Documente Academic
Documente Profesional
Documente Cultură
SIPROTEC 5
Transformer differential protection
7UT8x
© Siemens AG 2014 All rights reserved. Answers for infrastructure and cities.
87T Differential protection
Gustav Robert Kirchhoff
* 12.03.1824 in Königsberg (Prussia)
† 17.10.1887 in Berlin
Basic principle: Kirchhoff’s knot rule
I1
I2
I4
I3
I1 + I2 + I3 + I4 = 0 ∑I=0
Definition:
Currents, which flow into the knot (protected object), are counted positive.
Currents, which flow out of the knot (protected object), are counted negative.
Protection objects:
Line, Transformer, Generator/Motor, Bus bar
Page 4
Basic principles: current comparison
Assumption: ideal CT, ratio: 1/1 Assumption: ideal CT, ratio: 1/1
IP1 = I1F IP1 = IF
IP2 = I2F IP2 = -IF
IDiff = │IP1 + IP2 │ = │I1F + I2F │ IDiff = │IP1 + IP2 │ = IF - IF = 0
Trip no Trip
02/2011 Page 5
Basic principles : restraint current comparison
(1/2)
CT 1: CT 2:
IP1 ε1= - 5% ε2 = +5% IP2 = -IP1
Protected IF
object
I1= I2=
0.95·IP1 IDiff = 0.1·IP1
1.05·IP2
∆I
02/2011 Page 6
Basic principles: restrained current comparison
(2/2)
Example: external fault with linear CT- errors
CT 1: ε1= -5% CT 2: ε2 = + 5%
IP1 IP2 = -IP1
Protected
object
IF
IRest IRest
=│I1│+│I2│
IRest = 2·IP1
I 2=
I1= 1.05·IP2
0.95·IP1 Idiff = │I1+ I2│
IDiff
Idiff = 0.1·IP1
Different current values of the CT- sets on the high voltage side (HV) and on the low
voltage side (LV)
Zero sequence current in case of external faults will cause differential current
Inrush currents
CT-saturation
02/2011 Page 8
3-phase Transformer: primary values
Load: 100MVA ,vector group: Yd5
side 2: 20kV, 2887A side 1: 110kV, 525A
3000/1A 750/1A
2L1 1L1
I2L1 I1L1
I2*L1
2L2 1L2
I2L2 I1L2
I2*L2
2L3 1L3
I2L3 I1L3
I2*L3
kU = U1N/U2N = 110kV/20kV = 5.5
kWinding = w1/w2 = kU/√3
I2*L3
I1L1ku/√3
I1L1
5·30
I2*L2 °
I1L2ku /√3
I1L3 I1L2
-I1L1ku /√3
© Siemens AG 2015. All rights reserved.
I2*L1
Page 9 30.06.2015 Energy Automation Division Energy Management
3-phase Transformer : secondary values
SN I
I L1sec NCT1sec
3 U N I NCTlprim
100M VA 1A
I1L1sec 0.7A
3 110kV 750A
I1L1sec= 0.7A , 0°
100M VA 1A
I2L1sec 0.96A
3 20kV 3000A
L3
0.96A 0.7A
29 23
Diff.
IR Wdg. Wdg.
Rest. current
Conventional Matching transformer
Differential Prot. -Vector group adaptation
-Current value adaptation
-Zero seq. current handling
nominal Load (no fault): 0.70A ·23Wdg = 0.555A ·29Wdg, IR = 0.555·√3 = 0.96A
© Siemens AG 2015. All rights reserved.
Page 11 30.06.2015 Energy Automation Division Energy Management
Vector group and current value adaptation in case of
(2/2) conventional Transformer Differential Protection
Load: 100MVA ,vector group: YNd5
side 2: 20kV side1: 110kV
3000/1A 750/1A
~ L1
13654A
~ L2
~ L3
3I0
I P=
4.551A 5.73A 4300A
29 23
Diff.
IR Wdg. Wdg.
Rest. current
Conventional Matching transformer
Differential Prot. -Vector group adaptation
-Current value adaptation
-Zero seq. current handling
SN = 100 MVA
UN2 = 20 kV UN1 = 110 kV
3000/1A 750/1A
IP2 = 2750A IP1 = 500A
(load current) Side 2 Side 1 (load current)
InO2 = 2887A InO1 = 525A
IDiff = ?
IRest = ?
IP
Ixm 1A
IObj
02/2011 Page 14
Measuring Pre-processing, Example for CT Matching
(2/2)
SN
1. Calculation of the transformer nominal current IObj
3 UNT
2. Matching factor for each measuring point INCTprim
k xm
IObj
3. Matching current IS
Ixm k xm 1A
INCTsec
4. Calculation of the differential and restraint current
(7UT8x: IRest = max(|I1*|;|I2*|)
IDiff = |I1* + I2*| IRest = |I1*| + |I2*|
Calculation example:
02/2011 Page 15
Adaptation to tap changer position
Tap changer position connected to the 7UT8x
(pos i posbas ) ΔU
k i k bas 1
U bas
With motor supervision contact the tap position remains until the contact signalized that the new
tap position has been reached.
Page 16
Adaptation to tap changer position
Tap changer position connected to the 7UT8x
In case the tap position acquisition fails, an average adjustment factor is calculated
U 2 U min U max
k ref k bas ref U ref
U bas U min U max
e.g.; Umin = 0.8 Umiddle; Umax = 1.2 Umiddle => Uref = 0.96 Umiddle
Page 17
Transformer Differential Protection 87T
Logic diagram
Page 18 IC SG EA PRO
87T Differential protection
Basic principle for 7UT8x
Idiff = |I1+I2|
Istab = max(|I1| , |I2|)
Page 19 IC SG EA PRO
Transformer Differential Protection 87T
Saturation stabilization for external faults
Idiff
Unequal saturation of CTs on the sides of
the transformer
Apparent differential current on secondary
High current fault
side
Tripping
Low current faults
charactectistic
Low current fault Due to the long time constant of the
transient DC component also smaller
currents can lead to unequal CT
saturation on different sides
Istab
-> Trajectory can enter the tripping area
Page 20 IC SG EA PRO
Transformer Differential Protection 87T
Tripping Characteristic Idiff>
Page 21 IC SG EA PRO
87T: Demonstration of add-on stabilisation
Fault
Characteristic
No Trip
Trip
Add-on
Stabilisation
Page 22
Transformer Differential Protection 87
DC Component Recognition
Remedy:
Page 23 IC SG EA PRO
Transformer Differential Protection 87
DC Component Recognition
Page 24 IC SG EA PRO
Motor differential protection 87M
Start Up Recognition
Page 25 IC SG EA PRO
87T Inrush blocking: Inrush curves
i1 iDiff = i1
Inrush even
2. Harm.
Y Y
t=0
i1 i2 = 0
i1 I2 = 0
-T2
t=0
Inrush -T2 t=0 t
Page 26
Inrush blocking: 2nd harmonic detection and cross
block
filter window
1 cycle
Cross-block = No (phase separate blocking)
iRush
= iDiff Inrush current
L1-block IDiff, L1 > trip blocking
in one phase
1P 2P 3P t
I2har
Cross-block = Yes (blocking of all phases)
IDiff block
L1-block
Setting
15 %
value L2-block IDiff > trip blocking
OR
for an adjustable time
no block L3-block
0
0 t
Recognise inrush condition by evaluating the ratio 2nd harmonic I2har to 1st harmonic IDiff.
Time limit for cross-block. Reliable reaction to the inrush condition with cross-block.
Trip of a short circuit after the set time delay.
Recognise over excitation [V/Hz] by evaluating the ratio 3rd or 5th harmonic to 1st harmonic
Page 27
Inrush blocking: Current wave form analysis (CWA)
Flat areas in all 3 phases at the same time are typical for transformer inrush currents
Works as a supplement to the second harmonic method
Blocking of all 3 phases automatically
No special settings necessary
Page 28 IC SG EA PRO
Inrush current blocking: logic diagram
Page 29
87T: Demonstration of inrush with evolving fault (7UT6x)
Internal
fault
IDiff>>
Inrush
IDiff>
ca 3 cycles
cross blocking
Page 30
87T Overexcitation blocking
Overexcitation of the transformer can lead to primary differential currents which might cause
overfunction of the 87T differential protection.
3rd harmonic often eliminated by the transformer itself (e.g. delta winding), therefore 5th
harmonic is mainly used
Page 31
87T Overexcitation blocking: setting
Above 130% V/Vrated the I50/Irated,Tr exceeds the standard setting for Idiff> of 0.20 => risk of tripping
At 140% V/Vrated the I250/I50 ratio is ca 35%. Therefore a setting (_:11041:125) 5th harmonics
content = 30 % is normally adequate.
The blocking is activated only if the differential current exceeds the tripping characteristic.
Page 32
Overexcitation blocking: logic diagram
Page 33
87T: tripping logic of Idiff> stage
Page 34
87T: Idiff>> stage (fast stage)
Main task: switch off high internal fault currents in a very short time
Stable against CT saturation, also for external transversal faults (1.5 CB topology)
Combination of 2 methods:
Momentary samples
Filter based operation
Page 35
87T: Idiff>> stage (fast stage)
Tripping conditions
dIstab(t) / dt > internal threshold
Idiff(t) > 0.8 / Istab(t)
Idiff(t) > _11071:3 : Threshold
Page 36
87T: Idiff>> stage internal fault
Page 37
87T: Idiff>> stage external fault
Page 38
87T: Idiff>> stage external fault
slope = 0.8
Compared to SIPROTEC 4 the Idiff>> stage also contains a slope for high stabilising currents
Adapted for stabilisation against high bypassing external fault currents in 1.5 CB topology
Page 39
87T: Including a tap changer in the
differential current calculation
Page 40