Record Plus

Residual current devices with separate


sensors

RD5, RD6 and RD1D

Function
RCD Relay
The relay part of the RCD device is a DIN-rail mounted device containing
the electronics and the setting area. On receipt of a signal from the ­sensor
two contacts are operated.
Sensor
Placed around the phase and neutral current paths it detects the vectorial sum of
Order Codes

the current in the circuit. When this sum is no longer zero, a signal is sent to the
connected RCD relay.
The connection between the relay and the sensor should be as short as possible,
the maximum circuit resistance may not exceed 30 Ohm.
If the lead length is longer than 5 meters and/or the sensitivity is adjusted to
values < 0.5A the use of screened cables and earthed screening is recommended.
The same recommendation applies in cases where the sensor is installed in an
environment where strong magnetic fields occur.
Applications For high nominal currents or high sensitivities the cables must be centered within
the sensor.
Intro The use of an oversized sensor and/or reduced cable cross sections not centraly
passing within the sensor could result in inaccurate readings.

A
Characteristics

B RCD Relay
• Complies with EN 50082 and EN 60730
• For sinusoidal and pulsating earth leakages
• Test button and reset (memory clean) button
C • Permanent working signal (green) and tripping signal (red) by means of LED
• Adjustable time delay (except 30mA) by means of potentiometer
• Two output contacts, one potential free
• Automatic test feature of the combination relay/sensor is provided
D • On disconnection of the sensor, the relay trips
• Plug-in terminal block
• Width: 3 modules of 18 mm
E • For installation in modular enclosures, DIN-rail mounted
Sensor
• Accuracy: 3/10,000 of the phase current (TTO type 1/10,000)
• Frequency: from 4 to 400Hz
F • Sealable cover terminals
• For use with the relay types RD1D, RD5 and RD6 as described here.
Also applicable for use with the reconnection relay RRC1 and RRC2
G Dimensions pg G.33
(see seperate publications)

RD5 RD6 RD1D


X Operating voltage
Power consumption
110; 220; 380/400V  50/60Hz ±15%
2.5VA
110; 220; 380/400V 50/60Hz ±15%
2.5VA
110; 220; 380/400V  50/60Hz ±15%
2.5VA
Sensitivity settings 0.03 ; 0.3 ; 0.5 ; 1A 0.2 ; 0.5 ; 2 ; 5A 0.01 - 5A in steps of 10mA
Setting method Dipswitches Dipswitches Digital with LCD display
Frequency 50/60Hz 50/60Hz 50/60Hz
Time delay adjustment (1) 0 - 1 second 0.5 - 5 seconds 0 - 3 seconds in steps of 50ms
Tripping time 30mA type 1x IdN<50ms - 5 x Idn<35ms 1x IdN<50ms - 5 x Idn<35ms 1x IdN<50ms - 5 x Idn<35ms
Tripping threshold 75% of set sensitivity value 75% of set sensitivity value 75% of set sensitivity value
Pre Alarm at 50% setting ---- ---- Contact settable at 50% Idn
Contact ratings 5A / 230V 5A / 230 5A / 230V
Operating temperature - 20  to  + 50°C - 20 to + 50°C - 20 to + 50°C
Terminal capacity 2.5 mm2; plug-in terminal box 2.5 mm2; plug-in terminal box 2.5 mm2; plug-in terminal box
(1) Time setting ALWAYS disabled when 30mA setting is chosen.

A.46
Record Plus
RD range differential relay
No. of
I∆n Operating voltage Settable delay modules Cat. no. Ref. no. Pack.
RD5 0.03 ... 1A 110V AC 0-1s 3 RD5 110 704175 1
0.03 ... 1A 220/230V AC 0-1s 3 RD5 220 704169 1
0.03 ... 1A 380/400V AC 0-1s 3 RD5 380 704176 1

RD6 0.2 ... 5A 110V AC 0.5 - 5 s 3 RD6 110 704178 1


0.2 ... 5A 220/230V AC 0.5 - 5 s 3 RD6 220 704177 1
0.2 ... 5A 380/400V AC 0.5 - 5 s 3 RD6 380 704179 1

Residual current devices


RD1D 0.01 ... 5A 110V AC 0-3s 3 RD1D 110 872225 1
0.01 ... 5A 220/230V AC 0-3s 3 RD1D 220 872224 1
0.01 ... 5A 380/400V AC 0-3s 3 RD1D 380 872226 1

Sensor
Sensor Ø internal (mm)
(internal opening) Cat. no. Ref. no. Pack.
Round 28 closed TTR28 456090 1
35 closed TTR35 456091 1
60 closed TTR60 456092 1
80 closed TTR80 456093 1
110 closed TTR110 456094 1
140 closed TTR140 456095 1
210 closed TTR210 456096 1

Rectangular 70x175 closed BTR 175 704154 1


115x305 closed BTR 305 704155 1
130x350 closed BTR 350 704156 1

Intro
Accessories
Cat. no. Ref. no. Pack. A
Through Panel/Door mounting kit for relay with DIN-rail, RDFR 872227 1
mounting hardware and doorflange.

C
Wiring Diagram

When the Shunt Release in the D


Record Plus Breaker or Switch is con-
nected to point 11 and point 12 of
the release is supplied by the relay.
(Voltage rating = Phase Neutral E
Voltage of the network)

Alternately points 13, 14 and 15


can be used allowing the use of a
F
Shunt or Undervoltage release
of a different voltage rating.

Sensor type TT or BT
Sensor type TT or BT G

A.47