Sunteți pe pagina 1din 40

Overview and Applications

SIPROTEC 5
Transformer differential protection
7UT8x
© Siemens AG 2014 All rights reserved. Answers for infrastructure and cities.
87T Differential protection
Gustav Robert Kirchhoff
* 12.03.1824 in Königsberg (Prussia)
† 17.10.1887 in Berlin
Basic principle: Kirchhoff’s knot rule

Basis for Differential-Protection:

I1

I2
I4

I3

I1 + I2 + I3 + I4 = 0  ∑I=0

Definition:
Currents, which flow into the knot (protected object), are counted positive.
Currents, which flow out of the knot (protected object), are counted negative.

Protection objects:
Line, Transformer, Generator/Motor, Bus bar

Page 4
Basic principles: current comparison

IP1 IP2 IP1 IP2


I1F I2F IF
Protected Protected
object object
I1 I2 I1 I2
I1 I2
∆I IDiff =│I1 + I2│ ∆I IDiff =│I1 + I2│

internal fault external fault or load

Assumption: ideal CT, ratio: 1/1 Assumption: ideal CT, ratio: 1/1
IP1 = I1F IP1 = IF
IP2 = I2F IP2 = -IF
IDiff = │IP1 + IP2 │ = │I1F + I2F │ IDiff = │IP1 + IP2 │ = IF - IF = 0
 Trip  no Trip

Requirements for Differential Protection:


1) Internal faults ( faults between CT-sets )  Trip
2) External faults  no Trip

02/2011 Page 5
Basic principles : restraint current comparison
(1/2)

Example: external fault with linear CT-errors

CT 1: CT 2:
IP1 ε1= - 5% ε2 = +5% IP2 = -IP1
Protected IF
object

I1= I2=
0.95·IP1 IDiff = 0.1·IP1
1.05·IP2
∆I

assumption: CT- ratio: 1/1


IDiff = │I1 + I2 │= │(1+ε1)· IP1 + (1+ε2)·IP2 │=│0.95· IP1 – 1.05· IP1│= 0.1·IP1

-normal operation: IP1 = IN


IDiff = 0.1·IP1 = 0.1·IN

-external fault: assumption: IP1 = 10·IN


IDiff = 0.1·IP1 = 1·IN

As the setting IDiff> for usual applications


lies below nominal current,
it would cause a wrong trip in case of Restraint characteristic necessary!
external faults with big currents!

02/2011 Page 6
Basic principles: restrained current comparison
(2/2)
Example: external fault with linear CT- errors

CT 1: ε1= -5% CT 2: ε2 = + 5%
IP1 IP2 = -IP1
Protected
object
IF
IRest IRest
=│I1│+│I2│
IRest = 2·IP1
I 2=
I1= 1.05·IP2
0.95·IP1 Idiff = │I1+ I2│
IDiff
Idiff = 0.1·IP1

Setting due to magnetising or Linear error due to different


charging currents CT transformation
Idiff =
│I1+I2│ Resulting Under the following assumption
characteristic │ε1 │ = │ε2 │ and I1 = I2
IN the result for a conventional
Trip Differential Prot. characteristic
should be:
IDiff = IDiff> + ε1·I1 + ε2·I2
Block = IDiff> + 2·ε1 ·I1

IDiff> with IDiff> = setting

2 10 IRest =│I1│+│I2│ SIP5: IRest = max (| I1 | , | I2 |)


02/2011 Page 7
Transformer Differential Protection special requirements

Different current values of the CT- sets on the high voltage side (HV) and on the low
voltage side (LV)

Transformer tap changer, magnetizing current

Angle shifting N·30°due to vector group (0 ≤ N ≤ 11) for 3-phase transformers.

Zero sequence current in case of external faults will cause differential current

Inrush currents

CT-saturation

02/2011 Page 8
3-phase Transformer: primary values
Load: 100MVA ,vector group: Yd5
side 2: 20kV, 2887A side 1: 110kV, 525A
3000/1A 750/1A
2L1 1L1
I2L1 I1L1
I2*L1
2L2 1L2
I2L2 I1L2
I2*L2
2L3 1L3
I2L3 I1L3
I2*L3
kU = U1N/U2N = 110kV/20kV = 5.5
kWinding = w1/w2 = kU/√3

I2*L1 = -I1L1·ku /√3 + I1L2·ku /√3

I2*L3
I1L1ku/√3
I1L1

5·30
I2*L2 °

I1L2ku /√3
I1L3 I1L2

-I1L1ku /√3
© Siemens AG 2015. All rights reserved.
I2*L1
Page 9 30.06.2015 Energy Automation Division Energy Management
3-phase Transformer : secondary values

SN I
I L1sec   NCT1sec
3  U N I NCTlprim

100M VA 1A
I1L1sec    0.7A
3 110kV 750A
I1L1sec= 0.7A , 0°

100M VA 1A
I2L1sec    0.96A
3  20kV 3000A

IDiff L1 = │I1L1sec+ I2L1sec│


= 0.5A

I2L1sec = 0.96A , -150°

© Siemens AG 2015. All rights reserved.


Page 10 30.06.2015 Energy Automation Division Energy Management
Vector group and current value adaptation in case of
(1/2) conventional Transformer Differential Protection
Load: 100MVA ,vector group: YNd5
side 2: 20kV side1: 110kV
3000/1A 750/1A ILoad=
525A
L1
2887A
L2

L3

0.96A 0.7A

29 23
Diff.
IR Wdg. Wdg.

Rest. current
Conventional Matching transformer
Differential Prot. -Vector group adaptation
-Current value adaptation
-Zero seq. current handling
nominal Load (no fault): 0.70A ·23Wdg = 0.555A ·29Wdg, IR = 0.555·√3 = 0.96A
© Siemens AG 2015. All rights reserved.
Page 11 30.06.2015 Energy Automation Division Energy Management
Vector group and current value adaptation in case of
(2/2) conventional Transformer Differential Protection
Load: 100MVA ,vector group: YNd5
side 2: 20kV side1: 110kV
3000/1A 750/1A
~ L1
13654A
~ L2

~ L3

3I0
I P=
4.551A 5.73A 4300A

29 23
Diff.
IR Wdg. Wdg.

Rest. current
Conventional Matching transformer
Differential Prot. -Vector group adaptation
-Current value adaptation
-Zero seq. current handling

single pole fault HV -side: 5.73A ·23Wdg = 4.550A ·29Wdg , IR =AG


© Siemens 4.55A
2015. All rights reserved.
Page 12 30.06.2015 Energy Automation Division Energy Management
Vector group and current value adaptation in case of
(1/2) numerical Transformer Differential Protection

Load: 100MVA ,vector group: YNd5


CT 2 side 2: 20kV side 1: 110kV CT 1
3000/1A 750/1A
I2L1P  I1L1P
2L1 1L1
I2L2P  I1L2P
2L2 1L2
I2L3P  I1L3P
2L3 1L3

I2L1S I2A I1A I1L1S


Current Io – Vector Io – Current
I2L2S value handling group comparison handling value
I2B I1B I1L2S
adaptation
CT 2
adaptation
∆I adaptation
CT 1
I2L3S I2C I1C I1L3S

Numerical Transformer Differential Protection

© Siemens AG 2015. All rights reserved.


Page 13 30.06.2015 Energy Automation Division Energy Management
Measuring Pre-processing, Example for CT Matching
(1/2)

SN = 100 MVA
UN2 = 20 kV UN1 = 110 kV
3000/1A 750/1A
IP2 = 2750A IP1 = 500A
(load current) Side 2 Side 1 (load current)
InO2 = 2887A InO1 = 525A

IS2 = -0.916A IS1 = 0.66A measured


7UT8x secondary currents
7UM8x

IDiff = ?
IRest = ?

IP
Ixm   1A
IObj

The matching currrent is the secondary current of a CT with a


primary current equivalent to the object current and a secondary
nominal current of 1A

02/2011 Page 14
Measuring Pre-processing, Example for CT Matching
(2/2)

SN
1. Calculation of the transformer nominal current IObj 
3  UNT
2. Matching factor for each measuring point INCTprim
k xm 
IObj
3. Matching current IS
Ixm  k xm  1A
INCTsec
4. Calculation of the differential and restraint current
(7UT8x: IRest = max(|I1*|;|I2*|)
IDiff = |I1* + I2*| IRest = |I1*| + |I2*|

Calculation example:

SN = 100 MVA UN1 = 110kV UN2 = 20kV


IN1_CT = 750A IN2_CT = 3000A
IDiff = 0A
IN1_Ob = 524.86A IN2_Ob = 2886.75A
IRest = 1.9A
Matching factors: k1m = 1.429 k2m = 1.039
IDiff = 0 I/InO
Load conditions: Ip1 = 500A Ip2 = -2750A
IRest = 1.9 I/InO
Secondary currents: Is1 = 0.666A Is2 = -0.916A
Matched currents: I1m = 0.953A I2m = -0.953A

02/2011 Page 15
Adaptation to tap changer position
Tap changer position connected to the 7UT8x

Differential Protection 87T considers variable transformer ratio (UNTr,prim / UNTr,sec)


High sensitivity for all tap positions

Current value adaptation according to:

 (pos i  posbas ) ΔU 
k i  k bas  1  
 U bas 

kbas : current correction factor in middle (base) position


posi : current tap position
posbas : middle (base) tap position
∆U : voltage difference for 1 tap step
Ubas : voltage at middle (base) tap position

With motor supervision contact the tap position remains until the contact signalized that the new
tap position has been reached.

Page 16
Adaptation to tap changer position
Tap changer position connected to the 7UT8x

In case the tap position acquisition fails, an average adjustment factor is calculated

Current value adaptation according to:

U  2 U min U max
k ref  k bas   ref  U ref 
 U bas  U min  U max

kref : reference current correction factor


kbas : current correction factor in middle (base) position
Ubas : voltage at middle (base) tap position
Uref : reference voltage
Umin : minimum voltage
Umax : maximum voltage

e.g.; Umin = 0.8 Umiddle; Umax = 1.2 Umiddle => Uref = 0.96 Umiddle

Page 17
Transformer Differential Protection 87T
Logic diagram

Page 18 IC SG EA PRO
87T Differential protection
Basic principle for 7UT8x

Idiff = |I1+I2|
Istab = max(|I1| , |I2|)

Internal short circuit, fed from both sides


I2 = -I1
Idiff = |I1 - I2| = |I1 + I1| = 2*I1
Istab = max (|I1| ; |I2|) = |I1| = |I2|
-> Idiff twice as big as Istab
Normal operation
I2 = -I1
Internal short circuit, fed from one side
Idiff = |I1 + I2| = |I1 – I1| = 0
I2=0
Istab = max (|I1| ; |I2|) = |I1| = |I2|
Idiff = |I1 - 0| = |I1|
-> no tripping quantity,
stabilisation = flowing current Istab = max (|I1| ; |I2|) = |I1|
-> Idiff as big as Istab

Page 19 IC SG EA PRO
Transformer Differential Protection 87T
Saturation stabilization for external faults

High current faults

Idiff
Unequal saturation of CTs on the sides of
the transformer
Apparent differential current on secondary
High current fault
side

Tripping
Low current faults
charactectistic
Low current fault Due to the long time constant of the
transient DC component also smaller
currents can lead to unequal CT
saturation on different sides

Istab
-> Trajectory can enter the tripping area

Page 20 IC SG EA PRO
Transformer Differential Protection 87T
Tripping Characteristic Idiff>

Section a: constant fault currents


magnetizing currents

Section b: linear fault currents


CT errors
adaptation errors (tap changer, only if
the tap position is not connected)

Section c: non linear fault currents


transformer saturation

Add on stabilization area:


if the trajectory passes here first and
then enters the tripping area, the
tripping signal will be blocked
(setting: Time of add-on stabiliz.)

Page 21 IC SG EA PRO
87T: Demonstration of add-on stabilisation

Fault
Characteristic

No Trip

Trip

Add-on
Stabilisation

Page 22
Transformer Differential Protection 87
DC Component Recognition

Small external faults can cause CT


saturation due to their DC component

They might not pass through the add on


stabilization area

Remedy:

DC content in the stab current is evaluated

If a DC component is detected the


characteristic is raised (section a and b)

(setting: Factor increasing char. DC)

Small saturated currents do not reach


tripping area

If the DC component falls below a certain


value, the tripping characteristic falls
back

Page 23 IC SG EA PRO
Transformer Differential Protection 87
DC Component Recognition

Criteria to raise the characteristic

Jump in the restraint current


No pick up or external fault detection via
add on stabilization area
I rest DC > 0.6 Irest
Idiff < drop off limit of characteristic

Criteria to lower the characteristic

If the DC component drops below a certain


value, the tripping characteristic returns
after a certain delay time depending on
the up time

Page 24 IC SG EA PRO
Motor differential protection 87M
Start Up Recognition

Differential currents during start up can occur


due to different remanence points after
switching off the motor

Off time of motors are often short and motors


are more often switched than other devices

Criteria to raise characteristic

All 3 phase currents fall under a certain


threshold -> motor is switched off
(setting: Thresh. startup detection)

Criteria to lower characteristic

If at least one phase current exceeds the a.m.


threshold for a settable drop off time, the
original charact. returns, the motor is running
(setting: Max. perm. Start. Time)

Page 25 IC SG EA PRO
87T Inrush blocking: Inrush curves

i1 iDiff = i1
Inrush even
2. Harm.
Y Y

t=0
i1 i2 = 0

Inrush even i1 iDiff = i1


2. Harm.
Y

t=0
i1 I2 = 0

Connecting -T2 in parallel with -T1


(Sympathetic Inrush –T1) i1
-T1 -T1: iDiff = i1

i1 I2 = 0
-T2

t=0
Inrush -T2 t=0 t

Page 26
Inrush blocking: 2nd harmonic detection and cross
block

filter window
1 cycle
Cross-block = No (phase separate blocking)
iRush
= iDiff Inrush current
L1-block IDiff, L1 > trip blocking
in one phase

L2-block IDiff, L2 > trip blocking

L3-block IDiff, L3 > trip blocking

1P 2P 3P t

I2har
Cross-block = Yes (blocking of all phases)
IDiff block

L1-block
Setting
15 %
value L2-block IDiff > trip blocking
OR
for an adjustable time
no block L3-block
0
0 t

 Recognise inrush condition by evaluating the ratio 2nd harmonic I2har to 1st harmonic IDiff.
 Time limit for cross-block. Reliable reaction to the inrush condition with cross-block.
Trip of a short circuit after the set time delay.
 Recognise over excitation [V/Hz] by evaluating the ratio 3rd or 5th harmonic to 1st harmonic

Page 27
Inrush blocking: Current wave form analysis (CWA)

Flat areas in all 3 phases at the same time are typical for transformer inrush currents
Works as a supplement to the second harmonic method
Blocking of all 3 phases automatically
No special settings necessary

Page 28 IC SG EA PRO
Inrush current blocking: logic diagram

Both inrush blocking methods can be independently activated or deactivated.

Page 29
87T: Demonstration of inrush with evolving fault (7UT6x)

Internal
fault

IDiff>>

Inrush

IDiff>
ca 3 cycles
cross blocking

Page 30
87T Overexcitation blocking

Overexcitation of the transformer can lead to primary differential currents which might cause
overfunction of the 87T differential protection.

Odd harmonics like 3rd or 5th harmonic in the differential current

3rd harmonic often eliminated by the transformer itself (e.g. delta winding), therefore 5th
harmonic is mainly used

Blocking of all phases possible via built in cross blocking function

Overexcitation blocking resets if the fundamental component of the differential current


exceeds the threshold _11041:127: Limit Idiff 3., 5. harmonics

Page 31
87T Overexcitation blocking: setting

Above 130% V/Vrated the I50/Irated,Tr exceeds the standard setting for Idiff> of 0.20 => risk of tripping

At 140% V/Vrated the I250/I50 ratio is ca 35%. Therefore a setting (_:11041:125) 5th harmonics
content = 30 % is normally adequate.

The blocking is activated only if the differential current exceeds the tripping characteristic.

Page 32
Overexcitation blocking: logic diagram

Page 33
87T: tripping logic of Idiff> stage

Page 34
87T: Idiff>> stage (fast stage)

Main task: switch off high internal fault currents in a very short time

Additional to Idiff> stage

Stable against CT saturation, also for external transversal faults (1.5 CB topology)

Combination of 2 methods:
Momentary samples
Filter based operation

Page 35
87T: Idiff>> stage (fast stage)

Momentary samples method

Tripping conditions
dIstab(t) / dt > internal threshold
Idiff(t) > 0.8 / Istab(t)
Idiff(t) > _11071:3 : Threshold

All 3 conditions fulfilled => immediate tripping

Only 1st condition fulfilled => blocking of stage for 300ms

Page 36
87T: Idiff>> stage internal fault

dIrest / dt > internal setting


Idiff > k*Irest

=> Immediate tripping

Page 37
87T: Idiff>> stage external fault

dIrest / dt > internal setting


Idiff = 0 at the beginning, some ms later saturation

=> Blocking of the stage for 300ms

Page 38
87T: Idiff>> stage external fault

slope = 0.8

Compared to SIPROTEC 4 the Idiff>> stage also contains a slope for high stabilising currents
Adapted for stabilisation against high bypassing external fault currents in 1.5 CB topology

Page 39
87T: Including a tap changer in the
differential current calculation

Add a tap changer function group


(FG) from the library

Select the tap changer in the


transformer side FG
Set the basis (middle) position and
the voltage difference per step

Set use tap changer position to yes


in the general settings of FG
Transformer Diff

Page 40

S-ar putea să vă placă și