Sunteți pe pagina 1din 40

Micrologic™ 2.0A, 3.0A, 5.0A, and 6.

0A Electronic Trip
Units

Unidades de disparo electrónico Micrologic™ 2.0A, 3.0A,


5.0A y 6.0A

Déclencheurs électroniques MicrologicMC 2.0A, 3.0A, 5.0A et


6.0A

Instruction Bulletin
Boletín de instrucciones
Directives d'utilisation
48049-136-05
Rev. 01, 04/2012
Retain for Future Use. / 
Conservar para uso futuro. / 
À conserver pour usage ultérieur.
Micrologic™ 2.0A, 3.0A, 5.0A, and 6.0A
Electronic Trip Units

ENGLISH
Instruction Bulletin
48049-136-05
Rev. 01, 07/2012
Retain for future use.
Micrologic™ 2.0A, 3.0A, 5.0A, and 6.0A Electronic Trip Units 48049-136-05
Rev. 01, 07/2012

Hazard Categories and Special Read these instructions carefully and look at the equipment to become
Symbols familiar with the device before trying to install, operate, service or maintain
ENGLISH

it. The following special messages may appear throughout this bulletin or on
the equipment to warn of potential hazards or to call attention to information
that clarifies or simplifies a procedure.
The addition of either symbol to a “Danger” or “Warning” safety label
indicates that an electrical hazard exists which will result in personal injury if
the instructions are not followed.
This is the safety alert symbol. It is used to alert you to potential personal
ANSI
injury hazards. Obey all safety messages that follow this symbol to avoid
possible injury or death.

DANGER
DANGER indicates a hazardous situation which, if not avoided, will result
IEC in death or serious injury.

WARNING
WARNING indicates a hazardous situation which, if not avoided, can
result in death or serious injury.

CAUTION
CAUTION indicates a hazardous situation which, if not avoided, can
result in minor or moderate injury.

NOTICE
NOTICE is used to address practices not related to physical injury. The
safety alert symbol is not used with this signal word.

NOTE: Provides additional information to clarify or simplify a procedure.

Please Note Electrical equipment should be installed, operated, serviced, and


maintained only by qualified personnel. No responsibility is assumed by
Schneider Electric for any consequences arising out of the use of this
material.

FCC Notice This equipment has been tested and found to comply with the limits for a
Class A digital device, pursuant to part 15 of the FCC Rules. These limits
are designed to provide reasonable protection against harmful interference
when the equipment is operated in a commercial environment. This
equipment generates, uses, and can radiate radio frequency energy and, if
not installed and used in accordance with the instruction manual, may cause
harmful interference to radio communications. Operation of this equipment
in a residential area is likely to cause harmful interference in which case the
user will be required to correct the interference at his own expense. This
Class A digital apparatus complies with Canadian ICES-003.

2-EN © 1999–2012 Schneider Electric All Rights Reserved


48049-136-05 Micrologic® 2.0A, 3.0A, 5.0A and 6.0A Electronic Trip Units
Rev. 01, 07/2012 Table of Contents

Table of Contents

ENGLISH
SECTION 1: GENERAL INFORMATION ...................................................................................................................... 5
Introduction ................................................................................................. 5
Communications ......................................................................................... 5
Trip Unit Settings ........................................................................................ 5
Micrologic 2.0A Trip Unit ....................................................................... 6
Micrologic 3.0A Trip Unit ....................................................................... 6
Micrologic 5.0A Trip Unit ....................................................................... 7
Micrologic 6.0A Trip Unit ....................................................................... 8
Zone-Selective Interlocking ......................................................................... 9
Trip Unit Switches ..................................................................................... 10
Long-Time Protection .......................................................................... 10
Short-Time Protection ......................................................................... 11
Instantaneous Protection ..................................................................... 12
Ground-Fault Protection ...................................................................... 13
Indicator Lights .......................................................................................... 13
Overload Indicator Light ...................................................................... 13
Trip Indicator Lights ............................................................................. 14
Ammeter ................................................................................................... 14
Trip Unit Testing ........................................................................................ 14
Micrologic Trip Unit Configuration ............................................................. 14
Control Power ...................................................................................... 14
External Power Supply ........................................................................ 15

SECTION 2: AMMETER .................................................................................................................... 16


Display ...................................................................................................... 16
Ammeter Measurements ........................................................................... 16
Accessing Information ............................................................................... 16
Current Menu ...................................................................................... 17
Peak Menu .......................................................................................... 18
Switch Settings Menu .......................................................................... 19

SECTION 3: OPERATION .................................................................................................................... 20


Switch Setting Adjustment ........................................................................ 20
Examples .................................................................................................. 20
Micrologic 2.0A Trip Unit ..................................................................... 20
Micrologic 3.0A Trip Unit ..................................................................... 21
Micrologic 5.0A Trip Unit ..................................................................... 21
Micrologic 6.0A Trip Unit ..................................................................... 22
Zone-Selective Interlocking (ZSI) .............................................................. 23
Communication Module values ................................................................. 24
Trip Unit Settings Check ........................................................................... 26
Trip Unit Operation Verification ................................................................. 26
Equipment Ground-Fault Trip Functions Testing ...................................... 27
Trip Unit Resetting .................................................................................... 27
Trip Unit Status Check .............................................................................. 27

SECTION 4: TRIP UNIT REPLACEMENT .................................................................................................................... 28


Required Tools .......................................................................................... 28
Preparation ............................................................................................... 28
Record Switch Settings ....................................................................... 28
Circuit Breaker Disconnection ............................................................. 28
Circuit Breaker Accessory Cover Removal ......................................... 28
Rating Plug Removal ........................................................................... 29
Trip Unit Removal ................................................................................ 29

© 1999–2012 Schneider Electric All Rights Reserved 3-EN


Micrologic™ 2.0A, 3.0A, 5.0A, and 6.0A Electronic Trip Units 48049-136-05
Table of Contents Rev. 01, 07/2012

Trip Unit Replacement .............................................................................. 29


Battery Installation ............................................................................... 29
ENGLISH

Trip Unit Installation ............................................................................. 30


Circuit Breaker Accessory Cover Replacement ........................................ 31
Trip Unit Installation Check ....................................................................... 32
Secondary Injection Testing ................................................................ 32
Primary Injection Testing ..................................................................... 32
Check Accessory Operation ................................................................ 32
Trip Unit Setup .......................................................................................... 32
Circuit Breaker Reconnection ................................................................... 32

SECTION 5: ADJUSTABLE RATING PLUG REPLACEMENT .............................................................................................. 33


Rating Plug Removal ................................................................................ 33
New Rating Plug Installation ..................................................................... 33

SECTION 6: BATTERY REPLACEMENT .................................................................................................................... 34


Circuit Breaker Disconnection ................................................................... 34
Circuit Breaker Accessory Cover Removal ............................................... 34
Withstand Module Shifting ........................................................................ 34
Battery Replacement ................................................................................. 34
Withstand Module Replacement ............................................................... 35
Circuit Breaker Accessory Cover Replacement ........................................ 35
Circuit Breaker Reconnection ................................................................... 35

APPENDIX A: REGISTER LIST .................................................................................................................... 36


List of Registers ........................................................................................ 36

4-EN © 1999–2012 Schneider Electric All Rights Reserved


48049-136-05 Micrologic™ 2.0A, 3.0A, 5.0A, and 6.0A Electronic Trip Units
Rev. 01, 07/2012 Section 1—General Information

Section 1—General Information

ENGLISH
Introduction Figure 1: Micrologic Trip Unit

A—Micrologic Trip Unit


Micrologic™ trip units (A) provide adjustable A B—Product Name

06134858
tripping functions on electronic trip circuit

06133249
C—Switch Cover
7.0 A

breakers. The product name (B) specifies the Microlo


gic
D—Switch Cover Opening Slot
B E—Adjustable Rating Plug
level of protection provided by the trip unit.

Micrologic 3.0A
100 %
Type of protection
2—Basic IEC protection (LS0) 40 %
E
3—Basic UL protection (LI)
5—Selective protection (LSI) menu long
.8 .9
time tr
(s) 4
8 12
16
alarm

Ir 2 20

6—Selective protection plus ground fault


.7 .95
1 24
.6 .98 .5 Ir
.5 1 @6
.4 x In

protection for equipment (LSIG)

Trip unit series


D
0—Indicates the first version
C
Type of measurement
None—Provides protection only
A—Provides protection plus ammeter measurements

Micrologic trip units are field replaceable to allow


for upgrading of the trip unit in the field. For
complete information on available circuit breaker
models, frame sizes, interrupting ratings, sensor
plugs, rating plugs and trip units, see the product
catalog.

Communications Micrologic trip units can communicate with other devices if the optional
Circuit Breaker Communication Module (BCM) is installed. For information
on the communication module, see the product catalog and Modbus™
Communications System, Data Bulletin 0613IB1201.

Trip Unit Settings On the face of the trip unit are adjustable switches to allow changing of trip
characteristics. Trip units are shipped with the long-time pickup switch set at
1.0 and all other trip unit adjustments set at their lowest settings.

© 1999–2012 Schneider Electric All Rights Reserved 5-EN


Micrologic™ 2.0A, 3.0A, 5.0A, and 6.0A Electronic Trip Units 48049-136-05
Section 1—General Information Rev. 01, 07/2012

Micrologic 2.0A Trip Unit NOTE: For use with IEC circuit breakers only.
ENGLISH

Figure 2: 2.0A Trip Unit


The Micrologic 2.0A trip unit provides basic IEC
(LS0) protection and a built-in ammeter. A N M L
A. Trip unit name

06134246
Micrologic 2.0 A

B. Alphanumeric display K
C. Three-phase bar graph
D. Scroll button
B
E. Menu button
F. Long-time pickup (Ir) switch
t

06134245
G. Long-time delay (tr) switch C F
H. Short-time pickup (Isd) switch*
I. Test plug receptacle
G
J. Overload indicator light
D
K. Reset button for battery status check and trip
E menu H
indicator LED J
0 Ir Isd I
L. Self-protection indicator light Ir
long time
.8 tr
(s) 4
8
alarm
.7 .9 12

M. Short-time or instantaneous trip indicator F .6


.5
.95 2
.98 1
16
20
.4 1 .5 24
x In @ 6 Ir

light instantaneous

G Isd
3
4
5
2.5
N. Long-time trip indicator light 2
1.5 10
6
8

H x Ir
setting

Micrologic 3.0A Trip Unit Figure 3: 3.0A Trip Unit

The Micrologic 3.0A trip unit provides basic UL A N M L


(LI) protection and a built-in ammeter.
06133243

Micrologic 3.0 A

A. Trip unit name K


B. Alphanumeric display
C. Three-phase bar graph
B
D. Scroll button
E. Menu button
t
06133201

F. Long-time pickup (Ir) switch C F


G. Long-time delay (tr) switch
H. Instantaneous pickup (Ii) switch
G
I. Test plug receptacle D
J. Overload indicator light H
E menu
J
K. Reset button for battery status check and trip 0 Ir Ii I
indicator LED Ir
long time
.8 tr 8
alarm
.7 .9 (s) 4 12

L. Self-protection indicator light F .6


.5
.95 2
.98 1
16
20
.4 1 .5 24
x In @ 6 Ir

M. Short-time or instantaneous trip indicator G Ii


instantaneous

4
5
6

light 3
2
8
10

H 1.5
x In
12

N. Long-time trip indicator light setting

*Short-time delay is factory set at 0 (no delay), thus short-time


pickup provides instantaneous protection.

6-EN © 1999–2012 Schneider Electric All Rights Reserved


48049-136-05 Micrologic™ 2.0A, 3.0A, 5.0A, and 6.0A Electronic Trip Units
Rev. 01, 07/2012 Section 1—General Information

Micrologic 5.0A Trip Unit Figure 4: 5.0A Trip Unit

ENGLISH
The Micrologic 5.0A trip unit provides selective A P O N
(LSI) protection and a built-in ammeter.

06133244
Micrologic 5.0 A

A. Trip unit name M


B. Alphanumeric display
C. Three-phase bar graph
B
D. Scroll button
E. Menu button
C t

06133202
F. Long-time pickup (Ir) switch F
G. Long-time delay (tr) switch
G
H. Short-time pickup (Isd) switch
I. Short-time delay (tsd) switch D H
J. Instantaneous pickup (Ii) switch I
E menu
L J
K. Test plug receptacle
long time
L. Overload indicator light Ir
.7
.8
.9
tr
(s) 4
8
12
alarm 0 Ir Isd Ii I
F .6
.5
.95 2
.98 1
16
20
M. Reset button for battery status check and trip .4
x In
1 .5 24
@ 6 Ir

indicator LED G Isd


e
short time
tsd
instantaneous
Ii
3
4
5 (s) .4 .4 .3 6
8
10
2.5 6 .3 .2 4 12

N. Self-protection indicator light H 2


1.5 10
8 .2
.1 2 0
.1 3
2
15
off
x Ir on I t off x In
setting delay

O. Short-time or instantaneous trip indicator I


light K
J
P. Long-time trip indicator light

© 1999–2012 Schneider Electric All Rights Reserved 7-EN


Micrologic™ 2.0A, 3.0A, 5.0A, and 6.0A Electronic Trip Units 48049-136-05
Section 1—General Information Rev. 01, 07/2012

Micrologic 6.0A Trip Unit Figure 5: 6.0A Trip Unit


ENGLISH

The Micrologic 6.0A trip unit provides selective A T S R Q


and ground-fault protection for equipment

06133245
t

06133202
Micrologic 6.0 A
(d1200 A) (LSIG) and a built-in ammeter. F
P
A. Trip unit name G
B. Alphanumeric display
B H
C. Three-phase bar graph
I
D. Scroll button J
E. Menu button C
100 % 0 Ir Isd Ii I
F. Long-time pickup (Ir) switch
G. Long-time delay (tr) switch 40 %
H. Short-time pickup (Isd) switch t

06133247
I. Short-time delay (tsd) switch D
J. Instantaneous pickup (Ii) switch E menu
O 2
I t on
K. Ground-fault pickup (Ig) switch Ir
long time
.8 tr 8
alarm K
.7 .9 (s) 4 12 2
L. Ground-fault delay (tg) switch F .6
.5
.95 2
.98 1
16
20
I t off
.4
x In
1 .5 24
@ 6 Ir L
M. Test plug receptacle G Isd
short time
tsd Ii
instantaneous
.4 .3
3
4
5 tsd .4
(s)
5 6 10
.3 .2
N. Ground fault push-to-trip button H 2.5
2
6
8 .2 .1
4
3
12
15
1.5
x Ir
10 .1 2 0
on I t off
2
x In
off 0 Ig I
O. Overload indicator light I Ig
setting
tg
delay
test
N
J C
D
E
F (s)
.3
.4 .4 .3
.2
P. Reset button for battery status check and trip K B
G
H .2
.1 0
.1
M
A J 2
on I t off
indicator LED L ground fault

Q. Self-protection indicator light


R. Ground-fault trip indicator light
S. Short-time or instantaneous trip indicator
light
T. Long-time trip indicator light

8-EN © 1999–2012 Schneider Electric All Rights Reserved


48049-136-05 Micrologic™ 2.0A, 3.0A, 5.0A, and 6.0A Electronic Trip Units
Rev. 01, 07/2012 Section 1—General Information

Zone-Selective Interlocking

ENGLISH
Short-time and ground-fault protection can be NOTE: Use I2t off with ZSI for proper coordination. Using I2t on with ZSI is
interlocked to provide zone-selective not recommended as the delay in the upstream device receiving a restraint
interlocking. signal could result in the trip unit tripping in a time shorter than the published
trip curve.
Control wiring links several trip units in the
distribution network and in the event of a fault, a NOTE: Setting short-time delay (tsd) or ground-fault delay (tg) to the 0
trip unit will obey the set delay time only if setting will eliminate selectivity for that circuit breaker.
receiving a signal from a downstream trip unit.
If the trip unit does not receive a signal, tripping
will be instantaneous (with no intentional delay).
• The fault is cleared instantaneously by the
nearest upstream circuit breaker.
• Thermal stresses (I2t) in the network are
minimized without any effect on the correct
time delay coordination of the installation.
Figure 6 shows circuit breakers 1 and 2 zone- Figure 6: Zone-Selective Interlocking
selective interlocked.
• A fault at A is seen by circuit breakers 1 and
2. Circuit breaker 2 trips instantaneously and
06133376

also informs circuit breaker 1 to obey set


delay times. Thus, circuit breaker 2 trips and
clears the fault. Circuit breaker 1 does not
trip.
• A fault at B is seen by circuit breaker 1.
Circuit breaker 1 trips instantaneously since 1 B
it did not receive a signal from the
downstream circuit breaker 2. Circuit breaker
1 trips and clears the fault. Circuit breaker 2
does not trip.
2 A

© 1999–2012 Schneider Electric All Rights Reserved 9-EN


Micrologic™ 2.0A, 3.0A, 5.0A, and 6.0A Electronic Trip Units 48049-136-05
Section 1—General Information Rev. 01, 07/2012

Trip Unit Switches


ENGLISH

Long-Time Protection NOTE: Micrologic trip units are powered from the circuit to always provide
fault protection. All other functions (display, metering, communications, etc.)
Long-time protection protects equipment against require external power. See 15 for more information.
overloads.
Figure 7: Long-Time Protection Switches
• Long-time protection is standard on all trip
Micrologic 2.0A Trip Unit Micrologic 3.0A Trip Unit
units.
A B C A B C
• The long-time pickup (Ir) (A) sets the

06134243

06133203
long time long time
maximum current level (based on sensor Ir
.7
.8
.9
tr
(s) 4
8
12
alarm Ir
.7
.8
.9
tr
(s) 4
8
12
alarm

.6 .95 2 16 .6 .95 2 16
plug rating In) which the circuit breaker can .5 .98 1 20 .5 .98 1 20
.4 1 .5 24 .4 1 .5 24
x In
continuously carry. If current exceeds this instantaneous
@ 6 Ir x In
instantaneous
@ 6 Ir

Isd Ii
value, circuit breaker will trip after the preset 2.5
3 4 5
6
4 5 6
3 8
time delay. The long-time pickup (Ir) is 2
1.5 10
8 2
1.5 12
10
x Ir
adjustable from 0.4–1.0 times the sensor setting
x In
setting

plug rating (In).


• The long-time delay (tr) (B) sets the length of
the time that the circuit breaker will carry an
overcurrent (below the short-time or
instantaneous pickup current level) before
Micrologic 5.0A Trip Unit Micrologic 6.0A Trip Unit
tripping. See Table 1 for delay settings.
A B C A B C
• Both long-time pickup and long-time delay
06133204

06133351
long time long time
are on the field-replaceable adjustable rating Ir
.7
.8
.9
tr
(s) 4
8
12
alarm Ir
.7
.8
.9
tr
(s) 4
8
12
alarm

.6 .95 2 16
plug. To change settings to more precisely .5 .98 1 20
.6
.5
.95 2
.98 1
16
20
.4 1 .5 24 .4 1 .5 24
match the application, various rating plugs x In @ 6 Ir x In @ 6 Ir

short time instantaneous short time instantaneous


are available. For instructions on replacing Isd 4
3 5
tsd
(s) .4 .4 .3
Ii
6
8
10
Isd
3
4
5
tsd
(s) .4 .4 .3
Ii
5
8
10
2.5 6 .3 .2 4 12 2.5 6 .3 .2 4 12
the rating plug, see Section 5 —Adjustable 2 8 .2 .1 3 15 2 8 .2 .1 3 15
1.5 10 .1 2 0 2 off 1.5 10 .1 2
0 2 off
Rating Plug Replacement. x Ir
setting
on I t off
delay
x In x Ir
setting
on I t off
delay
x In
test
Ig tg
• For Masterpact™ NT and NW circuit D
E
F (s) .4 .4 .3
C G .3 .2
.1
breakers, the In value can be changed by B
A J
H .2
.1 2
0
on I t off
replacing the sensor plug below the trip unit. ground fault

For further information, see the instructions


packed with the sensor plug replacement kit.
• The overload indicator light (C) indicates that
Table 1: Micrologic Trip Unit Long-Time Delay Values
the Ir long-time pickup threshold has been
exceeded. Setting1 Long-Time Delay in Seconds2
• Long-time protection uses true RMS
tr at 1.5 x Ir 12.5 25 50 100 200 300 400 500 600
measurement.
tr at 6 x Ir 0.5 1 2 4 8 12 16 20 24
Thermal imaging provides continuous
temperature rise status of the wiring, both before tr at 7.2 x Ir 0.343 0.69 1.38 2.7 5.5 8.3 11 13.8 16.6

and after the device trips. This allows the circuit 1Ir= In x long-time pickup. In = sensor rating. Trip threshold between 1.05 and 1.20 Ir.
breaker to respond to a series of overload 2Time-delay accuracy +0/-20%
3For Micrologic 5.0A and 6.0A trip units, when tsd is set to 0.4 on or 4.0 off, then tr = 0.5 instead of 0.34.
conditions which could cause conductor
overheating, but would go undetected if the NOTE: If checking trip times, wait a minimum of 15 minutes after circuit
long-time circuit was cleared every time the load breaker trips before resetting to allow the thermal imaging to reset
dropped below the pickup setting or after every completely to zero or use a full-function test kit to defeat the thermal
tripping event. imaging.

10-EN © 1999–2012 Schneider Electric All Rights Reserved


48049-136-05 Micrologic™ 2.0A, 3.0A, 5.0A, and 6.0A Electronic Trip Units
Rev. 01, 07/2012 Section 1—General Information

Short-Time Protection Figure 8: Short-Time Protection Switches

ENGLISH
Micrologic 5.0A Trip Unit Micrologic 6.0A Trip Unit
Short-time protection protects equipment

06133204

06133351
long time
against short circuits. Ir
.7
.8
.9
tr
(s) 4
8
12
alarm Ir
.7
long time
.8
.9
tr
(s) 4
8
alarm
12
.6 .95 2 16 .6 .95 2 16

• Short-time protection is standard on 2.0A, .5


.4
x In
1
.98 1
.5
20
24
@ 6 Ir
.5
.4
x In
1
.98 1
.5
20
24
@ 6 Ir

5.0A and 6.0A trip units. It is not available on Isd 4


short time
tsd Ii
instantaneous
Isd
short time
tsd Ii
instantaneous
(s) .4 .4 .3 8 4 .4 .4 .3 8
3.0A trip units. 2.5
3 5
6 .3 .2 4
6 10
12 2.5
3 5
6
(s)
.3 .2 4
5 10
12
2 8 .2 .1 3 15 2 8 .2 .1 3 15
• Short-time protection is based on the long- 1.5 10
on
.1 2 0
I t off
2
x In
off 1.5
x Ir
10
on
.1 2 0
I t off
2
x In
off
A x Ir
setting delay A setting delay
time pickup (Ir). Ig
E
tg
(s) .4 .4 .3
test

D F
.3 .2
• The short-time pickup (Isd) (A) sets current B B C
B
G
H .2 .1
A J .1 2
0
level (below instantaneous trip level) at ground fault
on I t off

which circuit breaker will trip after the preset


time delay.
• The short-time delay (tsd) (B) sets the length
of time that the circuit breaker will carry an
overcurrent above the short-time pickup Table 2: Micrologic Trip Unit Short-Time Delay Values
current level before tripping. It is adjustable
Setting Short-Time Delay
on the 5.0A and 6.0A trip unit and factory set
to zero on the 2.0A trip unit. I2t off (Isd at 10 Ir) (seconds) 0 0.1 0.2 0.3 0.4
• The I2t on/I2t
off option provides improved I2t on (Isd at 10 Ir) (seconds) 0.1 0.2 0.3 0.4
selectivity with downstream protective
tsd (min. trip) (milliseconds) 20 80 140 230 350
devices:
tsd (max. trip) (milliseconds) 80 140 200 320 500
— With I2t off selected, fixed time delay is
provided.
— With I2t on selected, inverse time I2t
protection is provided up to 10 x Ir.
Above 10 x Ir, fixed time delay is
provided.
• Intermittent currents in the short-time tripping
range which do not last sufficiently long to
trigger a trip are accumulated and shorten
the trip delay appropriately. NOTE: Use I2t off with ZSI for proper coordination. Using I2t on with ZSI is
not recommended as the delay in the upstream device receiving a restraint
• Short-time protection can be zone-selective
signal could result in the trip unit tripping in a time shorter than the
interlocked (ZSI) with upstream or
published trip curve.
downstream circuit breakers.
• Setting tsd to the 0 setting turns off zone-
selective interlocking.
• Short-time protection uses true RMS
measurement.
• Short-time pickup and delay can be adjusted
to provide selectivity with upstream or
downstream circuit breakers.

© 1999–2012 Schneider Electric All Rights Reserved 11-EN


Micrologic™ 2.0A, 3.0A, 5.0A, and 6.0A Electronic Trip Units 48049-136-05
Section 1—General Information Rev. 01, 07/2012

Instantaneous Protection Figure 9: Instantaneous Protection Switches


ENGLISH

Micrologic 2.0A Trip Unit Micrologic 3.0A Trip Unit


Instantaneous protection protects equipment

06134243

06133203
long time long time
against short circuits with no intentional time Ir
.7
.8
.9
tr
(s) 4
8
12
alarm Ir
.7
.8
.9
tr
(s) 4
8
12
alarm

.6 .95 2 16
delay. .5 .98 1 20
.6
.5
.95 2
.98 1
16
20
.4 1 .5 24 .4 1 .5 24
x In @ 6 Ir x In @ 6 Ir

• Instantaneous protection (Ii) (A) is standard Isd


instantaneous
Ii
instantaneous

3 4 5 4 5 6
on the 3.0A, 5.0A and 6.0A trip units. 2.5 6 3 8
2 8 2 10

• Instantaneous protection on 2.0A trip units is A


1.5
x Ir
setting
10
A
1.5
x In
12
setting

achieved by using short-time protection (Isd)


with the short-time delay factory set to 0
(zero).
• Instantaneous protection on the 3.0A, 5.0A
and 6.0A trip units is based on the circuit
Micrologic 5.0A Trip Unit Micrologic 6.0A Trip Unit
breaker sensor rating (In).

06133204

06133351
long time long time

• Instantaneous protection on the 2.0A trip unit Ir

.6
.7
.8
.9
tr
(s) 4
.95 2
8
12
16
alarm Ir
.7
.8
.9
tr
(s) 4
8
12
alarm

.6 .95 2 16
is based on the long-time pickup setting (Ir). .5
.4 1
.98 1
.5
20
24
.5 .98 1 20
24
x In @ 6 Ir .4 1 .5
x In @ 6 Ir

• Circuit breaker open command is issued as Isd 4


short time
tsd Ii
instantaneous
Isd
short time
tsd Ii
instantaneous
(s) .4 .4 .3 8 4 .4 .4 .3 8
soon as threshold current is exceeded. 2.5
3 5
6 .3 .2 4
6 10
12 2.5
3 5
6
(s)
.3 .2 4
5 10
12
2 8 .2 .1 3 15 2 8 .2 .1 3 15
• Instantaneous protection uses peak current 1.5
x Ir
10
on
.1 2 0
I t off
2
x In
off
A 1.5
x Ir
10
on
.1 2 0
I t off
2
x In
off
A
setting delay setting delay
measurement. Ig
E
tg
(s) .4 .4 .3
test

D F
C G .3 .2
• When instantaneous protection switch is set B H .2
.1 0
.1
A J 2
to off, the instantaneous protection is ground fault
on I t off

disabled.

Table 3: Micrologic Instantaneous Values

Setting Interruption Current

2.0A Isd (= Ir x..) 1.5 2 2.5 3 4 5 6 8 10

3.0A Ii (= In x..) 1.5 2 3 4 5 6 8 10 12

5.0A Ii (= In x..) 2 3 4 6 8 10 12 15 off

6.0A Ii (= In x..) 2 3 4 6 8 10 12 15 off

Ii = UL and ANSI instantaneous


Isd = IEC instantaneous (short-time with zero delay)
In = sensor rating
Ir = long-time pickup

12-EN © 1999–2012 Schneider Electric All Rights Reserved


48049-136-05 Micrologic™ 2.0A, 3.0A, 5.0A, and 6.0A Electronic Trip Units
Rev. 01, 07/2012 Section 1—General Information

Ground-Fault Protection Figure 10: Ground-Fault Protection Switches

ENGLISH
Micrologic 6.0A Trip Unit
Equipment ground-fault protection protects

06133351
long time
Ir tr alarm
conductors against overheating and faults from .6
.7
.8
.9 (s) 4
.95 2
8
12
16
ground-fault currents (d1200 A). .5
.4 1
.98 1
.5
20
24
x In @ 6 Ir

• Equipment ground-fault protection is Isd


3
short time
4
5
tsd
(s) .4 .4 .3
Ii
instantaneous

5
8
10
.3 .2
standard on 6.0A trip units. 2.5
2
6
8 .2 .1
4
3
12
15
1.5 10 .1 2
0 2 off
• Ground-fault pickup (Ig) (A) sets ground x Ir
setting
on I t off
delay
x In
test

current level where circuit breaker will trip Ig


D
E
F
tg
(s) .4 .4 .3
.2
C G .3
after the preset time delay. B
A J
H .2
.1 0
.1
2
on I t off
• Ground-fault delay (tg) (B) sets the length of A ground fault

time that the circuit breaker will carry a


B
ground-fault current above the ground-fault
pickup current level before tripping.
Table 4: Micrologic Trip Unit Ground-Fault Pickup Values
• Equipment ground-fault protection can be
zone-selective interlocked (ZSI) with Ig (= In x....) A B C D E F G H J
upstream or downstream circuit breakers. In d 400 A 0.3 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1
• Setting the ground-fault delay (tg) to the 0 400 A < In d 1200 A 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1
setting turns off zone-selective interlocking.
In > 1200 A 500 A 640 A 720 A 800 A 880 A 960 A 1040 A 1120 A 1200 A
• Neutral protection and equipment ground-
fault protection are independent and can In = sensor rating.
Ig = ground-fault pickup.
operate concurrently.

Table 5: Micrologic Trip Unit Ground-Fault Delay Values

Setting Ground-Fault Delay

I2t off (ms at In) (seconds) 0 0.1 0.2 0.3 0.4

I2t on (ms at In) (seconds) – 0.1 0.2 0.3 0.4

tsd (min. trip) (milliseconds) 20 80 140 230 350

tsd (max. trip) (milliseconds) 80 140 200 320 500

NOTE: Use I2t off with ZSI for proper coordination. Using I2t on with ZSI is
not recommended as the delay in the upstream device receiving a restraint
signal could result in the trip unit tripping in a time shorter than the
published trip curve.

Indicator Lights

Overload Indicator Light Figure 11: Overload Indicator Light


06133352

long time
The overload indicator light (A) lights when the Ir Ir
.7
.8
.9
tr
(s) 4
8
12
alarm

long-time pickup level has been exceeded (over .6


.5
.95 2
.98 1
16
20
A
.4 1 .5 24
100% on the bar graph). x In @ 6 Ir

short time instantaneous


Isd
4
tsd
.4 .4 .3
Ii
4
100 %
3 5 3 5
2.5 6 .3 .2 2.5 6
2 8 .2 .1 2 8
1.5 10 .1 2 0 1.5 10
x Ir on I t x In
setting delay
test
IΔn ΔI
(A)
3
5
7 230
(ms)
350
40 %
2 10
140
1 20
.5 30 60 800

earth leakage

© 1999–2012 Schneider Electric All Rights Reserved 13-EN


Micrologic™ 2.0A, 3.0A, 5.0A, and 6.0A Electronic Trip Units 48049-136-05
Section 1—General Information Rev. 01, 07/2012

Trip Indicator Lights Figure 12: Trip Indicator Lights


ENGLISH

The Ir trip indicator light (A) lights when a trip A B C D


occurs because the Ir long-time pickup level was

06133245
Micrologic 6.0 A
exceeded.
The Isd/Ii trip indicator light (B) lights when a trip
occurs because the Isd short-time pickup or the
Ii instantaneous pickup was exceeded.
The Ig trip indicator light (C) lights when a trip
occurs because the Ig ground fault pickup was
exceeded.
The Ap self-protection indicator light (D) lights
when the trip unit overheats, the instantaneous
override level is exceeded, or a trip unit power
supply failure occurs.

Ammeter Figure 13: Ammeter

The ammeter monitors and displays the circuit A


breaker currents. An alphanumeric screen (A)
continuously displays the phase at the highest
load. Navigation buttons (B) can be pressed to
display the various monitored currents.
100 %
The process of checking the ammeter values
can be stopped at any time. After several 40 %
seconds, Micrologic trip units automatically B
return to displaying the phase at the highest
load. menu

See the following section for addition information


concerning the ammeter.

Trip Unit Testing Trip unit functions can be tested using primary injection testing or secondary
injection testing.

Micrologic Trip Unit Configuration

Control Power The A trip unit was designed to be used with or without an external 24 Vdc
power supply.
Table 6: Pickup Values
The following will be powered and functional even if the trip unit is not
Sensor Plug Value Minimum Ground-Fault externally powered:
(In) Pickup
• Fault protection for LSIG functions. The A trip unit is fully circuit powered
100–250 A 30% of Sensor Rating for fault protection.
400–1200 A 20% of Sensor Rating
• LED trip indication (powered by an onboard battery). The battery’s only
1600–6300 A 500 A function is to provide LED indication if all other power is off
• All display functions and trip unit features power-up with current flow on
one phase greater than or equal to the values in Table 6.
• Ground-fault push-to-trip button works for testing ground fault with
current flow on one phase greater than or equal to the values in Table 6.
The ground-fault push-to-trip is also functional if a Hand-Held Test Kit or
Full-Function Test Kit is powering the trip unit.

14-EN © 1999–2012 Schneider Electric All Rights Reserved


48049-136-05 Micrologic™ 2.0A, 3.0A, 5.0A, and 6.0A Electronic Trip Units
Rev. 01, 07/2012 Section 1—General Information

The following will be powered and functional with external power:


• All of the above functions which are functional without external power.

ENGLISH
• Ammeter and bar graph displays are functional with or without current
flowing through the circuit breaker. With current flow between 0 and 20%
of sensor value, the ammeter may not be accurate.
• Trip settings and max. current readings can be accessed on the display
be pressing the navigation buttons with or without current flowing
through the circuit breaker.
• Ground-fault push-to-trip button works for testing ground fault with or
without current flowing through the circuit breaker.
• Optional Modbus communications are functional, using a separate 24
Vdc power supply for the circuit breaker communications module. This
separate 24 Vdc power supply is required to maintain the isolation
between the trip unit and communications.
The ground-fault push-to-trip is also functional if a Hand-Held Test Kit or
Full-Function Test Kit is powering the trip unit.

External Power Supply


The trip unit display can be powered by a 24 Vdc external power supply.
CAUTION Table 7: Power Supply Specifications

HAZARD OF SHOCK, ARC FLASH OR Function Specification


EQUIPMENT DAMAGE Power for Trip Unit Alone 24 Vdc, 50 mA
Trip unit and communication module must use Minimum Input-to-Output Isolation 2400 V
separate power supplies. Output (Including Max. 1% Ripple) ±5%
Dielectric Withstand (Input/Output) 3 kV rms
Failure to follow this instruction can result
in personal injury or equipment damage. Connections UC3
Connections F1 (-)
24 Vdc
F2 (+)

Power supply is used for graphic scree display when the circuit breaker is
open or not carrying current.

© 1999–2012 Schneider Electric All Rights Reserved 15-EN


Micrologic™ 2.0A, 3.0A, 5.0A, and 6.0A Electronic Trip Units 48049-136-05
Section 2—Ammeter Rev. 01, 07/2012

Section 2—Ammeter
ENGLISH

Display NOTE: The ammeter display will function only if the trip unit is powered. The
trip unit is powered by the circuit breaker carrying more than 0.20 x In of
load current, by being connected to a 24 Vdc external power supply, or by
having the Full-Function Test Kit or Hand-Held Test Kit connected and on.
Even with external power supplied, current through the circuit breaker must
exceed 0.20 x In for the ammeter reading to be accurate to within 1.5%.

A. Alphanumeric screen: Displays ammeter Figure 14: Ammeter


information

06133245
B. Bar graph: Displays currents using an LED A
bar graph
C. Menu button: Used to navigate between the
various menus
D. Scroll button: Used to scroll to the next B
100 %
screen in the menus
The default display is the current value of the 40 %
phase at the highest load.
C
If no information is displayed, contact the local
field office. D
menu

Ammeter Measurements

Micrologic A trip units measure the true RMS


value of currents. They provide continuous
current measurement from 0.2 to 20 x In with an
accuracy of 1.5% (including sensors). No
auxiliary source is needed where I > 0.2 x In.
The optional external power supply (24 Vdc)
makes it possible to display currents where
I < 0.2 x In and to store values of the interrupted
current.
A digital LCD screen continuously displays the
most heavily loaded phases (Imax) or displays
the Ia, Ib, Ic, Ig, and (on 4-pole circuit breakers
only) In stored current and setting values by
successively pressing the navigation button.

Accessing Information Figure 15: Menus


A–Currents B–Peak Currents C–Switch Settings
06133354

06133355

06133353

Three different menus can be accessed: Max


A. Current measurements A A Ir=
A
B. Stored peak current measurements
C. Switch settings
In addition, the ammeter can be used to address
the circuit breaker communication module 1.125 x Ir
(BCM) in circuit breakers which have the 100 % 1 x Ir 100 % 100 %
optional circuit breaker communication module 0.8 x Ir
installed. 0.6 x Ir
40 % 0.4 x Ir 40 % 40 %

16-EN © 1999–2012 Schneider Electric All Rights Reserved


48049-136-05 Micrologic™ 2.0A, 3.0A, 5.0A, and 6.0A Electronic Trip Units
Rev. 01, 07/2012 Section 2—Ammeter

To access the next menu, press the menu Figure 16: Navigation Buttons
button (A). To access the next screen in a menu,

ENGLISH
A B
press the scroll button (B).

06133356
menu
u

Current Menu Figure 17: Current Menus


A–A-Phase Current (IA) B–B-Phase Current (IB)
The current (default) menu displays:

06133354

06133342
06134248

06134248
A. Phase current (IA) in A phase
A A
B. Phase current (IB) in B phase
C. Phase current (IC) in C phase
D. Ground-fault current (Ig) (Micrologic 6.0A trip
units only)
E. Neutral current (In) 100 % 100 %
To display next current, press scroll button.
NOTE: Neutral current is only displayed with a 40 % 40 %
4-pole circuit breaker with the neutral protection
set to half or full. Refer to bulletin 48041-082-03
C–C-Phase Current (IC) D–Ground-Fault Current (Ig)
for NC CT wiring guidelines.
06133343

06133344
06134248

06134248
A A

100 % 100 %

40 % 40 %

E–Neutral Current (In) Return to A-Phase Current


06133354
06133345

06134248

06134248

A A

100 % 100 %

40 % 40 %

© 1999–2012 Schneider Electric All Rights Reserved 17-EN


Micrologic™ 2.0A, 3.0A, 5.0A, and 6.0A Electronic Trip Units 48049-136-05
Section 2—Ammeter Rev. 01, 07/2012

Peak Menu Figure 18: Access the Peak Menu


ENGLISH

Current Menu Peak Menu


To access the peak menu:

06133354

06133355
06134247

06134248
menu Max
1. Current menu is displayed.
A A
2. Press menu button.
3. Peak menu appears.
To access menu screens, press scroll button.

100 % 100 %

40 % 40 %

The peak menu displays: Figure 19: Peak Menus


A. Peak current (IpA) in A phase A–Peak A-Phase Current (IpA) B–Peak B-Phase Current (IpB)

06133346
06133355

B. Peak current (IpB) in B phase

06134248
Max

06134248
Max
C. Peak current (IpC) in C phase A A
D. Peak ground-fault current (Ipg) (Micrologic
6.0A trip unit only)
E. Peak neutral current (Ipn)
To display next peak current, press scroll button.
100 % 100 %
To reset a max value, scroll to the particular max
value screen to be reset and hold the scroll
button for three seconds. 40 % 40 %

C–Peak C-Phase Current (IpC) D–Peak Ground-Fault Current (Ipg)


06133347

06133348
06134248

06134248
Max Max

A A

100 % 100 %

40 % 40 %

E–Peak Neutral Current (Ipn) Return to Peak A-Phase Current


06133349

06133355

Max Max
06134248

A A

100 % 100 %

40 % 40 %

18-EN © 1999–2012 Schneider Electric All Rights Reserved


48049-136-05 Micrologic™ 2.0A, 3.0A, 5.0A, and 6.0A Electronic Trip Units
Rev. 01, 07/2012 Section 2—Ammeter

Switch Settings Menu Figure 20: Access the Switch Settings Menu

ENGLISH
Peak Menu Switch Settings Menu
The switch settings menu displays the values at

06133355

06133353
06134247

06134248
which the switches are set. Max menu

A Ir=
To access the switch settings menu: A

1. Peak menu is displayed.


2. Press menu button.
3. Switch settings menu will appear.
To access menu screens, press scroll button. 100 % 100 %

The switch settings menu displays: Figure 21: Trip Unit Switch Settings
A. Long-time pickup (Ir) setting A–Ir Setting B–tr Setting

06133383
06133382
B. Long-time delay (tr) setting

06134248

06134248
tr=
C. Short-time pickup (Isd) setting Ir=
s
A
D. Short-time delay (tsd) setting
E. Instantaneous pickup (Ii) setting
F. Ground-fault pickup (Ig) setting (6.0A trip C–Isd Setting D–tsd Setting
units only)
06133384

06133385
06134248

06134248
tsd=
G. Ground-fault delay (tg) setting (6.0A trip Isd= s
units only) A

To display next switch setting, press scroll


button.
E–Ii Setting F–Ig Setting
06133387

06133388

06134248
06134248

Ii=
A Ig= A

G–tg Setting A–Ir Setting


06133389

06133382
06134248

s
Ir=
A
tg=

To return to the current menu: Figure 22: Return to Current Menu


1. Switch settings menu is displayed. Switch Settings Menu Current Menu
06133354
06133353

2. Press menu button.


06134247

menu
3. Current menu will appear. Ir=
A A
Or wait several seconds and ammeter will
automatically return to the current (i.e., default)
menu.

100 % 100 %

© 1999–2012 Schneider Electric All Rights Reserved 19-EN


Micrologic™ 2.0A, 3.0A, 5.0A, and 6.0A Electronic Trip Units 48049-136-05
Section 3—Operation Rev. 01, 07/2012

Section 3—Operation
ENGLISH

Switch Setting Adjustment Figure 23: Adjust Switch Settings

1. Open switch cover (A).

06133205

06133207
2. Adjust the appropriate switches (B) to

06133206
desired values.
3. Replace switch cover. Use wire seal
MICROTUSEAL (C, not provided), if
necessary, to provide tamper evidence.

A
C
B

Examples Figure 24: Circuit Breaker Rating

Circuit breaker is rated 2000 A.


06133208

In 2000 A

Micrologic 2.0A Trip Unit Figure 25: Set Pickup Levels


06134251

In = 2000 A
1. Set pickup levels. Ir
long time
.8
alarm
.7 .9 t
06134245

.6 .95
Ir = 0.7 x In = 1400 A
.5 .98
.4
x In
1 Isd = 2 x Ir = 2800 A
instantaneous
Isd
3 4 5
2.5 6
2 8
1.5 10
x Ir
setting

0 Ir Isd

20-EN © 1999–2012 Schneider Electric All Rights Reserved


48049-136-05 Micrologic™ 2.0A, 3.0A, 5.0A, and 6.0A Electronic Trip Units
Rev. 01, 07/2012 Section 3—Operation

2. Set time delay. Figure 26: Set Time Delay

ENGLISH
06133211
long time tr = 1 s (at 6 x Ir)
tr alarm
(s) 4
8
12
2 16
1 20 t

06133212
.5 24
@ 6 Ir

1s tr

0 I

6 x Ir
Micrologic 3.0A Trip Unit Figure 27: Set Pickup Levels
06133209 long time In = 2000 A
1. Set pickup levels. Ir
.7
.8
.9
alarm

Ir = 0.7 x In = 1400 A t

06133210
.6 .95
.5 .98 Ir
.4 1 Ii = 3 x In = 6000 A
x In
instantaneous
Ii
4 5 6
3 8
2 10
1.5 12
x In
setting
Ii

0 I

1400 A

6000 A
2. Set time delay. Figure 28: Set Time Delay
06133211

long time tr = 1 s (at 6 x Ir)


tr alarm
(s) 4
8
12
2 16
1 20 t

06133212
.5 24
@ 6 Ir

1s tr

0 I
6 x Ir

Micrologic 5.0A Trip Unit Figure 29: Set Pickup Levels


06133213

1. Set pickup levels. long time


In = 2000 A
Ir alarm
.8
.7 .9 Ir = 0.7 x In = 1400 A t
.6 .95 Ir
06133214

.5 .98
.4 1 Ii = 6 x In = 12000 A
x In
short time instantaneous Isd = 2 x Ir = 2800 A
Isd Ii 8
4 5 6 10
3
2.5 6 4 12
2 8 3 15
Isd
1.5 10 2 off
x Ir off x In
setting
Ii

0 I
1400 A

12000 A
2800 A

© 1999–2012 Schneider Electric All Rights Reserved 21-EN


Micrologic™ 2.0A, 3.0A, 5.0A, and 6.0A Electronic Trip Units 48049-136-05
Section 3—Operation Rev. 01, 07/2012

2. Set time delay. Figure 30: Set Time Delays


ENGLISH

06133215
long time
alarm
tr = 1 s (at 6 x Ir)
tr 8
(s) 4 12
2 16
1 20
t
tsd = 0.2 s I2t on

06133217
.5 24
@ 6 Ir

short time
tsd 1s tr
.4 .4 .3
.3 .2 I2t on I2t off
.2 .1
.1 2 0
on I t
delay tsd
0.2 s

10 x Ir
6 x Ir
Micrologic 6.0A Trip Unit Figure 31: Set Pickup Levels
t
Ir

06133214
1. Set pickup levels.
06133357

long time
Ir alarm
.8
.7 .9 In = 2000 A
.6 .95
.5 .98
Ir = 0.7 x In = 1400 A
.4
x In
1 Isd
short time instantaneous
Is I
3 4 5 6
8
10 Ii = 6 x In = 12000 A
2.5 6 4 12
Ii
2 8 3 15
1.5 1 2 off Isd = 2 x Ir = 2800 A 0 I

1400 A

12000 A
2800 A
x Ir x In
setting t

06133359
Ig
E
D F BoIg = 640 A
C G
B H
A J

ground fault
Ig

0 I

640 A
2. Set time delays. Figure 32: Set Pickup Levels
t
06133217
06133358

long time
tr alarm 1s tr
8
(s) 4 12 tr = 1 s (at 6 x Ir)
2 16
1 20
.5 24
@ 6 Ir
tsd
short time instantaneous 0.2 s
tsd .4 .4 .3
(s) tsd = 0.2 s I2t on
.3 .2
.2 .1
0 I
10 x Ir
6 x Ir

.1 2 0
on I t off I2t on I2t off
delay
tg
(s) .4 .4 .3 t
06133361

.3 .2
.2 .1
.1 2 0 tg = 0.2 s I2t on
on I t off
ground fault

tg
0.2 s

0 I

22-EN © 1999–2012 Schneider Electric All Rights Reserved


48049-136-05 Micrologic™ 2.0A, 3.0A, 5.0A, and 6.0A Electronic Trip Units
Rev. 01, 07/2012 Section 3—Operation

Zone-Selective Interlocking (ZSI) Table 8: ZSI Combinations

ENGLISH
Federal Pioneer USRC and USRCM Trip Units
The number of devices which can be interlocked

Square D GC-200 Ground-Fault Relay for


Square D Micrologic Series B Trip Units
are shown in Table 8. Upstream Device

Square D GC-100 Ground-Fault Relay


(receives input from RIM)

Merlin Gerin STR58 Trip Units


Micrologic #.0x Trip Units

for Equipment Protection

Equipment Protection
Downstream Device
(sends output to RIM)

Micrologic #.0x Trip Units 15 R R 15 15 R

Square D Micrologic Series B Trip Units R 26 R R R 15

Square D GC-100 Ground-Fault Relay


R R 7 R R R
for Equipment Protection

Square D GC-200 Ground-Fault Relay


15 R R 15 15 R
for Equipment Protection

Merlin Gerin STR58 Trip Units 15 R R 15 15 R

Merlin Gerin STR53 Trip Units 15 R R 15 15 R

Federal Pioneer USRC and USRCM Trip


R 15 R R R 15
Units

Square D Add-On Ground Fault Module


R 5 R R R R
for Equipment Protection

R—RIM module is required to restrain any devices.


Numerical References—Maximum number of upstream circuit breakers which can be restrained
without requiring a RIM Module.

Circuit breaker terminals are shipped with Figure 33: Jumpered Terminals
terminals Z3, Z4 and Z5 jumpered to self-
restrain the short-time and ground-fault
functions. Remove the jumpers when activating UC1
zone-selective interlocking. Z5 M1
Z3 Z4
Z1 Z2
Auxiliary Connections

© 1999–2012 Schneider Electric All Rights Reserved 23-EN


Micrologic™ 2.0A, 3.0A, 5.0A, and 6.0A Electronic Trip Units 48049-136-05
Section 3—Operation Rev. 01, 07/2012

Wire circuit breakers for zone-selective Figure 34: ZSI Wiring Example
interlocking.
ENGLISH

UC1
Z5 M1
Z3 Z4
Z1 Z2 UC1
Auxiliary Z5 M1
Connections 1
Z3 Z4
Z1 Z2 UC1
Secondary Auxiliary Z5 M1
Connector Connections 2
Position Description Z3 Z4
Z1 ZSI out signal Z1 Z2
Z2 ZSI out Auxiliary
Z3 ZSI in signal Connections 3
Z4 ZSI in short time
Z5 ZSI in ground fault

Communication Module values Figure 35: Access Communication Module Menu


Current Menu Communications Address
06133354

06133707
If the optional circuit breaker communication

06133703
menu

module (BCM) is installed, use the ammeter to


set communication module values. A

To access the communication module menu:


1. Current menu is displayed.
2. Simultaneously press both menu button and
scroll button down for three seconds. 100 % 100 %
3. Communication module addressing menu
will appear.

24-EN © 1999–2012 Schneider Electric All Rights Reserved


48049-136-05 Micrologic™ 2.0A, 3.0A, 5.0A, and 6.0A Electronic Trip Units
Rev. 01, 07/2012 Section 3—Operation

Set communication module values: Figure 36: Set Communication Module Values

ENGLISH
1. Press and release scroll button to sequence Communications Address Baud Rate
addresses (1 through 47). When the correct

06134248
06133703

06133704
06134248
address number is reached, enter the value
by pressing and holding scroll button until
the display stops flashing.
Baud rate screen will appear after address
has been entered.
2. Press and release scroll button to sequence Baud Rate Parity
baud rates (4.8k, 9.6k or 19.2k). When the

06133705
06134248
06134248

06133704
desired baud rate appears, enter the value
by pressing and holding scroll button until
the display stops flashing.
Parity screen will appear after baud rate has
been entered.

3. Press and release scroll button to sequence Parity Language

06134888
06134248
06134248

parities (E [even] or n [none]). When the 06133705

desired parity appears, enter the value by


pressing and holding scroll button until the
display stops flashing.
Languages screen will appear after parity
has been entered.
4. Press and release scroll button to scroll Language
through languages (French [Fr], US English
06134248

06134248
06134888

[En US], UK English [En], German [d],


Spanish [SP] or Italian [It]). When the
desired language appears, enter the value
by pressing and holding scroll button until
the display stops flashing.
Ammeter display will return to the default
screen after language is entered.
After the communication module values have
been set, ammeter will automatically return to
the current (i.e., default) menu.
After setting circuit breaker communication
module values, drawout circuit breakers must
have the cradle communication module, if
available, activated. For drawout circuit
breakers, refer to the cradle communication
module instructions to complete setup.

© 1999–2012 Schneider Electric All Rights Reserved 25-EN


Micrologic™ 2.0A, 3.0A, 5.0A, and 6.0A Electronic Trip Units 48049-136-05
Section 3—Operation Rev. 01, 07/2012

Trip Unit Settings Check Table 9: Trip Unit Settings


ENGLISH

Setting Window 2.0A 3.0A 5.0A 6.0A


Use the ammeter switch setting menu to check
the trip unit settings.

06134247
06134247

06133382
menu menu

1. Press menu button twice. Long-Time


Ir Ir= X X X X
Pickup A
2. Switch settings menu will appear.
3. Press scroll button to advance to next
screen.

06134248

06133383
4. After checking trip unit settings, press menu
tr=
button once to return to main menu. Long-Time s
tr X X X X
Delay

06133384
06134248
Short-Time Isd=
Isd X X X
Pickup A

06133385
06134248
tsd=
Short-Time s
tsd X X
Delay
06134248

06133387

Instantaneous
Ii Ii= X X X
Pickup A
06134248

06133388

Ground-Fault
Ig X
Pickup Ig= A
06134248

06133389

Ground-Fault s
tg X
Delay
tg=

Trip Unit Operation Verification Figure 37: Verify Trip Unit Operation
06133218
06133205

Use a test kit connected to the trip unit test plug


receptacle (A) to verify trip unit is functioning as
desired. See instructions shipped with test kit to
perform verification tests.
A

26-EN © 1999–2012 Schneider Electric All Rights Reserved


48049-136-05 Micrologic™ 2.0A, 3.0A, 5.0A, and 6.0A Electronic Trip Units
Rev. 01, 07/2012 Section 3—Operation

Equipment Ground-Fault Trip NOTE: Trip unit must be powered to test ground-fault trip function. The trip
unit is powered if the circuit breaker is carrying more than 0.20 x In of load
Functions Testing

ENGLISH
current, if the 24 Vdc external power supply is connected or if the Full-
Function Test Kit or Hand-Held Test Kit is connected and on.
Paragraph 230-95 (c) of the National Electrical
Code requires that all equipment ground-fault Figure 38: Test Equipment Ground-Fault Trip Function
protection systems be tested when first installed.
With the circuit breaker closed, test the ground-
fault (Micrologic 6.0A trip unit only) trip 6.0 A
logic

06134249
Micro

functions. For instructions on how to close circuit


breaker, refer to the circuit breaker installation
instructions shipped with the circuit breaker. 100 %

40 %

1. Press the ground-fault test button (A). Circuit


breaker should trip. menu

A
2. If circuit breaker does not trip, contact the
local field office.

Trip Unit Resetting Figure 39: Reset Trip Unit


A
06133379

Micrologic 6.0 A
When the circuit breaker trips, the fault indicator
will remain lit until the trip unit is reset.
Press the reset/test button (A) to reset the trip
unit after trip.
Do not return circuit breaker to service until cause
of trip is determined. For more information, refer
to the circuit breaker installation instructions
shipped with the circuit breaker.

Trip Unit Status Check NOTE: Trip unit must be powered to test battery. The trip unit is powered if
the circuit breaker is carrying more than 0.20 x In of load current, if the 24
Vdc external power supply is connected or if the Full-Function Test Kit or
Hand-Held Test Kit is connected and on.
To check trip unit battery and trip indicators, Figure 40: Check Trip Unit Status
press the test/reset button (A). B
A Charged
• All trip indicators (B) will light up
06133379

Micrologic 6.0 A Half-Charged


• Battery status will be displayed Change Battery

• If no battery status is displayed, there is no


battery installed.
• The battery bar graph reading is valid after
the reset button has been released.
• If the battery bar graph shows the battery
needs to be changed, use Square D battery
catalog number S33593:
— lithium battery
— 1.2AA, 3.6 V, 800 ma/h
For instructions on replacing battery, see
Section 6—Battery Replacement.

© 1999–2012 Schneider Electric All Rights Reserved 27-EN


Micrologic™ 2.0A, 3.0A, 5.0A, and 6.0A Electronic Trip Units 48049-136-05
Section 4—Trip Unit Replacement Rev. 01, 07/2012

Section 4—Trip Unit Replacement


ENGLISH

Trip unit replacement must be done by qualified


persons, as defined by the National Electric DANGER
Code, who are familiar with the installation and HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
maintenance of power circuit breakers.
• Failure to follow these instructions for installation, trip test and primary
Before replacing trip unit, confirm that the circuit injection testing may result in the failure of some or all protective function.
breaker is in good working condition. If the • Apply appropriate personal protective equipment (PPE) and follow safe
condition of the circuit breaker is unknown, do electrical work practices. See NFPA 70E or CSA Z462.
not proceed. For assistance in evaluating the
• Replacement/upgrading of a trip unit in the field must be done by
condition of the circuit breaker, call Technical
qualified persons, as defined by the National Electric Code, who are
Support.
familiar with the installation and maintenance of power circuit breakers.
Read this entire section before starting the • Before replacing/upgrading trip unit, confirm that the circuit breaker is in
replacement procedure. good working condition. If the condition of the circuit breaker is unknown,
NOTE: If trip unit being replaced is a Micrologic do not proceed. For assistance in evaluating the condition of the circuit
2.0, 3.0 or 5.0 trip unit, order connector block breaker, call Technical Support.
S33101 and circuit breaker or cradle wiring • If the circuit breaker fails to function properly in any manner upon
harness if necessary. completion of the trip unit installation, immediately remove the circuit
breaker from service and call Field Services.
• Turn off all power supplying this equipment before working on or inside
equipment. Follow instructions shipped with circuit breaker to disconnect
and reconnect circuit breaker.
• Replace all devices, doors and covers before returning equipment to
service.

Failure to follow this instruction will result in death or serious injury.

Required Tools • Torque-controlled screwdriver, set at 7 in-lbs (0.8 N•m) ± 10%


(Lindstrom torque driver MAL500-2 or equivalent)
• Micrologic Full-Function Test Kit (part number S33595)

Preparation

Record Switch Settings Record all trip unit switch settings for later use.

Circuit Breaker Disconnection Disconnect circuit breaker as directed in the circuit breaker instruction
bulletin shipped with the circuit breaker. The circuit breaker must be
completely isolated. (For a drawout circuit breaker, place circuit breaker in
the disconnected position. For a fixed-mounted circuit breaker, all voltage
sources, including auxiliary power, must be disconnected.)

Circuit Breaker Accessory Cover Remove circuit breaker accessory cover as directed in the Install
Removal Accessories section of the circuit breaker instruction bulletin shipped with
the circuit breaker.

28-EN © 1999–2012 Schneider Electric All Rights Reserved


48049-136-05 Micrologic™ 2.0A, 3.0A, 5.0A, and 6.0A Electronic Trip Units
Rev. 01, 07/2012 Section 4—Trip Unit Replacement

Rating Plug Removal Figure 41: Remove Adjustable Rating Plug

ENGLISH
B C
A small Phillips screwdriver is needed to remove
the adjustable rating plug.

06133205

06133221

06133222
1. Open switch cover (A).
2. Unscrew adjustable rating plug mounting Ir
.7
long
.8 .9
time

.95
tr
(s)
2
1
4
8 12
16
20
alarm

.6 .98 24

screw (B).
.5 @ 6 Ir ntaneous
.5 1 insta
.4 x In
Ii 4 5 ntaneous
insta
3 6
shor
t time tsd 4 .4 .3 Ii 4 5
. .2 2.5 8 3 6
Isd 4 5 .3 2 shor
t time tsd 4 .4 .3
3 6 .1 1.5 In
10 . .2 2.5 8
2.5 .2 0 x Isd 4 5 .3 2 alarm
8 .1 2t 3 6 .1 1.5 In
10
2 I .2 time 8 12
10 on delay 2.5 0 x long tr

3. Remove adjustable rating plug (C). Save for


1.5 Ir 8 .1 2 (s) 4 16
x 2 I t Ir .8 .9
settin
g 10 on delay .7 2 20
1.5 Ir .95
x .6 1 24
.98
setting .5
.5 @ 6 Ir
1
.4 x In

installation in replacement trip unit.

Trip Unit Removal Figure 42: Remove Existing Trip Unit

1. Remove connector block (A) from top of trip A

06134854
unit, if present.
06134853

2. Loosen two trip unit screws (B).


3. Slide out trip unit (C).

B
C

Trip Unit Replacement

Battery Installation NOTE: Battery holder with battery is located under the side flap in the
cardboard box the trip unit is shipped in.
If a new trip unit is being installed, install the trip
Figure 43: Install Battery
unit battery.
Install battery holder with battery (A) in trip unit, A
observing the correct polarity as indicated on the
battery compartment.
06133375
LITHIUM BATTERY
3.6V - SL - 550/S
SONNENSCHEIN

Press test/reset button (A). All four indicator Figure 44: Trip Indicator Lights
lights (B) should light. If they do not light, check
polarity of battery and retest. If indicator lights B A
still do not light up when test/reset button is
06133245

Micrologic 6.0 A
pressed, stop installation and contact the local
sales office for factory authorized service

© 1999–2012 Schneider Electric All Rights Reserved 29-EN


Micrologic™ 2.0A, 3.0A, 5.0A, and 6.0A Electronic Trip Units 48049-136-05
Section 4—Trip Unit Replacement Rev. 01, 07/2012

Trip Unit Installation


ENGLISH

1. Inspect trip unit connector pins and surfaces.


If there is any damage, misaligned pins, or
contamination, stop installation and contact
the local sales office for factory authorized
service.
2. Inspect trip unit mounting base on the circuit Figure 45: Install Trip Unit
breaker. Clear any debris from area and
Masterpact NW Circuit Breaker
check that all accessory wiring is properly
routed for the trip unit being installed. If there

06135453
is any damage or contamination, stop
installation and contact the local sales office

06135451
for factory authorized service.
3. For Masterpact NW circuit breaker only:
Manually depress trip unit interlock (A) and
hold it in place during steps 4–6 below.
4. Align guide rail (B) on bottom of trip unit with
guide rail slot (C) on trip unit mounting base
in circuit breaker and gently slide the trip unit
in until it stops.
NOTE: The Masterpact NT and NW trip unit
mounting bases are shock mounted and
therefore can flex slightly.
A C
B

NOTICE
HAZARD OF EQUIPMENT DAMAGE
Check installation of trip unit to assure proper
connections and seating.

Failure to follow this instruction can result


in equipment damage or improper circuit
breaker tripping.

30-EN © 1999–2012 Schneider Electric All Rights Reserved


48049-136-05 Micrologic™ 2.0A, 3.0A, 5.0A, and 6.0A Electronic Trip Units
Rev. 01, 07/2012 Section 4—Trip Unit Replacement

5. Align the trip unit so top mounting screw (A) Figure 46: Install Trip Unit
aligns with the top threaded insert and start

ENGLISH
the screw by turning the screw two full A
rotations.

06134855
6. Use a torque-controlled screwdriver to drive
Must be
the bottom screw (B) to 7 in-lbs (0.8 N•m) ± seated
10%. The back of the trip unit must be flush
with the trip unit mounting base.
7 lb-in
7. Use a torque-controlled screwdriver to drive [0.8 N•m]
the top screw to 7 in-lbs (0.8 N•m) ± 10%.
B
Mounting tab must be flush with the mounting
standoff and sensor plug.
NOTE: The face of the closed switch cover must
be flush with adjoining mounting base surfaces.
If these surfaces are not flush, stop installation
Must be flush
and contact the local sales office for factory C
authorized service.

06134856
NOTE: If you are upgrading from a Micrologic
2.0, 3.0 or 5.0 trip unit, the connector block must
be ordered separately (Part Number S33101).
See instructions shipped with the connector
block for installation into circuit breaker.
8. Install connector block (C) into top of trip
unit.

9. Install adjustable rating plug into the trip unit. Figure 47: Install Adjustable Rating Plug
a. Open switch cover (A) on new trip unit.
C
06134244
06133223

b. Inspect mounting area for debris and B


contamination.
alarm

c. Gently push adjustable rating plug (B) Ir

.6
.5
.7
long
.8 .9

1
time

.95
.98
tr
(s)
2
1
4
8 12
16
20
24
.5 @ 6 Ir
insta
ntaneous
.4 x In

into new trip unit.


Ii 4 5
ntaneous
3 6
t time tsd 4 .4 .3

7 lb-in
insta shor
. .2 2.5 8
Ii 4 5 Isd 4 5 .3 2
3 6 3 6 .1 1.5 In
10
shor
t time tsd 4 .4 .3 .2 0 x
. .2 2.5 8 2.5 8 .1 2t
Isd 4 5 2 alarm 2 I
3
.3 .1 10 1.5 Ir
10 on delay
6 1.5 In

[0.8 N•m]
2.5 8
.2 0 x long
time tr 8 12 x
g
.1 2 (s) 4 16 settin

d. Tighten adjustable rating plug mounting


test .8 .9
2 I t Ir 2
10 on delay .7 .95 20
1.5 Ir 1
x .6 .98 24
setting .5
.5 @ 6 Ir
1
.4 x In

screw (C). The plug will be drawn into


position flush with front face as screw is
tightened.
A A
10. Set trip unit switches to values recorded
above or per coordination study results.
11. Close switch cover (A).

Circuit Breaker Accessory Cover Replace circuit breaker accessory cover as directed in the Install
Replacement Accessories section of the circuit breaker instruction bulletin shipped with
the circuit breaker.

© 1999–2012 Schneider Electric All Rights Reserved 31-EN


Micrologic™ 2.0A, 3.0A, 5.0A, and 6.0A Electronic Trip Units 48049-136-05
Section 4—Trip Unit Replacement Rev. 01, 07/2012

Trip Unit Installation Check


ENGLISH

Secondary Injection Testing Field installation of a trip unit requires secondary injection testing with the
Full-Function Test Kit. to ensure that the newly-installed trip unit is
functioning properly. The test will require opening and closing the circuit
breaker. Follow the procedures outlined in the instruction bulletins shipped
with the circuit breaker and the test kit.
1. Make sure the circuit breaker is isolated from all upstream and
downstream devices.
2. Perform secondary injection testing as outlined in the instruction bulletin
shipped with the test kit. Verify that all applicable trip unit functions are
operating properly.
3. Repeat step 2 with the circuit breaker in the open position.
NOTE: The test kit states that the circuit breaker should be closed when
performing the test. Do not close the circuit breaker for this step.
4. If any test fails, do not put the circuit breaker into service and contact the
local sales office for factory authorization service.
Primary Injection Testing Primary injection testing is recommended to ensure that all trip system
connections have been correctly made. Perform primary injection testing
per the instructions in the Field Testing and Maintenance Guide, bulletin
number 0600IB1201.

Check Accessory Operation 1. Installed accessories – Validate the proper operation of all installed
accessories. See the corresponding accessory instruction bulletins for
operational testing procedures.
2. Zone selective interlocking – If the circuit breaker is part of a ZSI system,
follow the zone selective interlocking test procedures as outlined in the
Full Function Test Kit instruction bulletin.
3. Communications – If communication modules exist, validate circuit
breaker has re-established communications with the supervisor.

Trip Unit Setup 1. If an auxiliary power supply is being used for the Micrologic trip unit,
reconnect the auxiliary power supply.
2. Reset the trip unit switches to original values, as recorded at the
beginning of this section.

Circuit Breaker Reconnection Reconnect circuit breaker as directed in the circuit breaker instruction
bulletin shipped with the circuit breaker.

32-EN © 1999–2012 Schneider Electric All Rights Reserved


48049-136-05 Micrologic™ 2.0A, 3.0A, 5.0A, and 6.0A Electronic Trip Units
Rev. 01, 07/2012 Section 5—Adjustable Rating Plug Replacement

Section 5—Adjustable Rating Plug Replacement

ENGLISH
NOTE: To select correct replacement rating
plug, see the product catalog. DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
NOTE: If adjustable rating plug is removed, the
circuit breaker will default to a long-time pickup • Apply appropriate personal protective equipment (PPE) and follow safe
rating of 0.4 x In and a long-time delay at electrical work practices. See NFPA 70E or CSA Z462.
whatever setting was selected before the rating • This equipment must be installed and serviced only by qualified electrical
plug was removed. personnel.
• Turn off all power supplying this equipment before working on or inside
equipment. Follow instructions shipped with circuit breaker to disconnect
and reconnect circuit breaker.
• Replace all devices, doors and covers before returning equipment to
service.
Failure to follow this instruction will result in death or serious injury.

Rating Plug Removal Figure 48: Remove Adjustable Rating Plug

B C
1. Open circuit breaker contacts:
06133205

06133221

06133222
— For Masterpact NT and NW circuit
breakers, press the “Push to open”
button on the circuit breaker. Ir

.6
.7
long
.8 .9
time

.95
.98
tr
(s)
2
1
4
8 12
16
20
24
alarm

.5 @ 6 Ir ntaneous
.5 1 insta
.4 x In
Ii 4 5 ntaneous
insta

— For other circuit breakers, move handle


3 6
shor
t time tsd 4 .4 .3 Ii 4 5
. .2 2.5 8 3 6
Isd 4 5 .3 2 shor
t time tsd 4 .4 .3
3 6 .1 1.5 In
10 . .2 2.5 8
2.5 .2 0 x Isd 4 5 .3 2 alarm
8 .1 2t 3 6 .1 1.5 In
10
2 I .2 time 8 12
10 on delay 2.5 8 0 x long tr
1.5 Ir
x .1 2 (s) 4 16

to the off (O) position.


2 I t Ir .8 .9
settin
g 10 on delay .7 2 20
1.5 Ir .95
x .6 1 24
.98
setting .5
.5 @ 6 Ir
1
.4 x In

2. Open switch cover (A).


3. Unscrew adjustable rating plug mounting
screw (B).
A
4. Remove adjustable rating plug (C).

New Rating Plug Installation Figure 49: Install New Adjustable Rating Plug

B
06134244

1. Inspect mounting area for debris and


06133223

A
contamination.
2. Gently push in new adjustable rating plug Ir

.6
.7
long
.8 .9
time

.95
.98
tr
(s)
2
1
4
8 12
16
20
24
alarm

.5 @ 6 Ir ntaneous

(A).
.5 1 insta
.4 x In
Ii 4 5
ntaneous
3 6
insta shor
t time tsd 4 .4 .3
. .2 2.5 8
Ii 4 5 Isd 4 5 .3 2
3 6 3 6 .1 1.5 In
10
shor
t time tsd 4 .4 .3 .2 0 x
. .2 2.5 8 2.5 8 .1 2t
Isd 4 5 2 alarm 2 I
3
.3 .1 10 1.5 Ir
10 on delay
6 1.5 In
.2 x

3. Tighten adjustable rating plug mounting


0 x time tr 8 12
2.5 8 long g
.1 2 test .8 .9
(s) 4 16 settin
2 I t Ir 2
10 on delay .7 .95 20
1.5 Ir 1
x .6 .98 24
setting .5
.5 @ 6 Ir
1
.4 x In

screw (B).
4. Set the switches on the trip unit (see Section
3 —Operation).
C
5. Close switch cover (C).

© 1999–2012 Schneider Electric All Rights Reserved 33-EN


Micrologic™ 2.0A, 3.0A, 5.0A, and 6.0A Electronic Trip Units 48049-136-05
Section 6—Battery Replacement Rev. 01, 07/2012

Section 6—Battery Replacement


ENGLISH

Circuit Breaker Disconnection DANGER


HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
Disconnect circuit breaker as directed in the
circuit breaker instruction bulletin shipped with • Apply appropriate personal protective equipment (PPE) and follow safe
the circuit breaker. electrical work practices. See NFPA 70E or CSA Z462.
• This equipment must be installed and serviced only by qualified electrical
Circuit Breaker Accessory Cover personnel.
Removal • Turn off all power supplying this equipment before working on or inside
equipment. Follow instructions shipped with circuit breaker to disconnect
Remove circuit breaker accessory cover as and reconnect circuit breaker.
directed in the Install Accessories section of the • Replace all devices, doors and covers before returning equipment to
circuit breaker instruction bulletin shipped with service.
the circuit breaker.
Failure to follow this instruction will result in death or serious injury.

Withstand Module Shifting Figure 50: Shift Withstand Module

NOTE: R-frame and NS1600b–NS3200 circuit


06123145

breakers only.
Loosen screws (A) securing withstand module
(B). Swing module to side to access trip unit
battery cover. Do not remove withstand module
connector. B

Battery Replacement Figure 51: Remove Battery Cover

1. Insert small screwdriver blade into battery


housing cover notch and rotate to slide
battery housing cover (A) out of trip unit.

2. Remove battery (A). Figure 52: Replace Battery


3. Insert new battery (B). Make sure that the
polarity is correct.
06133374
06133373

LITHIUM BATTERY
LITHIUM BATTERY

4. Replace battery housing cover (C).


3.6V - SL - 550/S
SONNENSCHEIN
3.6V - SL - 550/S
SONNENSCHEIN

06133375
LITHIUM BATTERY
3.6V - SL - 550/S
SONNENSCHEIN

A B
C

34-EN © 1999–2012 Schneider Electric All Rights Reserved


48049-136-05 Micrologic™ 2.0A, 3.0A, 5.0A, and 6.0A Electronic Trip Units
Rev. 01, 07/2012 Section 6—Battery Replacement

Withstand Module Replacement Figure 53: Replace Withstand Module

ENGLISH
NOTE: R-frame and NS1600b–NS3200 circuit

06123146
breakers only.
Replace withstand module (A). Tighten screws
(B) securing withstand module.

B
4.4 lb-in
[0.5 N•m]

Circuit Breaker Accessory Cover Replace circuit breaker accessory cover as directed in the Install
Replacement Accessories section of the circuit breaker instruction bulletin shipped with
the circuit breaker.

Circuit Breaker Reconnection Reconnect circuit breaker as directed in the circuit breaker instruction
bulletin shipped with the circuit breaker.

© 1999–2012 Schneider Electric All Rights Reserved 35-EN


Micrologic™ 2.0A, 3.0A, 5.0A, and 6.0A Electronic Trip Units 48049-136-05
Appendix A—Register List Rev. 01, 07/2012

Appendix A—Register List


ENGLISH

List of Registers To access available registers, the following address scheme applies.

Module Module Name Equation Address Range


The quantities are listed in alphabetical order
according to the SMS topic name. BCM Circuit Breaker Communication Module -- 1–47

CCM Cradle Communication Module BCM + 50 51–97


NOTE: A system scan rate of 500 ms or greater
is recommended to minimize communications PM Protection Module (Internal to trip unit) BCM + 100 101–147
timeout issues. MM Meter Module (Internal to trip unit) BCM + 200 201–247
This is an abbreviated list of registers. For a
complete list of registers, contact your local
sales office.

Table 10: Register List

Number of
SMS Topic Name User Description Register* Module*† Units Scale/Bitmask
Registers*
810DBrkrStatus Circuit Breaker Status 1 661 BCM Bit 0; ON = closed, OFF = open
810DBrkrTripStat Circuit Breaker Trip Unit Status 1 661 BCM Bit 2; ON = tripped, OFF = not tripped
BCM_SN BCM Serial Number 4 516 BCM ASCII text
Bit 8 = disconnected
BkrPos Circuit Breaker Position 1 661 CCM Bit 9 = connected
Bit 10 = test position
DT_3Regs Device Clock Date/Time 3 679 BCM 3-register date/time format‡
EnableCloseBkr Remote Closing Enabled 1 669 BCM Bit 2; ON = enabled, OFF = not enabled
EnableOpenBkr Remote Opening Enabled 1 669 BCM Bit 1; ON = enabled, OFF = not enabled
Bit 3; ON = auto (enabled),
EnableRemCtrl Remote Control Enabled 1 669 BCM
OFF = manual (not enabled)
IA Current A 1 8821 PM A Unity
IA_PCT Current A % Load 1 8837 PM % Unity
IB Current B 1 8822 PM A Unity
IB_PCT Current B % Load 1 8838 PM % Unity
IC Current C 1 8823 PM A Unity
IC_PCT Current C % Load 1 8839 PM % Unity
IG Current G 1 8825 PM A Unity
IG_PCT Current G % Load 1 8841 PM % Unity
IG_PCT_VIGI Current G (VIGI) % Load 1 8842 PM % Hundredths
IG_VIGI Current G (VIGI) 1 8826 PM A Thousandths
IMax Current Max Present 1 8820 PM A Unity
IN Current N 1 8824 PM A Unity
IN_PCT Current N % Load 1 8840 PM % Unity
LDPUValue Long Delay Pickup Value 2 8756 PM A Modulo 10,000 format**
MaxIA Max Current A 1 8827 PM A Unity
MaxIB Max Current B 1 8828 PM A Unity
MaxIC Max Current C 1 8829 PM A Unity
MaxIG Max Current G 1 8831 PM A Unity
MaxIG_VIGI Max Current G (VIGI) 1 8832 PM A Thousandths
MaxIN Max Current N 1 8830 PM A Unity
NominalCurrent Circuit Breaker Nominal Current 1 8750 PM A Unity
ReadyToClose Circuit Breaker Ready to Close 1 661 BCM Bit 5; ON = yes, OFF = no
Continued on next page

36-EN © 1999–2012 Schneider Electric All Rights Reserved


48049-136-05 Micrologic™ 2.0A, 3.0A, 5.0A, and 6.0A Electronic Trip Units
Rev. 01, 07/2012 Appendix A—Register List

Table 10: Register List (continued)

Number of

ENGLISH
SMS Topic Name User Description Register* Module*† Units Scale/Bitmask
Registers*
TU_BATT_PCT Trip Unit % Battery 1 8843 PM % Unity
TU_SN Trip Unit Serial Number 4 8700 PM ASCII text
TUCommStatus Trip Unit Internal Comms Status 1 552 BCM Bit 11; ON = not responding, OFF = OK
* For register entries that are not listed, please refer to the Micrologic device type register list. Contact your local sales office.
† BCM = Circuit breaker communication module. CCM = Cradle communication module. PM = Trip unit protection module.
‡ 3-register date/time format: register 1: month (byte 1) = 1–12, day (byte 2) = 1–31; register 2: year (byte 1) = 0–199 (add to 1900 to determine the actual year), hour
(byte 2) = 0–23; register 3: minutes (byte 1) = 0–59, seconds (byte 2) = 0–59. Note: Bits 14 and 15 of the month/day register must be masked.
** Modulo 10,000 format: 1 to 4 sequential registers. Each register is Modulo 10,000 (range = –9,999 to +9,999). Result is [R4*10,000^3 + R3*10,000^2 + R2*10,000^1]
+ R1. Range is zero to 9,999,999,999,999,999.

© 1999–2012 Schneider Electric All Rights Reserved 37-EN


Micrologic® 2.0A, 3.0A, 5.0A, and 6.0A Electronic Trip Units
Instruction Bulletin
ENGLISH

Electrical equipment should be installed, operated, serviced, and maintained only by qualified
personnel. No responsibility is assumed by Schneider Electric for any consequences arising out of
the use of this material.
Square D™, Schneider Electric™, Micrologic™, Modbus, and Masterpact™ are trademarks or
registered trademarks of Schneider Electric. Other trademarks used herein are the property of
Schneider Electric their respective owners.
3700 Sixth St SW
Cedar Rapids, IA 52404 USA 48049-136-05 Rev. 01, 07/2012
1-888-778-2733 Replaces 48049-136-05 ECN 725D, 07/2008
www.schneider-electric.us © 1999–2012 Schneider Electric All Rights Reserved

S-ar putea să vă placă și