Models:

ACC 10 C/CR
ACC 15 C/CR
ACC 20 C/CR
ACC 25 C/CR
ACC 30 C/CR
ACC 40 C/CR
ACC 50 C/CR
ACC 60 C/CR

Ceiling Concealed
Split Systems
Manual No: TMA-ACC-CR-1200C
CONTENTS

1. FEATURES ................................................................................................................. 3

2. SPECIFICATIONS .......................................................................................................4

3. NOISE LEVEL ............................................................................................................12

4. OPERATION RANGE ................................................................................................12

5. PERFORMANCE TABLE ...........................................................................................13

6. FAN PERFORMANCE CURVE ..................................................................................15

7. OUTLINES AND DIMENSIONS ................................................................................. 17

8. WIRING DIAGRAMS ................................................................................................. 21

9. SPECIAL PRECAUTIONS FOR R407C .................................................................... 51

10. INSTALLATION ........................................................................................................53

11. OPERATION ........................................................................................................... 56

12. REMOTE CONTROL OPERATION GUIDE ............................................................ 60

13. SERVICING AND MAINTENANCE ..........................................................................61

14. TROUBLESHOOTING .............................................................................................63

15. PARTS LIST .............................................................................................................68

1
1. FEATURES

SPACE SAVING, ELEGANCE AND PRESTIGE


The unit is installed above the ceiling with only the supply and return air grille exposed to view. This ceiling concealed
type of design has made it an “Evergreen” model without sacrificing the precious floor space.

The air-conditioned space will appear as elegant and prestigious as centralized air-conditioned area but with only a
fraction of the cost. This model is ideal for small offices, hotel rooms, hospitals and restaurant applications.

DOUBLE PROTECTION DRAINAGE SYSTEM


High humidity inside the ceiling area is always the main cause of water leaking. By introducing “Built In” double drain
pans solution, i.e. primary drain pan and secondary drain pan, water leaking will not be a problem anymore. The high
quality Polystyrene (PS) primary drain pan come with a layer of thermal forming High Impact Polystyrene (HIPS) coating.

The primary drain pan is specially designed, with mould in gradient, for better condensate water drainage. Furthermore,
the drain pan is made of PS, which is a very good insulation material to prevent sweating. The secondary drain pan will
act as a drip pan to block any water that might be dripped down thus offering an additional protection to the ceiling. In
such a case, additional drain pan will not be necessary during installation which means more cost saving. A drain socket
is supplied to connect both drain pans to the drainage pipe.

EASY AND FLEXIBLE INSTALLATION


The physical height of the unit is only 261mm / 378mm, it is therefore offering greatest flexibility in selecting installation
location.

With its special designed installation accessories, the installation job become easy and better air distribution can be
achieved without extra spending on duct works.

EASY MAINTENANCE
The simple design concept has a friendly maintenance and servicing in mind. Just loosening a few screws, remove
secondary drain pan and drain guide, you can access to all the internal parts from the bottom of the unit. No water will
splash down when removing the secondary drain pan makes the servicing work never easier before.

MEDIUM STATIC PRESSURE WITH A LOW NOISE LEVEL


This new series has a static pressure between 0 to 15 mmAq depend on duct work installation. The casing is well
insulated internally to reduce the noise level.

2
2. SPECIFICATIONS

CEILING CONCEALED COOLING ONLY MODELS


MODEL INDOOR UNIT ACC 10C ACC 15C ACC 20C ACC 25C
OUTDOOR UNIT ALC 10B ALC 15B ALC 20B ALC 25B
NOMINAL kcal/h 2,444 3,200 4,914 6,300
COOLING W 2,843 3,722 5,715 7,327
CAPACITY Btu/h 9,700 12,700 19,500 25,000
POWER SOURCE V/Ph/Hz 220 - 240 / 1 / 50, 208 -230 / 1 / 60
REFRIGERANT / CONTROL R22 / CAPILLARY TUBE IN OUTDOOR
AIR FLOW cfm/cmm 300 / 8.50 430 / 12.2 620 / 17.0 840 / 23.8
STATIC PRESSURE mm Aq 5 5 5 5
50 Hz
FAN

4 POLES x 22W 4 POLES x 30W 4 POLES x 55W 4 POLES x 100W


FAN MOTOR
60 Hz 4 POLES x 30W 4 POLES x 50W 4 POLES x 80W 4 POLES x 100W
RATED INPUT POWER W (50/60Hz) 71 / 72 102 / 114 148 / 172 180 / 223
RATED RUNNING CURRENT A (50/60Hz) 0.30 / 0.33 0.43 / 0.53 0.65 / 0.80 0.77 / 1.01
MATERIAL SEAMLESS COPPER
TUBE

DIAMETER mm/in 9.52 / 3/8


THICKNESS mm/in 0.35 / 0.014
INDOOR UNIT

MATERIAL
COIL

ALUMINIUM
THICKNESS mm/in 0.11 / 0.0043
FIN

ROW 3 3 3 3
FIN PER INCH 12 14 12 12
2 2
FACE AREA m /ft 0.115 / 1.238 0.143 / 1.542 0.176 / 1.892 0.203 / 2.187
HEIGHT mm/in 261 / 10.28 261 / 10.28 261 / 10.28 261 / 10.28
DIMENSION WIDTH mm/in 765 / 30.12 905 / 35.63 1,065 / 41.93 1,200 / 47.24
DEPTH mm/in 411 / 16.18 411 / 16.18 411 / 16.18 411 / 16.18
WEIGHT kg 17 21 22 25
CONTROL ROOM TEMPERATURE MICROCOMPUTER CONTROLLED THERMOSTAT
OPERATION SLM WIRED HANDSET (OPTIONAL AC5300 REMOTE CONTROLLER)
CONDENSATE DRAIN SIZE mm/in 19.05 / 3/4
AIR FILTER WASHABLE SARAN NET (OPTIONAL)
PACKING HEIGHT mm/in 410 / 16.14 410 / 16.14 410 / 16.14 410 / 16.14
DIMENSION WIDTH mm/in 951 / 37.44 1,091 / 42.95 1,251 / 49.25 1,386 / 54.57
DEPTH mm/in 535 / 21.06 535 / 21.06 535 / 21.06 535 / 21.06
POWER SOURCE V/Ph/Hz 220 - 240 / 1 / 50 , 208 - 230 / 1 / 60
COMPRESSOR TYPE ROTARY HERMETIC ROT./RECIP. HER.
50 Hz 30 30 45 45 / 45
CAPACITOR (µµF)
60 Hz 30 30 40 35 (RECIP)
COMPRESSOR

50 Hz 20 25 56 56.5 / 68
LOCK ROTOR AMP. (A)
60 Hz 26 33 37 70 (RECIP)
50 Hz 3.60 5.80 10.00 13.80 / 10.53
RATED RUNNING CURRENT (A)
60 Hz 3.90 4.90 8.75 12.26 (RECIP)
50 Hz 812 1,277 2,080 2,710 / 2,250
RATED INPUT POWER (W)
60 Hz 843 1,055 1,909 2,635 (RECIP)
PROTECTION DEVICE OVERLOAD PROTECTION
FAN TYPE / DRIVE PROPELLER / DIRECT
BLADE MATERIAL GLASS REINFORCED ACRYL STYRENE RESIN
DIAMETER mm/in
FAN

355 / 14.0 420 / 16.5


RATED RUNNING CURRENT A (50/60Hz) 0.20 / 0.33 0.28 / 0.33 0.56 / 0.76
RATED OUTPUT POWER W (50/60Hz) 20 / 30 30 / 30 55 / 55
RATED INPUT POWER W (50/60Hz)
OUTDOOR UNIT

50 / 68 62 / 68 133 / 165
MATERIAL S.I.G.C S.I.G.C S.B.C. S.I.G.C
TUBE

DIAMETER mm/in 9.52 / 3/8


THICKNESS mm/in 0.35 / 0.014 0.36 / 0.014 AVERAGE
MATERIAL
COIL

ALUMINIUM (SLIT TYPE)


THICKNESS mm/in 0.127 / 0.005
FIN

ROW 1 1 2 2
FIN PER INCH 18 19 14 14
2 2
FACE AREA m /ft 0.32 / 3.5 0.51 / 5.53
HEIGHT mm/in 494 / 19.4 646 / 25.4
DIMENSION WIDTH mm/in 740 / 29.1 840 / 33.1
DEPTH mm/in 270 / 10.6 330 / 13.0
WEIGHT kg 31 34 57 58
MATERIAL GALVANISED MILD STEEL
CASING THICKNESS mm/in 0.8 / 0.031
FINISHING POLYESTER POWDER
TYPE FLARE VALVE
PIPE

SIZE LIQUID mm/in 6.35 / 1/4 6.35 / 1/4 6.35 / 1/4 9.52 / 3/8
GAS mm/in 9.52 / 3/8 12.70 / 1/2 15.88 / 5/8 15.88 / 5/8
PACKING HEIGHT mm/in 558 / 22.0 710 / 28.0
DIMENSION WIDTH mm/in 851 / 33.5 957 / 37.7
DEPTH mm/in 401 / 15.8 461 / 18.1

1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.
2) ALL UNITS ARE BEING TESTED AND COMPLY TO ARI 210/240-89
3) NOMINAL COOLING AND HEATING CAPACITY ARE BASED ON THE CONDITIONS BELOW :
a) COOLING - 26.7°C DB / 19.4°C WB INDOOR AND 35°C DB OUTDOOR
4) ALLOWABLE OPERATING RANGE
a) COOLING - 19.4°C DB / 13.9°C WB INDOOR AND 19.4°C DB OUTDOOR TO
26.7°C DB / 19.4°C WB INDOOR AND 46.1°C DB OUTDOOR

Abbreviation
S.B.C. - SEAMLESS BARE COPPER
S.I.G.C - SEAMLESS INNER GROOVE COPPER

3
CEILING CONCEALED COOLING ONLY MODELS
MODEL INDOOR UNIT ACC 30C ACC 40C ACC 50C ACC 60C
OUTDOOR UNIT ALC 30C ALC 40C ALC 50C ALC 60C
NOMINAL kcal/h 7,560 10,080 12,600 15,120
COOLING W 8,790 11,720 14,650 17,580
CAPACITY Btu/h 30,000 40,000 50,000 60,000
POWER SOURCE V/Ph/Hz 220 - 240 / 1 / 50
REFRIGERANT / CONTROL R22 / CAPILLARY TUBE IN INDOOR
AIR FLOW cfm/cmm 900 / 25.49 1,200 / 33.99 1,500 / 42.49 1,800 / 50.99
STATIC PRESSURE mm Aq 15 / 10 / 5
FAN

FAN MOTOR 4 POLES


RATED INPUT POWER W 421 550 670 748
RATED RUNNING CURRENT A 1.9 2.6 2.9 3.2
MATERIAL SEAMLESS BARE COPPER
TUBE

DIAMETER mm/in 9.52 / 3/8


THICKNESS mm/in 0.35 / 0.014
COIL

MATERIAL
INDOOR UNIT

ALUMINIUM
THICKNESS mm/in 0.127 / 0.005
FIN

ROW 3 3 3 3
FIN PER INCH 12 14 14 14
2 2
FACE AREA m /ft 0.27 / 2.98 0.31 / 3.44 0.40 / 4.40 0.47 / 5.16
HEIGHT mm/in 370 / 14.57 370 / 14.57 370 / 14.57 370 / 14.57
DIMENSION WIDTH mm/in 919 / 36.18 1,039 / 40.91 1,289 / 50.75 1,489 / 58.62
DEPTH mm/in 589 / 23.19 589 / 23.19 589 / 23.19 589 / 23.19
WEIGHT kg 39 42 54 62
CONTROL ROOM TEMPERATURE MICROCOMPUTER CONTROLLED THERMOSTAT
OPERATION SLM WIRED HANDSET (OPTIONAL AC5300 REMOTE CONTROLLER)
CONDENSATE DRAIN SIZE mm/in 19.05 / 3/4
AIR FILTER WASHABLE SARAN NET
PACKING HEIGHT mm/in 675 / 26.57 675 / 26.57 675 / 26.57 675 / 26.57
DIMENSION WIDTH mm/in 1,089 / 42.87 1,209 / 47.60 1,459 / 57.44 1,659 / 65.31
DEPTH mm/in 440 / 17.32 440 / 17.32 440 / 17.32 440 / 17.32
POWER SOURCE V/Ph/Hz 220 - 240 / 1 / 50 380 - 415 / 3 / 50
COMPRESSOR TYPE RECIPROCATING HERMETIC SCROLL
CAPACITOR µF 45 - - -
COMP.

LOCK ROTOR AMP. A 85 45 62 74


RATED RUNNING CURRENT A 13.0 6.0 8.1 8.2
RATED INPUT POWER W 2,650 3,380 4,694 4,750
PROTECTION DEVICE OVERLOAD PROTECTION / HI-LO PRESSURE SWITCH
FAN TYPE / DRIVE PROPELLER / DIRECT
BLADE MATERIAL GLASS REINFORCED ACRYL STYRENE RESIN
DIAMETER mm/in 610 / 24
FAN

RATED RUNNING CURRENT A 1.09 1.8


RATED OUTPUT POWER W 145 400
RATED INPUT POWER W 241 420
MATERIAL S.B.C. S.I.G.C
TUBE
OUTDOOR UNIT

DIAMETER mm/in 9.52 / 3/8


THICKNESS mm/in 0.35 / 0.014
COIL

MATERIAL ALUMINIUM (CORRUGATED) ALUMINIUM (SLIT)


THICKNESS mm/in 0.127 / 0.005
FIN

ROW 1 2 2 2
FIN PER INCH 16 14 16 16
2 2
FACE AREA m /ft 0.89 / 9.56 0.88 / 9.33
HEIGHT mm/in 850 / 33.46
DIMENSION WIDTH mm/in 1,030 / 40.55
DEPTH mm/in 400 / 15.75
WEIGHT kg 93 100 105 107
MATERIAL ELECTRO-GALVANISED MILD STEEL
CASING THICKNESS mm/in 0.8 / 0.031
FINISHING POLYESTER POWDER
TYPE FLARE VALVE
PIPE

SIZE LIQUID mm/in 9.52 / 3/8 9.52 / 3/8 9.52 / 3/8 12.7 / 1/2
GAS mm/in 15.88 / 5/8 19.05 / 3/4 19.05 / 3/4 19.05 / 3/4
PACKING HEIGHT mm/in 1,000 / 39.37
DIMENSION WIDTH mm/in 1,200 / 47.24
DEPTH mm/in 560 / 22.05

1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.
2) ALL UNITS ARE BEING TESTED AND COMPLY TO ARI 210/240-89
3) NOMINAL COOLING AND HEATING CAPACITY ARE BASED ON THE CONDITIONS BELOW :
a) COOLING - 26.7°C DB / 19.4°C WB INDOOR AND 35°C DB OUTDOOR
4) ALLOWABLE OPERATING RANGE
a) COOLING - 19.4°C DB / 13.9°C WB INDOOR AND 19.4°C DB OUTDOOR TO
26.7°C DB / 19.4°C WB INDOOR AND 46.1°C DB OUTDOOR

Abbreviation
S.B.C. - SEAMLESS BARE COPPER
S.I.G.C - SEAMLESS INNER GROOVE COPPER

4
CEILING CONCEALED HEAT PUMP MODELS
MODEL INDOOR UNIT ACC 10CR ACC 15CR ACC 20CR ACC 25CR
OUTDOOR UNIT ALC 10BR ALC 15BR ALC 20BR ALC 25BR
NOMINAL kcal/h 2,394 3,200 4,788 5,796
COOLING W 2,784 3,722 5,569 6,741
CAPACITY Btu/h 9,500 12,700 19,000 23,000
NOMINAL kcal/h 2,394 3,276 4,990 6,300
HEATING W 2,784 3,810 5,803 7,327
CAPACITY Btu/h 9,500 13,000 19,800 25,000
POWER SOURCE V/Ph/Hz 220 - 240 / 1 / 50, 208 - 230 / 1 / 60
REFRIGERANT / CONTROL R22 / CAPILLARY TUBE IN OUTDOOR
AIR FLOW cfm/cmm 300 / 8.50 430 / 12.2 620 / 17.0 840 / 23.8
STATIC PRESSURE mm Aq 5 5 5 5
50 Hz
FAN

4 POLES x 22W 4 POLES x 30W 4 POLES x 55W 4 POLES x 100W


FAN MOTOR
60 Hz 4 POLES x 30W 4 POLES x 50W 4 POLES x 80W 4 POLES x 100W
RATED INPUT POWER W (50/60Hz) 71 / 72 102 / 114 148 / 172 180 / 223
RATED RUNNING CURRENT A (50/60Hz) 0.30 / 0.33 0.43 / 0.53 0.65 / 0.80 0.77 / 1.01
MATERIAL SEAMLESS COPPER
TUBE

DIAMETER mm/in 9.52 / 3/8


THICKNESS mm/in 0.35 / 0.014
MATERIAL
COIL

ALUMINIUM
INDOOR UNIT

THICKNESS mm/in 0.11 / 0.0043


FIN

ROW 3 3 3 3
FIN PER INCH 12 14 12 12
FACE AREA m2 /ft2 0.115 / 1.238 0.143 / 1.542 0.176 / 1.892 0.203 / 2.187
HEIGHT mm/in 261 / 10.28 261 / 10.28 261 / 10.28 261 / 10.28
DIMENSION WIDTH mm/in 765 / 30.12 905 / 35.63 1,065 / 41.93 1,200 / 47.24
DEPTH mm/in 411 / 16.18 411 / 16.18 411 / 16.18 411 / 16.18
WEIGHT kg 17 21 22 25
CONTROL ROOM TEMPERATURE MICROCOMPUTER CONTROLLED THERMOSTAT
OPERATION SLM WIRED HANDSET (OPTIONAL AC5300 REMOTE CONTROLLER)
CONDENSATE DRAIN SIZE mm/in 19.05 / 3/4
AIR FILTER WASHABLE SARAN NET (OPTIONAL)
PACKING HEIGHT mm/in 410 / 16.14 410 / 16.14 410 / 16.14 410 / 16.14
DIMENSION WIDTH mm/in 951 / 37.44 1,091 / 42.95 1,251 / 49.25 1,386 / 54.57
DEPTH mm/in 535 / 21.06 535 / 21.06 535 / 21.06 535 / 21.06
POWER SOURCE V/Ph/Hz 220 - 240 / 1 / 50, 208 - 230 / 1 / 60
COMPRESSOR TYPE ROTARY HERMETIC
CAPACITOR µF (50/60Hz) 30 / - 30 / - 45 / 40 45 / 60
LOCK ROTOR AMP. A (50/60Hz) 20 / - 25 / - 56 / 39.6 57 / 50
COMP.

RATED RUNNING CURRENT (COOLING) A (50/60Hz) 3.70 / - 5.60 / - 9.84 / 8.30 13.00 / 11.60
RATED RUNNING CURRENT (HEATING) A (50/60Hz) 3.00 / - 5.30 / - 9.84 / 8.70 12.70 / 11.40
RATED INPUT POWER (COOLING) W (50/60Hz) 828 / - 1,236 / - 1,987 / 1,777 2,730 / 2,486
RATED INPUT POWER (HEATING) W (50/60Hz) 681 / - 1,169 / - 2,008 / 1,824 2,650 / 2,420
PROTECTION DEVICE OVERLOAD PROTECTION
FAN TYPE / DRIVE PROPELLER / DIRECT
BLADE MATERIAL GLASS REINFORCED ACRYL STYRENE RESIN
DIAMETER mm/in
FAN

355 / 14.0 420 / 16.5


RATED RUNNING CURRENT A (50/60Hz) 0.28 / 0.33 0.56 / 0.76
RATED OUTPUT POWER W (50/60Hz) 30 / 30 55 / 55
RATED INPUT POWER W (50/60Hz) 62 / 68 133 / 165
MATERIAL S.I.G.C S.I.G.C S.B.C. S.I.G.C
OUTDOOR UNIT

TUBE

DIAMETER mm/in 9.52 / 3/8


THICKNESS mm/in 0.35 / 0.014 0.36 / 0.014 AVERAGE
MATERIAL
COIL

ALUMINIUM
THICKNESS mm/in 0.127 / 0.005
FIN

ROW 1 1 2 2
FIN PER INCH 19 19 14 14
2 2
FACE AREA m /ft 0.32 / 3.5 0.51 / 5.53
HEIGHT mm/in 494 / 19.4 646 / 25.4
DIMENSION WIDTH mm/in 740 / 29.1 840 / 33.1
DEPTH mm/in 270 / 10.6 330 / 13.0
WEIGHT kg 31 34 57 58
MATERIAL GALVANISED MILD STEEL
CASING THICKNESS mm/in 0.8 / 0.031
FINISHING POLYESTER POWDER
TYPE FLARE VALVE
PIPE

SIZE LIQUID mm/in 6.35 / 1/4 6.35 / 1/4 6.35 / 1/4 9.52 / 3/8
GAS mm/in 9.52 / 3/8 12.70 / 1/2 15.88 / 5/8 15.88 / 5/8
PACKING HEIGHT mm/in 558 / 22.0 710 / 28.0
DIMENSION WIDTH mm/in 851 / 33.5 957 / 37.7
DEPTH mm/in 401 / 15.8 461 / 18.1

1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.
2) ALL UNITS ARE BEING TESTED AND COMPLY TO ARI 210/240-89
3) NOMINAL COOLING AND HEATING CAPACITY ARE BASED ON THE CONDITIONS BELOW :
a) COOLING - 26.7°C DB / 19.4°C WB INDOOR AND 35°C DB OUTDOOR
b) HEATING - 21.1°C DB / 15.6°C WB INDOOR AND 8.3°C DB / 6.1°C WB OUTDOOR
4) ALLOWABLE OPERATING RANGE
a) COOLING - 19.4°C DB / 13.9°C WB INDOOR AND 19.4°C DB OUTDOOR TO
26.7°C DB / 19.4°C WB INDOOR AND 46.1°C DB OUTDOOR
b) HEATING - 21.0°C DB INDOOR AND -8.3°C DB / -9.4°C WB OUTDOOR TO
26.7°C DB INDOOR AND 23.9°C DB / 18.3°C WB

Abbreviation
S.B.C. - SEAMLESS BARE COPPER
S.I.G.C - SEAMLESS INNER GROOVE COPPER

5
CEILING CONCEALED HEAT PUMP MODELS
MODEL INDOOR UNIT ACC 30CR ACC 40CR ACC 50CR ACC 60CR
OUTDOOR UNIT ALC 30CR ALC 40CR ALC 50CR ALC 60CR
NOMINAL kcal/h 7,560 10,080 12,600 14,620
COOLING W 8,790 11,720 14,650 16,990
CAPACITY Btu/h 30,000 40,000 50,000 58,000
NOMINAL kcal/h 8,317 10,459 13,105 16,633
HEATING W 9,672 12,163 15,240 19,343
CAPACITY Btu/h 33,000 41,500 52,000 66,000
POWER SOURCE V/Ph/Hz 220 - 240 / 1 / 50
REFRIGERANT / CONTROL R22 / CAPILLARY TUBE IN INDOOR
AIR FLOW cfm/cmm 900 / 25.49 1,200 / 33.99 1,500 / 42.49 1,800 / 50.99
STATIC PRESSURE mm Aq 15 / 10 / 5
FAN

FAN MOTOR 4 POLES


RATED INPUT POWER W 421 550 670 748
RATED RUNNING CURRENT A 1.9 2.6 2.9 3.2
MATERIAL SEAMLESS BARE COPPER
TUBE

DIAMETER mm/in 9.52 / 3/8


THICKNESS mm/in 0.35 / 0.014
COIL

MATERIAL ALUMINIUM
INDOOR UNIT

THICKNESS mm/in 0.127 / 0.005


FIN

ROW 3 3 3 3
FIN PER INCH 12 14 14 14
FACE AREA m2/ft2 0.27 / 2.98 0.31 / 3.44 0.40 / 4.40 0.47 / 5.16
HEIGHT mm/in 370 / 14.57 370 / 14.57 370 / 14.57 370 / 14.57
DIMENSION WIDTH mm/in 919 / 36.18 1,039 / 40.91 1,289 / 50.75 1,489 / 58.62
DEPTH mm/in 589 / 23.19 589 / 23.19 589 / 23.19 589 / 23.19
WEIGHT kg 39 42 54 62
CONTROL ROOM TEMPERATURE MICROCOMPUTER CONTROLLED THERMOSTAT
OPERATION SLM WIRED HANDSET (OPTIONAL AC5300 REMOTE CONTROLLER)
CONDENSATE DRAIN SIZE mm/in 19.05 / 3/4
AIR FILTER WASHABLE SARAN NET
PACKING HEIGHT mm/in 675 / 26.57 675 / 26.57 675 / 26.57 675 / 26.57
DIMENSION WIDTH mm/in 1,089 / 42.87 1,209 / 47.60 1,459 / 57.44 1,659 / 65.31
DEPTH mm/in 440 / 17.32 440 / 17.32 440 / 17.32 440 / 17.32
POWER SOURCE V/Ph/Hz 220 - 240 / 1 / 50 380 - 415 / 3 / 50
COMPRESSOR TYPE RECIPROCATING HERMETIC SCROLL
CAPACITOR µF 45 - - -
LOCK ROTOR AMP. A 85 45 62 74
COMP.

RATED RUNNING CURRENT (COOLING) A 13.0 6.0 8.1 8.2


RATED RUNNING CURRENT (HEATING) A 11.8 5.5 6.8 7.2
RATED INPUT POWER (COOLING) W 2,650 3,380 4,694 4,750
RATED INPUT POWER (HEATING) W 2,270 2,930 3,760 3,920
PROTECTION DEVICE OVERLOAD PROTECTION / HI-LO PRESSURE SWITCH
FAN TYPE / DRIVE PROPELLER / DIRECT
BLADE MATERIAL GLASS REINFORCED ACRYL STYRENE RESIN
FAN

DIAMETER mm/in 610 / 24


RATED RUNNING CURRENT A 1.09 1.8
RATED OUTPUT POWER W 145 400
RATED INPUT POWER W 241 420
OUTDOOR UNIT

MATERIAL S.B.C. S.I.G.C


TUBE

DIAMETER mm/in 9.52 / 3/8


THICKNESS mm/in 0.35 / 0.014
COIL

MATERIAL ALUMINIUM (CORRUGATED) ALUMINIUM (SLIT)


THICKNESS mm/in 0.127 / 0.005
FIN

ROW 1 2 2 2
FIN PER INCH 16 14 16 16
2 2
FACE AREA m /ft 0.89 / 9.56 0.88 / 9.33
HEIGHT mm/in 850 / 33.46
DIMENSION WIDTH mm/in 1,030 / 40.55
DEPTH mm/in 400 / 15.75
WEIGHT kg 93 100 105 107
MATERIAL ELECTRO-GALVANISED MILD STEEL
CASING THICKNESS mm/in 0.8 / 0.031
FINISHING POLYESTER POWDER
TYPE FLARE VALVE
PIPE

SIZE LIQUID mm/in 9.52 / 3/8 9.52 / 3/8 9.52 / 3/8 12.7 / 1/2
GAS mm/in 15.88 / 5/8 19.05 / 3/4 19.05 / 3/4 19.05 / 3/4
PACKING HEIGHT mm/in 1,000 / 39.37
DIMENSION WIDTH mm/in 1,200 / 47.24
DEPTH mm/in 560 / 22.05

1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.
2) ALL UNITS ARE BEING TESTED AND COMPLY TO ARI 210/240-89
3) NOMINAL COOLING AND HEATING CAPACITY ARE BASED ON THE CONDITIONS BELOW :
a) COOLING - 26.7°C DB / 19.4°C WB INDOOR AND 35°C DB OUTDOOR
b) HEATING - 21.1°C DB / 15.6°C WB INDOOR AND 8.3°C DB / 6.1°C WB OUTDOOR
4) ALLOWABLE OPERATING RANGE
a) COOLING - 19.4°C DB / 13.9°C WB INDOOR AND 19.4°C DB OUTDOOR TO
26.7°C DB / 19.4°C WB INDOOR AND 46.1°C DB OUTDOOR
b) HEATING - 21.0°C DB INDOOR AND -8.3°C DB / -9.4°C WB OUTDOOR TO
26.7°C DB INDOOR AND 23.9°C DB / 18.3°C WB
Abbreviation
S..B.C. - SEAMLESS BARE COPPER
S.I.G.C - SEAMLESS INNER GROOVE COPPER

6
CEILING CONCEALED COOLING ONLY MODELS (R407C)
MODEL INDOOR UNIT ACC 10C ACC 15C ACC 20C ACC 25C
OUTDOOR UNIT A4LC 10B A4LC 15B A4LC 20B A4LC 25B
NOMINAL kcal/h 2,268 2,772 4,612 5,292
COOLING W 2,637 3,223 5,363 6,155
CAPACITY Btu/h 9,000 11,000 18,300 21,000
POWER SOURCE V/Ph/Hz 220 - 240 / 1 / 50
REFRIGERANT / CONTROL R407C / CAPILLARY TUBE IN OUTDOOR
AIR FLOW cfm/cmm 300 / 8.50 430 / 12.2 620 / 17.0 840 / 23.8
STATIC PRESSURE mm Aq 5 5 5 5
FAN

FAN MOTOR 4 POLES x 22W 4 POLES x 30W 4 POLES x 55W 4 POLES x 100W
RATED INPUT POWER W 71 102 148 180
RATED RUNNING CURRENT A 0.30 0.43 0.65 0.77
MATERIAL SEAMLESS COPPER
TUBE

DIAMETER mm/in 9.52 / 3/8


THICKNESS mm/in 0.35 / 0.014
COIL

MATERIAL ALUMINIUM
INDOOR UNIT

THICKNESS mm/in
FIN

0.11 / 0.0043
ROW 3 3 3 3
FIN PER INCH 12 14 12 12
2 2
FACE AREA m /ft 0.115 / 1.238 0.143 / 1.542 0.176 / 1.892 0.203 / 2.187
HEIGHT mm/in 261 / 10.28 261 / 10.28 261 / 10.28 261 / 10.28
DIMENSION WIDTH mm/in 765 / 30.12 905 / 35.63 1,065 / 41.93 1,200 / 47.24
DEPTH mm/in 411 / 16.18 411 / 16.18 411 / 16.18 411 / 16.18
WEIGHT kg 17 21 22 25
CONTROL ROOM TEMPERATURE MICROCOMPUTER CONTROLLED THERMOSTAT
OPERATION SLM WIRED HANDSET (OPTIONAL AC5300 REMOTE CONTROLLER)
CONDENSATE DRAIN SIZE mm/in 19.05 / 3/4
AIR FILTER WASHABLE SARAN NET (OPTIONAL)
PACKING HEIGHT mm/in 410 / 16.14 410 / 16.14 410 / 16.14 410 / 16.14
DIMENSION WIDTH mm/in 951 / 37.44 1,091 / 42.95 1,251 / 49.25 1,386 / 54.57
DEPTH mm/in 535 / 21.06 535 / 21.06 535 / 21.06 535 / 21.06
POWER SOURCE V/Ph/Hz 220 - 240 / 1 / 50
COMPRESSOR

COMPRESSOR TYPE ROTARY HERMETIC


CAPACITOR µµF 30 30 45 50
LOCK ROTOR AMP. A 18 29 54 58
RATED RUNNING CURRENT A 4.00 6.20 9.91 12.50
RATED INPUT POWER W 900 1,350 2,112 2,660
PROTECTION DEVICE OVERLOAD PROTECTION
FAN TYPE / DRIVE PROPELLER / DIRECT
BLADE MATERIAL GLASS REINFORCED ACRYL STYRENE RESIN
DIAMETER mm/in 355 / 14.0 420 / 16.5
FAN

RATED RUNNING CURRENT A 0.2 0.28 0.56


RATED OUTPUT POWER W 20 30 55
RATED INPUT POWER W 50 62 133
MATERIAL S.I.G.C S.I.G.C S.B.C. S.I.G.C
TUBE
OUTDOOR UNIT

DIAMETER mm/in 9.52 / 3/8


THICKNESS mm/in 0.35 / 0.014 0.36 / 0.014 AVERAGE
COIL

MATERIAL ALUMINIUM (SLIT TYPE)


THICKNESS mm/in
FIN

0.127 / 0.005
ROW 1 1 2 2
FIN PER INCH 18 19 14 14
2 2
FACE AREA m /ft 0.32 / 3.5 0.51 / 5.53
HEIGHT mm/in 494 / 19.4 646 / 25.4
DIMENSION WIDTH mm/in 740 / 29.1 840 / 33.1
DEPTH mm/in 270 / 10.6 330 / 13.0
WEIGHT kg 31 34 57 58
MATERIAL GALVANISED MILD STEEL
CASING THICKNESS mm/in 0.8 / 0.031
FINISHING POLYESTER POWDER
TYPE FLARE VALVE
PIPE

SIZE LIQUID mm/in 6.35 / 1/4 6.35 / 1/4 6.35 / 1/4 9.52 / 3/8
GAS mm/in 9.52 / 3/8 12.70 / 1/2 15.88 / 5/8 15.88 / 5/8
PACKING HEIGHT mm/in 558 / 22.0 710 / 28.0
DIMENSION WIDTH mm/in 851 / 33.5 957 / 37.7
DEPTH mm/in 401 / 15.8 461 / 18.1

1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.
2) ALL UNITS ARE BEING TESTED AND COMPLY TO ARI 210/240-89
3) NOMINAL COOLING AND HEATING CAPACITY ARE BASED ON THE CONDITIONS BELOW :
a) COOLING - 26.7°C DB / 19.4°C WB INDOOR AND 35°C DB OUTDOOR
4) ALLOWABLE OPERATING RANGE
a) COOLING - 19.4°C DB / 13.9°C WB INDOOR AND 19.4°C DB OUTDOOR TO
26.7°C DB / 19.4°C WB INDOOR AND 46.1°C DB OUTDOOR

Abbreviation
S.B.C. - SEAMLESS BARE COPPER
S.I.G.C - SEAMLESS INNER GROOVE COPPER

7
CEILING CONCEALED COOLING ONLY MODELS (R407C)
MODEL INDOOR UNIT ACC 30C ACC 40C ACC 50C
OUTDOOR UNIT A4LC 30C A4LC 40C A4LC 50C
NOMINAL kcal/h 7,560 9,576 12,600
COOLING W 8,790 11,134 14,650
CAPACITY Btu/h 30,000 38,000 50,000
POWER SOURCE V/Ph/Hz 220 - 240 / 1 / 50
REFRIGERANT / CONTROL R407C / CAPILLARY TUBE (OUTDOOR) + (TXV)
AIR FLOW cfm/cmm 900 / 25.49 1,200 / 33.99 1,500 / 42.49
STATIC PRESSURE mm Aq 15 / 10 / 5
FAN

FAN MOTOR 4 POLES


RATED INPUT POWER W 421 550 670
RATED RUNNING CURRENT A 1.9 2.6 2.9
MATERIAL SEAMLESS BARE COPPER
TUBE

DIAMETER mm/in 9.52 / 3/8


THICKNESS mm/in 0.35 / 0.014
COIL

MATERIAL
INDOOR UNIT

ALUMINIUM
THICKNESS mm/in 0.127 / 0.005
FIN

ROW 3 3 3
FIN PER INCH 12 14 14
2 2
FACE AREA m /ft 0.27 / 2.98 0.31 / 3.44 0.40 / 4.40
HEIGHT mm/in 370 / 14.57 370 / 14.57 370 / 14.57
DIMENSION WIDTH mm/in 919 / 36.18 1,039 / 40.91 1,289 / 50.75
DEPTH mm/in 589 / 23.19 589 / 23.19 589 / 23.19
WEIGHT kg 39 42 54
CONTROL ROOM TEMPERATURE MICROCOMPUTER CONTROLLED THERMOSTAT
OPERATION SLM WIRED HANDSET (OPTIONAL AC5300 REMOTE CONTROLLER)
CONDENSATE DRAIN SIZE mm/in 19.05 / 3/4
AIR FILTER WASHABLE SARAN NET
PACKING HEIGHT mm/in 675 / 26.57 675 / 26.57 675 / 26.57
DIMENSION WIDTH mm/in 1,089 / 42.87 1,209 / 47.60 1,459 / 57.44
DEPTH mm/in 440 / 17.32 440 / 17.32 440 / 17.32
POWER SOURCE V/Ph/Hz 220 - 240 / 1 / 50 380 - 415 / 3 / 50
COMPRESSOR TYPE SCROLL
CAPACITOR µF 50 - -
COMP.

LOCK ROTOR AMP. A 78 45 62


RATED RUNNING CURRENT A 11.4 6.3 8.2
RATED INPUT POWER W 2,560 3,741 4,328
PROTECTION DEVICE OVERLOAD PROTECTION / HI-LO PRESSURE SWITCH
FAN TYPE / DRIVE PROPELLER / DIRECT
BLADE MATERIAL GLASS REINFORCED ACRYL STYRENE RESIN
DIAMETER mm/in 610 / 24
FAN

RATED RUNNING CURRENT A 1.09


RATED OUTPUT POWER W 145
RATED INPUT POWER W 241
MATERIAL S.B.C.
TUBE
OUTDOOR UNIT

DIAMETER mm/in 9.52 / 3/8


THICKNESS mm/in 0.35 / 0.014
COIL

MATERIAL ALUMINIUM (CORRUGATED)


THICKNESS mm/in 0.127 / 0.005
FIN

ROW 1 2 2
FIN PER INCH 16 14 16
2 2
FACE AREA m /ft 0.89 / 9.56 0.88 / 9.33
HEIGHT mm/in 850 / 33.46
DIMENSION WIDTH mm/in 1,030 / 40.55
DEPTH mm/in 400 / 15.75
WEIGHT kg 93 100 105
MATERIAL ELECTRO-GALVANISED MILD STEEL
CASING THICKNESS mm/in 0.8 / 0.031
FINISHING POLYESTER POWDER
TYPE FLARE VALVE
PIPE

SIZE LIQUID mm/in 9.52 / 3/8 9.52 / 3/8 9.52 / 3/8


GAS mm/in 15.88 / 5/8 19.05 / 3/4 19.05 / 3/4
PACKING HEIGHT mm/in 1,000 / 39.37
DIMENSION WIDTH mm/in 1,200 / 47.24
DEPTH mm/in 560 / 22.05

1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.
2) ALL UNITS ARE BEING TESTED AND COMPLY TO ARI 210/240-89
3) NOMINAL COOLING AND HEATING CAPACITY ARE BASED ON THE CONDITIONS BELOW :
a) COOLING - 26.7°C DB / 19.4°C WB INDOOR AND 35°C DB OUTDOOR
4) ALLOWABLE OPERATING RANGE
a) COOLING - 19.4°C DB / 13.9°C WB INDOOR AND 19.4°C DB OUTDOOR TO
26.7°C DB / 19.4°C WB INDOOR AND 46.1°C DB OUTDOOR

Abbreviation
S.B.C. - SEAMLESS BARE COPPER
S.I.G.C - SEAMLESS INNER GROOVE COPPER

8
CEILING CONCEALED HEAT PUMP MODELS (R407C)
MODEL INDOOR UNIT ACC 10CR ACC 15CR ACC 20CR ACC 25CR
OUTDOOR UNIT A4LC 10BR A4LC 15BR A4LC 20BR A4LC 25BR
NOMINAL kcal/h 2,268 2,772 4,536 5,170
COOLING W 2,637 3,223 5,274 6,008
CAPACITY Btu/h 9,000 11,000 18,000 20,500
NOMINAL kcal/h 2,394 3,150 4,790 6,050
HEATING W 2,784 3,663 5,569 7,034
CAPACITY Btu/h 9,500 12,500 19,000 24,000
POWER SOURCE V/Ph/Hz 220 - 240 / 1 / 50
REFRIGERANT / CONTROL R407C / CAPILLARY TUBE IN OUTDOOR
AIR FLOW cfm/cmm 300 / 8.50 430 / 12.2 620 / 17.0 840 / 23.8
STATIC PRESSURE mm Aq 5 5 5 5
FAN

FAN MOTOR 4 POLES x 22W 4 POLES x 30W 4 POLES x 55W 4 POLES x 100W
RATED INPUT POWER W 71 102 148 180
RATED RUNNING CURRENT A 0.30 0.43 0.65 0.77
MATERIAL
TUBE

SEAMLESS COPPER
DIAMETER mm/in 9.52 / 3/8
THICKNESS mm/in 0.35 / 0.014
COIL
INDOOR UNIT

MATERIAL ALUMINIUM
THICKNESS mm/in
FIN

0.11 / 0.0043
ROW 3 3 3 3
FIN PER INCH 12 14 12 12
2 2
FACE AREA m /ft 0.115 / 1.238 0.143 / 1.542 0.176 / 1.892 0.203 / 2.187
HEIGHT mm/in 261 / 10.28 261 / 10.28 261 / 10.28 261 / 10.28
DIMENSION WIDTH mm/in 765 / 30.12 905 / 35.63 1,065 / 41.93 1,200 / 47.24
DEPTH mm/in 411 / 16.18 411 / 16.18 411 / 16.18 411 / 16.18
WEIGHT kg 17 21 22 25
CONTROL ROOM TEMPERATURE MICROCOMPUTER CONTROLLED THERMOSTAT
OPERATION SLM WIRED HANDSET (OPTIONAL AC5300 REMOTE CONTROLLER)
CONDENSATE DRAIN SIZE mm/in 19.05 / 3/4
AIR FILTER WASHABLE SARAN NET (OPTIONAL)
PACKING HEIGHT mm/in 410 / 16.14 410 / 16.14 410 / 16.14 410 / 16.14
DIMENSION WIDTH mm/in 951 / 37.44 1,091 / 42.95 1,251 / 49.25 1,386 / 54.57
DEPTH mm/in 535 / 21.06 535 / 21.06 535 / 21.06 535 / 21.06
POWER SOURCE V/Ph/Hz 220 - 240 / 1 / 50
COMPRESSOR TYPE ROTARY HERMETIC
CAPACITOR µF 30 30 45 50
LOCK ROTOR AMP. A 18 29 54 58
COMP.

RATED RUNNING CURRENT (COOLING) A 4.00 6.20 9.50 12.60


RATED RUNNING CURRENT (HEATING) A 3.30 5.70 10.10 12.50
RATED INPUT POWER (COOLING) W 900 1,350 2,002 2,571
RATED INPUT POWER (HEATING) W 750 1,200 2,096 2,549
PROTECTION DEVICE OVERLOAD PROTECTION
FAN TYPE / DRIVE PROPELLER / DIRECT
BLADE MATERIAL GLASS REINFORCED ACRYL STYRENE RESIN
DIAMETER mm/in 355 / 14.0 420 / 16.5
FAN

RATED RUNNING CURRENT A 0.28 0.56


RATED OUTPUT POWER W 30 55
RATED INPUT POWER W 62 133
OUTDOOR UNIT

MATERIAL
TUBE

S.I.G.C S.I.G.C S.B.C. S.I.G.C


DIAMETER mm/in 9.52 / 3/8
THICKNESS mm/in 0.35 / 0.014 0.36 / 0.014 AVERAGE
COIL

MATERIAL ALUMINIUM
THICKNESS mm/in
FIN

0.127 / 0.005
ROW 1 1 2 2
FIN PER INCH 19 19 14 14
2 2
FACE AREA m /ft 0.32 / 3.5 0.51 / 5.53
HEIGHT mm/in 494 / 19.4 646 / 25.4
DIMENSION WIDTH mm/in 740 / 29.1 840 / 33.1
DEPTH mm/in 270 / 10.6 330 / 13.0
WEIGHT kg 31 34 57 58
MATERIAL GALVANISED MILD STEEL
CASING THICKNESS mm/in 0.8 / 0.031
FINISHING POLYESTER POWDER
TYPE FLARE VALVE
PIPE

SIZE LIQUID mm/in 6.35 / 1/4 6.35 / 1/4 6.35 / 1/4 9.52 / 3/8
GAS mm/in 9.52 / 3/8 12.70 / 1/2 15.88 / 5/8 15.88 / 5/8
PACKING HEIGHT mm/in 558 / 22.0 710 / 28.0
DIMENSION WIDTH mm/in 851 / 33.5 957 / 37.7
DEPTH mm/in 401 / 15.8 461 / 18.1

1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.
2) ALL UNITS ARE BEING TESTED AND COMPLY TO ARI 210/240-89
3) NOMINAL COOLING AND HEATING CAPACITY ARE BASED ON THE CONDITIONS BELOW :
a) COOLING - 26.7°C DB / 19.4°C WB INDOOR AND 35°C DB OUTDOOR
b) HEATING - 21.1°C DB / 15.6°C WB INDOOR AND 8.3°C DB / 6.1°C WB OUTDOOR
4) ALLOWABLE OPERATING RANGE
a) COOLING - 19.4°C DB / 13.9°C WB INDOOR AND 19.4°C DB OUTDOOR TO
26.7°C DB / 19.4°C WB INDOOR AND 46.1°C DB OUTDOOR
b) HEATING - 21.0°C DB INDOOR AND -8.3°C DB / -9.4°C WB OUTDOOR TO
26.7°C DB INDOOR AND 23.9°C DB / 18.3°C WB

Abbreviation
S.B.C. - SEAMLESS BARE COPPER
S.I.G.C - SEAMLESS INNER GROOVE COPPER

9
CEILING CONCEALED HEAT PUMP MODELS (R407C)
MODEL INDOOR UNIT ACC 30CR ACC 40CR ACC 50CR
OUTDOOR UNIT A4LC 30CR A4LC 40CR A4LC 50CR
NOMINAL kcal/h 7,310 9,830 12,100
COOLING W 8,499 11,430 14,068
CAPACITY Btu/h 29,000 39,000 48,000
NOMINAL kcal/h 7,812 10,332 12,600
HEATING W 9,083 12,013 14,654
CAPACITY Btu/h 31,000 41,000 50,000
POWER SOURCE V/Ph/Hz 220 - 240 / 1 / 50
REFRIGERANT / CONTROL R407C / CAPILLARY TUBE (OUTDOOR) + (TXV)
AIR FLOW cfm/cmm 900 / 25.49 1,200 / 33.99 1,500 / 42.49
STATIC PRESSURE mm Aq 15 / 10 / 5
FAN

FAN MOTOR 4 POLES


RATED INPUT POWER W 421 550 670
RATED RUNNING CURRENT A 1.9 2.6 2.9
MATERIAL SEAMLESS BARE COPPER
TUBE

DIAMETER mm/in 9.52 / 3/8


THICKNESS mm/in 0.35 / 0.014
COIL

MATERIAL ALUMINIUM
INDOOR UNIT

THICKNESS mm/in 0.127 / 0.005


FIN

ROW 3 3 3
FIN PER INCH 12 14 14
FACE AREA m2/ft2 0.27 / 2.98 0.31 / 3.44 0.40 / 4.40
HEIGHT mm/in 370 / 14.57 370 / 14.57 370 / 14.57
DIMENSION WIDTH mm/in 919 / 36.18 1,039 / 40.91 1,289 / 50.75
DEPTH mm/in 589 / 23.19 589 / 23.19 589 / 23.19
WEIGHT kg 39 42 54
CONTROL ROOM TEMPERATURE MICROCOMPUTER CONTROLLED THERMOSTAT
OPERATION SLM WIRED HANDSET (OPTIONAL AC5300 REMOTE CONTROLLER)
CONDENSATE DRAIN SIZE mm/in 19.05 / 3/4
AIR FILTER WASHABLE SARAN NET
PACKING HEIGHT mm/in 675 / 26.57 675 / 26.57 675 / 26.57
DIMENSION WIDTH mm/in 1,089 / 42.87 1,209 / 47.60 1,459 / 57.44
DEPTH mm/in 440 / 17.32 440 / 17.32 440 / 17.32
POWER SOURCE V/Ph/Hz 220 - 240 / 1 / 50 380 - 415 / 3 / 50
COMPRESSOR TYPE SCROLL
CAPACITOR µF 50 - -
LOCK ROTOR AMP. A 78 45 62
COMP.

RATED RUNNING CURRENT (COOLING) A 11.5 6.2 8.8


RATED RUNNING CURRENT (HEATING) A 11.4 5.9 7.8
RATED INPUT POWER (COOLING) W 2,424 3,565 4,615
RATED INPUT POWER (HEATING) W 2,407 3,280 3,734
PROTECTION DEVICE OVERLOAD PROTECTION / HI-LO PRESSURE SWITCH
FAN TYPE / DRIVE PROPELLER / DIRECT
BLADE MATERIAL GLASS REINFORCED ACRYL STYRENE RESIN
FAN

DIAMETER mm/in 610 / 24


RATED RUNNING CURRENT A 1.09
RATED OUTPUT POWER W 145
RATED INPUT POWER W 241
OUTDOOR UNIT

MATERIAL S.B.C.
TUBE

DIAMETER mm/in 9.52 / 3/8


THICKNESS mm/in 0.35 / 0.014
COIL

MATERIAL ALUMINIUM (CORRUGATED)


THICKNESS mm/in 0.127 / 0.005
FIN

ROW 1 2 2
FIN PER INCH 16 14 16
2 2
FACE AREA m /ft 0.89 / 9.56 0.88 / 9.33
HEIGHT mm/in 850 / 33.46
DIMENSION WIDTH mm/in 1,030 / 40.55
DEPTH mm/in 400 / 15.75
WEIGHT kg 93 100 105
MATERIAL ELECTRO-GALVANISED MILD STEEL
CASING THICKNESS mm/in 0.8 / 0.031
FINISHING POLYESTER POWDER
TYPE FLARE VALVE
PIPE

SIZE LIQUID mm/in 9.52 / 3/8 9.52 / 3/8 9.52 / 3/8


GAS mm/in 15.88 / 5/8 19.05 / 3/4 19.05 / 3/4
PACKING HEIGHT mm/in 1,000 / 39.37
DIMENSION WIDTH mm/in 1,200 / 47.24
DEPTH mm/in 560 / 22.05

1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.
2) ALL UNITS ARE BEING TESTED AND COMPLY TO ARI 210/240-89
3) NOMINAL COOLING AND HEATING CAPACITY ARE BASED ON THE CONDITIONS BELOW :
a) COOLING - 26.7°C DB / 19.4°C WB INDOOR AND 35°C DB OUTDOOR
b) HEATING - 21.1°C DB / 15.6°C WB INDOOR AND 8.3°C DB / 6.1°C WB OUTDOOR
4) ALLOWABLE OPERATING RANGE
a) COOLING - 19.4°C DB / 13.9°C WB INDOOR AND 19.4°C DB OUTDOOR TO
26.7°C DB / 19.4°C WB INDOOR AND 46.1°C DB OUTDOOR
b) HEATING - 21.0°C DB INDOOR AND -8.3°C DB / -9.4°C WB OUTDOOR TO
26.7°C DB INDOOR AND 23.9°C DB / 18.3°C WB

Abbreviation
S.B.C. - SEAMLESS BARE COPPER
S.I.G.C - SEAMLESS INNER GROOVE COPPER

10
3. NOISE LEVEL

1/1 Octave A-weighed sound pressure level (dBA), ref 20 µPa


Model 125 Hz 250 Hz 500 Hz 1 kHz 2 kHz 4 kHz 8 kHz Ave.
H M L H M L H M L H M L H M L H M L H M L H M L
ACC 10 C/CR 27 25 21 31 29 25 34 32 28 35 32 27 30 27 22 24 20 15 12 10 8 39 37 33
ACC 15 C/CR 28 25 22 34 31 26 36 33 29 35 32 27 32 29 23 26 21 16 14 12 10 41 38 33
ACC 20 C/CR 30 29 27 37 35 32 40 38 36 38 36 33 37 35 32 29 27 23 21 18 15 44 43 40
ACC 25 C/CR 32 31 27 37 36 32 41 40 37 38 37 34 38 37 33 32 31 30 23 22 21 46 44 41
ACC 30 C/CR 62 60 59 62 59 58 58 57 55 55 54 52 53 51 51 46 44 44 39 37 35 61 59 57

ACC 40 C/CR 61 60 58 64 58 58 59 57 54 55 53 53 54 52 51 45 42 41 35 33 32 61 59 58

ACC 50 C/CR 62 58 58 60 60 59 59 59 57 57 56 56 56 55 55 49 48 48 41 40 39 62 61 60
ACC 60 C/CR 62 57 57 61 59 57 61 59 58 57 56 55 55 54 53 48 47 47 42 41 40 62 61 60

MICROPHONE POSITION :
ACC10 ~ 25 C/CR – 1.4 BELOW THE CENTRE OF THE UNIT.
(WITH 2m LENGTH DUCT AT THE AIR OUTLET)

ACC30 ~ 60 C/CR – 1m INFRONT AND 1m BELOW THE UNIT.


(WITH 4.57m LENGTH DUCT)

4. OPERATION RANGE

Cooling
54
HIGH AMBIENT
UNIT
46
Outdoor temp. (°CDB)

35
STD

19

LOW AMBIENT
KIT

-5

15 24
Indoor temp. (°CWB)

Heatpump

Heating Cooling

18
HIGH AMBIENT
UNIT
Outdoor temp. (°CWB)

46
Outdoor temp. (°CDB)

35
STD
6

19

LOW AMBIENT
KIT

-8

21
24
Indoor temp. (°CDB) Indoor temp. (°CWB)

11
5. PERFORMANCE TABLE

MODEL : ACC10C/ALC10B

Indoor DB Indoor WB Capacity Outdoor DB, °C


°C °C kW 19.4 25 30 35 40 46
26.7 13.9 TC 2.532 2.424 2.328 2.231 2.134 2.018
SC 2.532 2.424 2.328 2.231 2.134 2.018
15 TC 2.765 2.617 2.485 2.353 2.221 2.063
SC 2.492 2.382 2.284 2.185 2.087 1.969
18 TC 3.399 3.143 2.915 2.687 2.459 2.185
SC 2.384 2.268 2.165 2.061 1.958 1.834
19.4 TC 3.695 3.389 3.116 2.843 2.570 2.242
SC 2.333 2.215 2.109 2.004 1.898 1.771
20 TC 3.822 3.504 3.220 2.936 2.653 2.312
SC 2.311 2.186 2.074 1.963 1.851 1.717
22 TC 4.245 3.887 3.567 3.248 2.928 2.545
SC 2.239 2.091 1.959 1.826 1.694 1.536
24 TC 4.667 4.270 3.914 3.559 3.204 2.778
SC 2.166 1.995 1.843 1.690 1.538 1.354

MODEL : ACC15C/ALC15B

Indoor DB Indoor WB Capacity Outdoor DB, °C


°C °C kW 19.4 25 30 35 40 46
26.7 13.9 TC 3.447 3.277 3.126 2.975 2.824 2.643
SC 3.283 3.148 3.028 2.908 2.787 2.643
15 TC 3.669 3.473 3.299 3.125 2.950 2.741
SC 3.187 3.058 2.942 2.826 2.710 2.572
18 TC 4.275 4.008 3.770 3.532 3.294 3.008
SC 2.925 2.810 2.707 2.604 2.501 2.378
19.4 TC 4.558 4.258 3.990 3.722 3.454 3.133
SC 2.802 2.694 2.597 2.500 2.403 2.287
20 TC 4.679 4.367 4.089 3.811 3.533 3.199
SC 2.750 2.636 2.534 2.433 2.331 2.209
22 TC 5.083 4.732 4.419 4.106 3.793 3.418
SC 2.575 2.443 2.326 2.208 2.091 1.950
24 TC 5.487 5.097 4.749 4.402 4.054 3.637
SC 2.400 2.250 2.117 1.984 1.850 1.690

12
MODEL : ACC20C/ALC20B

Indoor DB Indoor WB Capacity Outdoor DB, ° C


°C °C kW 19.4 25 30 35 40 46
26.7 13.9 TC 5.264 5.010 4.783 4.556 4.330 4.058
SC 4.788 4.634 4.497 4.360 4.223 4.058
15 TC 5.607 5.313 5.051 4.788 4.526 4.211
SC 4.749 4.585 4.439 4.292 4.146 3.970
18 TC 6.542 6.139 5.780 5.420 5.061 4.629
SC 4.643 4.451 4.279 4.108 3.936 3.730
19.4 TC 6.979 6.525 6.120 5.715 5.310 4.824
SC 4.594 4.388 4.205 4.022 3.838 3.618
20 TC 7.166 6.694 6.272 5.851 5.429 4.923
SC 4.572 4.347 4.145 3.944 3.742 3.501
22 TC 7.789 7.255 6.779 6.302 5.825 5.253
SC 4.502 4.209 3.947 3.685 3.424 3.110
24 TC 8.413 7.817 7.286 6.754 6.222 5.584
SC 4.431 4.070 3.749 3.427 3.105 2.719

MODEL : ACC25C/ALC25B

Indoor DB Indoor WB Capacity Outdoor DB, ° C


°C °C kW 19.4 25 30 35 40 46
26.7 13.9 TC 6.800 6.463 6.163 5.863 5.563 5.202
SC 5.808 5.680 5.567 5.453 5.339 5.202
15 TC 7.260 6.864 6.510 6.156 5.802 5.377
SC 5.689 5.557 5.439 5.321 5.203 5.061
18 TC 8.516 7.955 7.455 6.954 6.454 5.853
SC 5.366 5.221 5.091 4.961 4.831 4.676
19.4 TC 9.102 8.465 7.896 7.327 6.758 6.076
SC 5.215 5.064 4.929 4.793 4.658 4.496
20 TC 9.353 8.693 8.103 7.514 6.924 6.217
SC 5.151 4.978 4.825 4.671 4.517 4.332
22 TC 10.190 9.453 8.795 8.136 7.478 6.688
SC 4.935 4.693 4.477 4.261 4.045 3.786
24 TC 11.027 10.213 9.486 8.758 8.031 7.159
SC 4.720 4.408 4.130 3.852 3.574 3.240

All the data above are based on 26.7°C entering DB. To obtain data for different entering DB, please use the
formula below :

Sensible capacity (EDB) = Sensible capacity (26.7) + 1.23 x L/s x (1 - BPF) ( EDB - 26.7 ) / 1000

Where, BPF = Bypass factor


EDB = Entering dry bulb temperature, ° C

Model ACC10C ACC15C ACC20C ACC25C


Bypass factor 0.61 0.56 0.60 0.61

13
6. FAN PERFORMANCE CURVES

External Static Pressure (mmAq)


Model Fan Speed (CFM) 0 1 2 3 4 5 6 7
ACC10C High 430 406 382 355 331 300 278 248
Medium 375 351 327 304 280 254 226 198
Low 308 284 260 240 213 190 165 140

ACC15C High 632 595 558 515 476 430 390 337
Medium 522 485 440 395 310 295 250 200
Low 413 370 322 270 250 205 168 140

ACC20C High 860 810 765 720 675 620 580 530
Medium 787 750 700 660 610 570 520 470
Low 630 590 550 500 475 440 390 335

ACC25C High 1060 1023 985 938 893 840 790 732
Medium 950 908 872 828 790 743 691 647
Low 740 705 672 640 597 555 512 468

MODEL : ACC30C

MODEL : ACC40C

14
MODEL : ACC50C

MODEL : ACC60C

15
7. OUTLINES AND DIMENSIONS

INDOOR UNIT
MODEL : ACC10 C/CR

All dimensions are in mm

MODEL : ACC15 ~ 25 C/CR

All dimensions are in mm

Model A B C D E F G H
ACC15C/CR 881.0 225.0 842.0 802.0 261.0 411.0 351.0 905.0
ACC20C/CR 1041.0 225.0 1002.0 962.0 261.0 411.0 351.0 1065.0
ACC25C/CR 1176.0 225.0 1137.0 1097.0 261.0 411.0 351.0 1200.0

16
MODEL : ACC30 ~ 60 C/CR

All dimensions are in mm

Model A B C D E F G H I J K
ACC30 C/CR 929.0 999.0 956.0 917.0 408.5 378.0 541.0 256.0 173.0 311.0 70.5
ACC40 C/CR 1045.0 1115.0 1072.0 1033.0 466.5 378.0 541.0 256.0 173.0 311.0 128.5
ACC50 C/CR 1299.0 1369.0 1326.0 1287.0 593.5 378.0 541.0 256.0 173.0 311.0 255.5
ACC60 C/CR 1499.0 1569.0 1526.0 1487.0 693.5 378.0 541.0 256.0 173.0 311.0 355.5

Note :
(ACC10 ~ 25C/CR)
Terminal box position : With controller (left side)
Without controller (right side)

17
OUTDOOR UNIT

MODEL : ALC 10 / 15 B/BR


A4LC 10 / 15 B/BR

Note : Dimension in mm

MODEL : ALC 20 / 25 B/BR, ALC 30B


A4LC 20 / 25 B/BR

Note : Dimension in mm

18
MODEL : ALC 30 / 40 / 50 / 60 C/CR
A4LC 30 / 40 / 50 C/CR

Note : Dimension in mm

MODEL : AMC 60 C/CR

Note : Dimension in mm

19
8. WIRING DIAGRAMS

MODEL : ACC 10C / 15C – ALC/A4LC 10B / 15B


(FOR EXPORT SPEC. WITH SLM CONTROL C3.0B CC)

MODEL : ACC 10C / 15C – ALC/A4LC 10B / 15B


(FOR LOCAL SPEC.)

20
MODEL: ACC 20C / 25C – ALC/A4LC 20B / 25B
(FOR EXPORT SPEC. WITH SLM CONTROL C3.0B CC)

MODEL : ACC 20C / 25C – ALC/A4LC 20B / 25B


(FOR LOCAL SPEC.)

21
MODEL: ACC 30C – ALC/A4LC 30C
( FOR EXPORT SPEC. WITH SLM CONTROL C3.0BCC )

MODEL: ACC 30C – ALC/A4LC 30C


( FOR LOCAL SPEC. & EXPORT SPEC. )

22
MODEL: ACC 40C / 50C – ALC/A4LC 40C / 50C
( FOR EXPORT SPEC. WITH MC & SLM CONTROL C3.0BCC )

MODEL: ACC 40C / 50C – ALC/A4LC 40C / 50C


( For export spec. with MC )

23
MODEL: ACC 40C / 50C – ALC/A4LC 40C / 50C
( FOR LOCAL SPEC. )

MODEL: ACC 60C – ALC 60C


( FOR EXPORT SPEC. WITH MC & SLM C3.0BCC )

24
MODEL: ACC 60 – ALC 60C
( FOR EXPORT SPEC. WITH MC )

MODEL: ACC 60C – ALC 60C


( FOR LOCAL SPEC. )

25
MODEL: ACC 60C – AMC 60C
( FOR EXPORT SPEC. WITH SLM CONTROL C3.0BCC )

26
MODEL : ACC 10CR / 15CR – ALC/A4LC 10BR / 15BR

27
MODEL: ACC 20CR / 25CR – ALC/A4LC 20BR / 25BR

28
MODEL: ACC 30CR – ALC/A4LC 30CR

29
MODEL: ACC 40CR / 50CR – ALC/A4LC 40CR / 50CR

30
MODEL: ACC 60CR – ALC 60CR

31
MODEL: ACC 60CR – AMC 60CR
(FOR EXPORT SPEC. WITH SLM CONTROL C3.0BCC)

32
MODEL : ACC 10 / 15C – ALC / A4LC 10 / 15B
(FOR EXPORT SPEC. WITH SLM CONTROL U1.4)

MODEL : ACC 20 / 25C – ALC / A4LC 20 / 25B


(FOR EXPORT SPEC. WITH SLM CONTROL U1.4)

33
MODEL : ACC 30 C – ALC 30B
(FOR EXPORT SPEC. WITH SLM CONTROL U1.4)

MODEL : ACC 30C – ALC / A4LC 30C


(FOR EXPORT SPEC. WITH SLM CONTROL U1.4)

34
MODEL : ACC 40 / 50C – ALC / A4LC 40 / 50C
(FOR EXPORT SPEC. WITH SLM CONTROL U1.4)

MODEL : ACC 60C – ALC 60C


(FOR EXPORT SPEC. WITH SLM CONTROL U1.4)

35
MODEL : ACC 60C – AMC 60C
(FOR EXPORT SPEC. WITH SLM CONTROL U1.4)

36
MODEL : ACC 10 / 15CR – ALC / A4LC 10 / 15BR
(FOR EXPORT SPEC. WITH SLM CONTROL U1.4)

37
MODEL : ACC 20 / 25CR – ALC / A4LC 20 / 25BR
(FOR EXPORT SPEC. WITH SLM CONTROL U1.4)

38
MODEL : ACC 30CR – ALC / A4LC 30CR
(FOR EXPORT SPEC. WITH SLM CONTROL U1.4)

39
MODEL : ACC 40 / 50CR – ALC / A4LC 40 / 50CR
(FOR EXPORT SPEC. WITH SLM CONTROL U1.4)

40
MODEL : ACC 60CR – ALC 60CR
(FOR EXPORT SPEC. WITH SLM CONTROL U1.4)

41
MODEL : ACC 60CR – AMC 60CR
(FOR EXPORT SPEC. WITH SLM CONTROL U1.4)

42
ATTACHMENT
60HZ OUTDOOR UNIT

MODEL : ALC 30C (COOLING ONLY)


60HZ / 1 PHASE / 208 ~230V

MODEL : ALC 40 / 50C (COOLING ONLY)


60HZ / 3 PHASE / 200 ~230V

MODEL : ALC 40 / 50CR (COOLING ONLY)


60HZ / 3 PHASE / 200 ~230V

43
3 PHASE FOR 2 & 3 HP OUTDOOR UNIT

MODEL : ALC 20 / 25B (COOLING ONLY)


3 PHASE / 50 HZ / 380 ~ 415V

MODEL : ALC 30C (COOLING ONLY)


3 PHASE / 50 HZ / 380 ~ 415V

44
MODEL : ALC 20 / 25BR (HEAT PUMP)
3 PHASE / 50HZ / 380 ~ 415V

MODEL : ALC 30CR (HEAT PUMP)


3 PHASE / 50HZ / 380 ~ 415V

45
HIGH AMBIENT UNIT
OUTDOOR UNIT
MODEL : ALC 20 / 25B (COOLING ONLY)
50HZ / 1 PHASE / 220 – 240V, 60HZ / 1 PHASE / 208 – 230V

OUTDOOR UNIT
MODEL : ALC 30C (COOLING ONLY)
50HZ / 1 PHASE / 220 – 240V, 60HZ / 1 PHASE / 208 – 230V

OUTDOOR UNIT
MODEL : ALC 40 / 50C (COOLING ONLY)
50HZ / 3 PHASE / 380 – 415V, 60HZ / 3 PHASE / 200 – 230V

46
OUTDOOR UNIT
MODEL : ALC 20 / 25BR (HEAT PUMP)
50HZ / 1 PHASE / 220 – 240V

OUTDOOR UNIT
MODEL : ALC 30CR
50HZ / 1 PHASE / 220 – 240V, 60 HZ / 1 PHASE / 220V

OUTDOOR UNIT
MODEL : ALC 40 / 50CR
50HZ / 3 PHASE / 380 – 415V, 60HZ / 3 PHASE / 220V

47
LOW AMBIENT UNIT (OPTIONAL)

OUTDOOR UNIT
MODEL : ALC 10B / 15B (50HZ)

OUTDOOR UNIT
MODEL : ALC 20B / 25B (50HZ)

48
LOW AMBIENT UNIT
OUTDOOR UNIT
MODEL : ALC 10 / 15BR
50HZ / 1 PHASE / 220 – 240V

OUTDOOR UNIT
MODEL : ALC 20BR
50HZ / 1 PHASE / 220 – 240V

OUTDOOR UNIT
MODEL : ALC 25BR
50HZ / 1 PHASE / 220 – 240V

49
9. SPECIAL PRECAUTIONS FOR R407C

SPECIAL PRECAUTIONS WHEN DEALING WITH REFRIGERANT R407C UNIT

1) WHAT IS NEW REFRIGERANT R407C?


R407C is a zeotropic refrigerant mixture which has Zero Ozone Depletion Potential (ODP = 0) and thus conformed
to the Montreal Protocol regulation. It requires Polyol-ester oil (POE) oil for its compressor's lubricant. Its refrigerant
capacity and performance are about the same as the refrigerant R22.

2) COMPONENTS
Mixture weight composition R32(23%), R125(25%), R134a(52%)

3) CHARACTERISTIC
• R407C liquid and vapor components have different compositions when the fluid evaporates or condenses. Hence,
when leak occurs and only vapor leaks out, the composition of the refrigerant mixture left in the system will change
and subsequently affect the system performance. DO NOT add new refrigerant to leaked system. It is
recommended that the system should be evacuated thoroughly before recharging with R407C.
• When refrigerant R407C is used, the composition will differ depending on whether it is in gaseous or liquid phase.
Hence when charging R407C, ensure that only liquid is being withdrawn from the cylinder or can. This is to make
certain that only original composition of R407C is being charged into the system.
• POE oil is used as lubricant for R407C compressor, which is different from the mineral oil used for R22 compressor.
Extra precaution must be taken not to expose the R407C system too long to moist air.

4) CHECK LIST BEFORE INSTALLATION/SERVICING


• Tubing
Refrigerant R407C is more easily affected by dust of moisture compared with R22, make sure to temporarily cover
the ends of the tubing prior to installation
• Compressor oil
No additional charge of compressor oil is permitted.
• Refrigerant
No other refrigerant other that R407C
• Tools
Tools specifically for R407C only (must not be used for R22 or other refrigerant)
i) Manifold gauge and charging hose
ii) Gas leak detector
iii) Refrigerant cylinder/charging cylinder
iv) Vacuum pump c/w adapter
v) Flare tools
vi) Refrigerant recovery machine

5) HANDLING AND INSTALLATION GUIDELINES


Like R22 system, the handling and installation of R407C system are closely similar. All precautionary measures; such as
ensuring no moisture, no dirt or chips in the system, clean brazing using nitrogen, and thorough leak check and
vacuuming are equally important requirements. However, due to zeotropic nature of R407C and its hydroscopic POE oil,
additional precautions must be taken to ensure optimum and trouble-free system operation.

a) Filter-dryer must be installed along the liquid line for all R407C air conditioners. This is to minimise the
contamination of moisture and dirt in the refrigerant system. Filter-dryer must be of molecular sieve type. For a
heat-pump system, install a two-way flow filter dryer along the liquid line.

b) During installation or servicing, avoid prolong exposure of the internal part of the refrigerant system to moist air.
Residual POE oil in the piping and components can absorb moisture from the air.

50
c) Ensure that the compressor is not expose to open air for more than the recommended time specified by
its manufacturer (typically less than 10 minutes). Removed the seal-plugs only when the compressor is
about to be brazed.

d) The system should be thoroughly vacuumed to 1.0 Pa (-700mmHg) or lower. This vacuuming level is
more stringent than R22 system so as to ensure no incompressible gas and moisture in the system.

e) When charging R407C, ensure that only liquid is being withdrawn from the cylinder or can. This is to
ensure that only the original composition of R407C is being delivered into the system. The liquid
composition can be different from the vapor composition.

R32/R125/R134

33% / 33% / 34%

23% / 25% / 52%

Composition of R407C in vapour phase


is different from liquid phase.

f) Normally, the R407C cylinder or can is being equipped with a dip-pipe for liquid withdrawal. However, if
the dip-pipe is not available, invert the cylinder or can so as to withdraw liquid from the valve at the
bottom.

Invert cylinder
Dip-pipe
without dip-pipe

Liquid
withdrawal

g) When servicing leak, the top-up method, commonly practiced for R22 system, is not recommended for
R407C system. Unlike R22 where the refrigerant is of a single component, the composition of R407C,
which made-up of three different components, may have changed during the leak. Consequently, a
top-up may not ensure that the R407C in the system is of original composition. This composition shift
may adversely affect the system performance. It is recommended that the system should be evacuated
thoroughly before recharging with R407C.

51
10. INSTALLATION

PRELIMINARY SITE SURVEY


Electrical supply and installation is to conform to local authority's codes and regulations. (e.g. National Electricity Board).
Voltage supply fluctuation must not exceed +/- 10% of rated voltage. Electricity supply lines must be independent of
welding transformers which can cause high supply fluctuation. Ensure that the location is convenient for wiring and
piping.

INSTALLATION OF INDOOR UNIT


The indoor unit must be installed such that there is no short circuit of the cool discharge. Comply to the installation
clearance recommended. Do not put the indoor unit where there is direct sunlight on unit. Make sure the location is
suitable for piping and drainage. Precautions steps :

i) Use the hanger supplied with the unit.


ii) Ensure the support is strong enough to withstand the weight of the unit.
iii) Use the supplied drain socket to connect the drain pipe.

Install the unit in such a way


that the condensate water can
flow out smoothly.

The diagrams below show the screws position for duct work connection.

52
Model A B C D E F G H I J K
ACC 30 C/CR 929.0 999.0 956.0 917.0 408.5 378.0 541.0 256.0 173.0 311.0 70.5
ACC 40 C/CR 1045.0 1115.0 1072.0 1033.0 466.5 378.0 541.0 256.0 173.0 311.0 128.5
ACC 50 C/CR 1299.0 1369.0 1326.0 1287.0 593.5 378.0 541.0 256.0 173.0 311.0 255.5
ACC 60 C/CR 1499.0 1569.0 1526.0 1487.0 693.5 378.0 541.0 256.0 173.0 311.0 355.5

PIPINGS
Do not use contaminated or damaged copper tubings. If pipings, evaporator or condenser is exposed or had
been opened for 15 seconds or more, vacuum and purge with field supplied refrigerant. Generally, do not
remove plastic, rubber plugs or caps from fittings, tubings and coils unit ready to connect suction or liquid line
into fittings.

Piping connections are of flare type. If any brazing work is required, ensure that nitrogen gas is passed
through coil and joints while brazing work is being done. This will eliminate soot formation on the inside walls
of copper tubings.

ELECTRICAL CONNECTION
As wiring regulations differ from each country, please refer to your LOCAL ELECTRICAL CODES for field
wiring regulations and ensure that they are complied with. Besides, take note of the following general
precaution

- Ensure that the rated voltage of the unit correspond to the name plate before commencing wiring work.
- Provide a power outlet to be used exclusively for each unit and a power supply disconnect and a circuit
breaker for over-current protection should be provided in the exclusive line.
- The unit must be EARTHED to prevent possible hazards due to insulation failure.
- All wiring must be firmly connected.
- Electrical wiring should not touch the refrigerant piping, compressor and any moving parts of the fan motor,

OPERATIONAL CHECK
After all wiring is completed and system is charged with refrigerant, make sure unit is operating properly.
Check that: :

- Condenser fans are running with warm air blowing off the condenser coil.
- Evaporator fans are running and discharging cool air.
- Suction line pressures and condensing pressures are in the range of 60 - 75 psig. and 260 - 300 psig.
respectively in cooling cycle or 45 - 60 psig. and 245 - 285 psig. respectively in heating cycle.
- Microprocessor electronic thermostats as used in the remote controls incorporate a 3-minute delay in their
circuit. Thus it requires about 3-minute upon start-up before the outdoor unit is activated.

53
OUTDOOR UNIT
As condensing temperature rises, evaporating temperature rises and cooling capacity drops. In order to achieve
maximum cooling capacity, the location selected for outdoor unit should fulfill the following requirements :

• Install the condensing (outdoor) unit in away such that hot air distributed by the outdoor condensing unit cannot be
drawn in again (as in the case of short circuit of hot discharge air). Allow sufficient space for maintenance around the
unit.

• Ensure that there is no obstruction of air flow into or out of the unit. Remove obstacles which block air intake or
discharge.
• The location must be well ventilated, so that the unit can draw in and distribute plenty of air thus lowering the
condensing temperature.
• A place capable of bearing the weight of the outdoor unit and isolating noise and vibration.

• A place protected from direct sunlight. Otherwise use an awning for protection, if necessary.
The location must not be susceptible to dust or oil mist.

INSTALLATION CLEARANCE
• Outdoor units must be installed such that there is no short circuit of the hot discharge air or obstruction to smooth air
flow. Select the coolest possible place where intake air should not be hotter than the outside temperature (max.
45°C)

Minimum distance (mm) A B C D

ALC series 300 mm 1000 mm 300 mm 500 mm

AMC 60C 300 mm 1200 mm 500 mm -

CAUTION : If the condensing unit is operated in an atmosphere containing oils(including machine oils),
salt(coastal area), sulphide gas(near hot spring, oil refinery plant), such substances may lead to
failure of the unit.

54
11. OPERATION

MAXIMUM PIPE LENGTH AND MAXIMUM NUMBER OF BENDS


• When the pipe length becomes too long, both the capacity and reliability drop. As the number of bends
increases, system piping resistance to the refrigerant flow increases, thus lowering the cooling capacity,
and as the result the compressor may become defective. Always choose the shortest path and follow the
recommendation as tabulated below:

MODEL
10 15 20 25 30 40 50 *60
DATA
Max. Length, L 12 m 12 m 15 m 15 m 35 m 35 m 35 m 35 m
Max. Elevation, H 5m 5m 8m 8m 15 m 15 m 15 m 20 m
Max. No. of bends 10 10 10 10 10 10 10 10
* For cooling unit, need to add external accumulator (Recommended 6kg accumulator)

PIPING SIZES (FLARE CONNECTION TYPE)


• Piping sizes are as follows:

MODEL 10 15 20 25
Liquid (mm/in) 6.35 (1/4) 6.35 (1/4) 6.35 (1/4) 9.52 (3/8)
Suction (mm/in) 9.52 (3/8) 12.70 (1/2) 15.88 (5/8) 15.88 (5/8)

MODEL 30 40 50 60
Liquid (mm/in) 9.52 (3/8) 9.52 (3/8) 9.52 (3/8) 12.70 (1/2)
Suction (mm/in) 15.88 (5/8) 19.05 (3/4) 19.05 (3/4) 19.05 (3/4)

PIPING CONNECTION TO THE UNITS


• Align the center of the piping and sufficiently tighten the flare nut with fingers.
• Finally, tighten the flare nut with torque wrench until the wrench clicks.
• When tightening the flare nut with torque wrench, ensure the direction for tightening follows the arrow on the wrench.

PIPE SIZE (mm/in) TORQUE (Nm)


6.35 (1/4) 18
9.53 (3/8) 42
12.70 (1/2) 55
15.88 (5/8) 65
19.05 (3/4) 78

55
WIRING ELECTRICAL CONNECTIONS
• Wiring regulations on wire diameters differ from country to country. Please refer to your LOCAL
ELECTRICAL CODES for field wiring rules. Be sure that installation comply with such rules and regulations.

GENERAL PRECAUTIONS
• Ensure that the rated voltage of the unit corresponds to the name plate before carrying out proper wiring
according to the wiring diagram.
• Provide a power outlet to be used exclusively for each unit. A power supply disconnect and a circuit
breaker for over-current protection should be provided in the exclusive line.
• The unit must be GROUNDED to prevent possible hazards due to insulation failures.
• All wiring must be firmly connected.
• All wiring must not touch the hot refrigerant piping, compressor or any moving parts of fan motors.

VACUUMING AND CHARGING


• The precharged outdoor unit does not need any vacuuming or charging. However once it is connected,
the connecting pipe line and the indoor need to be vacuumed before releasing the R22/R407C from the
outdoor unit.
1) Open the service port core cap.
2) Connect pressure gauge to the service port.
3) Connect the line to vacuum pump. Open the charging manifold valve and turn the pump on. Vacuum
to –0.1 MPa (-760mmHg) or lower. (Evacuation time varies by the pump but averagely in 1 hour).

Diagram 1

4) After evacuation, unscrew the spindle (diagram 2B) for the gas to run to indoor unit.

Diagram 2

CAUTION FOR R407C


R407C must be charged as
liquid. Usually R407C cylinder
is equipped with a dip-pipe for
liquid withdrawal. If there is no
dip-pipe, the cylinder should
be inverted so as to withdraw
liquid R407C from the valve.

56
CAUTION FOR R407C
Do not top-up when servicing leak, as this will reduce the unit performance. Vacuum the unit
thoroughly and then charge the unit with fresh R407C according to the amount recommended
in the specification.

ADDITIONAL CHARGE
• The refrigerant gas has already charged into the outdoor unit. For the piping length of 5m. Additional refrigerant
charge after vacuuming is not necessary.
• When the piping length is more than 5m, please use the table below (unit in gram).

COOLING
MODEL ACC 10C ACC 15C ACC 20C ACC 25C ACC 30C ACC 40C ACC 50C ACC 60C
7m 30 30 30 76 100 100 100 100
10m 75 75 75 190 250 250 250 250
15m - - 150 380 500 500 500 500
20m - - - - 750 750 750 750
35m - - - - 1500 1500 1500 1500

HEAT PUMP
MODEL ACC 10CR ACC 15CR ACC 20CR ACC 25CR ACC 30CR ACC 40CR ACC 50CR ACC 60CR
7m 40 40 50 100 100 100 100 100
10m 100 100 125 250 250 250 250 250
15m - - 250 500 500 500 500 500
20m - - - - 750 750 750 750
35m - - - - 1500 1500 1500 1500

CAUTION FOR R407C


Avoid prolong exposure of an opened compressor, or the internal part of refrigerant piping to moist air.
The POE oil in the compressor and piping can absorb moisture from air.

OVERALL CHECKING
• Ensure the following, in particular :
1) The unit is mounted solidly and rigid in position.
2) Piping and connections are leak proof after charging.
3) Proper wiring has been done.

• Drainage check - pour some water into drain pan.


• Test run
1) Conduct a test run after water drainage test and gas leakage test.
2) Watch out for the following :
a) Is the electric plug firmly inserted into the socket?
b) Is there any abnormal sound from unit?
c) Is there any abnormal vibrations with regard to unit itself or piping?
d) Is there smooth drainage of water?
• Check that :
1) Outdoor fan is running, with warm air blowing off the outdoor unit (cooling cycle).
2) Indoor blower is running and discharge cool air (cooling cycle).
3) Suction (low side) pressure as recommended is before this.
4) The remote controller incorporate a 3 minute delay in there circuit. Thus, it requires about 3
minutes before the outdoor unit can start up.

57
STANDARD OPERATING CONDITION

COOLING ONLY UNIT


Temperature Ts °C Th °C
minimum indoor temperature 19.4 13.9
maximum indoor temperature 26.7 19.4
minimum outdoor temperature 19.4 13.9
maximum- outdoor temperature 46.0 24.0

HEAT PUMP UNIT


Temperature Ts °C Th °C
minimum indoor temperature 10.0 -
maximum indoor temperature 26.7 -
minimum outdoor temperature - 8.0 - 9.0
maximum- outdoor temperature 24 18

Ts : Dry bulb temperature


Th : Wet bulb temperature

OPERATING STATE AND FAULT TABLE


COOLING (C3B BOARD)
HIGH MED. LOW
COOL SLEEP TIMER OPERATION / FAULTY INDICATION ACTION
FAN FAN FAN
ROOM SENSOR CONTACT LOOSE / SHORT CALL YOUR DEALER
INDOOR COIL SENSOR CONTACT LOOSE /
CALL YOUR DEALER
SHORT
OUTDOOR COIL SENSOR CONTACT
CALL YOUR DEALER
LOOSE / SHORT

GAS LEAK CALL YOUR DEALER

COMPRESSOR OVERLOAD CALL YOUR DEALER

HEAT PUMP (C3B BOARD)


HIGH MED. LOW
COOL SLEEP TIMER HEAT OPERATION / FAULTY INDICATION ACTION
FAN FAN FAN
ROOM SENSOR CONTACT LOOSE / SHORT CALL YOUR DEALER
INDOOR COIL SENSOR CONTACT LOOSE /
CALL YOUR DEALER
SHORT
OUTDOOR COIL SENSOR CONTACT
CALL YOUR DEALER
LOOSE / SHORT

GAS LEAK CALL YOUR DEALER

COMPRESSOR OVERLOAD CALL YOUR DEALER


OUTDOOR DEFROST -

m ON m / l ON OR OFF BLINKING

COOLING & HEATPUMP (UNIVERSAL BOARD)


ERROR CODE AT 7 SEGMENT DISPLAY OPERATION / FAULTY INDICATION
E1 BLINKING ROOM SENSOR CONTACT LOOSE / SHORT
E2 BLINKING INDOOR COIL SENSOR CONTACT LOOSE / SHORT
E3 BLINKING OUTDOOR COIL SENSOR CONTACT LOOSE / SHORT
E4 BLINKING COMPRESSOR OVERLOAD
E5 BLINKING GAS LEAK
E6 BLINKING NA
HEAT LED BLINKING OUTDOOR DEFROST (FOR HEAT PUMP ONLY)

58
12. REMOTE CONTROL OPERATION GUIDE

8 10

9
SENSOR
4
4 1
FAN ON/OFF
ON/OFF
1
2
AUTO COOL
HIGH DRY 3
2 TEMP FAN MODE TEMP
MED HEAT
LOW FAN 7 6
5 SWING SLEEP
TIMER SWING SLEEP
6
5 3
TIMER MODE

1. “ON/OFF” switch 6. “Sleep” mode


• Press to start the air conditioner unit. • Press button to activate the sleep function.
• Press again to stop the unit. This function can only be activated under
“cool” or heating mode operation. When it is
2. Temperature setting activated under “cool” mode operation, the
• Set the desired room temperature. set temperature will increase 0.5oC after 30
• Press button to increase or decrease the minutes, 1oC after 1 hour and 2oC after 2
set temperature. Setting range are between hours. If it is activated under “HEAT” mode
16oC to 30oC (60oF to 80oF). operation, the set temperature will be
decreased 0.5° C after 30 minutes, 1° C
3. Operation Modes after 1 hour and 2° C after 2 hours.
• Press the “mode” button for select the type
of operating mode. 7. Air Swing
- Cooling Only : • Press button to activate the automatic air
COOL, DRY, FAN swing function.
- Heat Pump :
AUTO, COOL, DRY, HEAT, FAN 8. Sensor
(AUTO mode is represented by both • Infra red sensor to receive signals from
COOL and HEAT LED light on) wireless controller.

4. Fan Speed selection. 9. LED display


• Press the button until the desired fan speed • To display the set temperature (in º C) and
is achieved. timer delay setting (in hours).

5. Timer. 10. Transmission source


• Press the set button to select the switch • To transmit signals to the air conditioner.
timer of the air conditioner unit (the setting
range is between 1 to 10 hours).

59
13. SERVICING AND MAINTENANCE

Warning
Disconnect from Main Supply before Servicing the air conditioner

The unit is designed to give a long life operation with minimum maintenance required. However, it should be
regularly checked and the following items should be given due attention.

Components Maintenance Procedure Recommended Schedule


Air Filters 1. Clean with a vacuum cleaner, or by tapping lightly Every 2 weeks.
and then washing in lukewarm water (below 40°C)
With neutral soap. More frequently if required.

2. Rinse well to dry before re-installing.


3. Note : Never use petrol, thinner, benzene or any
other chemicals.
Indoor Unit 1. Clean away dirt or dust on grille or panel by wiping Every 2 weeks.
with a soft cloth soaked in lukewarm (or cold)
water or neutral detergent solution. More frequently if required.

2. Note: Never use petrol, thinner, benzene or any


other volatile chemicals, which may cause
plastic surface to deform.
Condensate Drain 1. Check and clean. Every 3 months.
Pan & Pipe
Indoor Fan 1. Check for unusual noise. As necessary.
Indoor/Outdoor Coil 1. Check and remove dirt which are clogged between Every month.
fins.
2. Check and remove obstacles which hinder air flow
in and out of indoor/outdoor unit. Every month.

Electrical 1. Check voltage, current and wiring. Every 2 months.


2. Check faulty contacts caused by loose connections, Every 2 months.
foreign matters, etc.
Compressor 1. No maintenance needed if refrigerant circuit Every 6 months.
remains sealed. However, check for refrigerant leak
at joints & fittings.
Compressor 1. Oil is factory charged. Not necessary to add oil if No maintenance required.
Lubrication circuit remains sealed.
Fan Motors 1. All motors pre-lubricated and sealed at factory. No maintenance required.
Lubrication

PRE-START UP MAINTENANCE (AFTER EXTENDED SHUTDOWN)


- Inspect thoroughly and clean indoor and outdoor units.
- Clean or replace air filters.
- Clean condensate drain line.
- Clean clogged indoor and outdoor coils.
- Check fan imbalance before operation.
- Tighten all wiring connections and panels.
- Check for refrigerant leakage.

60
The design of the ALC outdoor series allows servicing to be carried out readily and easily. The removal of the top side,
front and back panel make almost every part accessible.

Under normal circumstances, these outdoor units only require a check and cleaning of air intake coil surface once
quarterly. However, if a unit is installed in areas subjected to much oil mist and dust, the coils must be regularly
cleaned by qualified Air Conditioner Service Technicians to ensure sufficient heat exchange and proper operation.
Otherwise, the systems life span may be shortened.

CAUTION!
Do not charge OXYGEN, ACETYLENE OR OTHER FLAMMABLE and poisonous gases into the unit
when performing a leakage test or an air tight test. These gases could cause severe explosion
and damage if expose to high temperature and pressure.
It is recommended that only nitrogen or refrigerant be charged when performing the leakage or airtight test.

61
14. TROUBLESHOOTING

When any air-conditioner malfunction is noted, immediately switch off the power supply to the unit, and
contact the local dealer, if necessary. Some simple troubleshooting tips are given below :

FAULT CAUSE
1. Fan does not work 3 minutes after • Protection against the frequent starting. Wait 3 or 4 minutes.
starting

2. The air conditioning unit does not • Power failure or need to replace the fuse.
work
• The power plug is disconnected.
• Possibility of making a programming error in the controller.
• If the fault persist after these verifications, contact your installer.
3. The air conditioning unit does not • The air filter is dirty.
blow sufficiently
• The doors or windows are open.
• The air entrance and exit are clogged.
• The regulate temperature is not high enough.
4. The remote control light is deficient • The batteries are discharge.
• The batteries are not correctly inserted.
• The assembly is not good.
5. Air discharge flow has a bad odor • This odor can be caused by cigarette smoke particles, perfume,
sweat, which stick to the coil.
• Check if there is any moisture on the walls, garment, other.
• Check the drain pan.
6. Condensation on the air grille of • This is due to air humidity after a long time of operation.
indoor unit
• The unit has a lower temperature point, increase the point and
operate at high speed.
7. The water flow of air conditioning • Check the condensate evacuation.
unit
8. The air conditioning unit are noisy • “Air flow noise” : refrigerant fluid admission in evaporator.

62
FOR COOLING ONLY MODELS OR HEAT PUMP MODELS (COOLING CYCLE)

DIAGNOSIS BY FLOW CHART


The following chart are efficient checking procedures for troubleshooting when these fan-coil units, are
coupled with the condensing units using standard wiring. For dual circuited models, perform the procedures
for each circuit.

No Cooling

: Faulty : Check : Cause Remedy

No Cooling ( Compresor Does Not Start )

Evaporator Stop
Fan Motor

Faulty No Voltage or Low Voltage Get the Right Voltage


Unit Power
Supply
Single-Phase Repair the Power Line

Fuse For Blown Components Shorted Repair or Replace The Components


Operation
Circuit
Connections Loose Tighten The Connections
Running
Overcurrent Tripped High Volage or Low Voltage Get The Right Voltage
Relay For Check The Power Supply To The
Evaporator Fan Single-Phase
Motor : Repair When Necessary

Faulty Coil Burned Change The Contactor


Evaporator Fan
Contactor
Contact Faulty Repair The Contacts

Faulty Fan Motor Repair Or Change The Motor

Defective Operation Switch Repair Or Replace The Switch

Stop
Condenser
Fan Motor
Tripped
Overcurrent High Voltage or Low Voltage Get The Right Voltage
Relay For
Check The Power Supply To The
Condenser Fan Single-Phase
Motor : Repair When Necessary

Running
Faulty Coil Burnt Change The Contactor
Condenser Fan
Contactor
Contact Faulty Change The Contacts

Fan Motor Faulty Repair or Change The Motor

Other Electrical Component Faulty Repair or Change If Necessary

Coil Burnt Change The Contactor


Compressor Faulty
Contactor
Contact Faulty Repair The Contacts

Open Compressor Windings Change The Compressor

Incorrect Wiring Correct The Wiring

63
INSUFFICIENT COOLING
Insufficient Cooling

Cycling On
Compressor
Cycling
High Discharge Pressure or Low See "High Discharge Pressure" or
Tripping Suction Pressure "Low Suction Pressure"
Dual Pressure
Switch Clogged Capillary or Pressure Repair Clogging and Replace
Switch The Switch If Required

Switch Faulty Repair or Change If Necessary

Running Overcurrent Tripping High Voltage or Low Voltage Get The Right Voltage
Relay For
Compressor Check The Power Line To The
Single-Phase
Compressor : Repair When Necessary
High Discharge Pressure And See "High Discharge Pressure"
High Suction Pressure or "High Suction Pressure"
Loose Connections Tighten The Connections
Discharge Gas Tripping High Discharge Pressure And See "High Discharge Pressure"
Thermostat or Low Suction Pressure or "Low Suction Pressure"
Internal
Thermostat Refrigerant Short Charge or Add Refrigerant. Repair
Refrigerant Leakage Leakage If Detected.

High Suction Pressure See "High Suction Pressure"

High Discharge Pressure or Low See "High Discharge Pressure"


Suction Pressure or "Low Suction Pressure"

HIGH DISCHARGE PRESSURE


High Discharge
Pressure

Restricted
Condenser Clogged Condenser Coil Clean The Condenser
Air Flow
Check The Voltage And Get
Low Fan Speed
The Right Voltage

Malfunction Of Fan Cycling Check The System And


High System Repair If Required
Condenser
Secure Space For
Air Inlet Circulating Air Flow
Required Air Flow
Temperature
Overcharged Refrigerant Purge The Refrigerant

Non-Condensable Gas Purge The Gas

Restricted Liquid Line Remove The Restriction

High Suction Pressure See "High Suction Pressure"

LOW DISCHARGE PRESSURE

Low Discharge
Pressure

Excessive
Condenser Malfunction Of Fan Cycling Check The System And Repair The
Air Flow System Components If Required

Low Refrigerant Charge Add Refrigerant

Low Ambient Temperature See The Unit Working Range

64
HIGH SUCTION PRESSURE
High Suction
Pressure

Evaporator Low
Air Inlet Excessive Fresh Air Intake Reduce The Fresh Air Intake
Temperature
Insufficient Duct Insulation Reinforce The Duct Insulation

Defective Compressor Valve Change Or Repair The Compressor

Overcharged Refrigerant Purge The Refrigerant

LOW SUCTION PRESSURE

Low Suction Pressure

Evaporator Restricted Clogged Air Filter Clean The Air Filter


Air Flow
Restricted Duct Remove The Restriction

Low Fan Speed Adjust The Fan Speed


Evaporator
Low
Air Inlet Short Cycling Remove Obstacles To Air Circulation
Temperature
Faulty Thermostat Repair Or Replace If Necessary

Restricted Liquid LIne And


Remove The Restriction
Suction Line

Low Refrigerant Charge Add Refrigerant

Low Discharge Pressure See "Low Discharge Pressure"

NOISY OPERATION

Noisy Operation

Noisy
Compressor

Shipping Noisy Unremoved Shipping Bolt(s) Remove The Bolt(s)


Bolt(s)
Overcharged Refrigerant Purge The Refrigerant
Liquid
Refrigerant Low Suction Pressure See "Low Suction Pressure"
Backing Up
Worn Compressor Parts Replace Or Repair The Compressor

Evaporator Noisy
Knocking Runner Fix The Runner Or Casing Properly
Fan
Worn Bearing Change The Bearing
Strainer
Whistling
Liquid Line Noisy Partially Clogged Clean The Dryer

Refrigerant Short Charge Add Refrigerant

Loose Fixed Screws Tighten All Fixed Screws

Inadequate Duct Work Check Flexible Ducts

65
FOR HEAT PUMP MODELS

By means of pressure readings :


PRESSURE PROBABLE CAUSE

Data

Normal
A Little

A Little
High

High
Low

Low
Too

Too
Circuit

High Side = 1. Overcharged with refrigerant.


Low Side = 2. Non-condensable gases in refrigerant circuit (e.g. oil).
3. Obstructed air-intake/discharge.
4. Short circuiting of hot air outdoor unit.
High Side = 1. Poor compression/no compression (compressor defective.)
Low Side = 2. Check valve stick in open position.
3. Reversing valve leaking.
High Side = 1. Undercharged with refrigerant.
Low Side = 2. Refrigerant leakage.
3. Air filter clogged/dirty (indoor unit).
4. Indoor fan locked.
5. Defective defrost control, outdoor coil freeze up (heating).
6. Outdoor fan locked (heating).
High Side = 1. Outdoor fan blocked (cooling).
Low Side = 2. Outdoor coil dirty (cooling).
3. Indoor fan locked (heating).
4. Indoor filter clogged/dirty (heating).
5. Non-condensable gases in refrigerant circuit (e.g. air)
High Side = 1. Air intake temperature of indoor unit too high.
Low Side =

BY MEANS OF DIAGNOSIS FLOW CHART


Generally, there are two kind of problems, i.e. starting failure and insufficient cooling/heating. "Starting Failure" is
caused by electrical defect while "Insufficient Cooling/Heating" is caused by improper application or defects in
refrigerant circuit.

i) DIAGNOSIS OF ELECTRIC CIRCUIT


No Cooling / Heating

Unit fail to start


Check power supply
- voltage Check settings of remote control box
- phase
- frequency
Check power source cord
Check circuit breake & fuse

Fan fails to start Compressor fails to start

Fan Motor Capacitor defective Thermostat setting too high


Voltage supply not within range
Loose Connections, Protection Device Actuated
Contactors Loose Connections,
Improper wiring

Irregular motor resistance (Ω ) Reset Compressor


& insulation (M Ω ) Capacitor Defective

Replace Fan Motor Check motor resistance ( Ω ) and insulation (M Ω)


Regular but fails
to start Irregular

Compressor locked (to replace compressor) Compressor Motor damaged ( to replace compressor)

66
The most common causes of air conditioner failure to “start" are:
a) Voltage not within ±10% of rated voltage.
b) Power supply interrupted.
c) Control settings improper.
d) Air conditioner is disconnected from main power source.
e) Fuse blown or circuit breaker off.

ii) DIAGNOSIS OF REFRIGERANT CIRCUIT / APPLICATION


There might be some cases where the unit starts running but does not perform satisfactory, i.e.
insufficient cooling. Judgement could be made by measuring temperature difference of indoor
unit's intake and discharge air as well as running current.

Insufficient Cooling

Unit Starts

Check air circulation


High heat load

Indoor/Outdoor coil dirty Refrigerant circuit


Excessive heat
(clogged) source e.g. electric
Leakage kettle
Air filters dirty
Restriction e.g. at
strainer, capillary, Room overcrowded
filter dryer, etc. with people
Fan Malfunction
Windows / doors
Compressor wide open
Obstruction at air inlet/outlet
of indoor/outdoor unit
Less or no compression
(Low running current)

Satisfactory operation with temperature difference of


air intake & discharge of indoor unit 10°C - 15°C

Insufficient Heating

Unit Starts

Check air circulation


High heat load

Refrigerant circuit
Indoor/Outdoor coil dirty (clogged)
Leakage
Air filters dirty
Restriction e.g. at
strainer, capillary,
Fan Malfunction filter dryer, etc.
Windows / doors
Compressor wide open
Obstruction at air inlet/outlet
of indoor/outdoor unit
Less or no compression
(Low running current)

Satisfactory operation with temperature difference of


air intake & discharge of indoor unit 16°C - 25°C

67
15. PARTS LIST

MODEL: ACC 10 C/CR

1. TOP SIDE PANEL


2. FAN DECK
3. COIL
4. PRIMARY DRAIN PAN
5. SECONDARY DRIP PAN
6. HANGER
7. CONTROL BOX

68
MODEL: ACC 15 / 20 / 25 C/CR

1. TOP SIDE PANEL


2. FAN DECK
3. COIL
4. PRIMARY DRAIN PAN
5. SECONDARY DRIP PAN
6. HANGER
7. CONTROL BOX

69
MODEL: ACC 30 C

1. PANEL TOP ASSY.


2. TERMINAL BOX ASSY.
3. COIL TUBING ASSY.
4. DRAIN PAN SMALL ASSY.
5. DRAIN PAN BIG ASSY.
6. BLOWER ASSY.
7. BLOWER PANEL
8. BLOWER FLANGE

70
MODEL: ACC 30 CR

1. PANEL TOP ASSY.


2. TERMINAL BOX ASSY.
3. COIL TUBING ASSY.
4. DRAIN PAN SMALL ASSY.
5. DRAIN PAN BIG ASSY.
6. BLOWER ASSY.
7. BLOWER PANEL
8. BLOWER FLANGE

71
MODEL: ACC 40 C

1. PANEL TOP ASSY.


2. TERMINAL BOX ASSY.
3. COIL TUBING ASSY.
4. DRAIN PAN SMALL ASSY.
5. DRAIN PAN BIG ASSY.
6. BLOWER ASSY.
7. BLOWER PANEL
8. BLOWER FLANGE

72
MODEL: ACC 40 CR

1. PANEL TOP ASSY.


2. TERMINAL BOX ASSY.
3. COIL TUBING ASSY.
4. DRAIN PAN SMALL ASSY.
5. DRAIN PAN BIG ASSY.
6. BLOWER ASSY.
7. BLOWER PANEL
8. BLOWER FLANGE

73
MODEL: ACC 50 C

1. PANEL TOP ASSY.


2. TERMINAL BOX ASSY.
3. COIL TUBING ASSY.
4. DRAIN PAN SMALL ASSY.
5. DRAIN PAN BIG ASSY.
6. BLOWER ASSY.
7. BLOWER PANEL
8. BLOWER FLANGE

74
MODEL: ACC 50 CR

1. PANEL TOP ASSY.


2. TERMINAL BOX ASSY.
3. COIL TUBING ASSY.
4. DRAIN PAN SMALL ASSY.
5. DRAIN PAN BIG ASSY.
6. BLOWER ASSY.
7. BLOWER PANEL
8. BLOWER FLANGE

75
MODEL: ACC 60 C

1. PANEL TOP ASSY.


2. TERMINAL BOX ASSY.
3. COIL TUBING ASSY.
4. DRAIN PAN SMALL ASSY.
5. DRAIN PAN BIG ASSY.
6. BLOWER ASSY.
7. BLOWER PANEL
8. BLOWER FLANGE

76
MODEL: ACC 60 CR

1. PANEL TOP ASSY.


2. TERMINAL BOX ASSY.
3. COIL TUBING ASSY.
4. DRAIN PAN SMALL ASSY.
5. DRAIN PAN BIG ASSY.
6. BLOWER ASSY.
7. BLOWER PANEL
8. BLOWER FLANGE