Sunteți pe pagina 1din 6

Design, Procurement and Construction of 84 MW

Gorkin-Matiltan Hydropower Project


Component Hospital
Description Design of Slab Doc. No. GMHP-BK-C-HP-CA-003

�=(𝐴𝑠∗𝑓𝑦)/(0.85∗𝑓𝑐^′∗𝑏)
Thickness of the Slab 6 in. Depth of compression block

Crushing Strength of the Concrete 3 Ksi.


�=𝝓∗𝐴𝑠∗𝑓𝑦∗(𝑑−�/2)
Yield Strength of the Steel 40 Ksi. Moment Capacity

Minimum Reinforcement Ratio 0.002 in2/in2

Maximum Reinforcement Ratio 0.0203 in2/in2

Minimum Reinforcement area 0.144 in2/ft

Capacity/Deman
Applied Positive

Capacity of Slab
Efective Depth

Reinforcement
Moment (k-f)

Moment (k-f)
area Provided

Compression
Spacing (in)

Spacing (in)
Spacing (in)

Spacing (in)
Maximum

Maximum
Allowable

Allowable
Block (in)

Negative
Depth of

Moment

Applied
d Ratio

Check
Bar #

Bar #
(k-f)
(in2)
Description

(in)
1 2 3 4 5 6 7 8 9 10 11 12 13 14

Ground Floor

Male Ward 2.2 4 8.0 12.00 4.75 0.30 0.39 4.10 1.83 OK 2.9 4 8.0 12.00

Prayer Room 1.7 4 8.0 12.00 4.75 0.30 0.39 4.10 2.36 OK 1.4 4 8.0 12.00

Male Doctor 1.6 4 8.0 12.00 4.75 0.30 0.39 4.10 2.55 OK 1.8 4 8.0 12.00

Bathrooms 1.7 4 8.0 12.00 4.75 0.30 0.39 4.10 2.40 OK 1.8 4 8.0 12.00

Male Waiting Area 1.7 4 8.0 12.00 4.75 0.30 0.39 4.10 2.45 OK 1.6 4 8.0 12.00

Dressing Room 1.7 4 8.0 12.00 4.75 0.30 0.39 4.10 2.48 OK 1.8 4 8.0 12.00

Emergencey Room 1.8 4 8.0 12.00 4.75 0.30 0.39 4.10 2.29 OK 1.7 4 8.0 12.00

Sheet No: 003-1


Capacity/Deman
Applied Positive

Capacity of Slab
Efective Depth

Reinforcement
Moment (k-f)

Moment (k-f)
area Provided

Compression
Spacing (in)

Spacing (in)

Spacing (in)

Spacing (in)
Maximum

Maximum
Allowable

Allowable
Block (in)

Negative
Depth of

Moment

Applied
d Ratio

Check
Bar #

Bar #
(k-f)
(in2)
(in)
Description

Reception 1.6 4 8.0 12.00 4.75 0.30 0.39 4.10 2.56 OK 1.9 4 8.0 12.00

Corridor 1.0 4 8.0 12.00 4.75 0.30 0.39 4.10 4.10 OK 2.3 4 8.0 12.00

First Floor

Female Ward 1.8 4 8.0 12.00 4.75 0.30 0.39 4.10 2.26 OK 3.6 4 8.0 12.00

Nurse Station 1.6 4 8.0 12.00 4.75 0.30 0.39 4.10 2.61 OK 1.7 4 8.0 12.00

Female Doctor 1.6 4 8.0 12.00 4.75 0.30 0.39 4.10 2.61 OK 1.2 4 8.0 12.00

Bathrooms 1.8 4 8.0 12.00 4.75 0.30 0.39 4.10 2.33 OK 1.4 4 8.0 12.00

Female Waiting Area 1.7 4 8.0 12.00 4.75 0.30 0.39 4.10 2.47 OK 1.2 4 8.0 12.00

Laboratory 1.6 4 8.0 12.00 4.75 0.30 0.39 4.10 2.53 OK 1.1 4 8.0 12.00

Dispensary Room 1.8 4 8.0 12.00 4.75 0.30 0.39 4.10 2.30 OK 1.0 4 8.0 12.00

Medical Store 1.5 4 8.0 12.00 4.75 0.30 0.39 4.10 2.71 OK 1.2 4 8.0 12.00

Corridor 1.2 4 8.0 12.00 4.75 0.30 0.39 4.10 3.42 OK 1.6 4 8.0 12.00

Moments in Ramp 2.0 4 6.0 12.00 4.75 0.40 0.52 5.39 2.69 OK 4.5 4 6.0 12.00

Notes:

1 The values of Column-1 and 11 have been taken from ETABS Analysis Model which is submitted with these calculations.

Sheet No: 003-2


Description

Applied Positive
Moment (k-f)

Bar #

Spacing (in)

Maximum
Allowable
Spacing (in)

Efective Depth
(in)

Reinforcement
area Provided
(in2)

Depth of
Compression
Block (in)

Moment
Capacity of Slab
(k-f)

Capacity/Deman
d Ratio

Check

Applied
Negative
Moment (k-f)

Bar #

Spacing (in)

Maximum
Allowable
Spacing (in)
Sheet No: 003-3
Sheet No.

Designed TA
Checked AuH
R 01 Date 13-Jan-20

Spacing Provided Reinf. Provided Reinf.


bar # (in) Area (in2./ft) Ratio

4 9.0 0.27 0.004


4 8.0 0.30 0.004
4 7.0 0.34 0.005
4 6.0 0.40 0.006
Capacity/Deman
Capacity of Slab
Efective Depth

Reinforcement
area Provided

Compression
Block (in)
Depth of

Moment

d Ratio

Check
(k-f)
(in2)
(in)

15 16 17 18 19 20

4.75 0.30 0.39 4.10 1.42 OK

4.75 0.30 0.39 4.10 2.93 OK

4.75 0.30 0.39 4.10 2.30 OK

4.75 0.30 0.39 4.10 2.30 OK

4.75 0.30 0.39 4.10 2.50 OK

4.75 0.30 0.39 4.10 2.28 OK

4.75 0.30 0.39 4.10 2.40 OK

Sheet No: 003-4


Capacity/Deman
Capacity of Slab
Efective Depth

Reinforcement
area Provided

Compression
Block (in)
Depth of

Moment

d Ratio

Check
(k-f)
(in2)
(in)

4.75 0.30 0.39 4.10 2.11 OK

4.75 0.30 0.39 4.10 1.82 OK

4.75 0.30 0.39 4.10 1.15 OK

4.75 0.30 0.39 4.10 2.41 OK

4.75 0.30 0.39 4.10 3.36 OK

4.75 0.30 0.39 4.10 2.85 OK

4.75 0.30 0.39 4.10 3.36 OK

4.75 0.30 0.39 4.10 3.58 OK

4.75 0.30 0.39 4.10 4.10 OK

4.75 0.30 0.39 4.10 3.36 OK

4.75 0.30 0.39 4.10 2.56 OK

4.75 0.40 0.52 5.39 1.20 OK

Sheet No: 003-5


Efective Depth
(in)

Reinforcement
area Provided
(in2)

Depth of
Compression
Block (in)

Moment
Capacity of Slab
(k-f)

Capacity/Deman
d Ratio

Check

Sheet No: 003-6