Qc4003™ Load Take Over

The purpose of the Load Take Over mode is to transfer the load imported from the mains to the
generator for operation on generator supply only.

OPERATION FLOW

SINGLE RUNNING GENERATOR


INSTALLATION
• In AUTO mode, it is possible to enable AMF as a
second application. Once enabled, it will ALWAYS
overrule the selected application
• During AMF, it is possible to enable/disable the
back synchronisation feature

CONTROLLER SETTING TO ACTIVATE


Qc4003 THE LOAD TAKE OVER APPLICATION

Select the correct mode pushbutton


(SEMI-AUTO/ AUTO) MODE on display
• An optional Power Transducer (PT) is required to know the channel
power supplied by the mains Power ramp up / ramp down
2610-2620
Generator mode (=Load take over) channel 6070

Cooldown setting channel 6210


SEQUENCE
Back synchronisation setting of
channel 7080
• The generator will: Mains breaker

–– Start up on a local command Enable / disable AMF as 2nd application channel 7080

–– Synchronise with the mains Start command through internal channels


real time clock 6600-6670
–– Close the Generator breaker
Stop command through internal real channels
–– Take over the load according a user-defined ramp time clock 6600-6670
–– Disconnect the mains once the load measured by the PT is zero
• After a local stop command, the generator will:
–– Synchronise with the mains (= back synchronisation) NEEDED PARTS
–– Close the Mains breaker
–– Deload according a user-defined ramp • In AUTO mode a remote start switch is needed
–– Open the Generator breaker towards the dedicated binary input

–– Go into cooldown and stopGo into cooldown and stop • Wires for control and feedback of the Mains
breaker
FEATURES • Power Transducer
• Wires from the Power Transducer (voltage and
• In AUTO mode the generator will go through the same sequences current measurement)
once a remote command is given
• CTs to measure the mains current
• Use local commands when the module is in SEMIAUTO mode
(AMF as second mode is not possible)
• Use remote commands when the module is in AUTO mode
(AMF as second mode is possible)

www.atlascopco.com
Photos and illustrations contained herein might depict products with optional and/or extra components which are not included with the standard version of the product and, therefore, are not included in a purchase
of such product unless the customer specifically purchases such optional/extra components. We reserve the right to change the specifications and design of products described in this literature without notice.
Not all products are available in all markets.
APPLICATION DATA SHEET
Qc4003™ Load Take Over

MULTIPLE RUNNING GENERATOR


INSTALLATION CONTROLLER SETTING
TO ACTIVATE THE LOAD TAKE OVER
+ PMS APPLICATION (GENERATOR CONTROLLER)
Select the correct mode pushbutton
(SEMI-AUTO/AUTO) MODE on display
Qc4003
Power ramp up / ramp down channel 2610-2620

Generator mode (=Power Managment) channel 6070

Cool down setting channel 6210


Qc4003
Int. Communication ID channel 7531

Priority Select channel 8030

Manual priority selection channel 8080-8100


Qc4003 Number of ID ’s channel 8040-8070

Load dependent start channel 8000


• An optional Mains controller is required
• A Tie breaker is only required if AMF is selected as a second Load dedendent stop channel 8010
application

For Internal use only! 2954 5690 01 - © 2016 Atlas Copco Portable Energy All rights reserved.® Atlas Copco is a registered trademark of Atlas Copco AB
CONTROLLER SETTING
SEQUENCE TO ACTIVATE THE LOAD TAKE OVER
• The power management system (PMS) provides a fully intelligent + PMS APPLICATION (MAINS CONTROLLER)
system. After a local or remote start signal it will:
–– Start the necessary generators Generator mode (=Load take Over) channel 6070
–– Close individual Generator breakers after synchronisation Start command through internal channels
real time clock 6600-6670
–– Synchronise the generators with the mains
Stop command through internal channels
–– Close the Tie breaker, if installed real time clock 6600-6670
–– Take over the load according a user-defined ramp Back synchronisation setting of
channel 7080
Mains breaker
–– Disconnect mains once the load measured by the Mains
controller is zero Enable / disable AMF as 2nd application channel 7080
–– Start and stop generators to meet the actual load Int. Communication ID channel 7531
• After a local or remote stop command, the PMS system will:
PMS configuration channel 8020
–– Synchronise with the mains
–– Close the Mains breaker
–– Deload the generators according a userdefined ramp NEEDED PARTS
–– Open the Tie breaker
• Mains sensing lines L1 / L2 / L3
–– Open all Generator breakers
–– The generators will go into cooldown and stop • In AUTO mode a remote Start switch is needed
towards the dedicated binary input

FEATURES • Wires for control and feedback of the Tie and


Mains breaker
• Use local commands when the module is in SEMIAUTO mode • CAN communication lines
(AMF as second mode is not possible) • CTs to measure the mains current
• Use remote commands when the module is in AUTO mode • Qc4003 Mains Controller
(AMF as second mode is possible)
• Mains breaker (motorized)
• In AUTO mode, it is possible to enable AMF as a second application. • Tie breaker (motorized) only required if AMS is
Once enabled, it will ALWAYS overrule the selected application. With selected as second application
multiple generators a Tie breaker is needed!
• During AMF, it is possible to enable/disable the back synchronisation
feature

This Application Data Sheet does not replace the Instruction Manual delivered with the machine.
Please refer to the Instruction Manual for complete safety, operation and maintenance guidelines.
For a copy please contact your local Atlas Copco customer center, or visit:

www.atlascopco.com
Photos and illustrations contained herein might depict products with optional and/or extra components which are not included with the standard version of the product and, therefore, are not included in a purchase
of such product unless the customer specifically purchases such optional/extra components. We reserve the right to change the specifications and design of products described in this literature without notice.
Not all products are available in all markets.

S-ar putea să vă placă și