SIEMENS 8.14 Redundancy in PAS and PAS CC ‘The redundancy used in the project can be explained with the help of conceptual diagram shown below. nut view wove a fics z a FS cinemetcouies Sat IEC 61850 IEC 61850 Figure 22 Redundancy in PAS ‘As shown in the figure PAS (Controller) and the HMI is in a redundant configuration. The HMI node and the Station HMI are connected to the Controller and redundant Controller in dual LAN, ‘The HMI View node and Station HMI is in HOT-STANDBY configuration, The Controller and Redundant Controller is connected to the Ethernet double bus. The Controller and Redundant Controller is HOT-HOT configuration, which will ensure the required efficiency. ‘The communication mode will be in 1+1 mode, excluding the links between individual bay IEDs to switch, such that failure of one set, of fibre will not affect the normal operation of the Substation automation system Unrestricted SAS FDS Page 79 of 104 Document No. (4)-G719EA-JG9016-00-H500. Rey-0 Copyright © Fhegy, Siemens Led, AIT Righs Reserved This docamert shal ot be tarsmited or reproduced, no tall is coments be explo or dsclosed to hil persons witout pri writen conser fam Siemens. Ths documents Specialy designed for PGC Tur Poli 9, as must tbe spesfcally used for other projector pradact as a erence. Contents o this document are subject tovchage without peice notice witha reson.