Sunteți pe pagina 1din 12

NVA100

FEEDER, LoM & POWER PROTECTION RELAY


THE COMPREHENSIVE SOLUTION FOR FEEDERS
AND LOSS OF MAIN PROTECTION

— Application
The relay type NVA100 can be typically used in radial or meshed MV and LV networks as feeder or power transformer
protection:
• On radial, ring and parallel feeders of any length in solidly grounded, ungrounded, Petersen coil and/or resis-
tance grounded systems.
• On parallel connected generators and transformer on the same Busbar.
• In HV, MV and LV electrical machines and network, load shedding and separation of active users from the
grid.

NVA100
- Protective & control functions
74TCS BF 79
50/51, 67
50N/51N, 67N
24 Overflux (V/Hz)
74VT 26 Thermal protection with Pt100 probes (MPT opzional)
32P 24
27 Undervoltage
52
59N 67N 27V1 Positive sequence undervoltage
32Q 27 32P Directional active overpower
37P 27V1
32Q Directional reactive overpower
37P Directional active underpower
50N/51N
37Q 59 37Q Directional reactive underpower
50/51 59V2
46 Negative sequence overcurrent
I2/I1 Negative/positice sequence current ratio
51V 81U 49 Thermal image (for lines and transformers)
55 81U
50/51 Phase overcurrent
26 50N/51N Residual overcurrent
67 81R 51V Voltage-controlled overcurrent
DPHI
55 Minimum power factor
59 Overvoltage
74CT 46 I2/I1 49
59N Residual overvoltage
59V2 Negative sequence overvoltage
67 Phase directional overcurrent
67N Ground directional overcurrent
81O/81U Overfrequency and underfrequency
81R Frequency rate of change
DPHI Vector jump
Control functions COMMUNICATION
BF Circuit breaker failure
- RS232 79 Automatic reclosing
METERING
- I L1..I L3,I E - Modbus RS485 74CT CT supervision
- Oscillography - Modbus TCP/IP 74VT VT supervision
- IEC 870-5-103/DNP3
- Events & Faults log 74TCS Trip circuit supervision

NVA100 - Flyer- 10 - 2012


— Firmware updating — MMI (Man Machine Interface)
The use of flash memory units allows on-site firmware updating. The user interface comprises a membrane keyboard, a backlight
LCD alphanumeric display and eight LEDs.
— Two set point profiles (A,B) The green ON LED indicates auxiliary power supply and self di-
Two independent groups of settings are provided. Switching from agnostics, two LEDs are dedicated to the Start and Trip (yellow
profiles may be operated by means of MMI, binary input and com- for Start, red for Trip) and five red LEDs are user assignable.
munication.
— Communication
— Measuring inputs Multiple communication interfaces are implemented:
• Three phase current inputs and one residual current input, • One RS232 local communication front-end interface for com-
with nominal currents independently selectable at 1 A or 5 A munication with ThySetter setup software.
through DIP-switches. • Two back-end interfaces for communication with remote mon-
• Three phase voltage inputs with programmable nominal volt- itoring and control systems by:
ages within range 50...130 V (UR =100 V) or 200...520 V (UR =400 V) - RS485 port using ModBus® RTU, IEC 60870-5-103 or DNP3
and one residual voltage input, with programmable nominal protocol.
voltage within range 50...130 V (UER =100 V). - Ethernet port (RJ45 or optical fiber), ModBus/TCP or IEC61850
protocol.
— Construction .
According to the hardware configurations, the NVA100 protec-
tion relay can be shipped in various case styles depending on
the required mounting options (flush, projecting mounting, rack
or with separate operator panel).

— Modular design
In order to extend I/O capability, the NVA100 hardware can be
A PhV A PhV Pos Pos
customized through external auxiliary modules: Amps Volts Amps Volts Position Position
• MRI - Output relays and LEDs (provided with NVA100) MX DC ST CO
• MID16 - Binary inputs Measurements Descriptions Status Controls

• MCI - 4...20 mA converters


Logical Nodes
• MPT - Pt100 probe inputs.
• MMXU1 XCBR2
Measurement Unit #1 Circuit Breaker #2

Logical Device

Physical Device

Native integration with IEC61850


— Programming and settings
All relay programming and adjustment operations may be per-
formed through MMI (Keyboard and display) or using a Personal
Computer with the aid of the ThySetter software.
— Binary inputs The same PC setup software is required to set, monitor and con-
Two binary inputs are available with programmable active state figure all Pro_N devices.
(active-ON/active-OFF) and programmable timer (active to OFF/ Full access to the available data is provided:
ON or ON/OFF transitions). • Read status and measures.
Several presettable functions can be associated to each input. • Read/edit settings (on-line or off-line edit).
Two session level (User or Administrator) with password for sen-
— Blocking input/outputs sible data access are provided.
One output blocking circuit and one input blocking circuit are
provided. — Metering
The output blocking circuits of one or several Pro_N relays, NVA100 provides metering values for phase and residual cur-
shunted together, must be connected to the input blocking cir- rents, phase and residual voltage, making them available for
cuit of the protection relay, which is installed upstream in the reading on a display or to communication interfaces.
electric plant. The output circuit works as a simple contact, Input signals are sampled 24 times per period and the RMS value
whose condition is detected by the input circuit of the upstream of the fundamental component is measured using the DFT (Dis-
protection relay. Use of suitable pilot wire to fiber optic convert- crete Fourier Transform) algorithm and digital filtering.
ers (BFO) allows to perform fast and reliable accelerated logic With DFT the RMS value of 2nd, 3rd, 4th and 5th harmonic of
selectivity on radial and closed ring networks. phase current are also measured.
On the base of the direct measurements, several calculated
— Output relays (min, max, average,...), phase, sequence, power, harmonic, de-
Six output relays are available (two changeover, three make and mand and energy measures are processed.
one break contacts); each relay may be individually programmed Measures can be displayed with reference to nominal values or
as normal state (normally energized, de-energized or pulse) and directly expressed in amperes and volts.
reset mode (manual or automatic).
A programmable timer is provided for each relay (minimum
pulse width). The user may program the function of each relay
according to a matrix (tripping matrix) structure.

2 NVA100 - Flyer- 10 - 2012


— Control and monitoring Automatic reclosing
Several predefined functions are implemented: The automatic reclosure function is well-used on overhead lines
• Activation of two set point profiles. (when faults are self-extinguish after tripping of protection relays).
• Phase CTs and VTs monitoring (74CT and 74VT). The following sequences may be selected:
• Logic selectivity. • Rapid reclosure,
• Cold load pickup (CLP) with block or setting change. • Rapid reclosure followed by one slow reclosure,
• Trip circuit supervision (74TCS). • Rapid reclosure followed by one slow reclosure and one or
• Second harmonic restraint (inrush). more delayed reclosures (1...5).
• Remote tripping. Starting of the automatic reclosing function can be raised by in-
• Synchronization. ternal protective elements or externally by means binary input
• Automatic reclosing signals (eg: external protection device contacts or switches).
• Circuit Breaker commands and diagnostic. The following logics may be set (binary inputs allocation):
Moreover user defined logic must be customized in accordance • 52a - 52b (Circuit breaker state); the CB position is indispens-
with IEC 61131-3 protocol by means programmable logic control- able for the auto reclosure function.
ler (PLC). • Blocking; exclusion command (pulse),
• Enabling; activation command (pulse).
Circuit Breaker • The following output functions may be coupled to the output
Several diagnostic, monitoring and control functions are provided: relays:
• Health thresholds can be set; when the accumulated duty (ΣI • CB reclosing command;
or ΣI2t), the number of operations or the opening time exceeds • Reclosure fail.
the threshold an alarm is activated. • Cycle in progress.
• Breaker failure (BF); breaker status is monitored by means
52a-52b and/or through line current measurements. Second harmonic restraint
• Trip circuit supervision (74TCS). To prevent unwanted tripping of the protective functions on
• Breaker control; opening and closing commands can be car- transformer inrush current, the protective elements can be
ried out locally or remotely. blocked when the ratio between the second harmonic current
and the relative fundamental current is larger than a user pro-
Virtual I/O grammable threshold.
Through ThySetter and ThyVisor tools the type of operation and The function can be programmed to switch an output relay so
links between eight outputs (Virtual Output - VOUT1 ... 8) and as to cause a blocking protection relays lacking in second har-
ten virtual inputs (Virtual Inputs - VIN1 ... VIN10) may be defined monic restraint.
using RPC or IEC 61850 communication protocols over Ethernet
network. — Self diagnostics
The system allows: All hardware and software functions are repeatedly checked
• Availability of eight inputs and ten outputs independently pro- and any anomalies reported via display messages, communica-
grammable by the user tion interfaces, LEDs and output relays.
• Simplify wiring using one channel as the Ethernet Anomalies may refer to:
• Eliminate the need to install communication devices and / or • Hw faults (auxiliary power supply, output relay coil interrup-
external conversion tions, MMI board...).
• Significantly reduce costs • Sw faults (boot and run time tests for data base, EEPROM
• Dynamically change from sw connections and associated memory checksum failure, data BUS,...).
functions. • Pilot wire faults (break or short in the wire).
The virtual I / O can be usefully employed for: • Circuit breaker faults.
• Transmit information between protections installed in dis-
tance — Event storage
• Achieve accelerated logic discrimination in which some pro- Several useful data are stored for diagnostic purpose; the events
tection elements can be blocked by the activation of the down- are stored into a non volatile memory.
stream protection start They are graded from the newest to the older after the “Events
• Circuit Breaker commands, Selection of setting profiles, Re- reading” command (ThySetter) is issued:
mote trip, etc... • Sequence of Event Recorder (SER).
The event recorder runs continuously capturing in circular
Logic selectivity mode the last three hundred events upon trigger of binary in-
With the aim of providing a fast selective protection system put/output.
some protective functions may be blocked. • Sequence of Fault Recorder (SFR).
The selectivity logic may be accomplished by: The fault recorder runs continuously capturing in circular
• input and output block circuits, mode the last twenty faults upon trigger of binary input/output
• output relays and logic inputs, and/or element pickup (start-trip).
• virtual input and output with messages on Ethernet network. • Trip counters.
To guarantee maximum fail-safety, the relay performs a run time
monitoring for pilot wire continuity and pilot wire shorting. Ex- — Digital Fault Recorder (Oscillography)
actly the output blocking circuit periodically produces a pulse, Upon trigger of tripping/starting of each function or external sig-
with small width in order to be ignored as an effective blocking nals, the relay records in COMTRADE format:
signal by the input blocking circuit of the upstream protection, • Oscillography with instantaneous values for transient analysis.
but suitable to prove continuity of the pilot wire. • RMS values for long time periods analysis.
Furthermore a permanent activation (or better, with a duration • Logic states (binary inputs and output relays).
longer than a preset time) of the blocking signal is identified, as Note - A license for Digital Fault Recorder function is required, for purchase
a warning for a possible short circuit in the pilot wire or in the procedure please contact Thytronic.
output circuit of the downstream protection. The records are stored in non-volatile memory
Cold Load Pickup (CLP)
Cold load pickup element prevents unwanted tripping in case of
temporary overcurrents produced when a feeder is being con-
nected after an extended outage (e.g. motor starting).
Two different operating modes are provided:
• Each protective element can be blocked for a setting time.
• Each threshold can be increased for a setting time.

NVA100 - Flyer- 10 - 2012 3


SPECIF ICAT IONS
GENERAL INPUT CIRCUITS
— Mechanical data — Auxiliary power supply Uaux
Mounting: flush, projecting, rack or separated operator panel Nominal value (range) 24...48 Vac/dc, 115...230 Vac/110...220 Vdc
Mass (flush mounting case) 2.0 kg Operative range (each one of the above nominal values) 19...60 Vac/dc
85...265 Vac/75...300 Vdc
— Insulation tests Power consumption:
Reference standards EN 60255-5 • Maximum (energized relays, Ethernet TX) 10 W (20 VA)
High voltage test 50Hz 2 kV 60 s • Maximum (energized relays, Ethernet FX) 15 W (25 VA)
Impulse voltage withstand (1.2/50 μs) 5 kV
Insulation resistance >100 MΩ — Phase current inputs
Nominal current In 1 A or 5 A selectable by DIP Switches
— Voltage dip and interruption Permanent overload 25 A
Reference standards EN 61000-4-29 Thermal overload (1s) 500 A
Rated consumption (for any phase) ≤ 0.002 VA (In = 1 A)
— EMC tests for interference immunity ≤ 0.04 VA (In = 5 A)
1 MHz damped oscillatory wave EN 60255-22-1 1 kV-2.5 kV — Residual current input
Electrostatic discharge EN 60255-22-2 8 kV Nominal current IEn 1 A or 5 A selectable by DIP Switch
Fast transient burst (5/50 ns) EN 60255-22-4 4 kV Permanent overload 25 A
Conducted radio-frequency fields EN 60255-22-6 10 V Thermal overload (1s) 500 A
Radiated radio-frequency fields EN 60255-4-3 10 V/m Rated consumption ≤ 0.006 VA (IEn = 1 A)
High energy pulse EN 61000-4-5 2 kV ≤ 0.012 VA (IEn = 5 A)
Magnetic field 50 Hz EN 61000-4-8 1 kA/m — Voltage inputs
Damped oscillatory wave EN 61000-4-12 2.5 kV Reference voltage UR 100 V or 400 V selectable on order
Ring wave EN 61000-4-12 2 kV Nominal voltage Un 50...130 V or 200...520 V adjustable via sw
Conducted common mode (0...150 kHz) EN 61000-4-16 10 V Permanent overload 1.3 UR
1s overload 2 UR
— Emission Rated consumption (for any phase) ≤ 0.5 VA
Reference standards EN 61000-6-4 (ex EN 50081-2)
Conducted emission 0.15...30 MHz Class A — Residual voltage input
Radiated emission 30...1000 MHz Class A Reference voltage UER 100 V
Nominal voltage UEn 50...130 V adjustable via sw
— Climatic tests Permanent overload 1.3 UER
Reference standards IEC 60068-x, ENEL R CLI 01, CEI 50 1s overload 2 UER
Rated consumption ≤ 0.5 VA
— Mechanical tests
Reference standards EN 60255-21-1, 21-2, 21-3 — Binary inputs
Quantity 2
— Safety requirements Type dry inputs
Reference standards EN 61010-1 Max permissible voltage 19...265 Vac/19...300 Vdc
Pollution degree 3 Max consumption, energized 3 mA
Reference voltage 250 V
Overvoltage III — Block input (Logic selectivity)
Pulse voltage 5 kV Quantity 1
Reference standards EN 60529 Type polarized wet input (powered by internal isolated supply)
Protection degree: Max consumption, energized 5 mA
• Front side IP52
• Rear side, connection terminals IP20 OUTPUT CIRCUITS

— Environmental conditions — Output relays K1...K6


Ambient temperature -25...+70 °C Quantity 6
Storage temperature -40...+85 °C Type of contacts:
Relative humidity 10...95 % • K1, K2 changeover (SPDT, type C)
Atmospheric pressure 70...110 kPa • K3, K4, K5 make (SPST-NO, type A)
• K6 break (SPST-NC, type B)
— Certifications Nominal current 8A
Product standard for measuring relays EN 50263 Nominal voltage/max switching voltage 250 Vac/400 Vac
CE conformity Breaking capacity:
• EMC Directive 2004/108/EC • Direct current (L/R = 40 ms) 50 W
• Low Voltage Directive 2006/95/EC • Alternating current (λ = 0,4) 1250 VA
• Type tests IEC 60255-6 Make 1000 W/VA
Short duration current (0,5 s) 30 A
COMMUNICATION INTERFACES — Block output (Logic selectivity)
Local PC RS232 19200 bps Quantity 1
Network: Type optocoupler
• RS485 1200...57600 bps
• Ethernet 100BaseT 100 Mbps — LEDs
Protocol ModBus® RTU/IEC 60870-5-103/DNP3, Quantity 8
TCP/IP, IEC61850 • ON/fail (green) 1
• Start (yellow) 1
• Trip (red) 1
• Allocatable (red) 5
4 NVA100 - Flyer- 10 - 2012
GENERAL SETTINGS Inverse time
• 27 First threshold inverse time (U <inv) 0.05...1.10 U n /E n
— Rated values • U<inv Operating time (t U<inv) 0.10...100.0 s
Relay nominal frequency (f n) 50, 60 Hz
U<< Element
Relay phase nominal current (In) 1 A, 5 A
Definite time
Phase CT nominal primary current (Inp) 1 A...10 kA
• 27 Second threshold definite time (U <<def) 0.05...1.10 U n /E n
Relay residual nominal current (IEn) 1 A, 5 A
• U<<def Operating time (t U<<def ) 0.03...100.0 s
Residual CT nominal primary current (IEnp) 1 A...10 kA
Relay nominal voltage (phase-to-phase) (Un) 50...130 V or 200...520 V Note 1: With U ph-ph setting all threshold are in p.u. U n
Relay nominal voltage (phase-to-ground) En= Un/√3 - With U ph-n setting all threshold are in p.u. E n
Line VT primary nominal voltage (phase-to-phase) (Unp) 50 V..500 kV Note 2: The mathematical formula for INVERSE curves is:
Relay residual nominal voltage (direct measure) (UEn) 50...130 V t = 0.75 ∙ t U < inv / [1 - (U/U< inv)], where:
Residual primary nominal voltage (phase-to-phase) · √3 (UEnp) t = trip time (in seconds)
50 V...500 kV t U< inv = operating time setting (in seconds)
Relay nominal active power (Pn) Pn = √3 ∙ Un ∙ In = 3 ∙ En ∙ In U = input voltage
Relay nominal reactive power (Qn) Qn = √3 ∙ Un ∙ In = 3 ∙ En ∙ In U<inv = threshold setting
Relay nominal apparent power (Sn) Sn = √3 ∙ Un ∙ In = 3 ∙ En ∙ In
— Positive sequence undervoltage - 27V1
— Binary input timers U1< Element
ON delay time (IN1 tON...IN10 tON) 0.00...100.0 s • 27V1 First threshold definite time (U 1<def) 0.05...1.10 E n
OFF delay time (IN1 tOFF, IN2 tOFF) 0.00...100.0 s • 27V1 Operating time (t U1<def ) 0.07...100.0 s
Logic Active-ON/Active-OFF — Directional active overpower 32P
— Relay output timers P1> Element
Minimum pulse width 0.000...0.500 s • P1> Tripping direction (P1> DIR) P Forward/P Reverse/P Fw/Rv
• P1> Reset time delay (t P1> RES) 0.00...100.0 s
PROTECTIVE FUNCTIONS • 32P First threshold definite time (P1>def) 0.01...1.50 Pn
• P1>def Operating time (t P1>def) 0.07...100.0 s
— Base current IB [1] P2> Element
Base current (IB) 0.10...2.50 In • P2> Tripping direction (P 2> DIR) P Forward/P Reverse/P Fw/Rv
• P2> Reset time delay (t P2> RES) 0.00...100.0 s
Note - The basic current IB represents the nominal current of the line or trans-
former, referred to the nominal current of the CT’s for thermal image pro-
• 32P Second threshold definite time (P2>def) 0.01...1.50 Pn
tection. If the secondary rated current of the line CT’s equals the rated • P2> Operating time (t P2>def) 0.07...100.0 s
current oft he relay, as usually happens, the IB value is the ratio between
therated current of the protected element and the primary rated current of
— Directional reactive overpower 32Q
the CT’s
Q1> Element
• Q1> Tripping direction (Q1> DIR) Q Forward/Q Reverse/Q Fw/Rv
• Q1> Reset time delay (t Q1> RES) 0.00...100.0 s
— Overexcitation (24)
• 32Q First threshold definite time (Q1>def) 0.01...1.50 Qn
(U/f ) AL Element
• Q1> Operating time (t Q1>def) 0.07...100.0 s
• Alarm threshold definite time (U/f ) ALdef 0.50...2.00 Un /fn
• Operating time (definite time) t (U/f)ALdef 0.10...100.0 s
Q2> Element
• Q2> Tripping direction (Q2> DIR) Q Forward/Q Reverse/Q Fw/Rv
(U/f )> Element 0.50...2.00 Un /fn • Q2> Reset time delay (t Q2> RES) 0.00...100.0 s
• Curve type (U/f>Curve) DEFINITE, IEC/BS A, B, C • 32Q Second threshold definite time (Q2>def) 0.01...1.50 Qn
Definite time • Q2> Operating time (t Q2>def) 0.07...100.0 s
• (U/f )> threshold definite time (U/f )>def 0.50...2.00 Un /fn
• (U/f )>def Operating time (definite time) (t (U/f) > def) 0.10...100.0 s — Directional active underpower 37P
Inverse time Common configuration:
• (U/f )> threshold inverse time (U/f )>inv 0.50...2.00 Un /fn • CB-37P Enable (CB-37P) ON/OFF
• (U/f )>inv Operating time (inverse time) (t (U/f) > inv) 0.10...100.0 s • CB-37P Delay (tARM-P<) 0.07...300 s
(U/f )>> Element P1< Element
• (U/f )> threshold definite time (U/f )>>def 0.50...2.00 Un /fn • 37P First threshold definite time (P1<def) 0.01...1.50 Pn
• Soglia (U/f )>>def 0.50...2.00 Un /fn • P1< Operating time (t P1<def) 0.07...100.0 s
• (U/f )>def Operating time (definite time) (t (U/f) >> def) (0.10...100.0 s P2< Element
• 37P Second threshold definite time (P2<def) 0.01...1.50 Pn
— Thermal protection with RTD thermometric probes - 26 • P2< Operating time (t P2<def) 0.07...100.0 s
Alarm
• Alarm threshold θALx (x=1...8) 0...200 °C — Directional reactive underpower 37Q
• Operating time t θALx (x=1...8) 0....100 s Common configuration:
• CB-37Q Enable (CB-37Q) ON/OFF
Trip • CB-37Q Delay (tARM-Q<) 0.07...300 s
• Trip threshold θ>x (x=1...8) 0...200 °C Q1< Element
• Operating time t θ >x (x=1...8) 0....100 s • 37Q First threshold definite time (Q1<def) 0.01...1.50 Qn
Note: The element becomes available when the MPT module is enabled and • Q1< Operating time (t Q1<def) 0.07...100.0 s
connected to Thybus Q2< Element
• 37Q Second threshold definite time (Q2<def) 0.01...1.50 Qn
— Undervoltage - 27 • Q1< Operating time (t Q2<def) 0.07...100.0 s
Common configuration:
• Voltage measurement type for 27 (Utype27) [1] U ph-ph /U ph-n — Negative sequence - 46
• 27 Operating logic (Logic27) AND/OR I2> Element
• I2> Curve type DEFINITE
U< Element IEC/BS A, B, C - ANSI/IEEE MI, VI, EI, I2t , EM
• U< Curve type (U<Curve) DEFINITE, INVERSE [2] • I2CLP > Activation time (t 2CLP>) 0.00...100.0 s
Definite time • I2> Reset time delay (t 2 > RES) 0.00...100.0 s
• 27 First threshold definite time (U <def) 0.05...1.10 U n /E n Definite time
• U<def Operating time (t U<def ) 0.03...100.0 s • 46 First threshold definite time (I2 > def ) 0.100...10.00 In

NVA100 - Flyer- 10 - 2012 5


• I2 > def within CLP (I2CLP>def ) 0.100...10.00 In — Residual overcurrent - 50N/51N
• I2 > def Operating time (t 2 > def ) 0.03...200 s IE> Element
Inverse time • IE> Curve type (IE>Curve) DEFINITE,
• 46 First threshold inverse time (I2 >inv) 0.100...10.00 In IEC/BS A, B, C, ANSI/IEEE MI, VI, EI, EM
• I2 >inv within CLP (I2CLP>inv) 0.100...10.00 In • IECLP > Activation time (t ECLP>) 0.00...100.0 s
• I2 >inv Operating time (t 2 >inv) 0.02...60.0 s • IE> Reset time delay (t E> RES) 0.00...100.0 s
I2>> Element Definite time
• I2CLP >> Activation time (t 2CLP>>) 0.00...100.0 s • 50N/51N First threshold definite time (I E>def) 0.002...10.00 IEn
• I2>> Reset time delay (t 2 >> RES) 0.00...100.0 s • IE>def within CLP (IECLP>def ) 0.002...10.00 IEn
Definite time • IE>def Operating time (t E> def) 0.04...200 s
• 46 Second threshold definite time (I>> def ) 0.100...40.00 In Inverse time
• I2 >> def within CLP (I2CLP>>def ) 0.100...40.00 In • 50N/51N First threshold inverse time (IE >inv) 0.010...2.00 IEn
• I2 >> def Operating time (t 2 >> def ) 0.03...10.00 s • IE>inv within CLP (IECLP>inv) 0.010...2.00 IEn
• IE>inv Operating time (t E>inv) 0.02...60.0 s
— Negative sequence current / positive sequence current
IE>> Element
ratio - I2 /I1 • IECLP >> Activation time (t ECLP>>) 0.00...100.0 s
I21> Element • IE>> Reset time delay (t E>> RES) 0.00...100.0 s
• I21CLP > Activation time (t 21CLP>) 0.00...100.0 s Definite time
Definite time • 50N/51N Second threshold definite time (IE>>def) 0.002...10.00 IEn
• I2 /I1 First threshold definite time (I21>def ) 0.10...1.00 • IE>>def within CLP (IECLP>>def ) 0.002...10.00 IEn
• I21> def within CLP (I21CLP>def ) 0.10...1.00 • IE>>def Operating time (t E>> def ) 0.03...10.00 s
• I21> def Operating time (t 21>def ) 0.04..15000 s IE>>> Element
• IECLP >>> Activation time (t ECLP>>>) 0.00...100.0 s
— Thermal image - 49 • IECLP >>> Reset time delay (t E>>> RES) 0.00...100.0 s
Common configuration: Definite time
• Initial thermal image ΔθIN (Dth IN ) 0.0...1.0 ΔθB • 50N/51N Third threshold definite time (I E>>>def) 0.002...10.00 IEn
• Reduction factor at inrush (KINR) 1.0...3.0 • IECLP >>> def within CLP (IECLP>>>def ) 0.002...10.00 IEn
• Thermal time constant τ (T ) 1...200 min • IECLP >>> def Operating time (t E>>> def ) 0.03...10.00 s
• DthIN Activation time (tdthCLP) 0.00...100.0 s
• 49 Second harmonic restraint (Dth 2ndh-REST ) OFF/ON — Minimum power factor - 55
DthAL1 Element Common configuration:
• 49 First alarm threshold ΔθAL1 (Dth AL1) 0.3...1.0 ΔθB • CB-55 Delay (tARM-CPhi<) 0.07...300 s
DthAL2 Element • CPhi1< Element
• 49 Second alarm threshold ΔθAL2 (Dth AL 2 ) 0.5...1.2 ΔθB • CPhi1< Tripping direction (CPhi1<DIR)
CosPhi Lag/CosPhi Lead/Lag/CosPhi Lag-Lead
Dth> Element • 55 First threshold definite time (CPhi1<def ) 0.10...0.99
• 49 Trip threshold Δθ (Dth>) 1.100...1.300 ΔθB • CPhi1< Operating time (t CPhi1<def ) 0.04...100.0 s
— Phase overcurrent - 50/51 • CPhi2< Element
I> Element • CPhi2< Tripping direction (CPhi2<DIR)
• I> Curve type (I>Curve) DEFINITE, CosPhi Lag/CosPhi Lead/Lag/CosPhi Lag-Lead
IEC/BS A, B, C, ANSI/IEEE MI, VI, E, RECTIFIER, I2t, EM • 55 Second threshold definite time (CPhi2<def ) 0.10...0.99
• ICLP > Activation time (t CLP>) 0.00...100.0 s • CPhi2< Operating time (t CPhi2<def ) 0.04...100.0 s
• I> Reset time delay (t > RES) 0.00...100.0 s
Definite time — Overvoltage - 59
• 50/51 First threshold definite time (I> def ) 0.100...40.0 In Common configuration:
• I> def within CLP (ICLP>def ) 0.100...40.0 In • Voltage measurement type for 59 (Utype59) [1] U ph-ph /U ph-n
• I> def Operating time (t > def ) 0.04...200 s • 59 Operating logic (Logic59) AND/OR
Inverse time U> Element
• 50/51 First threshold inverse time (I>inv) 0.100...20.00 In • U> Curve type (U>Curve) DEFINITE, INVERSE [2]
• I>inv within CLP (ICLP>inv) 0.100...20.00 In Definite time
• I>inv Operating time (t >inv) 0.02...60.0 s • 59 First threshold definite time (U >def) 0.50...1.50 U n /E n
I>> Element • U>def Operating time (t U> def ) 0.03...100.0 s
• Type characteristic DEFINITE or I2t Inverse time
• ICLP >> Activation time (t CLP>>) 0.00...100.0 s • 59 First threshold inverse time (U >inv) 0.50...1.50 U n /E n
• I>> Reset time delay (t >> RES) 0.00...100.0 s • U>inv Operating time (t U>inv) 0.10...100.0 s
Definite time U>> Element
• 50/51 Second threshold definite time (I>> def ) 0.100...40.0 In Definite time
• I>> def within CLP (ICLP>>def ) 0.100...40.0 In • 59 Second threshold definite time (U >>def) 0.50...1.50 U n /E n
• I>> def Operating time (t >> def ) 0.03...10.00 s • U>>def Operating time (t U>> def ) 0.03...100.0 s
Inverse time Note 1: With U ph-ph setting all threshold are in p.u. U n
• 50/51 Second threshold inverse time (I>>inv) 0.100...20.00 In With U ph-n setting all threshold are in p.u. E n
• I>>inv within CLP (ICLP>>inv) 0.100...20.00 In Note 2 : The mathematical formula for INVERSE curves is:
• I>>inv Operating time (t >>inv) 0.02...10.00 s t = 0.5 ∙ t U>inv / [1 - (U/U>inv)], where:
I>>> Element t = trip time (in seconds), t U> inv = operating time setting (in seconds)
• ICLP >>> Activation time (t CLP>>>) 0.00...100.0 s U = input voltage, U>inv = threshold setting
• I>>> Reset time delay (t >>> RES) 0.00...100.0 s
• I>>> Voltage-controlled by U<< OFF-ON
— Residual overvoltage - 59N
Common configuration:
Definite time
• Residual voltage measurement for 59N- direct/calc. U E /U EC
• 50/51 Third threshold definite time (I>>> def ) 0.100...40.0 In
• 59N Operating mode from 74VT internal (74VTint59N) OFF/Block
• I>>>def within CLP (ICLP>>>def ) 0.100...40.0 In
• 59N Operating mode from 74VT external (74VText59N) OFF/Block
• I>>>def Operating time (t >>> def ) 0.03...10.00 s
U E > Element
• U E > Curve type (U E >Curve) DEFINITE, INVERSE [3]
• U E> Reset time delay (t UE>RES) 0.00...100.0 s
6 NVA100 - Flyer- 10 - 2012
Definite time — Directional earth fault overcurrent - 67N
• 59N First threshold definite time (U E >def) 0.01...0.70 U En Common configuration:
• U E>def Operating time (t UE >def) 0.07...100.0 s • 67N Operating mode (Mode67N) I /I ∙cos
Inverse time • Residual voltage measurement type for 67N - direct/calculated
• 59N First threshold inverse time (U E >inv) 0.01...0.50 U En (3VoType67N) U E / U EC
• U E>inv Operating time (t UE >inv) 0.10...100.0 s • 67N Multiplier of threshold for insensitive zone (M) 1.5...10.0
U E >> Element • 67N Operating mode from 74VT internal (74VTint67N)
• U E>> Reset time delay (t UE>>RES) 0.00...100.0 s OFF/Block/Not directional
• 59N Second threshold definite time (U E >>def) 0.01...0.70 U En • 67N Operating mode from 74VT external (74VText67N)
• U E>>def Operating time (t UE >>def) 0.07...100.0 s OFF/Block/Not directional
IED> Element
Note 1 The formula for INVERSE curves is: t = 0.5 ∙ t UE>inv / [(UE /UE > inv) - 1]
t = trip time (in seconds)
• IED> Curve type DEFINITE
t UE>inv = operating time setting (in seconds)
IEC/BS A, B, C, ANSI/IEEE MI, VI, EI, EM
UE = residual input voltage, U E> inv = threshold setting • IEDCLP > Activation time (t EDCLP>) 0.00...100.0 s
• IED> Reset time delay (t ED > RES) 0.00...100.0 s
— Negative sequence overvoltage - 59V2 Definite time
U2> Element 67N First threshold definite time (IED > def - UED > def )
Definite time • Residual current pickup value 0.002...10.00 IEn
• U2>def Operating time (t U2> def ) 0.07...100.0 s • Residual voltage pickup value 0.004...0.500 UEn
• Characteristic angle 0...359°
— Directional phase overcurrent - 67 • Half operating sector 1...180°
Common configuration: • IED > def within CLP (IEDCLP>def ) 0.002...10.00 IEn
• 67 Operating mode (Mode67) I /I ∙cos • IED > def Operating time (t ED > def ) 0.05...200 s
• 67 Operating logic (Logic67) 1/3 / 2/3 Inverse time
• 67 Operating mode from 74VT internal (74VTint67) 67N First threshold inverse time (IED >inv - UED >inv)
OFF/Block/Not directional • Residual current pickup value 0.002...2.00 IEn
• 67 Operating mode from 74VT external (74VText67) • Residual voltage pickup value 0.004...0.500 UEn
OFF/Block/Not directional • Characteristic angle 0...359°
IPD> Element • Half operating sector 1...180°
• IPD> Curve type (IPD>Curve) DEFINITE, • IED >inv within CLP (IEDCLP >inv) 0.002...2.00 IEn
IEC/BS A, B, C, ANSI/IEEE MI, VI, EI, RECTIFIER, I2t, EM • IED >inv Operating time (t ED >inv) 0.02...60.0 s
• IPDCLP > Activation time (t PDCLP>) 0.00...100.0 s
• IPD> Reset time delay (t PD > RES) 0.00...100.0 s IED>> Element
Definite time • IED> Curve type (IED>>Curve) DEFINITE
• 67 First threshold definite time (IPD > def ) 0.100...40.0 In IEC/BS A, B, C, ANSI/IEEE MI, VI, EI, EM
• IPD > def characteristic angle (ThetaPD>def ) 0...359° • IEDCLP >> Activation time (t EDCLP>>) 0.00...100.0 s
• IPD > def within CLP (IPDCLP>def ) 0.100...40.0 In • IED>> Reset time delay (t ED >> RES) 0.00...100.0 s
• IPD > def Operating time (t PD > def ) 0.05...200 s Definite time
Inverse time 67N Second threshold definite time (IED >> def - UED >> def )
• 67 First threshold inverse time (IPD >inv) 0.100...10.0 In • Residual current pickup value 0.002...10.00 IEn
• IPD >inv characteristic angle (ThetaPD>inv) 0...359° • Residual voltage pickup value 0.004...0.500 UEn
• IPD >inv within CLP (IPDCLP>inv) 0.100...10.0 In • Characteristic angle 0...359°
• IPD >inv Operating time (t PD >inv) 0.02...60.0 s • Half operating sector 1...180°
• IED >> def within CLP (IEDCLP >> def ) 0.002...10.00 IEn
IPD>> Element • IED >> def Operating time (t ED >> def ) 0.05...10.00 s
• IPD> Curve type (IPD>>Curve) DEFINITE, Inverse time
IEC/BS A, B, C, ANSI/IEEE MI, VI, EI, RECTIFIER, I2t or EM 67N Second threshold inverse time (IED >>inv - UED >>inv)
• IPDCLP >> Activation time (t PDCLP>>) 0.00...100.0 s • Residual current pickup value 0.002...2.00 IEn
• IPD>> Reset time delay (t PD >> RES) 0.00...100.0 s • Residual voltage pickup value 0.004...0.500 UEn
Definite time • Characteristic angle 0...359°
• 67 Second threshold definite time (IPD >> def ) 0.100...40.0 In • Half operating sector 1...180°
• IPD >> def characteristic angle (ThetaPD>>def ) 0...359° • IED >inv within CLP (IEDCLP>>inv) 0.002...2.00 IEn
• IPD >> def within CLP (IPDCLP>>def ) 0.100...40.0 In • IED >inv Operating time (t ED >>inv) 0.02...10.00 s
• IPD >> def Operating time (t PD >> def ) 0.04...200 s
Inverse time IED>>> Element
• 67 Second threshold inverse time (IPD >>inv) 0.100...10.0 In • IEDCLP >>> Activation time (t EDCLP>>>) 0.00...100.0 s
• IPD >>inv characteristic angle (ThetaPD>>inv) 0...359° • IED>>> Reset time delay (t ED >>> RES) 0.00...100.0 s
• IPD >>inv within CLP (IPDCLP>>inv) 0.100...10.0 In Definite time
• IPD >>inv Operating time (t PD >>inv) 0.02...60.0 s 67N Third threshold definite time (IED >>> def - UED >>> def )
• Residual current pickup value 0.002...10.00 IEn
IPD>>> Element • Residual voltage pickup value 0.004...0.500 UEn
• IPDCLP >>> Activation time (t PDCLP>>>) 0.00...100.0 s • Characteristic angle 0...359°
• IPD>>> Reset time delay (t PD >>> RES) 0.00...100.0 s • Half operating sector 1...180°
Definite time • IED >>> def within CLP (IEDCLP >>> def ) 0.002...10.00 IEn
• 67 Third threshold definite time (IPD >>> def ) 0.100...40.0 In • IED >>> def Operating time (t ED >>> def ) 0.05...10.00 s
• IPD >>> def characteristic angle (ThetaPD>>>def ) 0...359°
• IPD >>> def within CLP (IPDCLP>>>def ) 0.100...40.0 In IED>>>> Element
• IPD >>> def Operating time (t PD >>> def ) 0.04...10.00 s • IEDCLP >>>> Activation time (t EDCLP>>>>) 0.00...100.0 s
• IED>>>> Reset time delay (t ED >>>> RES) 0.00...100.0 s
IPD>>>> Element Definite time
• IPDCLP >>>> Activation time (t PDCLP>>>>) 0.00...100.0 s 67N Fourth threshold definite time (IED >>>> def - UED >>>> def )
• IPD>>>> Reset time delay (t PD >>>> RES) 0.00...100.0 s • Residual current pickup value 0.002...10.00 IEn
Definite time • Residual voltage pickup value 0.004...0.500 UEn
• 67 Fourth threshold definite time (IPD >>>> def ) 0.100...40.0 In • Characteristic angle 0...359°
• IPD >>>> def characteristic angle (ThetaPD>>>>def ) 0...359° • Half operating sector 1...180°
• IPD >>>> def within CLP (IPDCLP>>>>def ) 0.100...40.0 In • IED >>>> def within CLP (IEDCLP >>>> def ) 0.002...10.00 IEn
• IPD >>>> def Operating time (t PD >>>> def ) 0.04...10.00 s • IED >>>> def Operating time (t ED >>>> def ) 0.05...10.00 s
NVA100 - Flyer- 10 - 2012 7
— Underfrequency - 81U — Internal selective block - BLOCK4
f< Element • Output internal selective block dropout time for phase protec-
Definite time tions (t F-IPh) 0.00...10.00 s
• 81U First threshold definite time (f<def) 0.800...1.000 fn • Output internal selective block dropout time for ground protec-
• f<def Operating time (t f<def ) 0.05...100.0 s tions (t F-IE ) 0.00...10.00 s
f<< Element
— Breaker failure - BF
Definite time
BF Phase current threshold (IBF >) 0.05...1.00 In
• 81U Second threshold definite time (f<def) 0.800...1.000 fn
BF Residual current threshold (IEBF >) 0.01..2.00 IEn
• f<def Operating time (t f<def ) 0.05...100.0 s
BF Time delay (t BF) 0.06...10.00 s
f<<< Element
Definite time — Second Harmonic Restraint - 2ndh-REST
• 81U Third threshold definite time (f<def) 0.800...1.000 fn Second harmonic restraint threshold (I2ndh>) 10...50 %
• f<def Operating time (t f<def ) 0.05...100.0 s I2ndh> Reset time delay (t 2ndh>RES) 0.00...100.0 s
f<<<< Element
— VT supervision - 74VT
Definite time
• 81U Fourth threshold definite time (f<def) 0.800...1.000 fn 74VT Negative sequence overvoltage threshold (U2VT>) 0.05...0.50 En
• f<def Operating time (t f<def ) 0.05...100.0 s 74VT Negative sequence overvoltage threshold (I2VT>) 0.05...0.50 In
74VT Phase undervoltage threshold (U VT<) 0.05...0.50 En
— Overfrequency - 81O 74VT Minimum change of current threshold 74VT (DIVT<) 0.05...0.50 In
f> Element 74VT Undercurrent inhibition threshold (I VT<) 0.100...40.0 In
Definite time 74VT Alarm time delay (t V T-A L ) 0.0...10.0 s
• 81O First threshold definite time (f>def) 1.000....1.200 fn
• f>def Operating time (t f> def ) 0.05...100.0 s — CT supervision - 74CT
f>> Element 74CT Threshold (S<) 0.10...0.95
Definite time 74CT Overcurrent threshold (I * ) 0.10...1.00 I n
• 81O Second threshold definite time (f>>def) 1.000....1.200 fn S< Operating time (t S <) 0.03...200 s
• f>>def Operating time (t f>> def ) 0.05...100.0 s
— Circuit Breaker supervision
— Frequency rate of change - 81R Number of CB trips (N.Open) 0...10000
df> Element Cumulative CB tripping currents (SumI) 0...5000 In
• df> Operating mode (df >mode) Module/Positive/Negative CB opening time for I^2t calculation (t break ) 0.05...1.00 s
Definite time Cumulative CB tripping I^2t (SumI^2t) 0...5000 I n2.s
• 81R First threshold definite time (df > def) 0.1...10.0 Hz/s CB max allowed opening time (t break >) 0.05...1.00 s
• df> def Operating time (tdf > def) 0.00...100.0 s
— Pilot wire diagnostic
df>> Element BLOUT1 Diagnostic pulses period (PulseBLOUT1)
• df>> Operating mode (df>>mode) Module/Positive/Negative OFF - 0.1-1-5-10-60-120 s
Definite time BLIN1 Diagnostic pulses control time interval (PulseBLIN1)
• 81R First threshold definite time (df > def) 0.1...10.0 Hz/s OFF - 0.1-1-5-10-60-120 s
• df>> def Operating time (tdf>> def) 0.00...100.0 s
— Demand measures
df>>> Element Fixed demand period (t FIX ) 1...60 min
• df>>> Operating mode (df>>>mode)Module/Positive/Negative Rolling demand period (t ROL ) 1...60 min
Definite time Number of cycles for rolling on demand (N.ROL ) 1...24
• 81R First threshold definite time (df>>> def) 0.1...10.0 Hz/s
• df>>> def Operating time (tdf>>> def) 0.00...100.0 s METERING & RECORDING
df>>>> Element
• df>>>> Operating mode (df>>>>mode)Module/Positive/Negative — Measured parameters
Definite time Direct:
• 81R First threshold definite time (df>>>> def) 0.1...10.0 Hz/s • Frequency f
• df>>>> def Operating time (tdf>>>> def) 0.00...100.0 s • Fundamental RMS phase currents I L1, I L 2 , I L 3
• Fundamental RMS phase voltages U L1, U L 2 , U L 3
— Vector jump • Fundamental RMS residual current and voltage IE, UE
DPHI> Element Calculated:
dphi> Operating mode (Mode-dphi>) Module/Positive/Negative • Thermal image DTheta
Definite time • Flux Umax/f U /f
dphi> First threshold (dPHI>def ) 1...30 ° • Fundamental RMS phase-to-phase voltages U 12 , U 23 , U 31
dphi> Reset time delay (dPHI>RES) 0.00...100.0 s • Fundamental RMS calculated residual voltage U EC
— Auto-reclose - 79 • Maximum current between I L1-I L 2 -I L 3 I Lmax
79 Function mode (79 Mode) Rapid/Rapid+Slow • Minimum current between I L1-I L 2 -I L 3 I Lmin
Number of delayed reclosures (N.DAR) 0...5 • Average current between I L1-I L 2 -I L 3 IL
Rapid reclosure dead time (t rdt) 0.1...60 s • Maximum voltage between U L1-U L 2 -U L 3 U Lmax
Slow reclosure dead time (t sdt) 1...200 s • Average voltage between U L1-U L 2 -U L 3 UL
Reclaim time (t r) 1...200 s • Maximum voltage between U 12 -U 23 -U 31 U max
Slow reclosure fault discrimination time (t d1) 0...10 s • Average voltage between U 12 -U 23 -U 31 U
Delayed reclosure fault discrimination time (t d2) 0...10 s • Frequency rate of change df /dt
Manual close (R+S only) fault discrimination time (t d) 1...10 s Displacement:
• Displacement angle of I L1 respect to U L1 PhiL1
— Selective block - BLOCK2 • Displacement angle of I L 2 respect to U L 2 PhiL2
Selective block IN: • Displacement angle of I L 3 respect to U L 3 PhiL3
• BLIN Max activation time for phase prot. (t B-IPh) 0.10...10.00 s • Displacement angle of I L1 respect to U 23 Alpha1
• BLIN Max activation time for ground prot. (t B-IE ) 0.10...10.00 s • Displacement angle of I L 2 respect to U 31 Alpha2
Selective block OUT: • Displacement angle of I L 3 respect to U 12 Alpha3
• BLOUT Dropout time delay for phase elements (t F-IPh) 0.00...1.00 s • Displacement angle of U E respect to I E PhiE
• BLOUT Dropout time delay for ground elements (t F-IE ) 0.00...1.00 s • Displacement angle of U EC respect to I E PhiEC
• BLOUT Dropout time delay for all elements (t F-IPh/IE) 0.00...1.00 s
8 NVA100 - Flyer- 10 - 2012
Sequence: • Fundamental RMS residual current I Er
• Positive sequence current I1 • Fundamental RMS phase voltages U L1r, U L 2r, U L 3r
• Negative sequence current I2 • Fundamental RMS phase-to-phase voltages U 12r, U 23r, U 31r
• Negative sequence current/positive sequence current ratio I 2 /I 1 • Fundamental RMS residual voltages U Er, U ECr
• Positive sequence voltage U1 • Displacement angles (IL1-UL1, IL2-UL2, IL3-UL3) PhiL1r, PhiL2r, PhiL3r
• Negative sequence voltage U2 • Displacement angles (IL1-U23, IL2-U31, IL3-UL3) Alpha1r, Alpha2r, Alpha3r
Power: • Displacement angle (UE-IE) PhiEr
• Total active power P • Displacement angle (UEC-IE) PhiECr
• Total reactive power Q • Negative sequence current I2r
• Total apparent power S • Negative sequence current/positive sequence current ratio I2/I1r
• Power factor cosPhi • Positive sequence voltage U1r
• Phase active powers P L1, P L 2 , P L 3 • Negative sequence voltage U2r
• Phase reactive powers Q L1, Q L 2 , Q L 3 • Thermal image DTheta- r
• Power factors cosPhiL1, cosPhiL2, cosPhiL3 • Flux Umax/f U/fr
• Total active power Pr,
2nd harmonic: • Total reactive power Qr
• Second harmonic phase currents I L1-2nd , I L 2-2nd , I L 3-2nd • Power factor CosPhi
• Maximum of the second harmonic phase currents/fundamen- • Frequency fr
tal component percentage ratio I -2nd /I L • Frequency rate of change df/dtr
3rd harmonic: • Binary inputs state IN1, IN2...INx
• Third harmonic phase currents I L1-3rd , I L 2-3rd , I L 3-3rd • Output relays state K1...K6...K10
• Third harmonic residual current I E-3rd • Fault cause info (operating phase) L1, L2, L3
• Third harmonic residual voltage U E-3rd
4th harmonic: — Digital Fault Recorder (DFR)
• Fourth harmonic phase currents I L1-4th , I L 2-4th , I L 3-4th File format COMTRADE
Records depending on setting [1]
5th harmonic: Recording mode circular
• Fifth harmonic phase currents I L1-5th , I L 2-5th , I L 3-5th Sampling rate 24 samples per cycle
Demand phase: Trigger setup:
• Phase fixed currents demand I L1FIX , I L 2FIX , I L 3FIX • Pre-trigger time 0.05...1.00 s
• Phase rolling currents demand I L1ROL , I L 2ROL , I L 3ROL • Post-trigger time 0.05...60.00 s
• Phase peak currents demand I L1MA X , I L 2MA X , I L 3MA X • Trigger from inputs IN1, IN2...INx
• Phase minimum currents demand I L1MIN , I L 2MIN , I L 3MIN • Trigger from outputs K1...K6...K10
Demand power: • Manual trigger ThySetter
• Fixed active power demand P FIX Set sample channels:
• Fixed reactive power demand Q FIX • Instantaneous currents i L1, i L2, i L3, i E
• Rolling active power demand P ROL • Instantaneous voltages u L1, u L2, u L3, u E
• Rolling reactive power demand Q ROL
• Peak active power demand P MA X Set analog channels (Analog 1...12):
• Peak reactive power demand Q MA X • Frequency f
• Minimum active power demand P MIN • Fundamental RMS phase currents I L1, I L 2 , I L 3
• Minimum reactive power demand Q MIN • Fundamental RMS residual current IE
• Fundamental RMS phase voltages U L1, U L 2 , U L 3
Energy: • Fundamental RMS residual voltage UE
• Positive a active energy EA+ • Fundamental RMS phase-to-phase voltages U 12 , U 23 , U 31
• Negative active energy EA- • Fundamental RMS calculated residual voltage U EC
• Total active energy EA • Displacement angles (IL1-UL1, IL2-UL2, IL3-UL3) PhiL1, PhiL2, PhiL3
• Positive reactive energy EQ+ • Displacement angles (IL1-U23, IL2-U31, IL3-UL3) Alpha1, Alpha2, Alpha3
• Negative reactive energy EQ- • Displacement angle (UE-IE) PhiE
• Total reactive energy EQ • Displacement angle (UEC-IE) PhiEC
• Positive sequence current I1
— Event recording (SER) • Negative sequence current I2
Number of events 300
• Negative sequence current/positive sequence current ratio I2/I1
Recording mode circular
• Positive sequence voltage U1
Trigger: • Negative sequence voltage U2
• Start/Trip of enabled protection or control element • Total active power P
• Binary inputs switching (OFF/ON or ON/OFF) IN1...INx • Total reactive power Q
• Setting changes • Total apparent power S
• Auxiliary supply Power UP/Power DOWN • Total power factor CosPhi
Data recorded: • Second harmonic phase currents I L1-2nd , I L 2-2nd , I L 3 -2nd
• Counter (resettable by ThySetter) 0...10 9 • Maximum of the second harmonic phase currents/fundamen-
• Cause binary input/trip/setting change/Power ON/OFF tal component percentage ratio I -2nd /I L
• Time stamp Date and time • Frequency rate of change df/dt
• Temperature T1...T8
— Fault recording (SFR) Set digital channels (Digital 1...12):
Number of faults 20
• Output relays state K1...K6...K10
Recording mode circular
• Binary inputs state IN1, IN2...INx
Trigger:
Note 1 - For instance, with following setting:
• Output relays of enabled protection or control element (OFF-ON) • Pre-trigger time 0.25 s
• External trigger (binary inputs) IN1...INx • Post-trigger time 0.25 s
Data recorded: • Sampled channels i L1, i L2 , i L3 , i E , u L1, u L2 , u L3 , u E
• Counter (resettable by ThySetter) 0...10 9 • Analog channels I L1, I L2 , I L3 , I E , U L1, U L2 , U L3 , U E
• Time stamp Date and time • Digital channels K1, K2, K3, K4, K5, K6, IN1, IN2
• Cause tripped element about 100 records can be stored with f=50 Hz
• Fundamental RMS phase currents I L1r, I L2r, I L3r
NVA100 - Flyer- 10 - 2012 9
— Protective functions

L1
L2 BUSBAR
L3
NVA100

74TCS 79
50/51, 67
(*) Antiferrorisonance
50N/51N, 67N
dn da
dn db B7
dn dc (*) UE 59N
B8

A N n a B1
B N n b UL1
B2
C N n c
B3
74VT
UL2
B4
B5 32P 24
UL3
B6
32Q 27

37P 59

37Q 59V1

26 50/51 59V2

55 81U

67 81U

P1 C1
49 81R
S1
IL1
S2 C2
P2 I2/I1 DPHI
C3
IL2 74CT 46
C4
C5
IL3
C6
BF
OPERATION (**)

P1 C7
S1
IE 50N/51N 67N
S2 C8
P2
BINARY INPUTS

CB position

LINE (***)

(**) OPERATION FOR:


- 67 elements with characteristic angle adjusted within 0°... 90° or 270° ...359° ranges
- 67N elements for insulated neutral systems and characteristic angle setting = 90°
(***) MEASUREMENTS:
- Positive sign for measurement of active power and energy with passive load
- Negative sign for measurement of active power and energy with generators

10 NVA100 - Flyer- 10 - 2012


— Connection diagram example

L1
L2 BUSBAR
L3
A

dn
NVA100

da

K1 A3
a B1 A4
U L1 A5
B2
K2 A6
B3
A7
VOLTAGE INPUTS

U L2 A8
OUTPUT RELAYS
B4
B5 K3 A9
U L3 A10
B6 K4
B7
A11
R (*) B8 UE K5 A12

K6 A13
(*) Antiferrorisonance A14

F1
F2
P1 C1
RS485

F3
S1
I L1 F4
S2 C2 B-
Supervision
F5
P2
C3 A+
unit
CURRENT INPUTS

I L2
C4
C5
ETHERNET

I L3 D1
C6 HUB
P1 C7
S1
IE
S2 C8
P2
THYBUS

E1

A1 ≅
UAUX
A2
BLOCK OUT
BLOCK IN

BLOUT-
A17 A15
BLOUT+
A18 A16
OPERATION (**)
67, 67N

BINARY INPUTS

A19 FRONT PANEL


IN1
RS232

A20
A21
IN2
A22

LINE(***)

(**) OPERATION FOR:


- 67 elements with characteristic angle adjusted within 0°... 90° or 270° ...359° ranges
- 67N elements for insulated neutral systems and characteristic angle setting = 90°
(***) MEASUREMENTS:
- Positive sign for measurement of active power and energy with passive load
- Negative sign for measurement of active power and energy with generators

NVA100 - Flyer- 10 - 2012 11


DIMENSIONS
FRONT VIEW REAR VIEW
128.5
107 120 101 ø 4.5 110

D1 D1

A1 A1
A2 A2
C1 C2 C1 C2

ø 4.5 A3
A4 RX
F1
F2
A3
A4 RX
F1
F2
A5 F3 A5 F3
A6 TX F4 A6 TX F4
A7 F5 A7 F5
A8 C3 C4 A8 C3 C4
A9 B1 A9 B1
A10 B2 A10 B2
177

171
149

200
168
A11 B3 A11 B3
A12 B4 A12 B4
ON 1 2 3 4 5 START ON 1 2 3 4 5 START
A13 B5 A13 B5
80

TRIP TRIP A14 C5 C6 B6 A14 C5 C6 B6


A15 B7 A15 B7
A16 B8 A16 B8

A17 A17
A18 A18
A19 A19
A20 C7 C8 A20 C7 C8

A21 A21
A22 A22
31

E1 E1

20
FLUSH MOUNTING PROJECTING MOUNTING FLUSH MOUNTING PROJECTING MOUNTING
(Separate operator panel)

SIDE VIEW

212.5 275
25 15
205 30 5 30 ø 4.5
170

FLUSH MOUNTING SEPARATE PROJECTING MOUNTING PROJECTING MOUNTING


OPERATOR PANEL (Separate operator panel) (Stand alone)

RACK MOUNTING FLUSH MOUNTING CUTOUT

482.6 102.5 ±0.3


465 70
177 (4U)

161
101.6

154

ON 1 2 3 4 5 START ON 1 2 3 4 5 START ON 1 2 3 4 5 START ON 1 2 3 4 5 START

TRIP TRIP TRIP TRIP

N.4 holes ø 3.5

Headquarters: 20139 Milano - Piazza Mistral, 7 - Tel. +39 02 574 957 01 ra - Fax +39 02 574 037 63
Factory: 35127 Padova - Z.I. Sud - Via dell’Artigianato, 48 - Tel. +39 049 894 770 1 ra - Fax +39 049 870 139 0

www.thytronic.it www.thytronic.com thytronic@thytronic.it

S-ar putea să vă placă și