BASIC CONCEPTS FOR
BUSBAR TRUNKING
SYSTEMS
Flexible
With the use of tap-off outlets situated on the straight lengths, the busbar trunking systems provide high levels of
flexibility both during the planning stage (in the engineering department) and during the installation of the system
(installer), and the inevitable modifications of the electrical system to meet the end-user’s changing needs.
Tap-off boxes can be inserted and removed from their tap-off outlet when the busbar is live and can be inserted in
another tap-off outlet, hence avoiding downtime.
The engineer in charge of designing the busbar trunking system does not necessarily need to know the exact position of
machines or the electric loads that will be installed in the building.
The designer’s plan will take into consideration the end-customer’s modifications and variations which will be determined
during the operation of the system. No more point-to-point connections but just one power distribution system where
power can be tapped-off wherever there is a free tap-off point.
Due to its flexible and long-lasting features, the installation of Zucchini’s busbar in a building allows easy modification
of its use within business premises, thus providing benefits even to those who manage and rent out different
parts of the building.
ZUCCHINI 2
Quick installation
Zucchini’s jointing systems have been made and designed to allow easy installation of busbar trunking systems.
When using a traditional cable system, the time needed to install only one cabletray is equal to the same time needed
to install a complete system in a busbar trunking system. Furthermore, given the same capacity, a power busbar trunking
system – which is generally provided with aluminium conductors – is much lighter than an equivalent one made with
cabletrays and (copper) cables: lighter weights require a lower number of supports or, at least simpler and less
expensive supports. This is why the time to install a busbar trunking system is obviously shorter than a similar
traditional cable installation.
Reduced dimensions
The overall dimensions of busbar trunking systems are generally smaller than an equivalent traditional cable
installation, especially when the currents to be carried exceed 1000A and when several cables in parallel are
required to ensure such ratings. Further advantages can be found in route changes, where cables have a
minimum bending radius to avoid damage to the insulation; the busbar trunking systems allow route changes
with 90° angles, thus maximising the use of the reduced spaces available within technical premises.
Easy to rate
The electrical rating of busbar trunking systems is carried out by Zucchini in compliance with the product Standards.
The rated current of Zucchini’s busbars is guaranteed for room temperatures at 40°C (the Standard requires 35°C).
After choosing the appropriate current requirements for the busbar, it is extremely easy to check the voltage drop as
well as the protection against overcurrents. To do so, use the technical charts available for all Zucchini product lines.
These charts basically specify: the short-circuit currents and the peak current withstand of the busbar while waiting for
the protection device to start operating upstream, the voltage drop of the average cosϕ of the loads, the losses as
well as a series of additional data (R, X, Rpe, etc.) which allow the designer to make calculations using the results
from tests carried out in accredited LOVAG laboratories for heat and short-circuit tests which have been used to certify
all of our ranges. With busbar trunking systems, the protection device is located close to the load (decentralised
protection); as a result, protection devices such as thermal magnetic circuit breakers, fusecarriers and motorised
switches can be housed in the tap-off boxes, thus allowing easy and effective management of the system.
Fail-safe behaviour
Due to its particular features, a busbar trunking system does not normally use great amounts of insulating plastic material
potentially dangerous material in case of fire. Moreover, plastic material used for the insulating parts of busbar trunking
systems are always of the self-extinguishing type (from V0 to V2) and generally have low smoke emission (Halogen
Free). Another advantage of the busbar trunking system is in its low electromagnetic emission compared to that of an
equivalent traditional cable installation: as a result, the steel casing of the busbar serves as a shield for the electric field
(shielded enclosure) and the sandwiching of the phase conductors considerably reduces the emission of the magnetic
component, too. The Italian law, 8/7/2003 DPCM (Prime Ministerial Decree), sets 10 µTs as the “target level” and a
maximum limit of 3 µT as the “quality level”. Tests carried out on one of Zucchini’s 2500A SCP busbars at full rated
current show that the emission of the magnetic field (magnetic induction) is lower than the “target level” specified in the
Decree when at a distance of 0.3 m, whereas the threshold considered as the “acceptable level” is set at a distance of
only 0.7 m from the busbar. These features make busbar trunking systems the unavoidable choice for hospital facilities,
data processing centres and wherever it is necessary to supply great amounts of power for workplaces.
3 ZUCCHINI
ZUCCHINI follows a policy of continuous
development, and therefore reserves the right
to supply products which may differ in detail
from those shown in this publication.
ZUCCHINI 4
LB
LIGHTING BUSWAY I N D E X
25 - 40A
LB
GENERAL DATA 6
6 CONDUCTORS ELEMENTS 12
• END FEED UNITS
• END COVERS
• FLEXIBLE JOINTS
• OUTLET COVERS
PLUGS 14
FIXING DEVICES 16
CHANNEL ACCESSORIES 18
5 ZUCCHINI
LB
TECHNICAL DESCRIPTION
LB (Lighting Busbar) is part of the Zucchini Used for distributing power, suspending • tap-off outlets to accept plug-in units These enable the LB range to be supplied
range. It can be used for supplying power and powering light fittings. are located on the busbar with a spacing by cable ; the assembly is carried out with
to light fittings within the service sector, LB straight lengths include the following distance of 1 m (3 outlets every 3 m) a quick joint arrangement as with the
advanced service sector and in most components: or 0.5 m (6 outlets every 3 m). straight lengths.
manufacturing industries. • a closed and ribbed section casing The outlets in the LB version with 6 The end feed units have connection
Zucchini LB is extremely fast and simple to (26x41 mm, thickness 0.6 mm), made conductors (LB256/406) are situated on terminals to accept 25 mm2 flexible
install. In addition, its flexibility can be of hot-galvanised steel (Senzimir) which both sides of the busbar: 3+3 or 6+6 copper cables.
used during the planning stage, during also serves as a protective conductor due outlets; There is an anti-pull cable clamp
installation and during every day use. to its cross-section and electrical continuity. • an electrical joint block for automatically inside the unit.
The IP55 degree of protection makes it The straight lengths are also available connecting live conductors. The connection The entrance point for the cables is
suitable for false ceiling and raised floor in a painted version with RAL colours between two straight lengths is quick: located at the base of the end feed unit.
installations. (optional) and in a version with an with only one operation to make both the
LB, as with all Zucchini products, is fully anodized aluminium casing; electrical and mechanical connection.
compliant with the CEI EN 60439-1 / 2 • 2 – 4 or 6 rigid copper conductors with An IP55 degree of protection is standard
Harmonised Standards; specifically, the purity no less than 99.9%. without using additional IP protection kits.
rated current of the Zucchini busbar The cross-section of the conductors is 3.14 The continuity of the protective conductor
trunking systems is always rated at the mm2 for a 25A rating and 6.15 mm2 for a (casing) is ensured by tightening the
average ambient temperature of 40°C 40A rating; the conductors are separated special connection screw.
(nb.: the Standard requires 35°C), thus from each other by a self-extinguishing The whole busbar is “fire retardant” in
offering the market suitably oversized plastic insulating sheath, type V0 compliance with standard EN 60332-3.
products. (according to UL94) and in compliance
with the incandescent wire test as per
EN 60695-2-1 (CEI 50.11);
ZUCCHINI 6
LB
END COVERS HANGERS TRUNKING COMPONENTS AND PLUG-IN UNITS
ADDITIONAL ELEMENTS
End covers ensure the IP55 degree of In order to fix the run to the structure of Depending on the different installation These are used for connecting and
protection at the end of the run. the building, directly or with a steel chain, requirements, Zucchini is able to offer supplying light fittings. They include
Two versions are available, depending on it is necessary to use a set of special different technical solutions: the following features:
the end feed unit used at the start of the components to achieve any type of a) flexible joint: used for changing • they can be operated when energized
run: suspension: direction or to avoid possible obstacles and when under load conditions;
• the right (RH) end feed unit requires the • simple bracket: when used with its along the busbar run. • the PE contact (protective conductor) is
use of a right (RH) end cover . bracket-holder, it enables the installation They have the same quick joint connection the first to make an electrical connection
• the left (LH) end feed unit requires a of the busbar at a distance of about as the straight lengths. Similarly, they give when plugged into the outlet, and the
left (LH) end cover. 25 cm below the ceiling a mechanical connection and an IP55 last to disconnect when unplugged;
• wall bracket: enables the fixing of the degree of protection with just one • all insulating plastic components are in
run directly onto the wall of a building, operation. The continuity of the protective compliance with the incandescent wire
setting it at the required clearance conductor, made from the casing of the test (EN 60695-2-1) and have a V1
to enable the mounting of all the element itself, is ensured by tightening self-extinguishing degree (UL94);
necessary accessories; the special connection screw. • the standard degree of protection is
• snap clamp: the snap-on installation is b) cable channel with cover: this accessory IP55 without using additional IP protection
extremely fast. can be placed over the top of the busbar; kits;
This clamp can be used both for it can be used to distribute auxiliary • the plugs are polarised in the
suspending the busbar from the ceiling circuits, if any, and it is integral with the LB 6-conductor line, which means that the
and for hanging accessories such as busbar using appropriate spacers and plug installed on one side of the busbar
fluorescent lamps, tap-off boxes, etc. brackets which retain the cable-channel cannot be installed on the other side due
on the busbar; system. The channel is 3 m long. Its to a mechanical interlock on the outlet;
• snap clamp with ring or hook: the ring dimensions are 28x28 mm. • the plug-in units are common for the LB
or hook enables accessories to be c) centre feed unit: feeds the busbar 2-4 and 6 conductor offer; these include:
mounted onto the busbar . trunking system from an intermediate a) 10A fixed phase selection plug-in units,
The technical chart on page 138 shows point along the run, hence reducing the pre-wired with 1m, 3m or 5m of
the suspension centre distance according voltage drop at the end of the line 3x1.5mm2 FROR cable;
to the maximum load distributed between and/or to simplify the installation when b) 16A phase selection plug-in units, with
two fixing points. the power supply is near the middle terminals for connecting a L+N+PE cable;
of the run. b) 16A phase selection plug-in units,
with a 5x20 cylindrical ceramic fuse and
terminals for connecting a L+N+PE cable;
d) 16A three-phase plug-in units, with
cylindrical fuseholder – CH8 type (8x31) -
with terminals for connecting a 3L+N+PE
cable.
7 ZUCCHINI
LB
LIGHTING BUSWAY
LIGHTING AND DISTRIBUTION LINES
Right end cover: Straight elements with Plugs with phase Wall bracket Ring clamp to hang lamps Snap clamp, to
completes the installa- one outlet every metre on selection device, or other line accessoires suspend the busbar
tion and one side only, supplied empty or with fuse. (boxes, loudspeaker, etc.) or accessories etc.
guarantees the IP55 with installed outlet (fluorescent lamps)
protection degree. covers.
LINE DETAILS
Plug with phase selection device Three-phase fused plug Single-phase plugs with 1, 3, 5 m cable
ZUCCHINI 8
LB
Shopping centres Offices Warehouses Hospitals
L I G H T I N G B U S WAY
Hook clamp to hang lamps Single-phase 10A plug Right end feed unit with
or other line accessoires with prewired cable and cable gland and terminals
(boxes, loudspeakers, etc.) colour based identification for 25 mm2 flexible cables.
system.
Hook, ring and snap STAINLESS STEEL Simple suspension bracket Bracket for element coupling Outlet cover (spare part).
clamps Already installed on
element outlets
9 ZUCCHINI
TRUNKING COMPONENTS
Painted and aluminium
versions on request C
Cl o
os p
eO
e nn
C
Cl o
os p
eO
e nn
STRAIGHT LENGTHS Type Code Length [m] Rating [A] Conductors outlets n. Weight kg
C
Cl o
os p
eO
e nn
L2
LB 254 70160101 3 25 4 3 3,100
L1 (N2)
LB 254 70160102 3 25 4 6• 3,100
LB 254 70160111 1,5 25 4 2 1,550
26
37 2
Cl o
os p
eO
eenn
6,5
310 Max cable
size 25 mm2
43
30 17 30
ZUCCHINI
10
TRUNKING COMPONENTS
LB
Painted and aluminium
versions on request
60
LB 254 70161002 0,600
LB 404 70181002 0,630
80
Complete with integral electrical
150 310 and mechanical joint block.
6,5
6,5
Max cable
size 25 mm2
195
150 880
80
250
9
Max cable size 35 mm2
11 ZUCCHINI
TRUNKING COMPONENTS - LB6
Painted and aluminium
versions on request C
Cl o
os p
eO
e nn
C
Cl o
STRAIGHT LENGTHS
os p
eO
e nn
C
Cl o
os p
eO
e nn
L2
L
L1
26
37 2
Cl o
os p
eO
eenn
6,5
6,5
Max cable Removable upper and lower
65
43
30 17 30
ZUCCHINI 12
TRUNKING COMPONENTS - LB6
LB
Painted and aluminium
version on request
107
6,5
Complete with integral
6,5 electrical and mechanical
65 Max cable joint block.
150 size 25 mm2
333
Removable upper and
lower covers facilitating
cable connection.
195
150 926
13 ZUCCHINI
PLUGS FOR ALL LB VERSIONS
SINGLE PHASE PLUGS WITH CABLE LB Type Code Rating [A] Fuseholder Phase Cable length Cable type Colour
2 conductors side
=> • 70265001 10 - L1-N 1m FROR orange
• 70265101 10 - L1-N 3m FROR orange
• 70265111 10 - L1-N 5m FROR orange
• 70265004 10 - L1-N 1m FG7 orange
LB 256
LB 406
ZUCCHINI 14
PLUGS FOR ALL LB VERSIONS
LB
PLUGS LB Type Code Rating [A] Fuseholder Phase Cable length Cable type Colour
2 conductors side
=> • 70265002 16 Ø5x20 6,3A - - - orange
=> • 70265003 16 - - - - orange
• 70265102 16 - - 3m FROR orange
• 70265103 16 - - 5m FROR orange
CH8 FUSED 16A PLUGS - SINGLE PHASE Type LB Code Rating [A] Fuseholder Phase Cable length Cable type Colour
Max cable
size 2,5 mm2 (*) Fuses not included
135
CH8 FUSED 16A PLUGS - THREE-PHASE Type LB Code Rating [A] Fuseholder Phase Cable length Cable type Colour
4 conductors side
Ø3
• • 70105035 16 CH8 Ø8,5x31,5 (*) L1-L2-L3-N - - • grigio
Max cable
MAX 15 mm
243
(*) Fuses not included
53 8
For fuse characteristics
see page 146
15 ZUCCHINI
HANGERS
18
Ø 18
Suspension accessory to be
fixed on element edges.
41
Ø7
25
ZUCCHINI 16
HANGERS
LB
CEILING BRACKET HOLDER Type Code Weight k
67 50 73003312 0,136
Use it with code 71003001:
simple suspension hanger.
55
49 Ø 10
250
Ø 4,2
40
asola 8 x 25
Ø6 70105043 0,060
Bracket for running two
lines back to back.
Also for floor mounting
Ø8 applications.
55
Ø6
66 27 Cod. 71003008
17 ZUCCHINI
ACCESSORIES FOR CABLE CHANNELS
CABLE CHANNEL WITH COVER (PVC) Type Code Length [m] Weight kg
71000104 3 0,884
28 3000 28
28
28
30
28 71003007 0,006
30 In your Purchase Order add a
spacer for every metre of cable
2,4
28
channel.
20
27,6
30
20
1m
2 25 71003006 0,108
Suspension bracket for busbar
and cable channel.
Ø5
160
50
ZUCCHINI 18
LB
NOTES
19 ZUCCHINI
ZUCCHINI follows a policy of continuous
development, and therefore reserves the right
to supply products which may differ in detail
from those shown in this publication.
ZUCCHINI 20
HL
HL
H I G H L I G H T I N G INDEX
25 - 40A
GENERAL DATA 22
FIXING DEVICES 34
CHANNEL ACCESSORIES 36
21 ZUCCHINI
HL
TECHNICAL DESCRIPTION
HL (High Lighting) is part of the Zucchini Used for distributing power, suspending The HLd line is designed to be fully rated These enable the HL range to be supplied
range. It can be used for supplying power and powering light fittings. (25A+25A or 40A+40A) for both circuits with one (HLs) or two separate cables
to light fittings within manufacturing plants HL straight lengths include the following simultaneously without a derating factor; (HLd); the assembly is carried out with
and wherever it is necessary to hang very components: • tap-off outlets to accept plug-in units are a quick joint arrangement as with the
heavy accessories from a busbar. Zucchini • a “beam-type” section bar (HLs: located on the busbar with a spacing straight lengths.
HL is extremely fast and simple to install. 26x62mm; HLd: 40x70mm, thickness distance of 1 m (3 outlets every 3 m). The end feed units have connection
In addition, its flexibility in use can be 0.8 mm), made of hot-galvanised steel The outlets in the double versions (HLd ) terminals to accept 25 mm2 flexible
used during the planning stage and (Senzimir) which also serves as a are situated on both sides of the busbar cables. There is an anti-pull cable clamp
during installation. protective conductor due to its cross-section (3+3 outlets; inside the unit.
Its high mechanical strength, which is a and electrical continuity. • an electrical joint block for automatically The entrance point for the cables is located
main feature of the HL line, is the result of The straight lengths are also available in connecting live conductors. at the base of the end feed unit.
its particular “beam-type configuration”, the Aisi 304 stainless steel version; The connection between two straight
and also the use of sheet metal of • 2 – 4 – 6 or 8 conductors made of lengths is quick: with only one operation
increased thickness. HL is particularly rigid copper with purity no less than to make both the electrical and
suitable for installations in which the 99.9%. mechanical connection. An IP55 degree
bracket fixing centre is up to 6 m. The cross-section of the conductors is of protection is standard without using
HL, as all Zucchini products, is fully 3.14 mm2 for a 25A rating and 6.15 mm2 additional IP protection kits.
compliant with the CEI EN 60439-1 / 2 for a 40A rating ; the conductors are The continuity of the protective conductor
Harmonised Standards; specifically, the separated from each other by a (casing) is ensured by tightening the
rated current of the Zucchini busbar self-extinguishing plastic insulating sheath, special connection screw.
trunking system is always rated to the type V0 (according to UL94) and in The whole busbar is “fire retardant” in
average ambient temperature of 40°C compliance with the incandescent wire compliance with standard EN 60332-3.
(N.B.: the Standard requires 35°C), test as per EN 60695-2-1 (CEI 50.11).
thus offering the market suitably The straight lengths in the HLd version
oversized products. (double) are segregated over their entire
HL is available in two sizes: length by a sheet metal partition
- HLs single version for 2-4 conductors (thickness 0.8mm) which separates
- HLd double version for 2+2; 4+2; 4+4 the straight lengths into two sides,
conductors. hence making the two sections
totally independent.
With this segregation, the HLd busbar
can be used for supplying “normal”
and “emergency” loads.
ZUCCHINI 22
HL
END COVERS HANGERS TRUNKING COMPONENTS AND PLUG-IN UNITS
ADDITIONAL ELEMENTS
End covers ensure the IP55 degree of In order to fix the run to the structure of Depending on the different installation These are used for connecting and
protection at the end of the run. the building, directly or with a steel chain, requirements, Zucchini is able to offer supplying light fittings. They include
Two versions are available, depending on it is necessary to use a set of special different technical solutions: the following features:
the end feed used at the start of the run: components to achieve any type of a) flexible joint: used for changing • they can be operated when energized
• the right (RH) end feed unit requires suspension: direction or to avoid possible obstacles and when under load conditions;
the use of a right (RH) end cover . • simple bracket: when used with its along the busbar run. • the PE contact (protective conductor) is
• the left (LH) end feed unit requires bracket-holder , it enables the installation They have the same quick joint connection the first to make an electrical connection
a left (LH) end cover. of the busbar at a distance of about as the straight lengths. Similarly, they give when plugged into the outlet, and the last
25 cm below the ceiling a mechanical connection and an IP55 to disconnect when you unplugged;
• wall bracket: enables the fixing of the degree of protection with just one • all insulating plastic components are in
run directly onto the wall of a building, operation. compliance with the incandescent wire test
setting it at the required clearance to The continuity of the protective conductor, (EN 60695-2-1) and have a V1
enable the mounting of all the made from the casing of the element self-extinguishing degree (UL94);
necessary accessories; itself, is ensured by tightening the special • the standard degree of protection is
• snap clamp: the snap-on installation connection screw. IP55 without using additional IP
is extremely fast. b) cable channel with cover: this accessory protection kits;
This clamp can be used both for can be placed over the top of the busbar; • Some of the plugs are polarised in the
suspending the busbar from the ceiling it can used to distribute auxiliary circuits, HLd range, which means that the plug
and for hanging accessories such as if any, and it is integral with the busbar installed on one side of the busbar cannot
fluorescent lamps, tap-off boxes, using appropriate spacers and brackets be installed on the other side due to a
etc. on the busbar; which retain the cable-channel system. mechanical interlock on the outlet;
• snap clamp with ring or hook: the The channel is 3 m long. Its dimensions • the plug-in units are different for the 2,
ring or hook enables accessories to are 28x28 mm. 4 conductor HLs and 2+2, 4+2, 4+4
be mounted on the busbar. c) centre feed unit: feeds the busbar conductor HLd offer; these include:
The technical chart on page 139 shows trunking system from an intermediate a) 16A phase selection plug-in units,
the suspension centre distance according point along the run, hence reducing the pre-wired with 1m of 3x1.5mm2
to the maximum load distributed between voltage drop at the end of the line FROR cable;
two fixing points. and/or to simplify the installation b) 16A phase selection plug-in units,
when the power supply is near the with terminals for connecting a cable;
middle of the run. b) 16A phase selection plug-in units,
with a 5x20 cylindrical ceramic fuse and
terminals for connecting a L+N+PE cable;
d) 16A three-phase plug-in units, with
cylindrical fuseholder – CH8 type
(8x31) - with terminals for connecting a
3L+N+PE cable.
23 ZUCCHINI
HL
HIGH LIGHTING
LIGHTING AND DISTRIBUTION LINES
Right or left end cover: Straight elements with one Plugs with phase Ring clamp to hang lamps or Hook clamp to hang lamps
completes the outlet every metre on both selection device, other accessories (boxes, or other accessories (boxes,
installation of the line sides, supplied with installed empty or with fuse. loudspeakers, etc.). loudspeakers, etc.).
and guarantees the outlet covers.
IP55protection degree.
Snap clamp, to
suspend the busbar or
accessories
(fluorescent lamps).
LINE DETAILS
Plug with phase selection device Three-phase fused plug Ceiling bracket holder
ZUCCHINI 24
HL
Warehouses Car parks Factories Gymnasiums
HIGH LIGHTING
Single-phase 10A plugs with Wall bracket Right end feed unit with
pre-wired cable and colour cable gland and terminals
based identification system. for 25 mm2 flexible cables.
N - L1 = grey
N - L2 = orange
N - L3 = blue
for 3P+N circuits
and
N3 - L3 = blue
N2 - L2 = black
for two single-phase circuits.
Wall bracket Simple suspension bracket Hook, ring and snap STAINLESS STEEL Outlet cover (spare part).
clamps
25 ZUCCHINI
TRUNKING COMPONENTS - SINGLE HL
STRAIGHT LENGTHS Type Code Length [m] Rating [A] Conductors outlets n. Weight kg
N
HL 254 71020161 1,5 25 4 2 2,4
N
L3
HL 404 71040151 3 40 4 3 5,1
38
62
L2
L1 L1 HL 404 71040161 1,5 40 4 2 2,55
12
26
page 146.
d 1= MAX Ø 38
6,5
6,5
95
Max cable
345 size 25 mm2
36 39
ZUCCHINI 26
TRUNKING COMPONENTS - SINGLE HL
60
For cable glands see
HL
d 1= MAX Ø 38 page 146.
6,5
6,5
Complete with integral elec-
95
Max cable trical and mechanical joint
150 345 size 25 mm2 block
226
150 930
96
95
250
(*)
150 886
9
Max cable size 35 mm2
27 ZUCCHINI
PLUGS - SINGLE HL
PHASE SELECTION PLUG HL Type Code Rating [A] Fuseholder Phase Cable length Cable type Colour
252 254
402 404
67
Max cable
size 2,5 mm2 • 71015030 16 Ø5x20 L1-N - - blue
104
SINGLE PHASE PLUG WITH FUSEHOLDER HL Type Code Rating [A] Fuseholder Phase Cable length Cable type Colour
252 254
30
402 404
• • 71005068 16 CH8 Ø8,5x31,5 to be selected - - grey
MAX 15 mm
min 6,5 mm
AZZURRO
N N
GRIGIO
GRIGIO
L3
L2
L1 L1
THREEPHASE PLUG WITH FUSEHOLDER HL Type Code Rating [A] Fuseholder Phase Cable length Cable type Colour
252 254
50
402 404
• 71005035 16 CH8 Ø8,5x31,5 (*) L1-L2-L3-N - - grey
85
243
Ø3
Max cable
size 2,5 mm2
6,3A fuse
53 8
ZUCCHINI 28
NOTES
HL
29 ZUCCHINI
TRUNKING ACCESSORIES - DOUBLE HL
Painted and
STAINLESS STEEL
versions on request
STRAIGHT LENGTHS Type Code Length [m] Rating [A] Conductors outlets n. Weight kg
6,5
d 1= MAX Ø 35 6,5
Max cable
95
55 39
ZUCCHINI 30
TRUNKING COMPONENTS - DOUBLE HL
Painted and
STAINLESS STEEL
versions on request
HL
page 146.
120
55
6,5
d 1= MAX Ø 35 6,5 Complete with integral electrical
and mechanical joint block.
95 Max cable
size25 mm2 This feed unit has two different
cable entries, and completely
150 345 separate and independent
terminals.
226
150 930
250
(*)
150 886
9
Max cable size 35 mm2
31 ZUCCHINI
PLUGS - DOUBLE HL
PHASE SELECTION PLUG HL Type Code Rating [A] Fuseholder Phase Cable length Cable type Colour
SINGLE-PHASE PLUG WITH CH8 FUSEHOLDER HL Type Code Rating [A] Fuseholder Phase Cable length Cable type Colour
Ø3
• • 71505070 16 CH8 Ø8,5x31,5 L1-N 1m FROR grey
Max cable
64
THREEPHASE PLUG WITH FUSEHOLDER HL Type Code Rating [A] Fuseholder Phase Cable length Cable type Colour
243
Ø3
Max cable
size 2,5 mm2
53 8
ZUCCHINI 32
PLUGS COMPATIBLE FOR BUSBARS - DOUBLE HL
HL 2522
HL 4022
HL
blue outlets orange outlets
ORANGE
L1 L1
GREY
GREY
BLUE
N N
L2 L2
N N
HL 2542
HL 4042
N N L1
GREY
BLUE
GREY
L2
L3
L1 L1 N
HL 2544
HL 4044
L1 N
GREY
GREY
L2 L3
L3 L2
N L1
HL 2 x 4
BROWN
L1 Z
BLACK
BLUE
L3 L6
L4 L5
L2 X
33 ZUCCHINI
HANGERS
18
Ø 18
Ø7
25
ZUCCHINI 34
HANGERS
71003009 0,090
HL 252
HL
HL 402
13 x 6,5
HL 254
96
40
HL 404
55
77 25
HL 2522
HL 4022
13 x 6,5
HL 2544
96
40
HL 4044
HL 2542
55 HL 4042
77 25 HL 2 x 4
67 50 73003312 0,136
Use with code 71003001:
simple suspension hanger.
55
49 Ø 10
250
Ø 4,2
40
hole 8 x 25
compatibility: HL 252
96 55 HL 402
HL 254
HL 404
35 ZUCCHINI
ACCESSORIES FOR CABLE CHANNELS
CABLE CHANNEL WITH COVER (PVC) Type Code Length [m] Weight kg
28
30
28
20
27,6
30
36 20
1m
50
2 25
DOUBLE Type Code Weight kg
Ø5 71503006 0,108
compatibility: HL 2522
HL 4022
HL 2544
160
HL 4044
HL 2542
HL 4042
HL 2 x 4
50
Suspension bracket for busbar
and cable channel.
ZUCCHINI 36
NOTES
HL
37 ZUCCHINI
ZUCCHINI follows a policy of continuous
development, and therefore reserves the right
to supply products which may differ in detail
from those shown in this publication.
ZUCCHINI 38
S E R I E
40 - 63A
L U C E INDEX
SL
SL
GENERAL DATA 40
STRAIGHT LENGTHS 44
• END FEED UNITS
• END COVERS
• FLEXIBLE JOINTS
• OUTLET COVERS
• JOINT COVERS
FIXING DEVICES 47
CHANNEL ACCESSORIES 49
39 ZUCCHINI
SL
TECHNICAL DESCRIPTION
SL (Light Series) is part of the Zucchini Used for distributing power and for • tap-off outlets to accept plug-in units These enable the SL range to be supplied
range. It can be used for supplying power supplying low-powered loads. and/or tap-off boxes are located on the by a cable; the assembly is carried out
to three-phase and single-phase devices: SL straight elements include the following busbar with a spacing distance of 0.75 m with a quick joint arrangement as with
industrial refrigerators, lathes, handheld components: (4 outlets every 3 m). the straight lengths. The end feed units
tools, etc. The SL line has compact • a “beam-type” section casing The outlets have an IP40 degree of have connection terminals to accept
dimensions but it is extremely strong; it (26x62mm, thickness 0.8 mm), made of protection (IP55 with a plug outlet cover); 25 mm2 copper cables.
is the smallest line of the Low Power hot-galvanised steel (Senzimir) which also they open automatically when a box or There is an anti-pull cable clamp inside
range and has tap-off boxes which can serves as a protective conductor due to its plug is inserted and close immediately the unit.
house miniature circuit breakers (Btdin). cross-section and electrical continuity. when unplugged. The entrance point of the cables is located
Zucchini SL is extremely fast and simple • 4 copper conductors with purity no less 3-metre straight lengths are also available at the base of the end feed unit.
to install. In addition, its flexibility can than 99.9%. with 6 or 10 tap-off outlets; these
be appreciated during the planning stage The cross-section of the conductors is 9.5 versions, which are characterised by a high
and during installation. mm2 for a 40A rating and 12.3 mm2 for a density of tap-off points, are particularly
Its high mechanical strength, which is a 63A rating; the conductors are separated suited to raised floor applications or when
main feature of the SL line, is the result of from each other by a self-extinguishing distributing power when built into a
its particular “beam-type configuration”, plastic insulating sheath, type V0 machine;
and also the use of sheet metal of (according to UL94) and in compliance • an electrical junction block for
increased thickness. with the incandescent wire test as per automatically connecting live conductors.
This line is also suitable for installations in EN 60695-2-1 (CEI 50.11). The connection between two straight
which the bracket fixing centre distance is lengths is quick: with only one operation
up to 6 m. both the electrical and mechanical
SL, as all Zucchini products, is fully connections are made. At the same time
compliant with the CEI EN 60439-1 / 2 achieving an IP40 degree of protection.
Harmonised Standards; specifically, the Using an IP joint kit on the joint and a
rated current of the Zucchini busbar plug outlet cover for each outlet
trunking systems is always referred to the (plug-free) increases the degree of
average ambient temperature of 40°C protection to IP55
(N.B.: the Standard requires 35°C), thus The continuity of the protective conductor
offering the market suitably oversized (casing) is ensured by tightening the
products. special connection screw.
The whole busbar is “fire retardant” in
compliance with standard EN 60332-3.
ZUCCHINI 40
END COVERS HANGERS TRUNKING COMPONENTS AND PLUG-IN UNITS AND TAP-OFF
ADDITIONAL ELEMENTS BOXES
End covers ensure the IP55 degree of In order to fix the run to the structure of Depending on the different installation These are used for connecting and
protection at the end of the run. the building, directly or with a steel chain, requirements, Zucchini is able to offer supplying small single-phase and
SL
it is necessary to use a set of special different technical solutions: three-phase loads: they include the
components to achieve any type of a) flexible joint: used for changing following features:
suspension: direction or to avoid possible obstacles • they can be operated when energized
• simple bracket: when used with its along the busbar run. They have the and when under load conditions;
bracket-holder, it enables the installation same quick joint connection as the straight • the PE contact (protective conductor) is
of the busbar at a distance of about lengths. Similarly, they give a mechanical the first to make an electrical connection
25 cm below the ceiling ; connection and an IP40 degree of when plugged into the outlet, and the
• wall bracket: enables the fixing of the protection with just one operation last to disconnect when unplugged;
run directly onto the wall of a building, (IP55 when IP joint kits are added). • all insulating plastic components are in
setting it at the required clearance to The continuity of the protective conductor, compliance with the incandescent wire test
enable the mounting of all the necessary made from the casing of the element (EN 60695-2-1) and have a V1
accessories; itself, is ensured by tightening the self-extinguishing degree (UL94);
• snap clamp: the snap-on installation special connection screw. • the standard degree of protection is
is extremely fast. b) cable channel with cover: this accessory IP55 without using additional IP
This clamp can be used both for can be placed over the top of the busbar; protection kits;
suspending the busbar from the ceiling it can be used to distribute auxiliary a) 32A three-phase plug-in units with
and for hanging accessories such as circuits, if any, and it is integral with the 3L+N+PE terminals for 10 mm2 flexible
fluorescent lamps, tap-off boxes, busbar using appropriate spacers and cables;
etc. on the busbar; brackets which retain the cable-channel b) 32A three-phase plug-in units with
• snap clamp with ring or hook: the ring system. The channel is 3 m long. cylindrical fuseholder – CH10 type
or hook enables accessories to be Its dimensions are 28x28 mm. (10.3x38) and 3L+N+PE terminals
mounted onto the busbar. for 10 mm2 flexible cables;
The technical chart on page 140 shows • tap-off boxes are different from plug-in
the suspension centre distance according units as they can be fitted with miniature
to the maximum load distributed between circuit breakers (e.g. Btdin):
two fixing points. c) 32A empty tap-off box with an
isolating system integral with the cover.
When the box is installed on the busbar,
the opening of the cover electrically
disconnects its internal parts, in other
words no accessible metallic part is
energized when the cover is open.
d) 32A tap-off box with a 4 DIN module
hinged door: the hinged door makes
it possible to operate the
protection/operating devices placed
inside the box without opening the cover
(without disconnecting the load).
41 ZUCCHINI
SL
SERIE LUCE
LIGHTING AND DISTRIBUTION LINES
Unified end cover: it 32A tap-off box with Ring clamp for Snap clamp
completes the run and transparent cover and lamps or to hang
guarantees the degree door for 4 DIN modular the busbar
of protection of the run. switches/mcb. by a chain.
LINE DETAILS
ZUCCHINI 42
Shopping centres Small-sized industries
SL
SERIE LUCE
Hook clamp for lamps Three-phase 32A Straight lengths with one Right or left end feed
plugs, available with outlet every metre on one unit depending on line
3xCH fuseholder. side only, and already direction. Supplied
fitted outlet covers. with cable gland and
On request lengths with terminals for 25mm2
6 outlets every 500 mm flexible cables.
are also available.
Wall bracket Hook, ring and snap STAINLESS STEEL Simple suspension bracket Outlet cover (spare part).
clamps
43 ZUCCHINI
TRUNKING COMPONENTS
STRAIGHT LENGTHS Type Code Length [m] Rating [A] outlets n. Weight kg
L2
L3
12
26
150 3000
35 42
IP 55 70601061 0,750
For cable glands see page 146
95
6,5
Max cable
60
size 25 mm2
d 1= MAX Ø 38
IP 55 70601062 0,826
For cable glands see page 146
95
6,5
Max cable
60
size 25 mm2
d 1= MAX Ø 38
ZUCCHINI 44
TRUNKING COMPONENTS
SL
FLEXIBLE JOINT Type Code Weight kg
70601261 1,900
95
150 880
60
71002051 0,474
It guarantees the IP55 degree
of protection on the joint.
97
56 240
45 ZUCCHINI
TAP-OFF UNITS
32A PLUGS Type Code Rating [A] Fuse L= [mm] Weight [kg]
IP 55 70605051 32 - 80 0,070
IP 55 70605052 32 CH 10,3x38 • 105 0,100
35
5,5
5,5
Max cable (•)Fuses not included
size 10 mm2
60
For cable glands see page 146 IP 55 70605054 Grey cover 0,700
IP 55 70605055 Transparent cover 0,700
136
5,5
5,5
Max cable
115
size 10 mm2
d 1= MAX Ø 48 265
5,5
Max cablr
size 10 mm2
115
d 1= MAX Ø 48 265
ZUCCHINI 46
HANGERS
18
SL
SUSPENSION HOOK (MAX 15 kg) Type Code Weight kg
Ø 18
Ø7
25
47 ZUCCHINI
HANGERS
71003009 0,090
13 x 6,5
96
40
55
77 25
71003018 0,090
Suitable to fix elements on
the floor in flatwise position.
46
96 55
ZUCCHINI 48
ACCESSORIES FOR CABLE CHANNELS
50
SL
CABLE CHANNEL WITH COVER (PVC) Type Code Length [m] Weight kg
28
30
28
20
27,6
30
36 20
1m
49 ZUCCHINI
ZUCCHINI follows a policy of continuous
development, and therefore reserves the right
to supply products which may differ in detail
from those shown in this publication.
ZUCCHINI 50
M I N I S B A R R A INDEX
63 - 100 - 160A
MS
GENERAL DATA 52
STRAIGHT ELEMENTS 56
MS
TRUNKING COMPONENTS 56
PLUG-IN UNITS 59
END COVERS 61
OUTLET COVERS 61
SUSPENSION HANGERS 61
51 ZUCCHINI
MS
TECHNICAL DESCRIPTION
The MS (Mini Busbar) range is used Used for distributing power and for • tap-off outlets to accept tap-off boxes These enable the MS range to be supplied
for distributing low-medium power. supplying low-medium power loads. are located on the busbar with a spacing by cable ; the assembly is carried out with
The MS line has compact dimensions MS straight lengths include the following distance of 1 m (3+3 outlets every 3m). a quick connection device as with the
but it is extremely strong; it is the smallest components: The outlets are normally closed but open straight lengths.
line of the Medium Power range. • two “omega-shaped”, ribbed, automatically by inserting a tap-of box The end feed units have connection
The space inside the tap-off boxes is sealed section casing and reclose when the tap-off is removed. terminals to accept up to 35 mm2
enough to contain up to 16 DIN modules (39x97mm, thickness 0.8 mm), made • an electrical junction block for copper cables for a 63/100A supply and
(e.g. Btdin switches). of hot-galvanised steel (Senzimir) which automatically connecting live conductors 70 mm2 for a 160A supply.
Zucchini MS is extremely fast and simple also serve as a protective conductor due and the PE. The block is made of 4 The entrance point of the cables is located
to install. In addition, its flexibility can be to its good cross-section and electrical silver-plated copper contacts with at the base of the end feed unit.
appreciated during the planning stage and continuity. independent springs which make up the The MS range has centre feed units and
during installation, thus meeting the • 4 conductors with the same section live conductor series. The continuity of the end feed boxes with a switch; this solution
requirements when frequently changing 3L+N. protective conductor (casing) is completed makes it possible to disconnect the whole
the arrangement of the loads within a The conductors are made from an when the screws on the casing are run to carry out maintenance operations
small company or laboratory. aluminium alloy, copper plated with a tightened near the joint. or modifications to the layout.
MS, as all Zucchini products, is fully final coat of tin for the 63A rating A silver-plated contact, integral with the
compliant with the CEI EN 60439-1 / 2 whereas for the 100A and 160A ratings, electrical junction block, sets up and
Harmonised Standards;specifically, the the conductors are made ensures the continuity of the PE conductor.
rated current of the Zucchini busbar of electrolytic copper with purity no The connection between two straight
trunking system is always referred to the less than 99.9%. lengths is quick: with only one operation
average ambient temperature of 40°C The cross-section of the conductors is 26 both the electrical and mechanical
(N.B.: the Standard requires 35°C), thus mm2 (Al) for a 63A rating, 26 mm2 (Cu) connections are made. At the same time,
offering the market suitably oversized for a 100A rating and 39 mm2 (Cu) for a achievins an IP40 degree of protection.
products. 160A rating; the conductors are spaced Using a cover on the joint and a plug
with plastic insulators reinforced with 20% outlet cover for each outlet (tap-off free)
glass fibre. increases the degree of protection to IP55.
The insulators have a V1 self-extinguishing The whole busbar is “fire retardant” in
degree (as per UL94) and are in compliance with standard EN 60332-3.
compliance with the incandescent wire
test as per EN 60695-2-1 (CEI 50.11).
The electrical insulation between the
conductors and the casing is ensured
by suitable air distances maintained by
the insulators.
ZUCCHINI 52
END COVERS TRUNKING COMPONENTS AND TAP-OFF BOXES
ADDITIONAL ELEMENTS
An end cover ensures the IP55 degree of Depending on different installation These are used for connecting and Different versions are available:
protection at the end of the run. requirements, Zucchini offers different supplying single-phase and three-phase - empty box (with a terminal block for
technical solutions: loads up to 63A: they include the connecting the cables), with internal DIN
a) 90° angles: available for changing following features: guide and transparent hinged door to see
routes both horizontally and vertically. • the PE contact (protective conductor) is and operate the protection devices that
The joint is of the quick type as with the the first to make an electrical connection can be installed inside the box.
straight lengths. The degree of protection when the tap-off is plugged into the outlet, - with cylindrical fuseholder – CH10 type
is IP55. and the last to disconnect when the tap-off (10.3x38)
b) T and X elements: available for making is unplugged; - with cylindrical fuseholder – DIAZED
HANGERS elbows . The degree of protection is IP55. • all insulating plastic components comply (D01: 16A; D02: 32A)
MS
c) flexible angle: this element is available with the incandescent wire test (EN - 16A tap-off box up to 63A with a switch
for 63-100A ratings and makes possible 60695-2-1) and have a V1 self-extinguis- device integral with the cover.
directional changes with different angles. hing degree (UL94); When the box is installed on the busbar,
In order to fix the line to the structure
The protection degree is IP55. - the standard degree of protection is IP55 the opening of the cover electrically
of the building, directly or with a wall
d) Straight lengths with fire barrier without using additional IP protection kits; disconnects its internal parts, ensuring no
bracket, it is necessary to use a bracket
(internal+external). a) up to a rating of 32A, they can be accessible metallic part is energized when
which serves as a busbar collar.
These elements are used when fire-resistant operated when energized and when under the cover is open. Tap-off boxes with an
The bracket has holes so it can be easily
walls need to be passed through. load conditions; isolator have an interlock with the cover
used with the brackets available in the
The elements fitted with a fire barrier have These boxes are available in a wide range and can be inserted and removed only
Zucchini catalogue.
been lab-tested (in accordance with DIN of versions, all characterized by "total when the cover is open, namely with the
4102-9 and EN 1366-3) in order to isolation": no metallic part accessible isolating device in the“open” position.
confirm that, if correctly installed, they from the outside is connected directly with Different versions are available:
will maintain the essential fire resistant the inside of the box, hence no accessible - 16A with cylindrical fuseholder – CH10
features of the wall . metallic part can be energized, not (10.3x38)
e) straight lengths with thrust unit: even accidentally. - 50A with cylindrical fuseholder – CH14
when the busbar is installed vertically (14x51)
(rising mains), these elements are provided - 63A – empty for various applications
with a device which blocks the conductors - 63A with door – 4 DIN mod.
from slipping when supporting the weight - 63A with door – 7 DIN mod.
of the riser . - 63A with door – 16 DIN mod.
This type of element is required for vertical
installations (risers) every 10 m (approx.)
of the riser.
53 ZUCCHINI
MS
MINI SBARRA
BUSBAR TRUNKING SYSTEM
FOR LOW AND MEDIUM POWER
LINE DETAILS
ZUCCHINI 54
Laboratories Small and middle-sized industries Shopping centres
MS
MINI SBARRA
Tap-off box with terminals for cables Joint cover. It guarantees the End feed unit
up to 25mm2. Made from IP55 degree of protection at
self-extinguishing plastic material, it the joint.
has a good mechanical resistance
and withstands tracking well.
Plug-in tap-off boxes can be plugged
in and pulled out under load.
Ratings from 16A to 32A.
Tap-off boxes Gasket and joint cover IP55 IP55 outlet cover
55 ZUCCHINI
TRUNKING COMPONENTS
L2
18
3000
865 1000 1000 135 230
135 Right and left elbows differ MS63 51530351 IP55 1,600
365
because of the position of MS100 51500361 IP55 1,600
8
junction blocks. MS160 51520351 IP55 2,600
N
365
8
ZUCCHINI 56
TRUNKING COMPONENTS
135
N
365
MS
8
N
365
57 ZUCCHINI
TRUNKING COMPONENTS
END FEED UNIT IP55 MS63 - MS100 Type Code MS 63 MS 100 MS160 Weight kg
165 273 8
d 1= MAX Ø 55
Right 51511051 • • 1,732
Left 51511052 • • 1,874
10
125
10
SX DX Max cable
size 35 mm2
85
SX DX 16
Max cable
size 70 mm2
118
10
10
Max cable
size 35 mm2
DX SX
With in-line bus switches
on request.
CENTRE FEED UNIT MS63 - MS100 Type Code MS 63 MS 100 MS160 Weight kg
10
Max cable
n°2 d 1= MAX Ø 55 size 35 mm2
100
16
Max cable
n°2 d 1= MAX Ø 63 size 70 mm2
120
10
10
Max cable
size 35 mm2
ZUCCHINI 58
TAP-OFF BOXES WITH COMPLETE INSULATION
150
EMPTY TAP-OFF BOX WITH DIN 4MW
32A 51515071 0,680
6,5
d1 MAX = 38
160
6,5
TAP-OFF BOX WITH CH10 FUSEHOLDER (10,3X38)
Max cable 32A 51515076 0,680
size 25 mm2
MS
TAP-OFF BOX FOR 4 MODULES DIN
32A 51515072 0,730
Energy withstand
400.103 A2s
250
6,5
6,5
Max cable
size 25 mm2
97
Energy withstand
400.103 A2s
59 ZUCCHINI
TAP-OFF BOXES WITH ISOLATING DEVICE ON THE COVER
160
5,5
d 1= MAX Ø 29 16A 51515051 0,908
5,5
Max cable
145
size 10 mm2
• 10,3 x 38 fuses not included
d 1= MAX Ø 29
221,5
10
Max cable
117
d 1= MAX Ø 38
10
Energy withstand
400.103 A2S
TAP-OFF BOX WITH HINGED DOOR (UP TO 16 MODULES DIN) Type Code Weight kg
78
10
For cable glands see page 146
Max cable
487 size 35 mm2
511
ZUCCHINI 60
ACCESSORIES
MS
All 51500151 0,050
One set for each joint
Hole 7x11
131
64
Hole 7x11
68 20
Ø7
61 ZUCCHINI
ZUCCHINI follows a policy of continuous
development, and therefore reserves the right
to supply products which may differ in detail
from those shown in this publication.
ZUCCHINI 62
M E D I U M R AT I N G I N D E X
160 - 1000A
MR
GENERAL DATA 64
BENEFITS 68
ILLUSTRATED INDEX 70
STRAIGHT LENGTHS 72
TRUNKING COMPONENTS 76
MR
FEED UNITS 82
RATING REDUCERS 85
TAP-OFF BOXES 86
FIXING DEVICES 94
SB/MR ADAPTERS 98
RISING MAINS 97
63 ZUCCHINI
MR
TECHNICAL DESCRIPTION
MR (Medium Rating) is part of the Used for distributing power and for • a series of tap-off outlets to accept These enable the MR range to be supplied
Zucchini range used for the distribution supplying medium powered loads. plug-in tap-off boxes; the outlets are by cable or directly connected to an
of power in medium – large installations; MR straight lengths include the following located on the busbar with a spacing electrical distribution panel; the assembly
it is also particularly suitable in rising components: distance of 1 m on both sides of the of the line is carried out with a quick
main applications (trunking systems) • casing made from two busbar (3+3 outlets every 3m). monobloc connection as with the
within buildings used for the service sector “omega-shaped”, ribbed, sealed section The outlets are normally closed but open straight lengths.
(banks, insurance, commercial cases (75-135x196 mm, thickness automatically by inserting a tap-of box The 160 and 250A end feed units have
headquarters, etc.). The MR range is 0.8 mm), made of hot-galvanised steel and reclose when the tap-off is terminals to accept cables up to 150
available in sizes ranging from 160A to (Senzimir) which also serves as a unplugged. mm2; for higher ratings, the cable
800A with conductors made from an protective conductor due to its • an electrical junction "monobloc" system connection to the end feed units requires
aluminium alloy and from 250A to 1000A cross-section and electrical continuity; if for fast and reliable connection of the live terminals which need extensions
with copper conductors. required, the line can be provided with a conductors and PE. (11 mm hole).
MR has a wide range of tap-off boxes special earthing conductor whose section The “monobloc” is made from a system The cable entry is generally located at the
which are rated from 16A to 1000A, thus and material can be the same as the of copper plates which make up the live base of the end feed unit, in which there
allowing the supply and protection of all phases (MRfull) and/or with a conductor series. is a removable plate; it is also possible to
kinds of loads using different protection hot-galvanized and painted casing The “monobloc” has a shearhead bolt: insert the cables from side plates.
devices such as fuses, miniature circuit (RAL to be determined by the customer). use a 13mm-wrench to tighten the The MR range also has centre feed units
breakers and/or moulded case circuit • 4 conductors with the same section external head until the collar which and switched end feed boxes; the latter
breakers. 3L+N with PE made from the casing connects the two heads breaks; this will allows disconnection of the whole
Zucchini MR can be installed quickly. (5 conductors in case of MRfull: 3L+N+PE). ensure the correct nominal torque to line to carry out maintenance operations
It is easy to manage and suitable for The conductors are made from an aluminum guarantee optimum electrical continuity or modifications to the installation.
modifications and extensions, which is alloy, copper plated with a final coat of tin. over time. The protective conductor
always necessary for installations Alternatively, the MR range is available with (PE=casing) is also connected through
were MR is used. copper conductors with purity no less than the monobloc.
MR, as all Zucchini products, is fully 99.9% (electrolytic copper). In order to simplify storage and speed
compliant with the CEI EN 60439-1 / 2 The conductors are spaced with plastic up the installation of the line, straight
Harmonised Standards; specifically, the insulators reinforced with 20% glass fibre; lengths, trunking components and all
rated current of the Zucchini busbar They have a V1 self-extinguishing degree components of the MR line are already
trunking systems is always rated at the (as per UL94) and are in compliance with provided with a monobloc pre-installed at
average ambient temperature of 40°C the incandescent wire test as per EN the factory at one end and with IP
(the Standard requires 35°C), thus 60695-2-1 (CEI 50.11). The electrical covers fitted at the other end.
offering the market suitably oversized insulation between the conductors and The mechanical joint is completed by
products. the casing is ensured by air distances fitting the two IP covers; t with the use of
maintained by the insulators. an interlock the monobloc double-headed
nut, they cannot be installed before
properly tightening the electrical joint.
The IP covers are provided with anti-aging
gaskets which guarantee an IP55 degree
of protection.
All components and accessories of the MR
range are IP55 as standard; therefore,
the degree of protection of the line
depends only on whether or not plug
outlet covers are fitted to the tap-off
outlets: with plug outlet covers installed,
the line is always IP55; without plug
outlet covers and with an “upright” or
vertical (riser) line installed, there will be
an IP52 degree of protection.
With a “plane” line installed, without
outlet covers the degree of protection is
IP40 (“plane” installation means with
outlets facing up).
The whole busbar is “fire retardant” in
compliance with standard EN 60332-3.
ZUCCHINI 64
END COVERS TRUNKING COMPONENTS AND TAP-OFF BOXES
ADDITIONAL ELEMENTS
End covers ensure the IP55 degree of Depending on the different installation Used for supplying three-phase loads All insulating plastic components
protection at the end of the run. requirements, Zucchini is able to offer from 32A up to 1000A; they can be comply with the incandescent wire test
different technical solutions: divided into two main categories: (EN 60695-2-1) and have a V2
a) 90° angles: available for changing 1) Plug-in-type tap-off boxes (from 32A up self-extinguishing degree (UL94);
routes both horizontally and vertically. to 630A): they can be operated when the standard degree of protection is IP55
They have the same quick joint connection energized and when under load conditions without using additional IP protection kits;
as the straight lengths. up to a rating of 32A; for ratings from Plug-in type boxes are available in the
The protection degree is IP55. 63A to 630A, the boxes are equipped following versions: with fuseholder, with
HANGERS
b) T, X and double angle Z elements. with an isolating device integral with the miniature circuit breakers, with CEE
The degree of protection is IP55. cover. When the tap-off box is installed sockets, schuko, with switchfuse or
c) Straight lengths with fire barrier on the busbar, the opening of the cover with moulded case circuit breakers.
In order to fix the run to the structure of (internal+external) S120. electrically disconnects its internal parts, 2) Boxes bolted on the junction
the building, directly or with a wall, ceiling These elements are used when REI120 no accessible metallic part is live when (from 630A to 1000A): these high rated
or beam bracket, it is necessary to use a fire-resistant walls need to be passed the cover is open. current boxes are rigidly connected to
bracket which serves as a busbar collar. through. Tap-off boxes have an interlock with a the busbar with a special “monobloc”
The bracket has holes for use with the The elements fitted with a fire barrier have cover and can be inserted and removed connection system similar to that of the
support brackets available in the Zucchini been lab-tested (in accordance with DIN from the outlet only when the cover is straight lengths but this also allows for
MR
catalogue. 4102-9 and EN 1366-3) in order to in the “open” position, that is in the the power to be tapped-off.
confirm that, if correctly installed, they “isolated” position. The boxes can only be installed and
will maintain the essential fire resistant The cover of the box can be locked in removed when the system is
features of the wall. S120 means that the open-isolated position to allow safe de-energized (isolated busbar).
the barrier is certified for 120’ (minutes). maintenance of the loads connected to it. When the monobloc system is used,
d) Straight lengths with 5 outlets on All Zucchini plug-in type boxes have a PE installation is extremely easy,
one side are ideal for achieving rising contact (protective conductor), which is quick and reliable.
mains or sections with high density the first to make an electrical connection These tap-off boxes are available in the
of tap-off points. when plugged into the outlet, and the switchfuse and fuseholder version and
e) Straight lengths without outlets are last to disconnect when the tap-off is with moulded case circuit breakers.
available for feeder only applications. unplugged;
The MR range has more advantages when
used in vertical applications (rising mains)
because thrust units or thermal expansion
units are not required.
The monobloc joint used on the MR range
allows for the thermal expansions of the
conductors.
65 ZUCCHINI
MR
MEDIUM RATING
Joint cover Straight lengths with one Suspension hanger Tap-off box
outlet every metre on both
sides.
LINE DETAILS
Metal end feed unit Switchboard - transformer feed unit Horizontal elbow Vertical elbow
ZUCCHINI 66
Skyscrapers Factories
MR
M E D I U M R AT I N G
Tap-off box with terminals for Joint cover already End feed unit
cables up to 25mm2. Produced in installed on an
self-extinguishing plastic material, it element.
has a good mechanical resistance
and withstands tracking well.
Plug-in tap-off boxes can be plug-
ged in and pulled out under volta-
ge. Ratings from 16A to 32A.
Plug-in boxes Plug-in boxes with isolating device End cover Plug-outlet cover (spare part)
67 ZUCCHINI
BENEFITS
DYNAMOMETRIC MONOBLOC
Tighten the “dynamometric” bolt on the monobloc until the head
breaks to electrically connect the elements. Breaking the head of
the bolt guarantees long-term reliability and safety.
COVER PLATE
If the monobloc has not been tightened correctly, the head of the
dynamometric bolt will prevent the mechanical coupling from clo-
sing. The joint covers and the gaskets protect the element during
handling, and once installed, they guarantee mechanical rigidity
and the degree of protection.
“IP” PROTECTION
The MR busbar on edgewise position has a standard IP52 degree
of protection.
By simply adding covers to the tap-off outlets the degree of
protection of the run becomes IP55.
ZUCCHINI 68
BENEFITS
TYPES
The MR symbol indicates a busbar with 4 conductors with an
equal cross section (3L+N), and the casing acts as the protective
earth conductor (PE); the MRf (full) busbar has
5 conductors with an equal cross section (3L+N+PE). The MR and
MRf busbars are available with a galvanised sheet steel casing
and a version with a painted finish (RAL to be defined).
MR
even in considerably long systems. If the MR line is installed ver-
tically (rising main) there is no need to install a busbar thrust unit
because the new monobloc prevents the conductors from sliding.
MAXIMUM STRANGTH
The MR busbar has been designed and manufactured for heavy
industrial environments. The degree of impact-resistance of the
casing which houses the MR bus-line is the maximum stated in IEC
EN 60068-2-62: IK10.
69 ZUCCHINI
LINE ROUTE
75
92
76 76
81
63÷160A plug-in box
86
73 94
80
94
86 72 85
94
72 74 76
Straight length with internal S120 fire barrier
Suspension bracket
ZUCCHINI 70
Straight length with
5 outles
MR
End cover
“Cross” element
71 ZUCCHINI
TRUNKING COMPONENTS
STRAIGHT LENGTH 3 METRES WITH 3+3 OUTLES Rating [A] Length [mm] outlets n. Code Weight kg Code Weight kg
Aluminium Copper
75 135 Straight length with outlets 160 3000 3+3 5040 01 01 19,9 - -
in fixed position.
250 3000 3+3 5040 01 02 20,9 5540 01 02 25,7
L 315 3000 3+3 5040 01 03 22,8 5540 01 03 28,1
(PE)*
400 3000 3+3 5040 01 04 33,8 5540 01 04 36,9
162
196
162
L2
196
375
1000
1000
IP55
625
STRAIGHT LENGTH 3 METRES WITHOUT OUTLETS Rating [A] Length [mm] outlets n. Code Weight kg Code Weight kg
Aluminium Copper
Feeder element.
160 3000 0 5040 02 41 19,9
205
196
ZUCCHINI 72
Conductors Case Code
TRUNKING COMPONENTS Codes table
MR 4 Galvanized ---0----
MRf 5 Galvanized ---1----
MR-P 4 Painted ---2----
MRf-P 5 Painted ---3----
STRAIGHT LENGTH FROM 1501 TO 2999 MM WITH 2+2 OUTLETS Rating [A] Length [mm] outlets n. Code Weight kg Code Weight kg
Aluminium Copper
160 1501÷2999 2+2 5040 01 51 13,6
250 1501÷2999 2+2 5040 01 52 14,1 5540 01 52 16,5
375
315 1501÷2999 2+2 5040 01 53 14,9 5540 01 53 17,7
400 1501÷2999 2+2 5040 01 54 23,3 5540 01 54 22,0
500 1501÷2999 2+2 5040 01 58 25,2
Straight length with outlets
630 1501÷2999 2+2 5040 01 55 26,9 5540 01 55 34,3
in fixed position.
800 1501÷2999 2+2 5040 01 56 28,0 5540 01 56 42,2
625
1000 1501÷2999 2+2 5540 01 57 47,8
STRAIGHT LENGTH FROM 1501 TO 2999 MM WITHOUT OUTLETS Rating [A] Length [mm] outlets n. Code Weight kg Code Weight kg
Aluminium Copper
Feeder element. 160 1501÷2999 0 5040 01 21 13,6
205
196
MR
(see bolt-on tap-off boxes).
400 1501÷2999 0 5040 01 24 23,3 5540 01 24 22,0
75
90
135
73 ZUCCHINI
TRUNKING COMPONENTS
STRAIGHT LENGTHS FROM 600 TO 1500 MM WITH 1+1 OUTLET Rating[ ]A Length [mm] outlets n. Code Weight kg Code Weight kg
Aluminium Copper
Straight length with outlets 160 1000 ÷1500 1+1 5040 01 41 13,6
in fixed position.
250 1000 ÷1500 1+1 5040 01 42 14,1 5540 01 42 16,5
315 1000 ÷1500 1+1 5040 01 43 14,9 5540 01 43 17,7
375
400 1000 ÷1500 1+1 5040 01 44 23,3 5540 01 44 22,0
625 500 1000 ÷1500 1+1 5040 01 48 25,2
630 1000 ÷1500 1+1 5040 01 45 26,9 5540 01 45 34,3
800 1000 ÷1500 1+1 5040 01 46 28,0 5540 01 46 42,2
1000 1000 ÷1500 1+1 5540 01 47 47,8
In your Purchase Order please
specify the required length
(see page 96: How to measure
special elements)
STRAIGHT LENGTHS FROM 600 TO 1500 MM WITHOUT OUTLET Rating [A] Length [mm] outlets n. Code Weight kg Code Weight kg
Aluminium Copper
Feeder element.
205
75
135
ZUCCHINI 74
Conductors Case Code
TRUNKING COMPONENTS Codes table
MR 4 Galvanized ---0----
MRf 5 Galvanized ---1----
MR-P 4 Painted ---2----
MRf-P 5 Painted ---3----
STRAIGHT LENGTHS 3 METRES WITH 5 OUTLETS ONLY ON ONE SIDE Rating [A] Length [mm] outlets n. Code Weight kg Code Weight kg
Aluminium Copper
3 metres straight length with 160 3000 5+0 5040 02 51 19,9
5 outlets on one side only, sui-
table for rising mains (see 250 3000 5+0 5040 02 52 20,9 5540 02 52 25,7
page 97) 315 3000 5+0 5040 02 53 22,8 5540 02 53 28,1
400 3000 5+0 5040 02 54 33,8 5540 02 54 36,9
500 3000 5+0 5040 02 58 37,5
630 3000 5+0 5040 02 55 41,7 5540 02 55 56,0
800 3000 5+0 5040 02 56 44,3 5540 02 56 72,1
1000 3000 5+0 5540 02 57 83,7
375
500
500
500
500
625
MR
STRAIGHT LENGTHS WITH S120 FIRE BARRIER Rating [A] Length [mm] outlets n. Code Weight kg Code Weight kg
Aluminium Copper
160 600÷1500 0 5040 02 11 13,6
250 600÷1500 0 5040 02 12 14,1 5540 02 12 16,5
244
244
Please specify barrier position 315 600÷1500 0 5040 02 13 14,9 5540 02 13 17,7
(A= …mm) in your Purchase 400 600÷1500 0 5040 02 14 23,3 5540 02 14 22,0
158 244
Orders.
500 600÷1500 0 5040 02 18 25,2
160 - 315A Al 400 - 800A Al 630 600÷1500 0 5040 02 15 26,9 5540 02 15 34,3
250 - 400A Cu 630 - 1000A Cu
In your Purchase Order plea- 800 600÷1500 0 5040 02 16 28,0 5540 02 16 42,2
se specify the required posi- 1000 600÷1500 0 5540 02 17 47,8
tion of the internal fire bar-
rier. Measure as illustrated.
The internal fire barrier is
630mm long. L < 1,5 m - - - - - - 6 - L < 1,5 m - - - - - - 6 -
L ≥ 1,5 m - - - - - - 7 - L ≥ 1,5 m - - - - - - 7 -
200
630
00
A≥2
75 ZUCCHINI
TRUNKING COMPONENTS - ELBOWS
HORIZONTAL ELBOW (300 + 300 MM) Rating [A] Code Weight kg Code Weight kg
VERTICAL ELBOW (300 + 300 MM) Rating [A] Code Weight kg Code Weight kg
300
Aluminium Copper
Right (RH) 160 5040 04 01 8,1
250 5040 04 02 8,2 5540 04 02 9,2
315 5040 04 03 8,4 5540 04 03 9,6
300
ZUCCHINI 76
Conductors Case Code
TRUNKING COMPONENTS - ELBOWS Codes table
MR 4 Galvanized ---0----
MRf 5 Galvanized ---1----
MR-P 4 Painted ---2----
MRf-P 5 Painted ---3----
A Aluminium Copper
Right (RH) 160 5040 03 21
250 5040 03 22 5540 03 22
315 5040 03 23 5540 03 23
B
MR
In your Purchase Order please
specify the required length
(see page 96: How to measure
special elements)
A Aluminium Copper
Right (RH) 160 5040 04 21
250 5040 04 22 5540 04 22
315 5040 04 23 5540 04 23
B
77 ZUCCHINI
TRUNKING COMPONENTS - ELBOWS
DOUBLE HORIZONTAL ELBOW (300 + 300 + 300 MM) Rating [A] Code Weight kg Code Weight kg
300 (A) 300 (C) Aluminium Copper
Right + Left 160 5040 03 41 10,29
250 5040 03 42 10,55 5540 03 42 12,23
300 (B)
315 5040 03 43 11,06 5540 03 43 12,97
400 5040 03 44 18,37 5540 03 44 15,72
500 5040 03 48 19,50
630 5040 03 45 20,55 5540 03 45 25,77
800 5040 03 46 21,20 5540 03 46 30,88
1000 5540 03 47 34,55
Dimensions [ mm]
* min MAX Special element - - - - - - 6 *- ---- -- 6 *
-
250 ≤ A, B,C ≤ 900
DOUBLE VERTICAL ELBOW (300 + 300 + 300 MM) Rating [A] Code Weight kg Code Weight kg
* Dimensions - - - - - - 6 *- ---- -- 6 *
[ mm]
Special element -
min MAX
300 ≤ A, B,C ≤ 900
ZUCCHINI 78
Conductors Case Code
TRUNKING COMPONENTS - ELBOWS Codes table
MR 4 Galvanized ---0----
MRf 5 Galvanized ---1----
MR-P 4 Painted ---2----
MRf-P 5 Painted ---3----
VERTICAL ELBOW + HORIZONTAL ELBOW (300+300+300 MM) Rating [A] Type 1 Type 2 Type 3 Type 4 Weight kg
---- -- 4 *
- - - - - - - 5 *- - - - - - - 6 *- - - - - - - 7 *-
* Special element
Rating [A] Type 1 Type 2 Type 3 Type 4 Weight kg
Copper
250 5540 05 02 5540 05 12 5540 05 22 5540 05 32 12,23
➊ RH + RH ➋ RH + LH 315 5540 05 03 5540 05 13 5540 05 23 5540 05 33 12,97
400 5540 05 04 5540 05 14 5540 05 24 5540 05 34 15,72
630 5540 05 05 5540 05 15 5540 05 25 5540 05 35 25,77
800 5540 05 06 5540 05 16 5540 05 26 5540 05 36 30,88
1000 5540 05 07 5540 05 17 5540 05 27 5540 05 37 34,55
MR
---- -- 4 *
- - - - - - - 5 *- - - - - - - 6 *- - - - - - - 7 *-
➌ LH + RH
➍ LH + LH
* Dimensions [ mm]
* Special element
min MAX
300 ≤ A, B,C ≤ 900
HORIZONTAL ELBOW + VERTICAL ELBOW (300+300+300 MM) Rating [A] Type 1 Type 2 Type 3 Type 4 Weight kg
---- -- 4 *
- - - - - - - 5 *- - - - - - - 6 *- - - - - - - 7 *-
Special element
*
Rating [A] Type 1 Type 2 Type 3 Type 4 Weight kg
Copper
250 5540 06 02 5540 06 12 5540 06 22 5540 06 32 12,23
315 5540 06 03 5540 06 13 5540 06 23 5540 06 33 12,97
➊ RH + RH
➋ RH + LH
400 5540 06 04 5540 06 14 5540 06 24 5540 06 34 15,72
630 5540 06 05 5540 06 15 5540 06 25 5540 06 35 25,77
800 5540 06 06 5540 06 16 5540 06 26 5540 06 36 30,88
1000 5540 06 07 5540 06 17 5540 06 27 5540 06 37 34,55
---- -- 4 *
- - - - - - - 5 *- - - - - - - 6 *- - - - - - - 7 *-
* Dimensions
min
[ mm]
MAX * Special element
➌ LH + RH
➍ LH + LH
300 ≤ A, B,C ≤ 900
79 ZUCCHINI
TRUNKING ACCESSORIES - TEES
HORIZONTAL “TEE” ELEMENTS (300 + 300 + 300 MM) Rating [A] RH 1 RH 2 LH 1 LH 2 Weight kg
---- -- 4 *
- - - - - - - 5 *- - - - - - - 6 *- - - - - - - 7 *-
SX
➊ SX
➋ * Special element
CROSS ELEMENT (300 + 300 + 300 + 300 MM) Rating [A] Code Weight kg Code Weight kg
ZUCCHINI 80
Conductors Case Code
FEED UNITS AND END COVER Codes table
MR 4 Galvanized ---0----
MRf 5 Galvanized ---1----
MR-P 4 Painted ---2----
MRf-P 5 Painted ---3----
100
250 5040 11 02 5,85 5540 11 02 6,10
240
cable
200 350 entry
350 200
Cable connection: max. sect.
(3x120mm2 + 1x70mm2)
MR
or 3x150mm2, max PG 48.
81 ZUCCHINI
FEED UNITS
METAL END FEED UNITS Rating [A] Code Weight kg Code Weight kg
Aluminium Copper
Right (RH) 160 5040 11 21 16,64
400
250 5040 11 22 16,76 5540 11 22 17,37
315 5040 11 23 17,03 5540 11 23 17,70
250 600
400 5040 11 24 18,32 5540 11 24 18,88
850 500 5040 11 28 20,00
630 5040 11 25 19,43 5540 11 25 21,17
40
290
800 5040 11 26 19,80 5540 11 26 23,30
1000 5540 11 27 24,83
During shipment the stump
is positioned in the box to
reduce its bulk.Take it out
and screw it in the position
illustrated here.
23,20
630 5040 11 35 23,63 5540 11 35 26,07
290
ZUCCHINI 82
Conductors Case Code
FEED UNITS Codes table
MR 4 Galvanized ---0----
MRf 5 Galvanized ---1----
MR-P 4 Painted ---2----
MRf-P 5 Painted ---3----
END FEED UNIT WITH AC23 SWITCH DISCONNECTOR Rating [A] Dimensions RH up RH down LH up LH down Weight kg
Aluminium
This feed unit allows 160 1 5040 34 01 5040 34 11 5040 34 21 5040 34 31 17,94
isolation of the line
B
for maintenance. 250 1 5040 34 02 5040 34 12 5040 34 22 5040 34 32 18,10
315 1 5040 34 03 5040 34 13 5040 34 23 5040 34 33 18,86
250 A
400 2 5040 34 04 5040 34 14 5040 34 24 5040 34 34 21,79
D 500 2 5040 34 08 5040 34 18 5040 34 28 5040 34 38 22,42
630 2 5040 34 05 5040 34 15 5040 34 25 5040 34 35 23,64
40
Dimensions [ mm]
1 2
A 550 1050
B 350 450
C 280 300
D 800 1300
Cable entry
dimensions [ mm]
1 2
RH up 180 x 270 210 x 380
MR
RH down
Rating [A] Dimensions RH up RH down LH up LH down Weight kg
Copper
250 1 5540 34 02 5540 34 12 5540 34 22 5540 34 32 19,12
315 1 5540 34 03 5540 34 13 5540 34 23 5540 34 33 19,40
400 2 5540 34 04 5540 34 14 5540 34 24 5540 34 34 20,34
630 2 5540 34 05 5540 34 15 5540 34 25 5540 34 35 26,88
LH up
800 2 5540 34 06 5540 34 16 5540 34 26 5540 34 36 28,67
1000 2 5540 34 07 5540 34 17 5540 34 27 5540 34 37 29,95
LH down
83 ZUCCHINI
FEED UNITS
400 600
Aluminium Copper
It feeds a trunking system
from whatever joint point 160 5040 12 01 17,27
between two lengths. 250 5040 12 02 17,13 5540 12 02
290
Base cable
entry dimensions
180 x 290
➊ ➋
280
75 75 75 75
Ø11 Ø11
20
20
50
30
90
Al Cu
MR 160A 250A
➊ 250A 315A
315A 400A
MR 400A 630A
➋ 500A
630A
800A
1000A
800A
ZUCCHINI 84
Conductors Case Code
IN-LINE BUS SWITCH AND REDUCER Codes table
MR 4 Galvanized ---0----
MRf 5 Galvanized ---1----
MR-P 4 Painted ---2----
MRf-P 5 Painted ---3----
(D)
Aluminium
This device allows 160 1 5040 17 01 5040 17 21 23,54
(A)
disconnection of part of a
line, while the other is live. 250 1 5040 17 02 5040 17 22 23,56
315 1 5040 17 03 5040 17 23 23,63
(B)
MR
Right
Left
(C)
Dimensions [ mm]
1 2
A 550 1050
B 350 450
C 280 300
D 1050 1550
Type
➊
Type ➋
85 ZUCCHINI
PLUG-IN BOX WITH COMPLETE INSULATION
195
1
1 32A DIN rail (8MW) 5041 40 61 1,60
216
2 32A
195
1 32A Transparent hinged door and DIN rail (8MW) 5041 40 64 1,70
350
2 32A Transparent hinged door and DIN rail (12MW) 5041 40 75 2,05
2
16A 3xD01 - Fuseholder, transparent hinged door 5041 41 62 2,60
Fuse not supplied
and DIN rail (8MW), 1 socket CEE 3P+N+T 16A
2
32A 3xD02 - Fuseholder, transparent hinged door 5041 41 71 2,79
Fuse not supplied
and DIN rail (8MW), 1 socket CEE 3P+N+T 32A
2
16A 3xD01 - Fuseholder, transparent hinged door 5041 41 61 2,96
Fuse not supplied
and DIN rail (8MW), 2 sockets CEE 3P+N+T 16A
Energy withstand
400 .103 A2s
Version 1 16W
2 20W
ZUCCHINI 86
PLUG-IN BOX WITH COMPLETE INSULATION
WITH INTERNAL WIRING Rating Protection devices and accessories Codice Weight kg
195
1
1 10A 3x1P 10A MCB char. B, 5041 41 01 2,28
transparent hinged door and DIN rail (8MW)
216
2
1 10A 3P 10A MCB char. B, 5041 41 03 2,23
transparent hinged door and DIN rail (8MW)
216
MR
1 16A 4P 16A MCB char. B, 5041 41 30 2,29
transparent hinged door and DIN rail (4MW)
1
16A 3x(1P 16A MCB char. B) 5041 41 23 2,46
transparent hinged door and DIN rail (8MW),
3 N terminals; 3 PE terminals
1
16A 3x(1P+N 16A MCB char. B) 5041 41 24 2,38
transparent hinged door and DIN rail (8MW),
3 N terminals; 3 PE terminals
1
16A (3P 16A MCB char. B) 5041 41 25 2,42
transparent hinged door and DIN rail (8MW),
3 N terminals; 3 PE terminals
1
16A (4P 16A MCB char. B) 5041 41 26 2,56
transparent hinged door and DIN rail (8MW),
3 N terminals; 3 PE terminals
Energy withstand
400 .103 A2s
Version 1 16W
2 20W
87 ZUCCHINI
PLUG-IN BOX WITH COMPLETE INSULATION
WITH INTERNAL WIRING Rating Protection devices and accessories Code Weight kg
195
1
1 32A (3P 32A MCB char. C) transparent hinged 5041 41 41 2,48
door and DIN rail (8MW), 3 N terminals; 3 PE terminals
216
1 5041 41 31 2,10
door and DIN rail (4MW), 2 sockets Schuko 16A
216
1
16A (1P+N 16A/30mA RCCB) transparent hinged 5041 41 33 2,14
door and DIN rail (4MW), 2 sockets Schuko 16A
1
16A (1P+N 16A MCB char. B) transparent hinged 5041 41 21 2,10
door and DIN rail (4MW), 3 sockets Schuko 16A
1
16A 3x(1P 16A MCB char. C) transparent hinged 5041 41 52 2,52
door and DIN rail (8MW), 3 sockets Schuko 16A
1
16A 3x(1P+N 16A MCB char. C) transparent hinged 5041 41 51 2,37
door and DIN rail (8MW), 3 sockets Schuko 16A
1
16A (3P 16A MCB char. C) transparent hinged 5041 41 54 2,50
door and DIN rail (8MW), 3 sockets Schuko 16A
2
16A 2x(1P 16A MCB char. B) transparent hinged 5041 41 88 2,87
door and DIN rail (8MW), 4 sockets Schuko 16A
2
16A 2x(1P+N 16A MCB char. B) transparent hinged 5041 41 89 2,75
door and DIN rail (8MW), 4 sockets Schuko 16A
Energy withstand
400 .103 A2s
Version 1 16W
2 20W
ZUCCHINI 88
PLUG-IN BOX WITH COMPLETE INSULATION
WITH INTERNAL WIRING Rating Protection devices and accessories Code Weight kg
195
1
2 16A (3P 16A MCB char. C) transparent hinged 5041 41 86 2,78
door and DIN rail (8MW), 1 socket CEE 3P+N+T 16A
216
2
195
MR
2 16A (3P 16A MCB char. C) transparent hinged 5041 41 83 3,18
door and DIN rail (8MW), 3 sockets CEE 2P+T 16A
1 16A Transparent hinged door (4MW), 3 sockets Schuko 16A 5041 42 21 1,83
1 32A Transparent hinged door and DIN rail (8MW) 5041 42 41 1,94
3 N terminals; 3 PE terminals
89 ZUCCHINI
TAP-OFF BOXES WITH DISCONNECTING
DEVICE ON THE COVER
MR - MRf
These tap-off boxes are made
32 CH 10 (ø10,3x3) A 5565 50 51 0,85
from thermoplastic material
strengthened with fibreglass. 63 CH 22 (ø22x58) B 5505 50 52 3,20
They fit all MR versions and
125 NH 0 B 5505 50 53 3,35
are provided with a set of
three fuseholders. 125 NH 00 B 5505 50 57 3,35
160 NH 0 B 5040 40 04 3,60
250 NH 1 F 5565 50 57 14,90
* Neutral section 50% 400 NH 2 F 5565 50 58* 15,80
WITH TRANSPARENT HINGED DOOR FOR MCBS Rating [A] DIN modules Picture 5 conductors codes Weight kg
MR - MRf
All tap-off boxes with transpa-
63 8 D 5505 50 86 3,20
rent door are equipped with a
DIN 50022 rail for modular 63 11 E 5505 50 88 3,60
devices. The internal equip-
125 8 D 5505 50 56 3,20
ment is accessible through
the transparent door without 125 11 E 5505 50 68 3,60
opening the cover, thus isola-
125 4 C 5505 50 66 3,00
ting the load connected.
160 4 C 5040 40 24 3,60
400 7 G 5505 50 70* 13,40
* Neutral section 50% 400 11+11 H 5505 50 71* 15,30
EMPTY READY FOR MCCBS Rating [A] Characteristic Picture 5 conductors codes Weight kg
MR - MRf
* Neutral section 50%
125 empty B 5505 50 55 2,90
These boxes are for use with 400 empty F 5565 50 59* 14,30
MR. They can be plugged in
and unplugged only when
the cover is open i.e. when
the tap-off is isolated. They
can be plugged in and
unplugged with the busbar
live. They fit both aluminium
and copper conductors.
45 130
200
A
32A 3
115 400
250
B C D E
63÷160A 4 4 4 4
200 560
300
F G H
250÷400A
5 5 5
ZUCCHINI 90
TAP-OFF BOXES WITH COVER DISCONNECTING
DEVICE ON THE COVER
PE + FE **
Tap-off box with zinced and
painted steel sheet. Suitable 63 CH 22 (ø22x58) P 5041 40 21 8,75
for heavy loads and to shield 125 NH 00 P 5041 40 22 8,90
electrical fields caused with
flowing current. 160 NH 00 P 5041 40 23 9,10
250 NH 2 Q 5041 40 24
630 NH 3 Q 5041 40 25
WITH SWITCH DISCONNECTOR AND FUSE HOLDER (AC23) Rating [A] Picture 5 conductors codes Weight kg
PE + FE **
These tap-off boxes are
equipped with an isolator
63 P 5041 16 01
switch (AC23) and fuse hol- 125 P 5041 16 22
der. The switch is operated
through a rotary handle on
160 P 5041 16 23
the cover. N.B. It is not pos- 250 Q 5041 16 24
sible to open, close, install or
pull out the tap-off box if the
400 Q 5041 16 25
switch is in "ON" position. 630 Q 5041 16 46
MR
EMPTY VERSION Rating [A] Picture 5 conductors code Weight kg
PE + FE **
"PE+FE" tap-off boxes have
63 P 5041 40 01
separate terminals for the
These boxes are for use with MR. They can be plugged in and unplug- 125 P 5041 40 02
two parallel earths (casing
ged only when the cover is open i.e. when the tap-off is isolated.
and conductor).
They can be plugged in and unplugged with the busbar live. 160 P 5041 40 03
They fit both aluminium and copper conductors. 250 Q 5041 40 04
They can be customized 630 Q 5041 40 05
with MCCB from various
manufacturers.
* PE Protection earth
** FE Functional earth
185 400
240
Side cable
63÷160A P entry
6 70 x 105
284 750
250 600
410
360
Side cable
entry
150 x 220
7 250A 8 400÷630A Q 7 8
91 ZUCCHINI
TAP-OFF BOXES (BOLT-ON TYPE)
WITH SWITCH DISCONNECTOR AND FUSE HOLDER Rating [A] Dimensions Switch Code Code Code
280 750
Aluminium 630 800 1000
"Bolt-on" tap-off boxes.They
630 1 AC23 5040 18 01 5040 18 02 -
use the joint between
straight lengths. As this con- 800 2 AC23 - 5040 18 04 -
400
300 1050
Copper 630 800 1000
630 1 AC23 5540 18 01 5540 18 02 5540 18 03
800 2 AC23 - 5540 18 04 5540 18 05
450
10 800÷1000A
Cable entry
dimensions [ mm]
9 10
ZUCCHINI 92
MOUNTING TAP-OFF BOXES
1 2
1 2 3 4
1 2 3
3 4 5 6 1 2 3 4
4 5 6
5 6 5 6 7 8
1 2
7 8
3 4
5 6
7 8 1 2
3 4
1 2 3 4
5 6 1 2 3
1 2 5 6 7 8
7 8 4 5 6
3 4
5 6
1 2
7 8 Numbers in squares
3 4
9 10 refer to the dimen-
5 6 sions of the tap-off
boxes (see previous
1 2 3
pages). 1 2 3
4 5 6
4 5 6
9
9
MR
10
1 2 3 1 2 3
4 5 6 4 5 6
1 2
3 4
1 2
1 2 3 NON
5 6
1 2 3 4
4 5 6 USABLE
3 4 5 6
1 2
3 4 5 6
1 2 1 2 3 1 2 3
5 6 Numbers in squares
3 4 4 5 6 4 5 6
9 10 refer to the dimen-
5 6 sions of the tap-off
boxes (see previous
pages). NON 1 2 3
USABLE 4 5 6
1 2 3 1 2 3
In lengths with 5 outlets 4 5 6
(picture 5), using an 4 5 6
outlet excludes the use
of the next one. 9
9
10
93 ZUCCHINI
FIXING ELEMENTS
148 208 Al Cu
112 172 160 250
250 315 1 bracket every 2 metesr of line A 5063 20 01 0,55
315 400
260
146
260
146
400 630
500
A B 800 1 bracket each 2 meters of line B 5063 20 03 0,60
630
20 800 1000
Wall spacer. Needed when
the hanger has to be fixed
directly to the wall. Wall spacer 40 mm C 5063 22 05 0,05
206
143
C
C A-B
SUSPENSION HANGER FOR RISING MAIN Mounting Use Picture Code Weight kg
SPRING SUSPENSION HANGER FOR RISING MAIN Mounting Use Picture Code Weight kg
Spring suspension hanger for 1 bracket every 300 kg. min 4 m. distance E 5040 37 12 1,20
rising mains. Use 1 hanger
every 300 kg (see weight
table).
60
TS brackets.
50 25x7
40
ZUCCHINI 94
FIXING ELEMENTS
100
57
50 30
B C D
ø 8,2
500 / 1000 / 2000
100
ø 11
540
MR
Beam bracket. It has a an Beam shelf base p max= 65 kg A 5063 22 10 0,90
arm and two clamps to the Beam clamp B 5063 22 11 0,90
beam.
147 ø7 8,5x13
65
50
175
45
40
A
P
110
95 ZUCCHINI
MEASURING SPECIAL ELEMENTS
STRAIGHT LENGTHS
ELBOWS
A B
B
B
A
A
Ceiling
OK
min.
Wall
Spacer
5063 22 05
min.
80 mm
ZUCCHINI 96
RISING MAINS
MR
the floor.
➑
Please specify the position of the internal fire barrier
before placing an order (see pg. 75)
➍
97 ZUCCHINI
HOW TO CREATE CODES FOR SB/MR ADAPTERS
Conductors
0 Aluminium
5 Copper
40
290 Conductors
0 Galvanized
1 Full galvanized
2 Painted
3 Full painted
Type
MR 2 Right
3 Left
Rating
SB 1 160A
L1 2 250A Example code
PE LH 3 315A
L2 4 400A
N
50400226 means
5 630A
L3 6 800A Aluminium
7 1000A Galvanized
8 500A Type RH
800A
RH 55420235 means
Copper
Full galvanized
Type LH
630A
SB
L1
PE
L2
N
L3
ZUCCHINI 98
NOTES
MR
99 ZUCCHINI
ZUCCHINI follows a policy of continuous
development, and therefore reserves the right
to supply products which may differ in detail
from those shown in this publication.
ZUCCHINI 100
TROLLEY SYSTEM
63 - 250A
INDEX
TS
GENERAL DATA 102
TS5
TRUNKING COMPONENTS 106
ACCESSORIES 108
TS250
TRUNKING COMPONENTS 110
ACCESSORIES 112
TS
TROLLEYS 3P+N 80 A 113
MTS63
TRUNKING COMPONENTS 114
ACCESSORIES 115
HANGERS 115
101 ZUCCHINI
TS
TECHNICAL DESCRIPTION
TS (Trolley System) is part of the Zucchini TS straight lengths include the following • the slot along the underside of the These enable the TS busbar to be
range used for supplying moving devices components: busbar, allows a current trolley to slide in it. supplied by cable ; the assembly of the
such as: overhead cranes, traversing • casing made from a hot-galvanised The size of the slot gives an IP20 degree line is carried out with a quick terminal
motors, assembly lines, etc. steel section bar (Senzimir), which is of protection. connection as with the straight lengths.
TS is suitable for straight and curved characterised by optimum mechanical • an independent electrical junction The cable entry is generally located at
sections (route changes only in the rigidity due to its rectangular shape and terminal system for fast and reliable the base of the end feed unit.
horizontal). 1.2 mm sheet metal thickness connection of the live conductors and PE. The TS range has centre feed units which
Zucchini TS can be installed quickly using (1.5 mm for 250A). In addition, it The terminals are made with bronze plates, can be installed wherever there is a
an electrical terminal junction and a wide preserves its linearity over time. thus keeping their base smooth in order junction between the straight lengths.
range of supporting accessories. As for the 63A (MTS63) rating, the casing to make the trolleys slide more easily.
TS, as all Zucchini products, is fully is made of anodised extruded aluminium The mechanical junction can be completed
compliant with the CEI EN 60439-1 / 2 with a minimum thickness of 1.4 mm. by applying the connection flanges
Harmonised Standards; the rated current • 5 conductors with the same section to the casing.
of the Zucchini busbar trunking systems is 3L+N+PE (4 for the TS 250A), shaped to The whole busbar is “fire retardant” in
always rated at the average ambient guarantee excellent mechanical strength. compliance with standard EN 60332-3.
temperature of 40°C (the Standard The conductors are made of copper with
requires 35°C), thus offering the market purity no less than 99.9% (electrolytic
suitably oversized products. copper) and are spaced out with plastic
The TS line is available in the following insulators reinforced with 20% glass fibre.
versions: 3L+N+PE (5 conductors) for The insulators have a V1 self-extinguishing
ratings from 63-70-110-150A and 3L+PE degree (as per UL94) and comply with
(4 conductors) for a 250A rating in the incandescent wire test as per EN
which the connected loads are normally 60695-2-1 (CEI 50.11).
three-phase motors. The electrical insulation between the con-
ductors and the casing is ensured by air
distances maintained by the insulators.
ZUCCHINI 102
END COVERS TRUNKING COMPONENTS AND TROLLEYS
ADDITIONAL ELEMENTS
End covers ensure the IP20 degree of Depending on the different installation These are used for connecting and The drive arms are connected to the
protection at the end of the run. requirements, Zucchini offers different supplying 25A – 40A – 80A or 160A trolleys with special springs which reduce
technical solutions: three-phase loads (in the coupled version). the acceleration (so-called “sudden pulls”)
a) curved elements: available for making The trolleys are equipped with 5 graphite when starting up and when braking.
route changes (only horizontally) up brushes (3L+N+PE) which, due to the The maximum travelling speed of the
to a minimum radius of 1.5m. action of the springs, keep the correct trolleys is 90 m/min (150 m/min for
The joint is of the quick type as with the pressure on the conductors enabling them the MTS 63A).
straight lengths. Standard trolleys slide to pick up current from the line while A box used as an accessory can be
HANGERS efficiently even within the curved sections the trolley is moving (travel) inside the connected directly downstream of the
of the run. The protection degree is IP20. TS busbar. trolley; inside the box is a fuseholder
b) straight lengths with trolley introduction The trolleys can be coupled with a to protect the cable from overcurrents.
device: these elements are provided with mechanical joint so as to pickup twice the All insulating plastic components are in
In order to fix the run to the structure
an access door on the underside. rated current of a single trolley: comply with the incandescent wire test
of the building, directly to a wall, ceiling
With this door open, it makes it possible 40A trolleys are available for TS5 lines (EN 60695-2-1) and have a V1
or beam bracket, it is necessary to use
to insert or remove a trolley from the line. from 70 to 150A; if coupled, the trolleys self-extinguishing degree (UL94);
a bracket which serves as a busbar collar.
Trolleys can generally be introduced to the can pickup 80A from the line the standard degree of protection is
An electrical junction, set up for
line near the end covers. However, lines (40+40=80A); the trolley is 80A for IP20 without using additional
suspending the busbar, is available on the
with several operating trolleys or when the TS 250A line and, if coupled with a sealing accessories.
TS line. The bracket has holes so it can
using very long lines, it is recommended twin trolley, it can pickup up to 160A.
be easily used with the fixing brackets
to use an inserting element in the middle Trolleys are generally driven by the same
available in the Zucchini catalogue.
of the line so as to make maintenance electric motor they supply power to; the
operation on the trolleys easier. motor coupling is achieved with a “drive
The degree of protection is IP20. arm” which suitably releases the traction
c) straight lengths with a thermal forces on the trolley without risking
expansion device. These elements are a trolley malfunction.
necessary in lines exceeding 35-40 m in
TS
length. Expansion elements “absorb and
compensate” the thermal expansion of the
conductors preventing them from losing
their linearity, avoiding the reduction of
the air insulation distances and obstructing
the sliding action of the trolleys.
103 ZUCCHINI
TS
TROLLEY SYSTEM
LINE DETAILS
End feed unit End cover Electrical and mechanical joint Suspension and joint hanger
ZUCCHINI 104
Automated warehouses Gantry cranes Workbenches
TROLLEY SYSTEM
Trolley. It slides on the Coupling clamp with End feed unit
conductors, assuring contact suspension bracket.
with the conductors.
TS
105 ZUCCHINI
STRAIGHT LENGTH AND FITTINGS
TS5 - IP20
Three-pole + Neutral + copper earth bar
Trolley bars:
Current rating 63-70-110-150 A
70 80520101 12
110 80530101 12,5
150 80540101 13
65,5
L3 L2 L1 N
70 80530102 6
110 80530102 6
98 150 80540102 6,5
L = 3000
L = 1500
A straight element is made
up of:
• a shaped zinced steel sheet
to offer good mechanical
strength, gasket in rigid PVC
• conductors rack in polyami-
de resin reinforced with fibre-
glass with high insulating
level
• phase conductors in elec-
trolytic copper UNI5649 ETP
99,9, allowing smooth sliding
of the trolley.
3 m STRAIGHT ELEMENT WITH TROLLEY INTRODUCTION DEVICE Rating [A] Code L=3000 Weight kg
70 80530201 13
110 80530201 13
150 80540201 13,5
L = 3000
ZUCCHINI 106
STRAIGHT LENGTHS AND FITTINGS
3 m. STRAIGHT ELEMENT WITH EXPANSION JOINT Rating [A] Code L=3000 Weight kg
70 80530301 14
110 80530301 14
150 80540301 14,5
L = 3000
70 80530401 -
110 80530401 -
150 80540401 -
TS
BOX WITH NH 00 FUSE HOLDER FOR LINE 70A ÷ 250A Rating [A] Code Weight kg
320
130
240
107 ZUCCHINI
ACCESSORIES
150
115
130 70 80541101 --
It feeds a trunking system from
whatever central position. The
110 80541101 --
110
240
70 80542001 --
One for each element.
110 80542001 --
150 80542001 --
95
72
120
62 70 80542002 --
Ø 6,5 It allows to hang the line at its 110 80542002 --
60
15 junction points.
Hole 6,5 x 150 80542002 --
95
72
120
62 70 80042101 --
Ø 6,5 It can be positioned 110 80042101 --
15
60
50
98
The end cover can be
70 80531301 --
installed at one end 110 80531301 --
or the other of a line. 150 80541301 --
92
120
ZUCCHINI 108
ACCESSORIES
160 80545002 -
97
Always pull the tap-trolley
with the appropriate
springs (A).
(A)
182
(A)
With its graphite contacts assu-
ring the electrical continuity, this
trolley is available for 40A; but
its rating can be doubled to 80A
using two trolleys in parallel
with code 80045203. It works
properly up to a sliding speed of
90m/min and bears weights up
to 30kg.
SIMPLE 80045201 -
400
TS
DOUBLE 80045202 -
150 80045203 -
It joins two trolleys together,
obtaining a supply of 80A.
109 ZUCCHINI
STRAIGHT LENGTHS AND FITTINGS
TS250 - IP20
Three-conductors + copper earth bar:
Rating 250 A
250 82200102 15
L3 L2 L1
89
14
144
L = 3000
A straight element is made up
L = 1500 of:
• shaped zinced steel sheet to
offer good mechanical
strength
• conductors supported in pol-
yamide resin reinforced with
fibreglass with high insulating
level
• phase conductors in elec-
trolytic copper UNI5649 ETP
99,9, allowing smooth sliding
of the trolley.
• two rigid PVC gaskets assu-
ring an IP20 protection
degree against direct contact.
ZUCCHINI 110
STRAIGHT LENGTHS AND FITTINGS
3 m STRAIGHT ELEMENTS WITH TROLLEY INTRODUCTION DEVICE Rating [A] Code L=3000 Weight kg
L = 3000
3 m STRAIGHT ELEMENT WITH EXPANSION JOINT Rating [A] Code L=3000 Weight kg TS
250 82200301 32
L = 3000
111 ZUCCHINI
ACCESSORIES
250 82001001 -
The end feed unit can be
installed at one end or the
other of a line.
125
140
330
250 82001101 -
350
It feeds a trunking system from
whatever central position. The
centre feed unit is also used to
reduce the volt drop of the line.
140
225
200
15
Hole 6,5 x
t allows to hang the line at its
junction points.
115
200
15
Hole 6,5 x
It can be positioned anywhere
along the line. Use one every 2
metres.
120
70
200
ZUCCHINI 112
ACCESSORIES
82205001 -
186 144
Always pull the tap-trolley
with the appropriate
springs (A).
SIMPLE 80045201 -
400
Code Weight kg
TS
DOUBLE 80045202 -
150 80045203 -
It joins two trolleys together,
obtaining a supply of 160A.
113 ZUCCHINI
TRUNKING ACCESSORIES
MTS63-IP23
Three-pole + Neutral + copper earth bar
Trolley bars:
Current rating 63 A
63 84500101 5
63 84500111 2,5
L2 L1
57
N L3
44,8
ZUCCHINI 114
TRUNKING ACCESSORIES
63 84501001 1
63 84501002 1,5
84505001 0,32
er phase conductors in
UNI 5649 ETP 99,9
TS
With its graphite contacts assu-
ring the electrical continuity, the
25A trolley works properly up to
a sliding speed of 90m/min
and bears weights up to 30kg.
84505004 -
For local protection.
115 ZUCCHINI
BRACKET
170
60
500
35
50
hole 25x7
100
100
L
57 Ø 11
11x25
2 3 4
1
4 3 2
146,5 Ø7 8,5 x 12
65 7 x 42
175 1
45
40
* 2 for beam
2
ZUCCHINI 116
NOTES
TS
117 ZUCCHINI
ZUCCHINI follows a policy of continuous
development, and therefore reserves the right
to supply products which may differ in detail
from those shown in this publication.
ZUCCHINI 118
SUPER COMPACT
630 - 5000A
SCP
For detailed information on this product,
please request the specialized catalogue
(see cover)
1988
© DiskArt™
© DiskArt™
1988
SCP
119 ZUCCHINI
SCP
TECHNICAL DESCRIPTION
SCP (SuperCompact Painted) is part of Used for distributing power and for The conductors are packed against each The mechanical joint is completed by
the Zucchini range used for the distribution supplying high-powered loads. other ( sandwiched) so as to minimise fitting the IP covers which are provided
of power in large installations;it is SCP straight lengths include the following the distance between one phase and the with anti-aging gaskets which guarantee
also particularly suitable in riser feeder components: other, thus achieving the advantage of an IP55 degree of protection.
units (trunking systems) within buildings • casing made from four “C-shaped” minimising the mutual reactance, hence The" monobloc" making the junction
used for the service sector (banks, ribbed, crimped and riveted section bars the impedance of the busbar. between the elements can also be used
insurance, commercial headquarters, (130x130-480 mm, thickness 1.5 mm) • an electrical junction "monobloc" system for tapping off power, by fitting a “bolted”
skyscrapers, etc.). made of hot-galvanised and painted steel for fast and reliable connection of the live tap-off box to it; therefore, each junction
The SCP range is available in sizes ranging (Senzimir). conductors and PE. of the SCP line is already set up for a
from 630A to 4000A with conductors It also serves as a protection conductor The “monobloc” is made from a system tap-off in a fixed position.
made from an aluminium alloy and from (PE) thanks to its suitable section and of silver-plated copper plates which make The junction monobloc is also equipped
800A to 5000A with copper conductors. electrical continuity; if required, the line up the live conductor series. with a device (positioning pin) which
The ultra-compact dimensions of the SCP can be provided with a special PE The conducting plates are separated from ensures the correct polarity of the
enhance the short-circuit stress resistance conductor whose section and material can each other with thermosetting plastic phase-neutral sequence, thus avoiding
features, reduce the impedance of the be the same as the one for the phases insulators (temperature class “B”) which installation errors.
circuit by limiting voltage drops and (SCP5) or, for systems where third maintain their electrical and mechanical • straight lengths are available with
enables the installation of high power harmonics are significant (e.g. Data features over time. The" monobloc" has a tap-off outlets to accept plug-in type
electrical systems even in extremely Processing Centre), even in the version bolt (2 bolts per bar h=160; 3 per bar tap-off boxes.
cramped spaces. with double-section neutral conductors h≥190) with a shearhead nut: use a The outlets are located on both sides of
SCP has a wide range of tap-off boxes relative to the phase (SCP2N). 19mm wrench to tighten the external the busbar with a spacing distance of
rated from 63A to 1250A, thus allowing The SCP range is totally painted which head until the collar which connects the 1 m (3+3 outlets every 3m).
the supply and protection of all kinds of offers resistance to chemical agents, two heads of the nut breaks; this will The outlets are closed by a plug outlet
loads due to the availability of different improves resistance to galvanised sheet ensure the correct nominal torque to cover which guarantees an IP55 degree
protection devices such as fuses, moulded metal corrosion and gives better heat guarantee optimum electrical continuity of protection; when the outlet is open, the
case circuit breakers and motorised dissipation; the standard colour is over time. The protective conductor plug outlet cover has an IP2x degree of
switches. RAL7035 (light grey). (PE=casing) is also connected through the protection.
Zucchini SCP can be installed quickly. • 4 conductors with the same section monobloc. A pair of Belleville washers for All components and accessories of the
It is easy to manage and suitable for 3L+N with PE made from the casing (5 each bolt ensures the correct distribution SCP line are available as the IP55
modifications and extensions, which is conductors in case of SCP5: 3L+N+PE). of the contact pressures as well as main- version as standard the same degree
always necessary for installations The conductors are made from an taining the pressure even when exposed of protection as the line.
where SCP is used. aluminum alloy copper plated with a final to the temperature ranges, during the The whole busbar is “fire retardant” in
SCP, as all Zucchini products, complies coat of tin. Alternatively, the SCP line is operation of a busbar trunking system. compliance with standard EN 60332-3.
with the CEI EN 60439-1 / 2 Harmonised available with copper conductors with In order to simplify the storage and speed
Standards; specifically, the rated current purity no less than 99.9% (electrolytic up the installation of the line, straight
of the Zucchini busbar trunking systems copper). lengths, trunking components and all
is always rated at the average ambient The conductors are insulated and components of the SCP line are already
temperature of 40°C (the Standard separated from each other by a double fitted with a monobloc pre-installed at the
requires 35°C), thus offering the layer of polyester film (2x0,20mm), factory. Each element with its own
market suitably oversized products. a V1 self-extinguishing insulating material, pre-installed monobloc is checked at the
non-desiccant, with high di-electric strength factory with a 5 kV applied voltage test
and in compliance with the incandescent both between the phases and to earth so
wire test as per IEC 695-2-1 (CEI 50.11). as to guarantee proper insulation (test
sequence at 5 kV: L1-L2; L2-L3; L1-L3;
L1-N; L2-N; L3-N; L1-PE; L2-PE; L3-PE;
N-PE), (the Standard requires 3.5 kV). END COVERS
ZUCCHINI 120
END FEED UNITS TRUNKING COMPONENTS AND TAP-OFF BOXES
ADDITIONAL ELEMENTS
These enable the SCP range to be Depending on the different installation These are used for connecting and Plug-in type boxes are available in the
supplied by cable or directly connected to requirements, Zucchini is able to offer supplying three-phase loads from 63A up following versions: with fuseholder, with
an electric distribution panel; the assembly different technical solutions: to 1250A: they can be divided into two switchfuse or with moulded case circuit
of the line is carried out with a quick a) 90° angles: available for changing main categories: breakers.
monobloc connection as with the straight routes both horizontally and vertically. 1) Plug-in tap-off boxes (from 63A up If the boxes are equipped with a switch,
lengths. The end feed units are provided The joint is of the quick type as with to 630A): they can be operated when the rotary handle extension is carried
with LV connections for the connection of the straight lengths. energized but not when under load out with a handle on the cover of the
cables equipped with compatible terminals The protection degree is IP55. conditions; the boxes are equipped with box which makes it possible to open
with a 15x20 mm slotted hole. b) T, X and double angle Z elements. an isolator integral with the cover. the switch before removing the box
The cable entry is generally located at the The degree of protection is IP55. When the tap-off box is installed on the from the busbar.
base of the end feed unit, in which there c) Straight lengths with fire barrier busbar, the opening of the cover 2) Boxes bolted on the junction (from
is a removable plate; it is also possible to (external) S120. electrically disconnects its internal parts, 125A to 1250A): these high rated current
insert the cables through the side plates. These elements are used when REI120 in other words no accessible metallic part boxes are rigidly connected to the busbar
The SCP line has centre feed units and fire-resistant walls need to be passed is live when the cover is open. Tap-off with a special “monobloc” connection
end feed units with a switch ; the latter through. The elements provided with a boxes have an interlock with a cover and system similar to that of the straight
allows disconnection of the whole line fire barrier have been lab-tested can be inserted and removed from the lengths but this also allows for power to
to carry out maintenance operations (in accordance with DIN 4102-9 and EN outlet only when the cover is in the“open” be tapped-off from the busbar.
or modifications of the installation. 1366-3) in order to confirm that, if position, that is in the ‘isolated’ position. The boxes can only be installed and
correctly installed, they will maintain the The cover of the box can be locked in removed when the system is
essential fire resistant features of the wall. the open-isolated position to allow safe de-energized (isolated busbar).
S120 means that the barrier is certified maintenance of the loads connected to it. When the monobloc system is used,
for 120’ (minutes). All Zucchini plug-in type boxes have a PE installation will be extremely easy,
d) Straight lengths with a thermal contact (protective conductor), which is quick and reliable.
expansion device; these elements should the first to make an electrical connection These boxes are available in the
be inserted in long runs to compensate when the box is plugged into the outlet, switchfuse and fuseholder version and
for the thermal expansions due to the and the last to disconnect when the tap-off with moulded case circuit breakers
temperature ranges of the conductors is unplugged; all insulating plastic
during their operation. components comply with the incandescent
HANGERS The expansion elements must be wire test (EN 60695-2-1) and have a V1
inserted every 35-40 m of line. self-extinguishing degree (UL94); the
e) Straight lengths with phase standard degree of protection is IP55
transpositions or with a “neutral rotation”; without using additional IP protection kits;
In order to fix the run to the structure of these elements are suitable for changing
the building, directly or with a wall, ceiling the position of the phase sequence and for
or beam bracket, it is necessary to use a reducing and balancing the mutual phase
reactances and for balancing the
SCP
bracket which serves as a busbar collar.
The bracket has holes for use i with the impedances (currents) when lines
support brackets available in the Zucchini exceeding 100-150 m are installed.
catalogue. f) Additional protective cowl; the SCP
Vertical installation brackets (rising busbar trunking system has a basic IP55
mains), type-approved brackets for degree of protection.
ships and type-approved brackets for For outdoor applications, it is necessary
seismic environments are available to protect the busbar with a cowl to
for the SCP line. protect the busbar from bad weather
and direct sunlight.
g) protective bellows and flexible braids
for transformer connection (oil or resin),
generators and, in general, equipment that
vibrates during its normal operation.
These devices are used for mechanically
isolating the vibrating equipment from the
rest of the busbar trunking system.
121 ZUCCHINI
SCP
SUPER COMPACT
LINE DETAILS
ZUCCHINI 122
Hospitals Switchboard-transformer connections Skyscrapers Large industries
S U P E R C O M PA C T
SCP
123 ZUCCHINI
ZUCCHINI follows a policy of continuous
development, and therefore reserves the right
to supply products which may differ in detail
from those shown in this publication.
ZUCCHINI 124
HIGH RATING
1000 - 5000A
HR
For detailed information on this product,
please request the specialized catalogue
(see cover)
1988
© DiskArt™
© DiskArt™
1988
HR
125 ZUCCHINI
HR
TECHNICAL DESCRIPTION
The Zucchini HR (High Rating) range is Used for carrying low voltage power. The conductors are separated from A pair of Belleville washers for each bolt
frequently used for a connection between HR straight lengths include the following each other by an insulating, non-desiccant ensures the correct distribution of the
electric panels or for a panel-transformer components: double-tape with high di-electric strength. contact pressures as well as maintaining
connection. • casing made from four “C-shaped” the conductors are spaced from each the pressure even when exposed to the
The HR line is available in sizes ranging ribbed and bolted section bars (thickness other with plastic insulators reinforced with temperature ranges, typical of the
from 1000A to 4500A with conductors 2.0 mm), made of hot-galvanised steel 20% glass fibre. All components have a operation of a busbar trunking system.
made from an aluminium alloy and (Senzimir). V1 self-extinguishing degree (as per Each element is checked at the factory
from 1000A up to 5000A with It also serves as a protection conductor UL94) and comply with the incandescent with a 5 kV applied voltage test both
copper conductors. (PE) due to its good section and electrical wire test as per EN 60695-2-1 between the phases and to earth so
The monobloc joint makes Zucchini HR continuity; if required, the line can be (CEI 50.11). The electric insulation as to guarantee proper insulation (test
quick to install, thus considerably reducing provided with a special PE conductor between the conductors and the sequence at 5 kV: L1-L2; L2-L3; L1-L3;
installation time even when dealing whose section and material can be the casing is ensured by air distances L1-N; L2-N; L3-N; L1-PE; L2-PE; L3-PE;
with very complex systems. same as the one for the phases or, for maintained by the insulators. N-PE), (the Standard requires 3.5 kV).
HR, as all Zucchini products, complies systems where third harmonics are • an electrical joint "monobloc" system The mechanical joint is completed by
with the CEI EN 60439-1 / 2 Harmonised significant (e.g. Data Processing Centre), for fast and reliable connection of the applying the covers which guarantee an
Standards; specifically, the rated current even in the version with double size elements. The “monobloc” is made from a IP30 degree of protection. (IP31 with
of the Zucchini busbar trunking systems neutral conductors relative to the phase. system of silver-plated copper plates which a dedicated cover).
is always rated at the average ambient The top and bottom plates of the HR line make up the live conductor series. The" monobloc" making the joint between
temperature of 40°C (the Standard are perforated to allow air to circulate The conducting plates are separated from the elements can also be used for tapping
requires 35°C), thus offering the market inside the busbar and to effectively each other with thermosetting plastic insu- off power, by fitting a “bolted” tap-off box
suitably oversized products. dissipate the heat produced by the current lators (temperature class “B”) which to it; therefore, each junction of the HR
running through it. The protection degree maintain their electrical and mechanical line is already set up for a tap-off in a
is IP30 and can be increased to IP31 by features over time. The" monobloc" has a fixed position.
adding an accessory on the joint between bolt (2 bolts per bar h=160; 3 per bar The whole busbar is “fire retardant” in
the elements. h≥190) with a shearhead nut: using a compliance with standard EN 60332-3.
• 4 conductors with the same section 19mm wrench to tighten the external
3L+N with PE made from the casing head until the collar which connects the
(versions: 3L; 3L+2N; 3L+N+dedicated two heads of the nut breaks; this will
PE, on request). ensure the correct nominal torque to
The conductors are made from an guarantee optimum electrical continuity
aluminum alloy copper plated and a over time. The protective conductor
final coat of tin. Alternatively, the HR (PE=casing) is connected through the
line is available with copper conductors two copper plates.
with purity no less than 99.9%
(electrolytic copper).
ZUCCHINI 126
END FEED UNITS END COVERS TRUNKING COMPONENTS AND TAP-OFF BOXES
ADDITIONAL ELEMENTS
These enable the HR range to be supplied End covers ensure the nominal degree of Depending on the different installation The HR line is primarily used for feeder
by cable or directly connected to an elec- protection at the end of the run. requirements, Zucchini is able to offer bar; however, the range also has tap-off
tric distribution panel; the assembly on the different technical solutions: boxes up to 1250A to be fitted at the
line is carried out with a quick monobloc a) 90° angles: available for changing junction between the elements:
connection as with the straight lengths. routes both horizontally and vertically. Boxes bolted on the junction (from 125A
The end feed units are provided with The joint is of the quick type as with to 1250A): these high rated current boxes
extensions for the connection of cables the straight lengths. are connected to the busbar with a special
equipped with compatible terminals with HANGERS b) T, X and double angle Z elements. “monobloc” connection system similar to
a 15x20 mm slotted hole. c) Straight lengths with fire barrier that of the straight lengths but this allows
The cable entry is generally located at the (internal + external). for power to be tapped-off from the
base of the end feed unit, in which there These elements are used when fire- busbar.
is a removable plate; it is also possible to In order to fix the run to the structure of resistant walls need to be passed through. The boxes can only be installed and
insert the cables through the side plates. the building, directly or with a wall, ceiling d) Straight lengths with a thermal removed when the system is de-energized
The HR range has centre feed units and or beam bracket, it is necessary to use a expansion device; these elements should (isolated busbar). When the monobloc
also end feed units with a switch ; bracket which serves as a busbar collar. be inserted in long runs to compensate system is used, installation will be
the latter allows disconnection of The bracket has holes for use with the for the thermal expansions due to the extremely easy, quick and reliable.
the whole line so as to carry out fixing brackets available in the Zucchini temperature ranges of the conductors These boxes are available in the switched
maintenance operations or modifications catalogue. during their operation. and fuseholder version and with moulded
of the installation. The expansion elements must be inserted case circuit breakers.
every 35-40 m along the run.
e) Straight lengths with phase
transpositions or with a “neutral rotation”;
these elements are suitable for changing
the position of the phase sequence and for
reducing and balancing the mutual phase
reactances and for balancing the currents
when lines exceeding 100-150 m are
installed.
HR
127 ZUCCHINI
HR
HIGH RATING
LINE DETAILS
ZUCCHINI 128
Switchboard connections Heavy industries
H I G H R AT I N G
Drilled sheet to allow heat loss.
IP 30 protection degree.
HR
Monobloc
129 ZUCCHINI
ZUCCHINI follows a policy of continuous
development, and therefore reserves the right
to supply products which may differ in detail
from those shown in this publication.
ZUCCHINI 130
CAST RESIN TRANSFORMERS
100 - 16000 kVA
CRT
For detailed information on this product,
please request the specialized catalogue
(see cover)
e r s
o r m
n s f
T r a
s i n
R e
s t
C a
arn ate
di M
nica
ecca
trom
Elet
CRT
131 ZUCCHINI
CRT
TRANSFORMERS
TECHNICAL DESCRIPTION
GENERAL FEATURES RESIN MEDIUM VOLTAGE (HV) LOW VOLTAGE (LV) WINDING
WINDING
EdM transformers are cast resin Used for encapsulating medium-voltage Medium Voltage windings are made on The Low Voltage winding is made
transformers with power ranging from windings: it is of the epoxy type filled highly automated winding machines and from an aluminium sheet whose height
100 up to 3500 kVA (standard), whereas with silica and trihydrate alumina. are made with aluminium strip conducting is the same as the coil.
there are transformers up to 16000 kVA The resin is treated in high vacuum material. The winding is formed using special
for specific EdM projects. chambers to obtain optimum degassing The winding is continuously wound winding machines through a process which
All machines are built according to the to reduce the presence of air or other directly onto the internal shape of the ensures a compactness able to form
requirements specified in the main gases which could produce partial earth mould onto which there is a fiberglass net a single cylinder.
national and international standards: discharges. used as a static support for the winding Compactness is essential to withstand the
Standards CEI EN 60076 - 1…5 The epoxy compound is characterised which prevents the misalignment of the axial and radial stresses resulting from
Standards CEI EN 60076 - 11 by optimum di-electric and mechanical aluminium winding coils during the various short-circuit phenomena to which the
Document CENELEC HD 538.1.S1 properties, able to resist the various stages prior to the insertion in the casting transformer may be required to deliver.
ed. 1992 stresses to which the transformer may system. All the welds of the conducting sheet
be exposed throughout its life. This type of process enables the EdM (plate) along with the connection taps are
When using the special epoxy along with transformers to keep the thickness of the butt welding (inert gas) to prevent any
a targeted project, all EdM transformers resin consistent both inside and outside. welding remnants from affecting or
are classified E2-C2-F1 (Certificate of It also ensures constant mechanical damaging the insulation placed between
conformity CESI No. 98/012355). resistance to di-electric stresses to which the coil end and the next coil.
the transformer is exposed both during The LV winding is suitably treated
the testing phase and during its (vacuum epoxy resin dipping) to avoid the
technical lifetime. absorption of moisture throughout its life.
Off load tap changers of the primary This treatment is suitable for any
voltage +/-2 x 2.5% are used on environment in which the transformer
the primary winding. is to be used, including those with a high
The thermal class of the insulating humidity value (tropical or sea
materials used conforms to class F and environments), thus allowing for
the permitted temperature rises are those the F1 classification of the system
specified in the specific Standards for in compliance with the specific
the product. Standards for the product.
ZUCCHINI 132
CORE PROTECTION SYSTEMS ADDITIONAL COMPONENTS AND
ACCESSORIES
The magnetic core is made of sheets of All transformers are protected against Each machine can be equipped with
laminated grain oriented magnetic steel possible temperature rise risks resulting the following accessories:
with losses, depending on the actual from extended overload phenomena and - Medium voltage connections on fixed
design specifications. improper ventilation of the room where insulator integral with the HV column;
The core (totally designed by EdM) is the machine is installed. - Low voltage bars in aluminium with
purchased at selected suppliers which The protection is achieved through a suitable holes for connecting cables
guarantees optimum quality of the product PT 100 Ohm triad of platinum thermal or bars;
as well as a no-load loss certification. resistances (one for each LV column) - Connections for horizontal travel and
which communicate with a temperature lifting eye-bolts;
sensing and monitoring apparatus - Voltage-change terminal board for
(control unit). adjusting the primary voltage
The unit is supplied as a separate part by ± 2x2.5%, to be carried out when
to be installed, if required, on the the transformer is disconnected;
control panel. - 90° adjustable travel wheels;
By following the operating instructions - Earthing connections;
supplied with the EdM transformer, the - Features and performance data plate
unit can be used to programme the two - Temperature control device
temperature values corresponding to the (control unit).
“alarm level” and to the “disabling level” - Indoor and outdoor enclosures
of the transformer. The two levels are (IP21…IP43)
based on the thermal class of the - HV quick connectors (Elastimold)
insulating materials used for making - LV connection adaptor to Zucchini’s
the HV and LV coils. busbar trunking systems
- Special accessories and solutions,
on request.
CRT
133 ZUCCHINI
CRT
CAST RESIN
TRANSFORMERS
ZUCCHINI 134
Industries Naval applications Wind generation plants
135 ZUCCHINI
ZUCCHINI follows a policy of continuous
development, and therefore reserves the right
to supply products which may differ in detail
from those shown in this publication.
ZUCCHINI 136
T E C H N I C A L D ATA INDEX
LB 138
HL 139
SL 140
MS 141
MR 142
TS 144
TECHNICAL DATA
137 ZUCCHINI
TECHNICAL DATA
∆V1F = 1 (2 R20 cos ϕ + 2 X sen ϕ) ∆V [V/m/A]10-3 cosϕ = 0,75 5,11 4,50 4,50 • 5,11 2,75 2,37 2,37 • 2,75
2 ∆V [V/m/A]10-3 cosϕ = 0,80 5,33 4,68 4,68 • 5,33 2,85 2,45 2,45 • 2,85
Voltage drop with distribuited load (k) ∆V [V/m/A]10-3 cosϕ = 0,85 5,53 4,85 4,85 • 5,53 2,94 2,53 2,53 • 2,94
∆V [V/m/A]10-3 cosϕ = 0,90 5,72 5,01 5,01 • 5,72 3,01 2,60 2,60 • 3,01
∆V3F = √ 3 (R20 cos ϕ + X sen ϕ) ∆V [V/m/A]10-3 cosϕ = 0,95 5,87 5,12 5,12 • 5,87 3,06 2,65 2,65 • 3,06
2
∆V [V/m/A]10-3 cosϕ = 1,00 5,80 5,03 5,03 • 5,80 2,96 2,57 2,57 • 2,96
Straight length weight p [kg/m] 0,95 1,0 1,10 1,0 1,1 1,20
Fire load [kWh/m] 0,82 0,82 0,82 0,82 0,82 0,82
Protection degree IP 55 55 55 55 55 55
Losses for the Joule effect at full load P [W/m] 7,3 10,9 10,9 • 7,3 9,5 14,2 14,2 9,5
Ambient temperature min./MAX. t [°C] -5/+50 -5/+50 -5/+50 -5/+50 -5/+50 5/+50
SHORT CIRCUIT PROTECTION FOR ZUCCHINI’S PRODUCT RANGES TEMPERATURE RATING SCHEDULE
(In≤100A)
Zucchini’s busbar system with a nominal current less or equal to 100A (LB-HL-SL-MS 63 and Mean room temperature [°C] 15 20 25 30 35 40 45 50 55 60
100) are correctly protected against short circuit effects through a MCB (MCB Modular
Circuit Breaker) with a nominal current less or equal to the one of the busbar. K1 factor 1,15 1,12 1,08 1,05 1,025 1 0,975 0,95 0,93 0,89
This protection is assured up to MCB short circuit withstand.
Multiplier coefficient of nominal rating for room temperture values different from 40° C
The busbar trunking systems LB-HL-SL-MS are not flame propogating in
compliance with IEC 332-3: 1992.
For evenly distributed loads the maximum weight (kg) that can be supported is given in the tables below:
For point loads multiply the values in the below tables by 0,5.
Product in compliance to:
IEC 439-1 e 2, EN 60439 parte 1 e 2, fixing centres (span) m.
DIN VDE 0660 parte 500 e 502 maximum deflection = 1/350 x span m 2,3 2,4 2,5 2,6 2,7 2,8 2,9 3,0
Product suited to these climates: kg 17,2 15,8 14,6 13,4 12,5 11,6 11 10
Constant humid climate (DIN IEC 68 et 2- 3) maximum deflection = 1/500 x span m 2,3 2,4 2,5 2,6 2,7 2,8 2,9 3,0
Cyclical humid climate (DIN IEC 68 et 2- 30) kg 15,4 14 13 12 11,2 10,4 9,6 9
ZUCCHINI 138
TECHNICAL DATA
HLs HLd
SINGLE DOUBLE
252 402 254 404 2522 4022 2542 4042 2544 4044 2x4
side side side side
Live conductors n° 2 2 4 4 2+2 2+2 4 • 2 4 • 2 4+4 4+4 2+2+2+2
Casing overal dimension A x B [mm] 26x62 26x62 26x62 26x62 40,4x70 40,4x70 40,4x70 40,4x70 40,4x70 40,4x70 40,4x70
Rated current In [A] 25 40 25 40 25 40 25 40 25 40 25
Cross-section of conductors (3P+N) S [mm2] 3,14 6,15 3,14 6,15 3,14 6,15 3,14 6,15 3,14 6,15 3,14
Cross-section of protective conductor eq. Cu SPE [mm2] 17 17 17 17 20 20 20 20 20 20 20
Operational voltage Ue [V] 400 400 400 400 400 400 400 400 400 400 400
Insulation voltage Ui [V] 500 500 500 500 500 500 500 500 500 500 500
Rated frequency f [Hz] 50/60 50/60 50/60 50/60 50/60 50/60 50/60 50/60 50/60 50/60 50/60
Rated short-time current (0,1 s) ICW [kA]rms 2,5 3,2 2,5 3,2 2,5 3,2 2,5 3,2 2,5 3,2 2,5
Peak current Ipk [kA] 10 10 10 10 10 10 10 10 10 10 10
Maximum thermal limit I2t [A2s x 106] 0,64 1,00 0,64 1,00 0,64 1,00 0,64 1,00 0,64 1,00 0,64
Phase resistance R20 [mΩ/m] 5,73 2,93 5,73 2,93 5,73 2,93 5,73 • 5,73 2,93• 2,93 5,73 2,93 5,73
Phase reactance (50Hz) X [mΩ/m] 1,40 1,58 1,27 0,77 1,40 1,58 1,27 • 1,40 0,77• 1,58 1,27 0,77 1,27
Phase impedance Z [mΩ/m] 5,90 3,33 5,87 3,03 5,90 3,33 5,87 • 5,90 3,03• 3,33 5,87 3,03 5,87
Resistance of the protective bar RPE [mΩ/m] 1,06 1,06 1,06 1,06 0,90 0,90 0,90 • 0,90 0,90• 0,90 0,90 0,90 0,90
Reactance of the protective bar (50Hz) XPE [mΩ/m] 1,10 1,10 1,10 1,10 1,00 1,00 1,00 • 1,00 1,00• 1,00 1,00 1,00 1,00
Resistance of the fault loop Ro [mΩ/m] 6,79 3,99 6,79 3,99 6,63 3,83 6,63 • 6,63 3,83• 3,83 6,63 3,83 6,63
Reactance of the fault loop (50Hz) Xo [mΩ/m] 2,50 2,68 2,37 1,87 2,40 2,58 2,27 • 2,40 1,77• 2,58 2,27 1,77 2,27
Impedance of the fault loop Zo [mΩ/m] 7,24 4,80 7,19 4,40 7,05 4,62 7,01 • 7,05 4,22• 4,62 7,01 4,22 7,01
∆V [V/m/A]10-3 cosϕ = 0,70 5,01 3,18 4,26 2,25 5,01 3,18 4,26 • 5,01 2,25• 3,18 4,26 2,25 4,92
= 0,75
∆V1F = 1 (2 R20 cos ϕ + 2 X sen ϕ) 5,23 3,24 4,45 2,34 5,23 3,24 4,45 • 5,23 2,34• 3,24 4,45 2,34 5,14
2 = 0,80 5,43 3,29 4,63 2,43 5,43 3,29 4,63 • 5,43 2,43• 3,29 4,63 2,43 5,35
Voltage drop with distribuited load (k) = 0,85 5,61 3,32 4,80 2,51 5,61 3,32 4,80 • 5,61 2,51• 3,32 4,80 2,51 5,54
= 0,90 5,77 3,32 4,95 2,57 5,77 3,32 4,95 • 5,77 2,57• 3,32 4,95 2,57 5,71
∆V3F = √ 3 (R20 cos ϕ + X sen ϕ) = 0,95
2 5,88 3,27 5,06 2,62 5,88 3,27 5,06 • 5,88 2,62• 3,27 5,06 2,62 5,84
= 1,00 5,73 2,93 4,96 2,53 5,73 2,93 4,96 • 5,73 2,53• 2,93 4,96 2,53 5,73
Straight length weight p [kg/m] 1,5 1,6 1,6 1,7 2,8 2,9 2,9 3,1 2,9 3,2 2,9
Fire load [kWh/m] 0,82 0,82 0,82 0,82 1,64 1,64 1,64 1,64 1,64 1,64 1,64
Protection degree IP 55 55 55 55 55 55 55 55 55 55 55
Losses for the Joule effect at full load P [W/m] 7,2 9,4 10,7 14,0 7,2 9,4 10,7 7,2 14,0 9,4 10,7 14,0 7,2
Ambient temperature min./MAX. t [°C] -5/+50 -5/+50 -5/+50 -5/+50 -5/+50 -5/+50 -5/+50 -5/+50 -5/+50 -5/+50 -5/+50
SHORT CIRCUIT PROTECTION FOR ZUCCHINI’S PRODUCT RANGES TEMPERATURE RATING SCHEDULE
(In≤100A)
Zucchini’s busbar system with a nominal current less or equal to 100A (LB-HL-SL-MS 63 and Mean room temperature [°C] 15 20 25 30 35 40 45 50 55 60
100) are correctly protected against short circuit effects through a MCB (MCB Modular
Circuit Breaker) with a nominal current less or equal to the one of the busbar. K1 factor 1,15 1,12 1,08 1,05 1,025 1 0,975 0,95 0,93 0,89
This protection is assured up to MCB short circuit withstand.
Multiplier coefficient of nominal rating for room temperture values different from 40° C
The busbar trunking systems LB-HL-SL-MS are not flame propogating in
compliance with IEC 332-3: 1992.
For evenly distributed loads the maximum weight (kg) that can be supported is given in the tables below:
For point loads multiply the values in the below tables by 0,6.
Product in compliance to:
IEC 439-1 e 2, EN 60439 parte 1 e 2, fixing centres (span) m.
DIN VDE 0660 parte 500 e 502 maximum deflection = 1/250 x span m 2,5 3,0 3,5 4,0 4,5 5,0 5,5 6,0
kg 82,3 71,1 52,2 40,0 31,6 25,6 21,1 17,8
TECHNICAL DATA
139 ZUCCHINI
TECHNICAL DATA
40 63
Live conductors n° 4 4
Casing overal dimension A x B [mm] 26 x 62 26 x 62
Rated current In [A] 40 63
Cross-section of conductors (3P+N) S [mm2] 9,5 12,3
Cross-section of protective conductor eq. Cu SPE [mm2] 17 17
Operational voltage Ue [V] 400 400
Insulation voltage Ui [V] 750 750
Rated frequency f [Hz] 50/60 50/60
Rated short-time current (0,1 s) ICW [kA]rms 2,70 3,10
Peak current Ipk [kA] 10 10
Maximum thermal limit I2t [A2s x 106] 7,29 9,6
Phase resistance R20 [mΩ/m] 1,811 1,373
Phase reactance (50Hz) X [mΩ/m] 0,290 0,637
Phase impedance Z [mΩ/m] 1,834 1,514
Resistance of the protective bar RPE [mΩ/m] 0,870 0,870
Reactance of the protective bar (50Hz) XPE [mΩ/m] 0,090 0,087
Resistance of the fault loop Ro [mΩ/m] 2,68 2,24
Reactance of the fault loop (50Hz) Xo [mΩ/m] 0,380 0,724
Impedance of the fault loop Zo [mΩ/m] 2,71 2,36
∆V [V/m/A]10-3 cosϕ = 0,70 1,28 1,23
∆V1F = 1 (2 R20 cos ϕ + 2 X sen ϕ) ∆V [V/m/A]10-3 cosϕ = 0,75 1,34 1,26
2 ∆V [V/m/A]10-3 cosϕ = 0,80 1,41 1,28
Voltage drop with distribuited load (k) ∆V [V/m/A]10-3 cosϕ = 0,85 1,47 1,30
∆V [V/m/A]10-3 cosϕ = 0,90 1,52 1,31
∆V3F = √ 3 (R20 cos ϕ + X sen ϕ) ∆V [V/m/A]10-3 cosϕ = 0,95
2 1,57 1,30
∆V [V/m/A]10-3 cosϕ = 1,00 1,57 1,19
Straight length weight p [kg/m] 2,2 2,3
Fire load [kWh/m] 0,80 0,80
Protection degree IP 40/55 40/55
Losses for the Joule effect at full load P [W/m] 8,7 16,3
Ambient temperature min./MAX. t [°C] -5/+50 -5/+50
SHORT CIRCUIT PROTECTION FOR ZUCCHINI’S PRODUCT RANGES TEMPERATURE RATING SCHEDULE
(In≤100A)
Zucchini’s busbar system with a nominal current less or equal to 100A (LB-HL-SL-MS 63 and Mean room temperature [°C] 15 20 25 30 35 40 45 50 55 60
100) are correctly protected against short circuit effects through a MCB (MCB Modular
Circuit Breaker) with a nominal current less or equal to the one of the busbar. K1 factor 1,15 1,12 1,08 1,05 1,025 1 0,975 0,95 0,93 0,89
This protection is assured up to MCB short circuit withstand.
Multiplier coefficient of nominal rating for room temperture values different from 40° C
The busbar trunking systems LB-HL-SL-MS are not flame propogating in
compliance with IEC 332-3: 1992.
ZUCCHINI 140
TECHNICAL DATA
63 100 160
Live conductors n° 4 4 4
Casing overal dimension A x B [mm] 39 x 97 39 x 97 39 x 97
Rated current In [A] 63 100 160
Cross-section of conductors (3P+N) S [mm2] 26 26 39
Cross-section of protective conductor eq. Cu SPE [mm2] 21 21 21
Operational voltage Ue [V] 400 400 400
Insulation voltage Ui [V] 750 750 750
Rated frequency f [Hz] 50/60 50/60 50/60
Rated short-time current (0,1 s) ICW [kA]rms 2,30 4,50 5,50
Peak current Ipk [kA] 10 10 10
Maximum thermal limit I2t [A2s x 106] 5,29 20,25 30,25
Phase resistance R20 [mΩ/m] 1,250 0,658 0,478
Phase reactance (50Hz) X [mΩ/m] 0,366 0,366 0,247
Phase impedance Z [mΩ/m] 1,302 0,753 0,538
Resistance of the protective bar RPE [mΩ/m] 0,857 0,857 0,857
Reactance of the protective bar (50Hz) XPE [mΩ/m] 0,090 0,090 0,102
Resistance of the fault loop Ro [mΩ/m] 1,85 1,26 1,08
Reactance of the fault loop (50Hz) Xo [mΩ/m] 0,456 0,456 0,349
Impedance of the fault loop Zo [mΩ/m] 1,91 1,34 1,13
∆V [V/m/A]10-3 cosϕ = 0,70 0,98 0,63 0,44
∆V1F = 1 (2 R20 cos ϕ + 2 X sen ϕ) ∆V [V/m/A]10-3 cosϕ = 0,75 1,02 0,64 0,45
2 ∆V [V/m/A]10-3 cosϕ = 0,80 1,06 0,65 0,46
Voltage drop with distribuited load (k) ∆V [V/m/A]10-3 cosϕ = 0,85 1,09 0,65 0,46
∆V [V/m/A]10-3 cosϕ = 0,90 1,11 0,65 0,47
∆V3F = √ 3 (R20 cos ϕ + X sen ϕ) ∆V [V/m/A]10-3 cosϕ = 0,95
2 1,13 0,64 0,46
∆V [V/m/A]10-3 cosϕ = 1,00 1,08 0,57 0,41
Straight length weight p [kg/m] 2,0 2,6 2,8
Fire load [kWh/m] 1,64 1,64 1,64
Protection degree IP 40/55 40/55 40/55
Losses for the Joule effect at full load P [W/m] 14,9 19,7 36,7
Ambient temperature min./MAX. t [°C] -5/+50 -5/+50 -5/+50
SHORT CIRCUIT PROTECTION FOR ZUCCHINI’S PRODUCT RANGES TEMPERATURE RATING SCHEDULE
(In≤100A)
Zucchini’s busbar system with a nominal current less or equal to 100A (LB-HL-SL-MS 63 and Mean room temperature [°C] 15 20 25 30 35 40 45 50 55 60
100) are correctly protected against short circuit effects through a MCB (MCB Modular
Circuit Breaker) with a nominal current less or equal to the one of the busbar. K1 factor 1,15 1,12 1,08 1,05 1,025 1 0,975 0,95 0,93 0,89
This protection is assured up to MCB short circuit withstand.
Multiplier coefficient of nominal rating for room temperture values different from 40° C
The busbar trunking systems LB-HL-SL-MS are not flame propogating in
compliance with IEC 332-3: 1992.
141 ZUCCHINI
TECHNICAL DATA
ALUMINIUM
MR [3L+N+PE]
Rated current In [A] 160 250 315 400 500 630 800
Operational voltage Ue [V] 1000 1000 1000 1000 1000 1000 1000
Insulation voltage Ui [V] 1000 1000 1000 1000 1000 1000 1000
Frequency f [Hz] 50/60 50/60 50/60 50/60 50/60 50/60 50/60
Rated shortcircuit current withstand for 3-phase fault (1 s) ICW [kA]rms 15* 25* 25* 25 30 36 36
Specific Energy withstand for 3-phase fault I2t [M A2s] 23 63 63 625 900 1296 1296
Peak current Ipk [kA] 30 53 53 53 63 76 76
Rated short-time current for single-phase fault Ph-N(1 s) ICW [kA]rms 9* 15* 15* 15 18 22 22
Peak current for single-phase fault Ph-N Ipk [kA] 15 30 30 30 36 45 4a5
Rated short-time current single-phase fault Ph-PE (1 s) ICW [kA]rms 9* 15* 15* 15 18 22 22
Peak current single-phase fault Ph-PE Ipk [kA] 15 30 30 30 36 45 45
Phase resistance at 20 °C R20 [mΩ/m] 0,492 0,328 0,197 0,120 0,077 0,060 0,052
Phase resistance at thermal conditions (In; 40°C) Rt [mΩ/m] 0,665 0,443 0,266 0,163 0,104 0,081 0,070
Phase reactance (50 Hz) X [mΩ/m] 0,260 0,202 0,186 0,130 0,110 0,097 0,096
Neutral resistance at 20 °C Rn20 [mΩ/m] 0,492 0,328 0,197 0,120 0,077 0,060 0,052
Neutral reactance (50 Hz) Xn [mΩ/m] 0,260 0,202 0,186 0,130 0,110 0,097 0,096
Resistance of the protective bar RPE [mΩ/m] 0,341 0,341 0,341 0,283 0,283 0,283 0,283
Reactance of the protective bar (50 Hz) XPE [mΩ/m] 0,220 0,220 0,220 0,180 0,180 0,180 0,180
Resistance of the phase-Pe fault loop RPh-Pe fault loop [mΩ/m] 1,006 0,784 0,607 0,445 0,387 0,364 0,353
Reactance of the phase-Pe fault loop (50 Hz) XRPh-Pe fault loop [mΩ/m] 0,480 0,414 0,396 0,333 0,333 0,283 0,275
Resistance of the phase-neutral fault loop RPh-N fault loop [mΩ/m] 1,157 0,771 0,463 0,283 0,181 0,141 0,121
Reactance of the phase-neutral fault loop (50 Hz) XRPh-N fault loop [mΩ/m] 0,480 0,422 0,406 0,310 0,290 0,277 0,276
∆v [V/m/A]10-3 cosϕ = 0,70 0,564 0,394 0,276 0,179 0,131 0,109 0,102
∆v [V/m/A]10-3 cosϕ = 0,75 0,581 0,404 0,279 0,180 0,130 0,108 0,100
Voltage “k” drop coeff. with ∆v [V/m/A]10-3 cosϕ = 0,80 0,596 0,412 0,281 0,180 0,129 0,107 0,098
distribuited load (k) ∆v [V/m/A]10-3 cosϕ = 0,85 0,608 0,418 0,281 0,179 0,127 0,104 0,095
∆v [V/m/A]10-3 cosϕ = 0,90 0,616 0,422 0,277 0,176 0,122 0,100 0,091
∆v [V/m/A]10-3 cosϕ = 0,95 0,617 0,419 0,269 0,169 0,115 0,093 0,083
∆v [V/m/A]10-3 cosϕ = 1,00 0,576 0,384 0,230 0,141 0,090 0,070 0,060
Losses for the Joule effect at nominal current P [W/m] 51 83 79 78 78 97 134
Fire load [kWh/m] 1,3 1,3 1,3 1,8 1,8 1,8 1,8
Weight p [kg/m] 7,4 7,7 8,4 10,7 12,3 13,8 14,7
Overall dimensions of the busbar LxH [mm] 76x195 76x195 76x195 136x195 136x195 136x195 136x195
Degree of protection(CEI EN60529) IP 52-55 52-55 52-55 52-55 52-55 52-55 52-55
IK code CEI EN60068-2-62 IK 10 10 10 10 10 10 10
Coordination table with Megatiker Bticino at page 147 TEMPERATURE RATING SCHEDULE
Multiplier coefficient of nominal rating for room temperture values different from 40° C
ZUCCHINI 142
TECHNICAL DATA
COPPER
MR [3L+N 100%+PE]
Coordination table with Megatiker Bticino at page 147 TEMPERATURE RATING SCHEDULE
Multiplier coefficient of nominal rating for room temperture values different from 40° C
143 ZUCCHINI
TECHNICAL DATA
SHORT CIRCUIT PROTECTION FOR ZUCCHINI’S PRODUCT RANGES TEMPERATURE RATING SCHEDULE
(In≤100A)
Zucchini’s busbar system with a nominal current less or equal to 100A (LB-HL-SL-MS 63 and Mean room temperature [°C] 15 20 25 30 35 40 45 50 55 60
100) are correctly protected against short circuit effects through a MCB (MCB Modular
K1 factor 1,15 1,12 1,08 1,05 1,025 1 0,975 0,95 0,93 0,89
Circuit Breaker) with a nominal current less or equal to the one of the busbar.
This protection is assured up to MCB short circuit withstand. Multiplier coefficient of nominal rating for room temperture values different from 40° C
The busbar trunking systems LB-HL-SL-MS are not flame propogating in
compliance with IEC 332-3: 1992.
ZUCCHINI 144
CALCULATION OF CURRENT RATING
In order to determine the current rating certain planning data must be known in VOLTAGE DROP
advance: If the length of the run is particularly long it is necessary to check the voltage drop (vd).
For installations with a three phase system and a power factor (cos ϕ) not lower than 0.7 the
• type of load inputs: three phase or single phase; three phases voltage drop may be calculated with the coefficients of the voltage drop in the
• type of circuit input: from one end, from both ends, central input, etc ; technical table.
• Nominal input voltage;
k . Ib . L .
• number, power and cosϕ of loads which are to be fed by the busbar;
• load diversity factor; ∆v% = 2 . a 100
• load use nominal factor; Vn . 103
• input point short circuit current,
• room temperature;
• busbar orientation. defined
Ib = the current that supplies the busbar [A]
The current rating in case of a three phase supply is determined by the following for- Vn = the voltage supply of the busbar [V]
mula: L = the length of the line [m]
∆v% = the voltage drop percentage
a = the distribution factor of current [.]
PTOT • α • β • b k = the coefficient stated in the table that it corresponds to coϕ [ V/m/A]
Ib = [A]
√3 • Ue • cosϕmedium The current distribution factor “a” depends on how the circuit is fed and the distribution of the
loads along the busbar.
where:
Ib current rating [A]; Ib
a =1 feed from one end only with load Ib
α load contemporaneity factor [.]; concentrated at one end L
β load use factor [.];
Ib
b feed factor [.]; a =1/2 feed from one end only with
PTOT sum of the total active power of installed loads [W]; load uniformly distributed L
Ue operational voltage [V];
Ib Ib
cosϕmedium average load power factor [.]; a =1/4 feed from both end only with
uniform load distribution L
Ib
a =1/4 central feed with load concentrated I_b I_b
The “b” input factor has a value 1 in the case of busbar fed from one end only. at one and ...... 2
The value is 1/2 if fed from the centre or if it is fed from each end. L 2
Ib
Once the operating current has been determined, choose the busbar with a nominal current a =1/8 central feed with load uniformly distributed
rating immediately greater than the one calculated.
In the case where the room temperature is other than 40 °C, the nominal rating of the busbar
must be adjusted as follows. ex: MR 400 Al
All Zucchini products have been designed and tested for an average room temperature of 40 Ib= 80A operational voltage
°C, should they be installed in rooms with average daily temperatures different than 40 °C b=1 end feed unit from one end
k . Ib . L .
the nominal current of the busbar should be multiplied by a k1 that is greater than the unit ∆v% = b 100 =
for lower temperatures at 40°C and lower than the unit if the room temperature is higher
k=0,608 see table technical data
Vn . 103
than 40°C. Cosϕ = 0,85
L= 100m the length of line
Vn= 400V the voltage supply of the busbar
The table below lists the correction coefficients of loads for installation in rooms 179 . 350 . 100 .
where the average daily temperature is between 15 °C and 50 °C. ∆v% = 100 = 1,57%
400 . 106
Room
temperature [°C] 15 20 25 30 35 40 45 50 55 60
SHORT CIRCUIT CURRENT
Thermal correction The nominal short circuit current value which the busbar trunking can withstand makes provi-
1,15 1,12 1,08 1,05 1,025 1 0,975 0,95 0,93 0,89
k1 factor [.] sion for both electrodynamic stress and thermal energy dissipated during the fault. The busbar
must be able to sustain the short circuit current for the entire duration of the fault i.e for the
time required for the protection device to intervene, cutting off the metal continuity and extin-
Finally, the following should be considered for the most appropriate busbar choice: guishing the electric arch. The electrodynamic stresses are directly proportional to the product
of the instant current value which affects the line and is not proportional to the spacing of the
bars.
where Int stands as maximum current loaded by a busbar for an indefinite time at the envi- While in the single-phase system.
ronmental specified temperature. P = 3 Rt Ib 10 [W/m]
• •
2
•
-3
P = 2 Rt Ib2 10-3 [W/m]
• • •
I 2
TECHNICAL DATA
d1 d2 Cable
CERAMIC FUSE 5 x 20
FUSE
• In = 6,3 A
Operating characteristics
20
ZUCCHINI 146
COORDINATION TABLE
between BTicino switches
and Zucchini Busbar Trunking System
SL SL MS MS MS MR MR MR MR MR MR MR MR
40A 63A 100A 160A 250A 315A 400A 500A 630A 800A 1000A
MA 125 - 40A 16 16
ME 125B - 40A 25 25
ME 125N - 40A 36 36
MA 125 - 63A 16 16
ME 125B - 63A 25 25
ME 125N - 63A 36 36
MA 125 - 100A 16
ME 125B - 100A 25
ME 125N - 100A 36
ME 160B - 160A 25 25
ME 160N - 160A 36 36
ME 160H - 160A 50 50
ME 250B - 250A 25 25
ME 250N - 250A 36 36
Megatiker ME 250H - 250A 50 50
Bticino
MA 250 - 250A 36 36
MH 250 - 250A 70 70
ML 250 - 250A 100 100
MA 400 - 400A 36 36
MH 400 - 400A 70 70
ML 400 - 400A 100 100
MA 630 - 630A 36 36
MH 630 - 630A 70 70
ML 630 - 630A 100 100
MA 1250 - 800A 50 50
MH 1250 - 800A 70 70
ML 1250 - 800A 100 100
MA 1250 - 1000A 50 50
MH 1250 - 1000A 70 70
ML 1250 - 1000A 100 100