DESIGN OF DOBLY REINFORCED BEAM

fc' = 4 (ksi)

fy = 40 (ksi)

Mu = 8000 (kips-in)

CHECK :

BUT HERE FIRST FINDING THE CAPACITY BY PROVIDING

0.02709375

9.9705

CHECKING THE CAPACITY :

Assume
a= 7.33125

6939.84189375

HENCE Md < Mu (given) so we shall design DOUBLY R

1060.15810625

FINDING STEEL USED IN COMPRESSION AS WELL AS TENSION IE As’

Assume :fs=fy

As' = 1.4365285993
THE TOTAL TENSILE STEEL AREA = 11.4070285993

CHECK :

0.0309973603

0.0039036103

0.0184404975

HENCE COMPRESSION STEEL IS YIELDI


The above formula also showing the compression steel yielding or not

c= 8.625

fs' = 61.7826086957

0.005

0.0349009706

FOR COMPRESSION STEEL NOT YIELDI


1= OK COMPRESSION STEEL IS YIELDING
2= OK COMPRESSION STEEL IS YIELDING

0.9300537025

CODE DUCTILITY REQUIREMENT

0.0025273198

0.0335246802
0.005

DESIGN IS OK
ρ provided <ρmax'
DESIGN IS OK
By: Engr Abdul Raziq

b= 16 (inch) araziq013@gmail.com
h= 25.5 (inch)

d= 23 (inch) b
d'= 2.5 (inch)

0.003
h
0.85

APACITY BY PROVIDING MAX REINFORCEMENT

taking

(in^2)

0.9
(kips-in) DOUBLY REINF Mu1

l design DOUBLY REINF BEAM

(kips-in)

ENSION IE As’

(in^2)
(in^2)

ESSION STEEL IS YIELDING Its OK


pression steel yielding or not

a' as we found above in 1st step

(inch)

(ksi) OK YIELDING

DESIGN IS OK

ρ(Provided)< ρ max
DESIGN IS OK

SION STEEL NOT YIELDING :

OR
L IS YIELDING
L IS YIELDING

in^2 DON’T GO FOR THIS AREA THE ABOVE RESULTS ARE CORRECT
DON’T TRUST THESE STATEMENTS