DATE: 22/11/12 PACKAGE: WATER SYSTEM FOR MILLS AND
FIRE FIGHTING PUMP HOUSES
THIS DRAWING IS PROPERTY OF MBE
(PACKAGE NO. 077-22)
AND MUST NOT BE USED EXCEPT IN DOC. TITLE:
CONNECTION WITH WORK OF MBE,
REPRODUCTION, USE OR
DESIGN CALCULATION OF VENTILATION SYSTEM
DISCLOSURE OF THE CONTENTS OF
THIS DRAWING TO THIRD PARTY/IES
FOR BRM
WITHOUT EXPRESS / WRITTEN
PERMISSION OF MBE IS STRICTLY NO. OF
PROHIBITTED. MBE PROJECT NO. W021 13
SHTS.
MBE DOC. NO. 2-W021-TD00-0112 REV. NO. 1
PROJECT DOC. NO. BSP-MBE-10-077-20-000-15-BD-00012 REV. NO. 1

AE-M007C16-M-DCA-011-R-1C.xls
Bhilai Steel Plant Design Calculation of Ventilation
Water System: Package No. 077-02 System for BRM

COOLING LOAD TEMPERATURE DIFFERENCE (CLTD) CORRECTION CALCULATION


Input Design Data
Latitude = 21.15 º N
Solar Time considered = 12.00 p.m
CLTD = Cooling Load Temp. Diff. for :
Roof = 4.00 °C [ From ASHRAE handbook, chapter-26, Table-29]
NE Wall = 8.00 °C
NW Wall = 7.00 °C
SE Wall = 9.00 °C [ From ASHRAE handbook, chapter-26, Table-31]
SW Wall = 8.00 °C
LM = latitude-Month Correction for :
Roof = 0.50
NE Wall = 1.60
NW Wall = 1.60 [ From ASHRAE handbook, chapter-26, Table-32]
SE Wall = -2.20
SW Wall = -2.20
K = Color adjustment
For dark or light colored in an industrial area, K = 1.00
Permanently Medium Colored (rural area), K = 0.83 [ From ASHRAE handbook(Page-26.37)]
Permanently Light Colored (rural area), K = 0.65
CLTDg = Cooling Load Temp. Diff. for Glass = 5.00 °C [ From ASHRAE handbook, chapter-26, Table-33]

►CLTD CORRECTION FOR DRY VENTILATION SYSTEM


Outdoor Temperature, tO = 45.00 °C
Room Temperature, tR = 48.00 °C [Allowable temp. rise = 3 °C]

Calculation
1) CLTD CORRECTION FOR ROOF & WALL (CLTDcorr)
= (CLTD+LM)K+(25.5-tR)+(tO-29.4) :
Roof = -2.40 °C
NE Wall = 2.70 °C
NW Wall = 1.70 °C [The cooling load temp. difference is negative,
SE Wall = -0.10 °C due to higher indoor temp. than outdoor temp.]
SW Wall = -1.10 °C
2) CLTD CORRECTION FOR GLASS (CLTDcorr)
= CLTDg+(25.5-tR)+(tO-29.4) : = -1.90 °C

►CLTD CORRECTION FOR WET VENTILATION SYSTEM


Outdoor Temperature, tO = 28.00 °C (assumed)
Room Temperature, tR = 38.00

Calculation
1) CLTD CORRECTION FOR ROOF & WALL (CLTDcorr)
= (CLTD+LM)K+(25.5-tR)+(tO-29.4) :
Roof = -9.40
NE Wall = -4.30
NW Wall = -5.30
SE Wall = -7.10
SW Wall = -8.10
2) CLTD CORRECTION FOR GLASS (CLTDcorr)
= CLTDg+(25.5-tR)+(tO-29.4) : = -8.90 °C

McNally Bharat Engineering Company Ltd, Kolkata


(2-W021-TD00-2-0112)
Page 1 of 1
Bhilai Steel Plant Design Calculation of Ventilation
Water System: Package No. 077-02 System for BRM

Design Heat Transfer Co-efficient (U) Calculation

1) U-value calculation for 200 mm common brick wall & partition wall
2
a. Outside surface resistance (R1) = 0.059 m °C/w
2
b. 20 mm plaster (R4) = 0.026 m °C/w
2
c. 200 mm common brick (R3) = 0.279 m °C/w [ From ASHRAE handbook, chapter-26, Table-11]
2
d. 20 mm plaster (R4) = 0.026 m °C/w
2
e. Inside surface resistance (R5) = 0.121 m °C/w

"U" value for 200 mm common brick wall & 1


=
partition wall [R1+R2+R3+R4+R5]
= 1.957 w/m2°C

2) U-value calculation for 200 mm light-weight conc. Blk. (filled) roof & floor
2
a. Outside surface resistance (R1) = 0.059 m °C/w
2
b. 20 mm plaster (R4) = 0.026 m °C/w
2
c. 200 mm conc. Blk. (R3) = 1.467 m °C/w [ From ASHRAE handbook, chapter-26, Table-11]
2
d. 20 mm plaster (R4) = 0.026 m °C/w
2
e. Inside surface resistance (R5) = 0.121 m °C/w

1
"U" value for 200 mm conc. Blk. Roof & floor =
[R1+R2+R3+R4+R5]
= 0.589 w/m2°C

McNally Bharat Engineering Company Ltd, Kolkata


(2-W021-TD00-2-0112)
Page 1 of 1
Bhilai Steel Plant Design Calculation of Ventilation
Water System: Package No. 077-02 System for BRM

CALCULATION FOR WET VENTILATION IN SCALE PIT PUMP HOUSE(WTP-5)

Maximum warm condition considered on month of June Solar Time considered 12.p.m
Space SWPH Latitude 21.15º N Total Volume
a. Scale Water Pump House Area For Scale Pit (M3)
Under Ground
Length (M) Width (M) Area (M2) Height (M)
Height (M)
29.000 7.500 217.50 0.000 9.000
b. Cable Sreader Room area
Under Ground
Length (M) Width (M) Area (M2) Height (M)
Height (M)
29.00 7.50 217.50 1.350 3.000
c. Scale Water Pump House Elec. Switchgear Room Area
Length (M) Width (M) Area (M2) Height (M) 3989.36
22.00 7.50 165.00 5.200
d. Scale Water Pump House Control Room
3.70 2.80 10.36 5.200
e. Scale Water Pump House Battery Room
3.70 2.80 10.36 5.200
f. Scale Water Pump House Air Washer Room
7.50 7.10 53.25 6.300

Heat Gain by Roof & Overground Wall


TOTAL
Item Area U factor CLTDCorrected
Roof 197.53 0.589 -9.40 1,093
NE Wall 16.54 1.96 -4.30 139
NW Wall 178.45 1.96 -5.30 1,851
SE Wall 143.82 1.96 -7.10 1,998
SW Wall 34.6275 1.96 -8.10 549
1. Total Transmission & Solar Heat Gain, Roof & Overground Wall (Watt) 5,630
Heat Gain by Conduction, Glass
ITEM Area U factor CLTDCorrected
NE Wall 1.84 6.300 -8.9 103
NW Wall 19.83 6.300 -8.9 1,112
SE Wall 15.98 6.300 -8.9 896
SW Wall 3.85 6.300 -8.9 216
Solar Heat Gain, Glass
ITEM Area SC SHGF CLF
NE Wall 1.84 0.94 596.0 0.31 319
NW Wall 19.83 0.94 596.0 0.18 2,000
SE Wall 15.98 0.94 341.0 0.48 2,459
SW Wall 3.85 0.94 341.0 0.25 308
2. Total Transmission & Solar Heat Gain by Glass (watt) 7,412

McNally Bharat Engineering Company Ltd, Kolkata


(1-W021-TD00-0112)
Page 1 of 2
Bhilai Steel Plant Design Calculation of Ventilation
Water System: Package No. 077-02 System for BRM

Heat Gain by Partitions, Ceilings, Floors


ITEM Area U factor ∆t
NE Wall 104.56 1.96 7.0 1,432
NW Wall 348.00 1.96 7.0 4,767
SE Wall 386.48 1.96 7.0 5,294
SW Wall 108.90 1.96 7.0 1,492
Ceilings 0.00 0
Floors 0.00 0
3. Total Heat Gain By Partitions, Ceilings, Floors (Watt) 12,985
Internal Load
Sensible heat 300
Latent heat 220
Item Area (m2) F (W/m2) CLF
Lights 642.9 21.50 1.00 13,822
Item Heat Gain (W)
Eqp.Heat(SWPH) 9900 9,900
Eqp.Heat(MCC) 5000 5,000
4. Total Internal Heat Gain By People, Lights & Eqpt. (Watt) 29,242
Ventilation & Infiltration
Supply Fan Heat Gain 1,651
Supply Duct Leakage Loss/Heat Gain 0
5. Total Heat Gain By Ventilation & Infiltration (watt) 1,651

Grand Total Heat (Watt) 56921

Outside Air condition (summer) Inside Air condition (summer)


DBT ( ºC ) % RH WBT ( ºC ) Room temp. (°C)
45 26% 28.0 38
DB Depression temp. (°C) 17.0
Saturation efficiency 90%
Air Washer Outlet Air Temp. ( ºC ) 29.7

Air flow based on cooling load (m3/hr) 20072


60000
Air flow based on air changes (m3/hr) 59840

Capacity of wet ventilation system to suit air requirement of 60000 m3/hr for SWPH.

Notes
1. Shading coefficient (SC), Solar heat gain factor (SHGF) and Cooling load factor (CLF) data
as per ASHRAE handbook, chapter 27, table-20 and chapter 26, table-34, 36.
2. Considering 10% glass area.
3. No. of air changes considered/hr = 15
4. Ref. drg. No:BSP-MBE-10-077-20-005-15-DE-00101 (1-W021-DS00-3-0203-R-3)

McNally Bharat Engineering Company Ltd, Kolkata


(1-W021-TD00-0112)
Page 2 of 2
Bhilai Steel Plant Design Calculation of Ventilation
Water System: Package No. 077-02 System for BRM

CALCULATION FOR WET VENTILATION IN HOT & COLD WATER PUMP HOUSE(WTP-6)

Maximum warm condition considered on month of June Solar Time considered 12.p.m
Space H&CWPH Latitude 21.15º N Total Volume
a. Hot & Cold Water Pump House (WTP-6) (M3)
Length (M) Width (M) Area (M2) Height (M)
47.80 13.80 659.64 8.200 5839.02
b. Air Washer Room
10.50 7.00 73.50 5.850

Heat Gain by Roof & Overground Wall


TOTAL
Item Area U factor CLTDCorrected
Roof 659.64 0.589 -9.40 3,650
NE Wall 138.70 1.96 -4.30 1,167
NW Wall 408.05 1.96 -5.30 4,232
SE Wall 408.05 1.96 -7.10 5,670
SW Wall 138.70 1.96 -8.10 2,199
1. Total Transmission & Solar Heat Gain, Roof & Overground Wall (Watt) 16,917
Heat Gain by Conduction, Glass
ITEM Area U factor CLTDCorrected
NE Wall 15.41 6.300 -8.9 864
NW Wall 45.34 6.300 -8.9 2,542
SE Wall 45.34 6.300 -8.9 2,542
SW Wall 15.41 6.300 -8.9 864
Solar Heat Gain, Glass
ITEM Area SC SHGF CLF
NE Wall 15.41 0.94 596.0 0.31 2,676
NW Wall 45.34 0.94 596.0 0.18 4,572
SE Wall 45.34 0.94 341.0 0.48 6,976
SW Wall 15.41 0.94 341.0 0.25 1,235
2. Total Transmission & Solar Heat Gain by Glass (watt) 22,272
Heat Gain by Partitions, Ceilings, Floors
ITEM Area U factor ∆t
NE Wall 0.00 1.96 7.0 0
NW Wall 0.00 1.96 7.0 0
SE Wall 0.00 1.96 7.0 0
SW Wall 0.00 1.96 7.0 0
Ceilings 0.00 0
Floors 0.00 0
3. Total Heat Gain By Partitions, Ceilings, Floors (Watt) 0
Internal Load
Sensible heat 300
Latent heat 220
Item Area (m2) F (W/m2) CLF
Lights 733.1 21.50 1.00 15,763
McNally Bharat Engineering Company Ltd, Kolkata
(2-W021-TD00-2-0112)
Page 1 of 2
Bhilai Steel Plant Design Calculation of Ventilation
Water System: Package No. 077-02 System for BRM

Item Heat Gain (W)


Eqp.Heat(H&CWPH) 9900 9,900
Eqp.Heat(MCC) 5000 5,000
4. Total Internal Heat Gain By People, Lights & Eqpt. (Watt) 31,183
Ventilation & Infiltration
Supply Fan Heat Gain 2,105
Supply Duct Leakage Loss/Heat Gain 0
5. Total Heat Gain By Ventilation & Infiltration (watt) 2,105

Grand Total Heat (Watt) 72476

Outside Air condition (summer) Inside Air condition (summer)


DBT ( ºC ) % RH WBT ( ºC ) Room temp. (°C)
45 26% 28.0 38
DB Depression temp. (°C) 17.0
Saturation efficiency 90%
Air Washer Outlet Air Temp. ( ºC ) 29.7

Air flow based on cooling load (m3/hr) 25557


88000
Air flow based on air changes (m3/hr) 87585

Capacity of wet ventilation system to suit air requirement of 88000 m3/hr

Notes
1. Shading coefficient (SC), Solar heat gain factor (SHGF) and Cooling load factor (CLF) data
as per ASHRAE handbook, chapter 27, table-20 and chapter 26, table-34, 36.
2. Considering 10% glass area.
3. No. of air changes considered/hr = 15
4. Ref. drg. No:BSP-MBE-10-077-20-006-15-DE-00103 (1-W021-DS00-2-0110 -(1 OF 4)-R-3)

McNally Bharat Engineering Company Ltd, Kolkata


(2-W021-TD00-2-0112)
Page 2 of 2
Bhilai Steel Plant Design Calculation of Ventilation
Water System: Package No. 077-02 System for BRM

CALCULATION FOR WET VENTILATION IN ELECTRICAL SWITCHGEAR ROOM(WTP-6)

Maximum warm condition considered on month of June Solar Time considered 12.p.m
Space Switchgear Room(WTP-6) Latitude 21.15º N Total Volume
a. Electrical Switchgear room(WTP-6) (M3)
Length (M) Width (M) Area (M2) Height (M)
31.50 8.50 267.75 5.850 1935.06
b. Air Washer Room
9.55 6.60 63.03 5.850

Heat Gain by Roof & Overground Wall


TOTAL
Item Area U factor CLTDCorrected
Roof 330.78 0.589 -9.40 1,830
NE Wall 165.85 1.96 -4.30 1,396
NW Wall 44.75 1.96 -5.30 464
SE Wall 50.28 1.96 -7.10 699
SW Wall 80.03 1.96 -8.10 1,269
1. Total Transmission & Solar Heat Gain, Roof & Overground Wall (Watt) 5,657
Heat Gain by Conduction, Glass
ITEM Area U factor CLTDCorrected
NE Wall 18.43 6.300 -8.9 1,033
NW Wall 4.97 6.300 -8.9 279
SE Wall 5.59 6.300 -8.9 313
SW Wall 22.35 6.300 -8.9 1,253
Solar Heat Gain, Glass
ITEM Area SC SHGF CLF
NE Wall 18.43 0.94 596.0 0.31 3,200
NW Wall 4.97 0.94 596.0 0.18 501
SE Wall 5.59 0.94 341.0 0.48 860
SW Wall 8.89 0.94 341.0 0.25 713
2. Total Transmission & Solar Heat Gain by Glass (watt) 8,152
Heat Gain by Partitions, Ceilings, Floors
ITEM Area U factor ∆t
NE Wall 0.00 1.96 7.0 0
NW Wall 0.00 1.96 7.0 0
SE Wall 0.00 1.96 7.0 0
SW Wall 121.10 1.96 7.0 1,659
Ceilings 0.00 0
Floors 0.00 0
3. Total Heat Gain By Partitions, Ceilings, Floors (Watt) 1,659
Internal Load
Sensible heat 300
Latent heat 220
Item Area (m2) F (W/m2) CLF
Lights 330.8 21.50 1.00 7,112
McNally Bharat Engineering Company Ltd, Kolkata
(2-W021-TD00-2-0112)
Page 1 of 2
Bhilai Steel Plant Design Calculation of Ventilation
Water System: Package No. 077-02 System for BRM

Item Heat Gain (W)


Eqp.Heat(SWGR) 9900 9,900
Eqp.Heat(MCC) 5000 5,000
4. Total Internal Heat Gain By People, Lights & Eqpt. (Watt) 22,532
Ventilation & Infiltration
Supply Fan Heat Gain 1,133
Supply Duct Leakage Loss/Heat Gain 0
5. Total Heat Gain By Ventilation & Infiltration (watt) 1,133

Grand Total Heat (Watt) 39133

Outside Air condition (summer) Inside Air condition (summer)


DBT ( ºC ) % RH WBT ( ºC ) Room temp. (°C)
45 26% 28.0 38
DB Depression temp. (°C) 17.0
Saturation efficiency 90%
Air Washer Outlet Air Temp. ( ºC ) 29.7

Air flow based on cooling load (m3/hr) 13800


29500
Air flow based on air changes (m3/hr) 29026

Capacity of wet ventilation system to suit air requirement of 29500 m3/hr

Notes
1. Shading coefficient (SC), Solar heat gain factor (SHGF) and Cooling load factor (CLF) data
as per ASHRAE handbook, chapter 27, table-20 and chapter 26, table-34, 36.
2. Considering 10% glass area.
3. No. of air changes considered/hr = 15
4. Ref. drg. No:BSP-MBE-10-077-20-600-15-DE-03002 (1-W021-DS00-3-0204-R-3)

McNally Bharat Engineering Company Ltd, Kolkata


(2-W021-TD00-2-0112)
Page 2 of 2
Bhilai Steel Plant Design Calculation of Ventilation
Water System: Package No. 077-02 System for BRM

CALCULATION FOR WET VENTILATION IN ELECTRICAL SWITCHGEAR ROOM & PUMP HOUSE(WTP-7)

Maximum warm condition considered on month of June Solar Time considered 12.p.m
Space Switchgear Room & PH(WTP-7) Latitude 21.15º N Total Volume (M3)
a. Electrical Switchgear room(WTP-7)
Length (M) Width (M) Area (M2) Height (M)
29.30 8.50 249.05 5.500
b. Pump House 3031.52
23.70 8.00 189.60 7.150
c. Air Washer Room
6.85 6.25 42.81 7.150
Heat Gain by Roof & Overground Wall
TOTAL
Item Area U factor CLTDCorrected
Roof 481.46 0.589 -9.40 2,664
NE Wall 93.56 1.96 -4.30 787
NW Wall 40.22 1.96 -5.30 417
SE Wall 152.51 1.96 -7.10 2,119
SW Wall 86.15 1.96 -8.10 1,366
1. Total Transmission & Solar Heat Gain, Roof & Overground Wall (Watt) 7,353
Heat Gain by Conduction, Glass
ITEM Area U factor CLTDCorrected
NE Wall 15.84 6.300 -8.9 888
NW Wall 18.33 6.300 -8.9 1,028
SE Wall 20.61 6.300 -8.9 1,156
SW Wall 13.39 6.300 -8.9 751
Solar Heat Gain, Glass
ITEM Area SC SHGF CLF
NE Wall 10.40 0.94 596.0 0.31 1,805
NW Wall 4.47 0.94 596.0 0.18 451
SE Wall 16.95 0.94 341.0 0.48 2,607
SW Wall 9.57 0.94 341.0 0.25 767
2. Total Transmission & Solar Heat Gain by Glass (watt) 9,453
Heat Gain by Partitions, Ceilings, Floors
ITEM Area U factor ∆t
NE Wall 48.98 1.96 7.0 671
NW Wall 124.77 1.96 7.0 1,709
SE Wall 33.00 1.96 7.0 452
SW Wall 34.38 1.96 7.0 471
Ceilings 0.00 0
Floors 0.00 0
3. Total Heat Gain By Partitions, Ceilings, Floors (Watt) 3,303
Internal Load
Sensible heat 300
Latent heat 220
Item Area (m2) F (W/m2) CLF
Lights 291.9 21.50 1.00 6,275

McNally Bharat Engineering Company Ltd, Kolkata


(2-W021-TD00-2-0112)
Page 1 of 2
Bhilai Steel Plant Design Calculation of Ventilation
Water System: Package No. 077-02 System for BRM

Item Heat Gain (W)


Eqp.Heat(SWPH) 9900 9,900
Eqp.Heat(MCC) 5000 5,000
4. Total Internal Heat Gain By People, Lights & Eqpt. (Watt) 21,695
Ventilation & Infiltration
Supply Fan Heat Gain 1,248
Supply Duct Leakage Loss/Heat Gain 0
5. Total Heat Gain By Ventilation & Infiltration (watt) 1,248

Grand Total Heat (Watt) 43051

Outside Air condition (summer) Inside Air condition (summer)


DBT ( ºC ) % RH WBT ( ºC ) Room temp. (°C)
45 26% 28.0 38
DB Depression temp. (°C) 17.0
Saturation efficiency 90%
Air Washer Outlet Air Temp. ( ºC ) 29.7

Air flow based on cooling load (m3/hr) 15181


45500
Air flow based on air changes (m3/hr) 45473

Capacity of wet ventilation system to suit air requirement of 45500 m3/hr

Notes
1. Shading coefficient (SC), Solar heat gain factor (SHGF) and Cooling load factor (CLF) data
as per ASHRAE handbook, chapter 27, table-20 and chapter 26, table-34, 36.
2. Considering 10% glass area.
3. No. of air changes considered/hr = 15
4. Ref. Area Layout drg. No:BSP-MBE-10-077-20-000-15-BD-00012 (1-W021-DS00-3-0205-R-3)

McNally Bharat Engineering Company Ltd, Kolkata


(2-W021-TD00-2-0112)
Page 2 of 2
Bhilai Steel Plant Design Calculation of Ventilation
Water System: Package No. 077-02 System for BRM

Exhaust Ventilation System For BRM


Total Fan
No. of Air Volume to Capacity
Sl. Length Width Height Volume Type of No. of fan Fan head
Location Change be with 10%
No. (m) (m) (m) (m3) Ventilation selected (mmWC)
per hour replaced margin
(m3/hr.) (m3/hr.)

1 Toilet block for WTP- 5 3 3 3 27 20 540 Exhaust 1 600 15

2 Toilet block for WTP- 6 & 7 3 7 5.5 116 20 2310 Exhaust 2 1275 15
Tranformer Room-9 of
3 Switchgear Room for WTP- 6 6 5.5 198 20 3960 Exhaust 4 1100 15
6
Tranformer Room-10 of
4 Switchgear Room for WTP- 6 6 5.5 198 20 3960 Exhaust 4 1100 15
6
Tranformer Room-5 of
5 Switchgear Room for WTP- 6 6.25 5.5 206 20 4125 Exhaust 4 1150 15
7
Tranformer Room-6 of
6 Switchgear Room for WTP- 5.75 6.25 5.5 198 20 3953 Exhaust 4 1100 15
7
Tranformer Room-7 of
7 Switchgear Room for WTP- 5.75 6.25 5.5 198 20 3953 Exhaust 4 1100 15
7
Tranformer Room-8 of
8 Switchgear Room for WTP- 5.75 6.25 5.5 198 20 3953 Exhaust 4 1100 15
7

McNally Bharat Engineering Company Ltd, Kolkata


(2-W021-TD00-2-0112)
Page 1 of 1
Bhilai Steel Plant Design Calculation of Ventilation
Water System: Package No. 077-02 System for BRM

SCHEDULE OF VENTILATION

Supply Fan Detail

Area Type of Ventilation Capacity of C/S of Duct


No. of Head (mmWC
Fans Type
Fans )
(M3/Hr)
75 (Vendor to 1 no.Centrifugal fan with dry
Pressurised ventilation As per IS-655 and
Scale Pit Pump House finalise during filter,filter frame, filter
system by air washer unit 1 60000 with GI sheet IS-
(WTP-5) detail box,intake louvre,ducting,
through duct. 277- Gr.120
engineering) supply grills
50 (Vendor to 2 no.Centrifugal fan with dry
Pressurised ventilation As per IS-655 and
Hot & cold water pump 2(Ref. finalise during filter,filter frame, filter
system by air washer unit 44000 with GI sheet IS-
house(WTP-6) Note-2) detail box,intake louvre,ducting,
through duct. 277- Gr.120
engineering) supply grills
50 (Vendor to 1 no.Centrifugal fan with dry
Pressurised ventilation As per IS-655 and
finalise during filter,filter frame, filter
Electrical room (WTP-6) system by air washer unit 1 29500 with GI sheet IS-
detail box,intake louvre,ducting,
through duct. 277- Gr.120
engineering) supply grills
50 (Vendor to 1 no.Centrifugal fan with dry
Pressurised ventilation As per IS-655 and
Electrical room & pump finalise during filter,filter frame, filter
system by air washer unit 1 45500 with GI sheet IS-
house(WTP-7) detail box,intake louvre,ducting,
through duct. 277- Gr.120
engineering) supply grills

Exhaust Fan Detail


Capacity of
Area Type of Ventilation No. of Head (mmWC
Fans Type
Fans )
(M3/Hr)

Wall mounted axial type with


Toilet block for WTP- 5 Exhaust Ventilation system 1 600 15
rain cowl & bird screen

Wall mounted axial type with


Toilet block for WTP- 6 & 7 Exhaust Ventilation system 2 1275 15
rain cowl & bird screen

Tranformer Room-9 of
Wall mounted axial type with
Switchgear Room for WTP- Exhaust Ventilation system 4 1100 15
6 rain cowl & bird screen

Tranformer Room-10 of
Wall mounted axial type with
Switchgear Room for WTP- Exhaust Ventilation system 4 1100 15
6
rain cowl & bird screen

Tranformer Room-5 of
Wall mounted axial type with
Switchgear Room for WTP- Exhaust Ventilation system 4 1150 15
7 rain cowl & bird screen

Tranformer Room-6 of
Wall mounted axial type with
Switchgear Room for WTP- Exhaust Ventilation system 4 1100 15
7
rain cowl & bird screen

Tranformer Room-7 of
Wall mounted axial type with
Switchgear Room for WTP- Exhaust Ventilation system 4 1100 15
7
rain cowl & bird screen

Tranformer Room-8 of
Wall mounted axial type with
Switchgear Room for WTP- Exhaust Ventilation system 4 1100 15
7 rain cowl & bird screen

ACCESSORIES TO BE PROVIDED : Drive motor, Ducting air inlet cowl with bird screen, Supporting arrangement, back draft damper etc.
Note - 1) The capacities shown are tentative. Vendor to specify the actual capacities on the basis of Plant Layout and technical specification of
MECON and submit the same for approval.

2) Ventilation Capacity for Hot & cold water pump house(WTP-6) is 88000m3/hr.

NOTE:-Pressurized ventilation system shall be supplied with Make up water (1W+1S).the capacity of the same
shall be finalized during detail engineering.

McNally Bharat Engineering Company Ltd, Kolkata


(2-W021-TD00-2-0112)
Page 1 of 1