PT PLN (PERSERO) Doc. No.

TJBB/01/05/2019/150
UNIT INDUK TRANSMISI JAWA BAGIAN BARAT
Cinere 16514 – Jakarta Selatan Valid. JULI 2019
DAFTAR SETELAN RELAI PROTEKSI GI 150kV KARET LAMA

1. Proteksi Utama : Penghantar 150 KV arah Angke


Jenis relai : Distance Relay
Merek/Tipe relai : ALSTHOM / MICOM P442
LOKASI : GI KARET LAMA
PROTEKSI : BAY ANGKE #1, #2
L1, L2 : 7.9 km , 4.1 km
L3, L4 : 3.6 km , 0.7 km
2
Penghantar : OHL-150kV--ACFR 2x315mm
CCC : 2500 A
Z0 : 0.216 +j 0.823 /km
Z1 : 0.0623 +j 0.301 /km
Z2 : 0.0685 +j 0.2045 /km
Z3 : 0.075 +j 0.468 /km
Z4 : 0.0411 +j 0.2812 /km
XT : 12.5 % ; 60 MVA ; 46.875  (at 150 kV side)
CT : 1600 A / 5 A
PT : 150 KV / 100 Volt
SCHEME : PUTT
Address Remarks Setting Address Remarks Setting
Number Number
09 CONFIGURATION
0903 Active Sett Group 1 0915 SEF/REF Prot’n Disabled
0907 Sett Group 1 Enabled 0916 Residual O/V NVD Disabled
0908 Sett Group 2 Disabled 0917 Thermal Overload Disabled
0909 Sett Group 3 Disabled 0918 Power Swing Block Enabled
090A Sett Group 4 Disabled 091D Volt Protection Disabled
090B Distance Enabled 091E Freq Protection Disabled
090C Directional E/F Disabled 091F Df/dt Protection Disabled
0910 Overcurrent Disabled 0920 CB Fail Disabled
0911 Neg Seq O/C Disabled 0921 Supervision Enabled
0912 Broken Conductor Enabled 0923 System Checks Enabled**)
0913 Earth Fault Disabled 0924 Auto Reclose Enabled
092E Setting Values Secondary
0A CT & VT RATIOS
0A01 Main VT Primary 150 KV 0A08 Phase CT Secondary 5A
0A02 Main VT Secondary 100 V 0A0D MComp CT Primary 1600 A
0A03 C/S VT Primary 150 KV 0A0E MComp CT Secondary 5A
0A04 C/S VT Secondary 100 V 0A0F C/S Input B-N*)
0A07 Phase CT Primary 1600 A 0A10 Main VT Location Line
30 GROUP 1 LINE PARAMETERS
3001 Line Length 7.9 km 3006 kZN res Angle -4.713 deg
3003 Line Impedance 0.518 Ohm 3007 Mutual Comp Disabled
3004 Line Angle 78.3 deg 300B Phase Sequence Standard ABC
3005 kZN Res Comp 0.59 300C Trip Mode 1 and 3 Pole

1/4 Daftar Setelan Rele Proteksi Dibuat : IDF Diperiksa : HIK Disetujui : AJI
Rev. 00 GI 150kV KARET LAMA Tgl : Tgl : Tgl :
PT PLN (PERSERO) Doc. No. TJBB/01/05/2019/150
UNIT INDUK TRANSMISI JAWA BAGIAN BARAT
Cinere 16514 – Jakarta Selatan Valid. JULI 2019
DAFTAR SETELAN RELAI PROTEKSI GI 150kV KARET LAMA

31 GROUP 1 DISTANCE SETUP


3101C Setting Mode Advanced 31A0 Zone 3 Gnd Status Enabled
3110 PHASE DISTANCE 31A2 Zone 3 Gnd Offset Disabled
3111 Phase Chars. Mho 31B0 Zone P Gnd Status Disabled
3120 Zone 1 Ph Status Enabled 31C0 Zone 4 Gnd Status Disabled
3130 Zone 2 Ph Status Enabled 31D0 Digital Filter Standard
3140 Zone 3 Ph Status Enabled 31D1 CVT Filter Passive
3142 Zone 3 Ph Offset Disabled 31D2 SIR Setting 25
3150 Zone P Ph Status Disabled 31D3 Load Blinders Enabled
3160 Zone 4 Ph Status Disabled 31D4 Z< Blinder Imp 5.1 Ohm
3170 GROUND DISTANCE 31D5 Load/B Angle 47, 00 deg
3171 Ground Chars. Quad 31D6 Load Blinder V< 40, 00 V
3180 Zone 1 Gnd Status Enabled 31D7 Dist. Polarizing 5, 00
3190 Zone 2 Gnd Status Enabled
32 GROUP 1 DIST. ELEMENTS
3201 PHASE DISTANCE 3259 R1 Gnd. Resistive 4.73 Ohm
3202 Z1 Ph. Reach 0.414 Ohm 325B Z1 Sensit Ignd>1 50, 00 mA
3203 Z1 Ph. Angle 78.3 deg 3260 Z2 Gnd. Reach 0.622 Ohm
3209 Z1Sensit. Iph>1 50, 00 mA 3261 Z2 Gnd. Angle 78.3 deg
3210 Z2 Ph. Reach 0.622 Ohm 3263 Z2 Dynamic Tilt Disabled
3211 Z2 Ph. Angle 78.3 deg 3265 KZN2 Res. Comp 0.59
3217 Z2 Sensit. Iph>2 50, 00 mA 3266 kZN2 Res. Angle -4.713 deg
3220 Z3 Ph. Reach 1.058 Ohm 3269 R2 Gnd. Resistive 5.91 Ohm
3221 Z3 Ph. Angle 78.3 deg 326B Z2 Sensit Ignd>2 50, 00 mA
3228 Z3 Sensit. Iph>3 50, 00 mA 3270 Z3 Gnd. Reach 1.058 Ohm
3250 GROUND DISTANCE 3271 Z3 Gnd. Angle 78.3 deg
3251 Z1 Gnd. Reach 0.414 Ohm 3273 Z3 Dynamic Tilt Disabled
3252 Z1 Gnd. Angle 78.3 deg 3275 kZN3 Res. Comp 0.59
3253 Z1 Dynamic Tilt Disabled 3276 kZN3 Res. Angle -4.713 deg
3255 kZN1 Res. Comp 0.59 3279 R3 Gnd. Res. Fwd. 7.39 Ohm
3256 kZN1 Res. Angle -4.713 deg 327C Z3 Sensit. Ignd>3 50, 00 mA

2/4 Daftar Setelan Rele Proteksi Dibuat : IDF Diperiksa : HIK Disetujui : AJI
Rev. 00 GI 150kV KARET LAMA Tgl : Tgl : Tgl :
PT PLN (PERSERO) Doc. No. TJBB/01/05/2019/150
UNIT INDUK TRANSMISI JAWA BAGIAN BARAT
Cinere 16514 – Jakarta Selatan Valid. JULI 2019
DAFTAR SETELAN RELAI PROTEKSI GI 150kV KARET LAMA

34 GROUP 1 SCHEME LOGIC


3401 BASIC SCHEME 3440 AIDED SCHEME 1
3408 Zone 1 Tripping Phase & ground 3441 Aid. 1 Selection PUR
3409 tZ1 Ph. Delay 0s 3442 Aid. 1 Distance Phase & ground
340A tZ1 Gnd. delay 0s 3443 Aid. 1 Dist. Dly 0s
3410 Zone 2 Tripping Phase & ground 3460 AIDED SCHEME 2
3411 tZ2 Ph. Delay 0.400 s 3461 Aid. 2 Selection Disabled
3412 tZ2 Gnd. delay 0.400 s 3480 TRIP ON CLOSE
3418 Zone 3 Tripping Phase & ground 3481 SOTF Status Enabled Pole Dead
3419 tZ3 Ph. Delay 1.600 s 3482 SOTF Delay 30 s
341A tZ3 Gnd. delay 1.600 s 3483 SOTF Tripping 000011 (Z1 Z2)
3420 ZoneP Tripping Disabled 3484 TOR Status Enabled
3421 Zone4 Tripping Disabled 3485 TOR Tripping 000011 (Z1 Z2)
3486 TOC Reset Delay 100ms
37 BROKEN CONDUCTOR
3701 Broken Conductor Enabled 3703 I2/I1 Time Delay 60 s
3702 I2/I1 Setting 0.2
3D GROUP 1 POWER SWING BLK
3D01 PSB Status Blocking 3D0D Zone 1 Gnd. PSB Blocking
3D03 Zone 1 Ph. PSB Blocking 3D0F Zone 2 Gnd. PSB Blocking
3D05 Zone 2 Ph. PSB Blocking 3D11 Zone 3 Gnd. PSB Blocking
3D07 Zone 3 Ph. PSB Blocking 3D13 Zone P Gnd. PSB Blocking
3D09 Zone P Ph. PSB Blocking 3D15 Zone 4 Gnd. PSB Blocking
3D0B Zone 4 Ph. PSB Blocking
48 SYSTEM CHECKS**)
4815 V B/L Live 52 V 481D CS2 Status Disabled
4816 V B/L Dead 11.5 V 4822 CS Undervoltage 52 V
4818 CS1 Status Enabled 4823 CS Overvoltage 64 V
4819 CS1 Phase Angle 15 4824 CS Diff Voltage 6V
481A CS1 Slip Control Frequency 4825 CS Voltage Block V<
481B CS1 Slip Freq 0.167 Hz 4827 SS Status Disabled
49 GROUP 1 AUTO RECLOSE (MODE A/R : SPAR*)
4902 1 P Trip Mode 1 4909 Reclaim Time 40 s
4903 3 P Trip Mode 3 490A Reclose Pulse Time 0.2 s
4904 1 P Dead Time 1 1s
4905 3 P Dead Time 1 3s
Ket:
*) : Sesuaikan dengan kondisi riil di lapangan
**) : Apabila check synchronizing menggunakan BCU, maka fungsi system checks di-disabled

Agar pelaksana pekerjaan menyiapkan signal rekaman relay, antara lain : Anytrip, Status CB R-S-T, Fault Ph. R,
Fault Ph. S, Fault Ph. T, Trip R, Trip S, Trip T, Z1 Start, Z2 Start, Z3 Start, Initiate A/R, Sending, Receive, Power
Swing Detected, CT/VT Fail.
3/4 Daftar Setelan Rele Proteksi Dibuat : IDF Diperiksa : HIK Disetujui : AJI
Rev. 00 GI 150kV KARET LAMA Tgl : Tgl : Tgl :
PT PLN (PERSERO) Doc. No. TJBB/01/05/2019/150
UNIT INDUK TRANSMISI JAWA BAGIAN BARAT
Cinere 16514 – Jakarta Selatan Valid. JULI 2019
DAFTAR SETELAN RELAI PROTEKSI GI 150kV KARET LAMA

2. Proteksi Cadangan : Penghantar 150 KV arah Angke

JENIS TIPE SETELAN YANG DIUSULKAN EVALUASI PLN TJBB


RELAI RELAI ( nilai sekunder ) ( nilai sekunder )
OCR dan MCGG OCR/GFR (CT 1600/5), In = 5 A
GFR 82
OCR
Is : 4.5 A (sec’y)
Tap : 0.9 x In
TMS : 0.43 (SI)
Moment OCR
Im : Blok

GFR
Is : 0.75 A (sec’y)
Tap : 0.15 x In
TMS : 0.59 (SI)
Moment GFR
Im : Blok

4/4 Daftar Setelan Rele Proteksi Dibuat : IDF Diperiksa : HIK Disetujui : AJI
Rev. 00 GI 150kV KARET LAMA Tgl : Tgl : Tgl :