Project: Al Mina; Block - D (First Floor Transfer Level along X12/X14 Column)

Calculation of Punching Shear for Average depth of 675mm

LOAD CALCULATIONS AND OTHER DATA

Grade of concrete = 60

Grade of steel = 460

Factored Shear Force (As per Adapt analysis) = 10230 kN

EFFECTIVE DEPTH AND CRITICAL PUNCHING SHEAR CALCULATION

Overall average Depth of section @ critical perimeter (Average of 500mm and 850mm) = 675 mm

Clear cover for Reinforcement = 30 mm

Dia of Rebar in X Direction = 32 mm

Dia of Rebar in Y Direction = 32 mm

Effective depth = 613 mm

CALCULATION OF SHEAR STRESS AT LOADED FACE

Multiplication factor to account Unbalanced Moments = 1.15

Veff = 11764.5 kN

Length of column = 2000 mm

Bredth of column = 450 mm

Punching perimeter at column face u0 = 4900 mm

Punching perimeter at 1.5d from column face = 12256 mm

Maximum shear stress at column face vmax = (Veff/(u0*d)) = 3.9 N/mm2


The shear stress is lesser than the least value of 0.8√fcu and 5N/sqm. Hence safe

CALCULATION OF DESIGN SHEAR STRESS (VC)

Reinforcement assumed to be provided at the top of section (T32 @ 100 spacing) = 8040 mm2/m

bv = 1000 mm

100As/bv*d = 1.31

Take 100As/bv*d as = 1.31

Design Concrete shear stress (vc) from Table 3.8 = 0.66 N/mm2

Multiplication factor for concrete grade higher than M25 = 1.17

Design Concrete shear stress (vc) = 0.77 N/mm2

2*vc = 1.54 N/mm3

Design shear stress at first perimeter (v)

Design shear stress at first perimeter (v) = 1.57


vc < v < 2*vc

Section is safe against punching with shear reinforcement


One way shear Check along horizontal direction beam (PB - 2) at 500mm thick region
=
Factored shear force from Adapt analysis 2400 kN/m
=
Width of section 2400 mm
=
Depth of section 500.00
=
Effective depth 454
=
Nominal Shear Stress v 2.20 N/mm2

Nominal shear stress is less than the allowable limit as per BS 8110. Hence beam is safe under one way shear