL

10

11

12

13

14

15

16

This Document is the property of INDIAN OIL CORPORATION LTD and is lent without PARADIP REFINERY PROJECT
NOTES: DESCRIPTION : BMS SEQUENCE STEP 1.3.2 (SHUTDOWN) consideration other than the Borrower’s agreement that it shall not be reproduced, copied,
lent or disposed of directly or indirectly, nor used for any purpose other than that for which it
Paradip, Orissa State, India
is specifically furnished. The apparatus shown in the document is covered by patents.
Information contained in this document may be proprietary to Indian Oil Corporation Ltd
and/or licensors, and is subject to obligations of confidentiality. INDIAN OIL
REFERENCE DOCUMENTS : CORPORATION LIMITED
1. P&IDS : PDRP4220-271-8110-25-086 F2 12/06/12 ISSUED FINAL VIAR CHIPA OPT
2. SIS LOGIC NARRATIVE : PDRP4200-271-8110-RP-085-0002 F1 14/02/12 ISSUED FINAL VIAR CHIPA OPT
FUNCTIONAL ESD LOGIC DIAGRAM
3. CAUSE & EFFECT SUMMARY : PDRP4220-271-8110-24-085-0001 CLAUS REACTION FURNACE 086-F-001
A1 24/08/11 ISSUED FOR DESIGN VIAR CHIPA OPT
UNIT - 086
Rev Date Description By Chkd Appd
Class DSN Contract No. Scale Document No. Sheet Rev
xx xxxxxxx xxxxxxxxxxx NTS PDRP271-8550-64-086-0004 22 of 31 F2
A B C D E F G H I J K L M

INPUT LOGIC OUTPUT


TAG NO. EQPT. NO.
LOCATION INTERNAL TAG INTERLOCK - 086-IZ-0900 TAG NO. LOCATION
SERVICE SERVICE

086-HZS-0121
1 – I/O BYPASSED 086-HZA-0121A
1
1 – BYPASS 086-HZA-0121A LCP
BYPASS ENABLE SWITCH LCP 086-HZS-0121 I/O BYPASSED

0 >=1
086-HZA-0121B
1 SH21 1 0 & 0
1 SH24 1
1 – I/O BYPASSED
086-HZA-0121B ESD HMI
2 I/O BYPASSED
0 0

0
1 SH22 1

10

11

12

13

14

15

16

This Document is the property of INDIAN OIL CORPORATION LTD and is lent without PARADIP REFINERY PROJECT
NOTES: DESCRIPTION : BMS SEQUENCE STEP 1.3.2 (SHUTDOWN) consideration other than the Borrower’s agreement that it shall not be reproduced, copied,
lent or disposed of directly or indirectly, nor used for any purpose other than that for which it
Paradip, Orissa State, India
is specifically furnished. The apparatus shown in the document is covered by patents.
Information contained in this document may be proprietary to Indian Oil Corporation Ltd
and/or licensors, and is subject to obligations of confidentiality. INDIAN OIL
REFERENCE DOCUMENTS : CORPORATION LIMITED
1. P&IDS : PDRP4220-271-8110-25-086 F2 12/06/12 ISSUED FINAL VIAR CHIPA OPT
2. SIS LOGIC NARRATIVE : PDRP4200-271-8110-RP-085-0002 F1 14/02/12 ISSUED FINAL VIAR CHIPA OPT
FUNCTIONAL ESD LOGIC DIAGRAM
3. CAUSE & EFFECT SUMMARY : PDRP4220-271-8110-24-085-0001 CLAUS REACTION FURNACE 086-F-001
A1 24/08/11 ISSUED FOR DESIGN VIAR CHIPA OPT
UNIT - 086
Rev Date Description By Chkd Appd
Class DSN Contract No. Scale Document No. Sheet Rev
xx xxxxxxx xxxxxxxxxxx NTS PDRP271-8550-64-086-0004 23 of 31 F2
A B C D E F G H I J K L M

INPUT LOGIC OUTPUT


TAG NO. EQPT. NO.
LOCATION INTERNAL TAG INTERLOCK - 086-IZ-0900 TAG NO. LOCATION
SERVICE SERVICE
086-XZA-0120A
086-HZS-0122 RESET 086-XZA-0129A LCP
1 SRU SYSTEM TRIPPED
LOGIC RESET
ESD HMI 086-HZS-0122 S
1 SH06 1
R 086-XZA-0120B
1 SH07 2 086-XZA-0129B ESD HMI
2
1 SH20 1 0 & SRU SYSTEM TRIPPED
1 SH08 3
0

0 1 SH09 4 086-XZA-0122A
1 SH23 1
086-XZA-0122A LCP INTERLOCK RESET STATUS
1 SH10 5 LAMP
3
1 SH11 6
086-XZA-0122B
1 SH12 7 086-XZA-0122B ESD HMI INTERLOCK RESET STATUS
LAMP
4 1 SH26 8
1 SH28 9 1 – SRU RUNNING 086-SIS-0001
086-SIS-0001 ESD
SRU RUNNING
5

0 >=1 ON DELAY

0
T 0 &
0
6
2 SH20 1 0
10 MINS
0
2 SH05 1
0

086-KZI-0126C
7

0 >=1 1 – OK TO RESET
0
086-XZL-0122
9 086-XZL-0122 ESD HMI INTERLOCK READY TO RESET
0 INDICATION

10

11

12

13

14

15

16

This Document is the property of INDIAN OIL CORPORATION LTD and is lent without PARADIP REFINERY PROJECT
NOTES: DESCRIPTION : BMS SEQUENCE STEP 1.3.2 (SHUTDOWN) consideration other than the Borrower’s agreement that it shall not be reproduced, copied,
lent or disposed of directly or indirectly, nor used for any purpose other than that for which it
Paradip, Orissa State, India
is specifically furnished. The apparatus shown in the document is covered by patents.
Information contained in this document may be proprietary to Indian Oil Corporation Ltd
and/or licensors, and is subject to obligations of confidentiality. INDIAN OIL
REFERENCE DOCUMENTS : CORPORATION LIMITED
1. P&IDS : PDRP4220-271-8110-25-086 F2 12/06/12 ISSUED FINAL VIAR CHIPA OPT
2. SIS LOGIC NARRATIVE : PDRP4200-271-8110-RP-085-0002 F1 14/02/12 ISSUED FINAL VIAR CHIPA OPT
FUNCTIONAL ESD LOGIC DIAGRAM
3. CAUSE & EFFECT SUMMARY : PDRP4220-271-8110-24-085-0001 CLAUS REACTION FURNACE 086-F-001
A1 24/08/11 ISSUED FOR DESIGN VIAR CHIPA OPT
UNIT - 086
Rev Date Description By Chkd Appd
Class DSN Contract No. Scale Document No. Sheet Rev
xx xxxxxxx xxxxxxxxxxx NTS PDRP271-8550-64-086-0004 24 of 31 F2
A B C D E F G H I J K L M

INPUT LOGIC OUTPUT


TAG NO. EQPT. NO.
LOCATION INTERNAL TAG INTERLOCK - 086-IZ-0900 TAG NO. LOCATION
SERVICE SERVICE

086-HZS-0123A RESET
&
1 0
LCP 086-HZS-0123A
START PURGE CYCLE 0
S
0
1 SH14 1 1 SH05 1
R
2
0 >=1
0
1 SH13 1 1 – ON 086-XZL-0123A
0
086-XZL-0123A LCP
2 SH15 1 READY TO PURGE LAMP
3
1 SH16 1 0 >=1
0 1 – ON
1 SH17 1 0 0 2 SH14 1 086-XZL-0123E
0 S 086-XZL-0123E ESD HMI
0 READY TO PURGE INDICATION
4 1 SH18 1 0
R 0 &
1 SH19 1 ON DELAY 0 1 – PURGING
086-XZL-0123B LCP 086-XZL-0123B
0 >=1 T 0 0
PURGE IN PROGRESS
5 2 SH21 1 0

0 10 MINS
3 SH21 1
0 >=1 086-KZI-0123A 1 – PURGE COMPLETE 086-XZL-0123F
4 SH21 1 0 086-XZL-0123F ESD HMI PURGE CYCLE COMPLETE
0 0
0
6 6 SH21 1 0
0
1 SH12 1 1 – PURGE COMPLETE 086-XZL-0123C
0 & 086-XZL-0123C LCP PURGE CYCLE COMPLETE
1 – SET FLOW 0

7 REACHED 0

1 – ENABLE FLOW 0 – TIMER NOT


ACCUMULATOR EXPIRED
086-FZT-0177 >468 Nm3 ON DELAY
8 NITROGEN PURGE FLOW FIELD 086-FZQI-0177
0 & T 0
0
3 SH26 1
0 10 MINS

9 086-KZI-0123B
2 SH05 1
2 SH05 2
10
1 – PURGE FAILED 086-XZL-0177A
0 &
086-XZL-0177A LCP PURGE FAILED
0

11
1 – PURGE FAILED
086-XZL-0177B
086-XZL-0177B ESD HMI
PURGE FAILED

12

13

14

15

16

This Document is the property of INDIAN OIL CORPORATION LTD and is lent without PARADIP REFINERY PROJECT
NOTES: DESCRIPTION : BMS SEQUENCE STEP 1.3.3 (START-UP PURGE MODE) consideration other than the Borrower’s agreement that it shall not be reproduced, copied,
lent or disposed of directly or indirectly, nor used for any purpose other than that for which it
Paradip, Orissa State, India
is specifically furnished. The apparatus shown in the document is covered by patents.
Information contained in this document may be proprietary to Indian Oil Corporation Ltd
and/or licensors, and is subject to obligations of confidentiality. INDIAN OIL
REFERENCE DOCUMENTS : CORPORATION LIMITED
1. P&IDS : PDRP4220-271-8110-25-086 F2 12/06/12 ISSUED FINAL VIAR CHIPA OPT
2. SIS LOGIC NARRATIVE : PDRP4200-271-8110-RP-085-0002 F1 14/02/12 ISSUED FINAL VIAR CHIPA OPT
FUNCTIONAL ESD LOGIC DIAGRAM
3. CAUSE & EFFECT SUMMARY : PDRP4220-271-8110-24-085-0001 CLAUS REACTION FURNACE 086-F-001
A1 24/08/11 ISSUED FOR DESIGN VIAR CHIPA OPT
UNIT - 086
Rev Date Description By Chkd Appd
Class DSN Contract No. Scale Document No. Sheet Rev
xx xxxxxxx xxxxxxxxxxx NTS PDRP271-8550-64-086-0004 25 of 31 F2
A B C D E F G H I J K L M

INPUT LOGIC OUTPUT


TAG NO. EQPT. NO.
LOCATION INTERNAL TAG INTERLOCK - 086-IZ-0900 TAG NO. LOCATION
SERVICE SERVICE

1
3 SH14 1
4 SH14 1
2 SH15 2 0 >=1
2 0
1 SH16 2 0 0
0
0
1 SH17 2

3
0 >=1
1 SH18 2 0 0 0 >=1
0 0

4
1 SH19 2 0
0 >=1
2 SH21 2 0
0 0
0
3 SH21 2 0 1 SH24 8
5 2 SH17 1

4 SH21 2 0 >=1 0 &


6
0 0 0
1 SH27 1
3 SH25 1 0
0
6 SH21 1
7

1 SH13 3 0 >=1
8 0
0
2 SH21 3 0
0
0 >=1
3 SH21 3 0 >=1 0

9 3 SH15 1 0 0

4 SH15 1 0 >=1
10
0 0
5 SH21 1
0

6 SH21 3

11

12

13

14

15

16

This Document is the property of INDIAN OIL CORPORATION LTD and is lent without PARADIP REFINERY PROJECT
NOTES: DESCRIPTION : BMS SEQUENCE STEP 1.3.4 (PILOT IGNITION) consideration other than the Borrower’s agreement that it shall not be reproduced, copied,
lent or disposed of directly or indirectly, nor used for any purpose other than that for which it
Paradip, Orissa State, India
is specifically furnished. The apparatus shown in the document is covered by patents.
Information contained in this document may be proprietary to Indian Oil Corporation Ltd
and/or licensors, and is subject to obligations of confidentiality. INDIAN OIL
REFERENCE DOCUMENTS : CORPORATION LIMITED
1. P&IDS : PDRP4220-271-8110-25-086 F2 12/06/12 ISSUED FINAL VIAR CHIPA OPT
2. SIS LOGIC NARRATIVE : PDRP4200-271-8110-RP-085-0002 F1 14/02/12 ISSUED FINAL VIAR CHIPA OPT
FUNCTIONAL ESD LOGIC DIAGRAM
3. CAUSE & EFFECT SUMMARY : PDRP4220-271-8110-24-085-0001 CLAUS REACTION FURNACE 086-F-001
A1 24/08/11 ISSUED FOR DESIGN VIAR CHIPA OPT
UNIT - 086
Rev Date Description By Chkd Appd
Class DSN Contract No. Scale Document No. Sheet Rev
xx xxxxxxx xxxxxxxxxxx NTS PDRP271-8550-64-086-0004 26 of 31 F2
A B C D E F G H I J K L M

INPUT LOGIC OUTPUT


TAG NO. EQPT. NO.
LOCATION INTERNAL TAG INTERLOCK - 086-IZ-0900 TAG NO. LOCATION
SERVICE SERVICE

086-BZY-0101
086-HZS-0124A RESET
& 086-BZY-0101 FIELD
1 0
FIELD RESET PILOT LCP 086-HZS-0124A S PILOT IGNITOR
IGNITION 0
1 SH06 1
0
1 SH23 1
R 1 SH06 2
2
1 SH06 3
0 &
086-HZS-0124B 0 – STOP 0
2 SH06 1
LCP 086-HZS-0124B
3 STOP PILOT 2 SH27 1 0
2 SH06 2
0 >=1 ON DELAY 1 – FAIL 086-XZL-0124
086-XZV-0193 0 – OPEN 086-XZL-0124 LCP
0 0 PILOT FAILED TO LIGHT
4 MAIN FUEL VENT ON/OFF FIELD 086-XZSH-0193 T 0
0 &
VALVE 0
10 MINS
0 0
3 SH06 1
0
ESD 086-XZI-0124
086-KZI-0124 086-XZI-0124
HMI PILOT FAILED TO LIGHT
5

6 6 SH21 4

10

11

12

13

14

15

16

This Document is the property of INDIAN OIL CORPORATION LTD and is lent without PARADIP REFINERY PROJECT
NOTES: DESCRIPTION : BMS SEQUENCE STEP 1.3.4 (PILOT IGNITION) consideration other than the Borrower’s agreement that it shall not be reproduced, copied,
lent or disposed of directly or indirectly, nor used for any purpose other than that for which it
Paradip, Orissa State, India
is specifically furnished. The apparatus shown in the document is covered by patents.
Information contained in this document may be proprietary to Indian Oil Corporation Ltd
and/or licensors, and is subject to obligations of confidentiality. INDIAN OIL
REFERENCE DOCUMENTS : CORPORATION LIMITED
1. P&IDS : PDRP4220-271-8110-25-086 F2 12/06/12 ISSUED FINAL VIAR CHIPA OPT
2. SIS LOGIC NARRATIVE : PDRP4200-271-8110-RP-085-0002 F1 14/02/12 ISSUED FINAL VIAR CHIPA OPT
FUNCTIONAL ESD LOGIC DIAGRAM
3. CAUSE & EFFECT SUMMARY : PDRP4220-271-8110-24-085-0001 CLAUS REACTION FURNACE 086-F-001
A1 24/08/11 ISSUED FOR DESIGN VIAR CHIPA OPT
UNIT - 086
Rev Date Description By Chkd Appd
Class DSN Contract No. Scale Document No. Sheet Rev
xx xxxxxxx xxxxxxxxxxx NTS PDRP271-8550-64-086-0004 27 of 31 F2
A B C D E F G H I J K L M

INPUT LOGIC OUTPUT


TAG NO. EQPT. NO.
LOCATION INTERNAL TAG INTERLOCK - 086-IZ-0900 TAG NO. LOCATION
SERVICE SERVICE

1
4 SH21 3
1 SH16 3
1 SH17 3 0 &
2 0
1 SH18 3 0 0
0
0
1 SH19 3

3
0 &
6 SH21 5 0 1 – OK 086-XZL-0125A
0
086-XZL-0125A LCP OK TO RESET MAIN FUEL GAS
2 SH28 1 AND COMBUSTION AIR
4
0 &
2 SH21 4 0
0 0
0
2 SH15 3 0
0 >=1
5 1 SH24 9 0
1 SH29 1
0

0 &
6 0 0

0 &
0
7
0

0 &
0
8 0
3 SH22 1 0
0

3 SH17 1

9 2 SH16 1

10

11

12

13

14

15

16

This Document is the property of INDIAN OIL CORPORATION LTD and is lent without PARADIP REFINERY PROJECT
NOTES: DESCRIPTION : BMS SEQUENCE STEP 1.3.5 (MAIN BURNER IGNITION) consideration other than the Borrower’s agreement that it shall not be reproduced, copied,
lent or disposed of directly or indirectly, nor used for any purpose other than that for which it
Paradip, Orissa State, India
is specifically furnished. The apparatus shown in the document is covered by patents.
Information contained in this document may be proprietary to Indian Oil Corporation Ltd
and/or licensors, and is subject to obligations of confidentiality. INDIAN OIL
REFERENCE DOCUMENTS : CORPORATION LIMITED
1. P&IDS : PDRP4220-271-8110-25-086 F2 12/06/12 ISSUED FINAL VIAR CHIPA OPT
2. SIS LOGIC NARRATIVE : PDRP4200-271-8110-RP-085-0002 F1 14/02/12 ISSUED FINAL VIAR CHIPA OPT
FUNCTIONAL ESD LOGIC DIAGRAM
3. CAUSE & EFFECT SUMMARY : PDRP4220-271-8110-24-085-0001 CLAUS REACTION FURNACE 086-F-001
A1 24/08/11 ISSUED FOR DESIGN VIAR CHIPA OPT
UNIT - 086
Rev Date Description By Chkd Appd
Class DSN Contract No. Scale Document No. Sheet Rev
xx xxxxxxx xxxxxxxxxxx NTS PDRP271-8550-64-086-0004 28 of 31 F2
A B C D E F G H I J K L M

INPUT LOGIC OUTPUT


TAG NO. EQPT. NO.
LOCATION INTERNAL TAG INTERLOCK - 086-IZ-0900 TAG NO. LOCATION
SERVICE SERVICE

086-HZS-0125B RESET
1 LCP 086-HZS-0125B 0 &
MAIN FUEL GAS AND S
COMBUSTION AIR 0
1 SH07 1
0
1 SH28 1
R 1 SH08 2
2

0 &
0
2 SH07 1
3 3 SH15 2 5 SH15 1 0
2 SH07 2
4 SH15 2 0 & ON DELAY
086-FZT-0171A 0
086-F-001 MAIN FUEL GAS INLET 0 0 0
ESD 086-FZSLL-0171 T &
4 0 0
FLOW CONTROL 0 – FLOW LO LO 0
10 MINS
0 0
3 SH07 1
0
086-KZI-0125
5

6 4 SH21 4

0 – CLOSE
086-XZV-0202 ON DELAY
8 086-F-001 COMBUSTION FIELD 086-XZSL-0202 S T 0 0 >=1 0 & ON DELAY
OUTLET
0 0 0 T 0
R 5 MINS S
0 0
30 SECS
0 >=1
0 – TRIP
0
9 R
0

10

11
4 SH08 1

086-FZT-0175A 0 – FLOW LO LO
086-F-001 COMBUSTION AIR ESD 086-FZSLL-0175
12
INLET FLOW CONTROL

13

14

15

16

This Document is the property of INDIAN OIL CORPORATION LTD and is lent without PARADIP REFINERY PROJECT
NOTES: DESCRIPTION : BMS SEQUENCE STEP 1.3.5 (MAIN BURNER IGNITION) consideration other than the Borrower’s agreement that it shall not be reproduced, copied,
lent or disposed of directly or indirectly, nor used for any purpose other than that for which it
Paradip, Orissa State, India
is specifically furnished. The apparatus shown in the document is covered by patents.
Information contained in this document may be proprietary to Indian Oil Corporation Ltd
and/or licensors, and is subject to obligations of confidentiality. INDIAN OIL
REFERENCE DOCUMENTS : CORPORATION LIMITED
1. P&IDS : PDRP4220-271-8110-25-086 F2 12/06/12 ISSUED FINAL VIAR CHIPA OPT
2. SIS LOGIC NARRATIVE : PDRP4200-271-8110-RP-085-0002 F1 14/02/12 ISSUED FINAL VIAR CHIPA OPT
FUNCTIONAL ESD LOGIC DIAGRAM
3. CAUSE & EFFECT SUMMARY : PDRP4220-271-8110-24-085-0001 CLAUS REACTION FURNACE 086-F-001
A1 24/08/11 ISSUED FOR DESIGN VIAR CHIPA OPT
UNIT - 086
Rev Date Description By Chkd Appd
Class DSN Contract No. Scale Document No. Sheet Rev
xx xxxxxxx xxxxxxxxxxx NTS PDRP271-8550-64-086-0004 29 of 31 F2
A B C D E F G H I J K L M

INPUT LOGIC OUTPUT


TAG NO. EQPT. NO.
LOCATION INTERNAL TAG INTERLOCK - 086-IZ-0900 TAG NO. LOCATION
SERVICE SERVICE

1
3 SH14 3
1 SH15 2
1 SH17 4 0 &
2 0
1 SH18 4 0 0
0
0
1 SH19 4

3
0 &
1 – OK
0
LCP 086-XZL-0126
2 SH22 2 0
086-XZL-0126
OK TO RESET AMINE ACID GAS
4 3 SH22 2 SOLENOIDS
0 & 1 SH31 1
0
5 SH21 2 0
0
0
1 SH09 3
5

10

11

12

13

14

15

16

This Document is the property of INDIAN OIL CORPORATION LTD and is lent without PARADIP REFINERY PROJECT
NOTES: DESCRIPTION : BMS SEQUENCE STEP 1.3.6 (ACID GAS MODE) consideration other than the Borrower’s agreement that it shall not be reproduced, copied,
lent or disposed of directly or indirectly, nor used for any purpose other than that for which it
Paradip, Orissa State, India
is specifically furnished. The apparatus shown in the document is covered by patents.
Information contained in this document may be proprietary to Indian Oil Corporation Ltd
and/or licensors, and is subject to obligations of confidentiality. INDIAN OIL
REFERENCE DOCUMENTS : CORPORATION LIMITED
1. P&IDS : PDRP4220-271-8110-25-086 F2 12/06/12 ISSUED FINAL VIAR CHIPA OPT
2. SIS LOGIC NARRATIVE : PDRP4200-271-8110-RP-085-0002 F1 14/02/12 ISSUED FINAL VIAR CHIPA OPT
FUNCTIONAL ESD LOGIC DIAGRAM
3. CAUSE & EFFECT SUMMARY : PDRP4220-271-8110-24-085-0001 CLAUS REACTION FURNACE 086-F-001
A1 24/08/11 ISSUED FOR DESIGN VIAR CHIPA OPT
UNIT - 086
Rev Date Description By Chkd Appd
Class DSN Contract No. Scale Document No. Sheet Rev
xx xxxxxxx xxxxxxxxxxx NTS PDRP271-8550-64-086-0004 30 of 31 F2
A B C D E F G H I J K L M

INPUT LOGIC OUTPUT


TAG NO. EQPT. NO.
LOCATION INTERNAL TAG INTERLOCK - 086-IZ-0900 TAG NO. LOCATION
SERVICE SERVICE

086-HZS-0126B RESET
&
1 0
1 SH09 1
RESET AMINE ACID GAS LCP 086-HZS-0126B S
SOLENOIDS 0
1 SH32 2
0
1 SH30 1
R 1 SH10 3
2
1 SH11 4
0 & 1 – OK
LCP 086-XZL-0127
086-SIS-0001 0 086-XZL-0127
ESD 086-SIS-0001 OK TO RESET SWS GAS
3 SRU RUNNING 1 SH18 5 0
SOLENOIDS

2 SH22 3 0 & 1 – OK
086-XZL-0128
086-XZL-0128 LCP
0 0 OK TO RESET SO2 GAS
4 0 & SOLENOIDS
0
3 SH22 3 0

6 SH21 4 0

10

11

12

13

14

15

16

This Document is the property of INDIAN OIL CORPORATION LTD and is lent without PARADIP REFINERY PROJECT
NOTES: DESCRIPTION : BMS SEQUENCE STEP 1.3.6 (ACID GAS MODE) consideration other than the Borrower’s agreement that it shall not be reproduced, copied,
lent or disposed of directly or indirectly, nor used for any purpose other than that for which it
Paradip, Orissa State, India
is specifically furnished. The apparatus shown in the document is covered by patents.
Information contained in this document may be proprietary to Indian Oil Corporation Ltd
and/or licensors, and is subject to obligations of confidentiality. INDIAN OIL
REFERENCE DOCUMENTS : CORPORATION LIMITED
1. P&IDS : PDRP4220-271-8110-25-086 F2 12/06/12 ISSUED FINAL VIAR CHIPA OPT
2. SIS LOGIC NARRATIVE : PDRP4200-271-8110-RP-085-0002 F1 14/02/12 ISSUED FINAL VIAR CHIPA OPT
FUNCTIONAL ESD LOGIC DIAGRAM
3. CAUSE & EFFECT SUMMARY : PDRP4220-271-8110-24-085-0001 CLAUS REACTION FURNACE 086-F-001
A1 24/08/11 ISSUED FOR DESIGN VIAR CHIPA OPT
UNIT - 086
Rev Date Description By Chkd Appd
Class DSN Contract No. Scale Document No. Sheet Rev
xx xxxxxxx xxxxxxxxxxx NTS PDRP271-8550-64-086-0004 31 of 31 F2