“Something better than protective relays”

PROTECTION RELAY
Auxiliary boards

—— General
The hardware resources of the Pro-NX devices are easily upgradable by means of auxiliary modules.
Without additional modules the protection relays are equipped with a board with sixteen digital inputs (IN1) and
a board with eight output relays (OC1).
Various installation requirements can be adapted by the inclusion of:
• one OC2 board with eight output relays,
• one IN2 board with sixteen binary inputs,
• one CL board with six current loop converters,
• one RTD board with eight RTD inputs (Pt100 probes),
• one IRIG-B board.
• a AUX-IN external board
• a M-REF external board for 64F function

Modules-Pro-NX - Flyer - 02 - 2018


GENER A L T ECHNICA L DATA
—— Mechanical data —— Climatic tests
Mounting pcb board Reference standards IEC 60068-x, ENEL R CLI 01, CEI 50
Dimensions 175 x 150 mm
—— Mechanical tests
—— Insulation tests Reference standards EN 60255-21-1, 21-2, 21-3
Reference standards EN 60255-5
High voltage test 50 Hz 2 kV 60 s —— Safety requirements
Impulse voltage withstand (1.2/50 ms) 5 kV Reference standards EN 61010-1
Insulation resistance >100 MW Pollution degree 3
Reference voltage 250 V
—— Voltage dip and interruption Overvoltage III
Reference standards EN 61000-4-29 Pulse voltage 5 kV

—— EMC tests for interference immunity —— Environmental conditions


1 MHz damped oscillatory wave EN 60255-22-1 1 kV-2.5 kV Ambient temperature -25...+70 °C
Electrostatic discharge EN 60255-22-2 8 kV Storage temperature -40...+85 °C
Fast transient burst (5/50 ns) EN 60255-22-4 4 kV Relative humidity 10...95 %
Conducted radio-frequency fields EN 60255-22-6 10 V Atmospheric pressure 70...110 kPa
Radiated radio-frequency fields EN 60255-4-3 10 V/m
High energy pulse EN 61000-4-5 2 kV —— Certifications
Magnetic field 50 Hz EN 61000-4-8 1 kA/m Product standard for measuring relays EN 50263
Damped oscillatory wave EN 61000-4-12 2.5 kV CE conformity
Ring wave EN 61000-4-12 2 kV • EMC Directive 2004/108/EC
Conducted common mode (0...150 kHz) EN 61000-4-16 10 V • Low Voltage Directive 2006/95/EC
Type tests IEC 60255-6
—— Emission
Reference standards EN 61000-6-4 (ex EN 50081-2)
Conducted emission 0.15...30 MHz Class A
Radiated emission 30...1000 MHz Class A

DIMENSIONS
173
150

ON
OFF
1

Board address

2 Modules-Pro-NX - Flyer - 02 - 2018


8 r elay s m odule O U T 2
—— General
In order to increase the number of logic inputs the Pro_NX pro-
tection relays can be equipped with the OUT2 module.
Eight output relays are available (KC2-1...KC2-8).

OUTPUT CIRCUITS
—— Output relays
Quantity 8
Type of contacts changeover (SPDT, type C)
Nominal current 8A
Nominal voltage/max switching voltage 250 Vac/400 Vac
Breaking capacity:
• Direct current (L/R = 40 ms) 50 W
• Alternating current (l = 0,4) 1250 VA
• Make 1000 W/VA
Short duration current (0,5 s) 30 A
ON

Board address
OFF
1

OC1E OC2F Optional board


1 1
KC1-1 3 KC2-1 3
2 2
4 4
KC1-2 6 KC2-2 6
IN1C OC2F OC1E
5 5
7 7
KC1-3 KC2-3
8 8
9 9
KC1-4 KC2-4
10
OUTPUT RELAYS

10
OUTPUT RELAYS

11 11
KC1-5 KC2-5
12 12
13 13
KC1-6 KC2-6
14 14
15 15
KC1-7 17 KC2-7 17
16 16
18 18
KC1-8 20 KC2-8 20
19 19

Standard board Optional board

Modules-Pro-NX - Flyer - 02 - 2018 3


16 binar y inpu t s m odule I N 2
—— General
In order to increase the number of logic inputs the Pro_NX pro-
tection relays can be equipped with the IN2 module.
The input circuits are voltage-free; activation requires the appli-
cation of a power source, preferably the same auxiliary voltage
present in the switchboard.
The inputs are dimensioned for a wide range of operation and
does not require any hw and / or sw programming; the switching
threshold is 20 Vcc/15 Vac.
An AUX-IN external modules (see next page) allow the thresh-
olds setting for the binary inputs activation so that the command
voltage is comparable to the supply voltage.

INPUT CIRCUITS
—— Binary inputs
Quantity 16
Type dry inputs
Max permissible voltage 19...265 Vac/19...300 Vdc
Max consumption, energized 3 mA
Activation threshold 15 V or 55 V with jumper
Max consumption, energized 3 mA

Board address

ON
OFF
1

8
+UAUX IN1C IN2D
1
1
A B IN1-1 IN2-1

2 2
IN1-2 IN2-2

3 3
-UAUX IN1-3 IN2-3

4 4
Optional board 5 IN1-4 IN2-4
5
7 7
IN1-5 IN2-5

8 8
IN1-6 IN2-6
IN2D IN1C OC1E
9 9
IN1-7 IN2-7

10 10
IN1-8 IN2-8
BINARY INPUTS

BINARY INPUTS

6 6
11 11
IN1-9 IN2-9

12 12
IN1-10 IN2-10

13 13
IN1-11 IN2-11

14 14
IN1-12 IN2-12
15 15
17 17
IN1-13 IN2-13

18 18
IN1-14 IN2-14

19 19
IN1-15 IN2-15

20 20
IN1-16 IN2-16
16 16

Standard board Optional board

4 Modules-Pro-NX - Flyer - 02 - 2018


A U X- I N ex t er nal boar d
—— Threshol setting —— Mechanical data
AUX-IN external modules, coupled with the Pro-NX protection Mounting: direct on Pro-NX terminal board
relay, allow the thresholds setting for the binary inputs activa- Fixing 3MA screws
tion. Mass (flush mounting case) 150 g
The binary inputs switching threshold can be set during instal-
lation so that the command voltage is comparable to the supply —— Binary inputs
voltage. Quantity 16
The change on switching threshold of a binary input can be car- Max permissible voltage 19...265 Vac/19...300 Vdc
ried out by means of dip switches (externally accessible) and Switching threshold set by dip-swithes and jumpers
jumpers (accessible after removing the metal housing). • ON 110V 82...84 Vdc/61...63 Vac
• ON 230V 200...204 Vdc/144...147 Vac
• ON 230V + jumper 20 Vdc/15 Vac

24 V

IN1
110 V

230 V

IN1 threshold Setting


230 V
X10
24 V O
N
110 V
IN1
IN2
IN3
IN4

230 V
X10
110 V O
N
110 V
IN1
IN2
IN3
IN4

230 V
X10
230 V O
(Default) N
110 V
IN1
IN2
IN3
IN4

With jumpers X10 ... X25 positioned as illustrated in the figure (factory default), the switching
thresholds can be set to:
- 110 V (dip ON),
- 230 V (dip OFF)

Modules-Pro-NX - Flyer - 02 - 2018 5


M - R E F ex t er nal boar d
—— General setting —— Rotor earth fault input circuit
A 50 Hz or 60 Hz voltage is applied in the field circuit of the alter- Max voltage 600 Vdc +10%
nator and a ground; in the absence of earth fault (RF = ∞) only a Max alternating component 100 Vac
few mA current is established in the circuit through the capaci- Max rotor earth capacitance 2 μF
ties between the field circuit and the earth. In case of earth fault, Auxiliary power supply 110, 230 Vac 50 Hz
the current increases in inverse proportion to the value of fault —— Rotor earth fault (64F)
resistance. With reference to the simplified diagram shown in Pickup RFAL<, RF<< 0.50...5.00 kΩ steps 0.01 kΩ
the drawing, by calculating the ratio UF/IRF is obtained by mea- Time delays tRFAL<, tRF<< (definite time) 0.07...100.0 s
suring the insulation resistance to ground RF circuit excitation.
(0.07...9.99 s steps 0.01 s,
Using M-REF module, connected to the reserved pin on the
10.0...100.0 s steps 0.1 s)
NVA100X-G (since 3.00 sw. version), Rotor earth fault protection Pickup times 0.05 s
can be implemented. Dropout ratio 1.02...1.05
Dropout time 0.08 s
—— Mechanical data Overshoot time 0.03 s

Mounting: direct or DIN rail Reference values rest: R= ∞
Fixing 4MA screws operation: 2/3 R FAL<, R F<<
Mass 2500 g
Pickups accuracy ± 3% + 20 Ω
Time delays accuracy ± 1% ± 8 ms

ProNext Input Blocks

250

M4 M4

86

M4
M4

Modules-Pro-NX - Flyer - 02 - 2018 6


L1
NVA100X-G
L2
L3

GS L+

L-

Rotor Ground

L+ L-
M-REF TO ROTOR

MB MA

1 2 1 2 3 4 5 6

UAUX 64F = 110V~ UAUX 64F = 230V~

MA-1 MA-1

MA-2 MA-2

MA-3 MA-3
230V~

MA-4 MA-4

MA-5 MA-5
110V~

MA-6 MA-6

Wiring diagram of M-REF module related to the functions 64F in the ProNext NVA100X-G relay.
Wiring have to be made according to the Uaux voltage.

Modules-Pro-NX - Flyer - 02 - 2018 7


P t 10 0 I N P U T BOA R D R T D
—— General INPUT CIRCUITS
In order to direct-measurement of temperature the Pro_NX re-
lays can be customized through external auxiliary RTD module. —— RTD inputs
Eight Pt100 inputs are acquired to provide thermal protective Quantity 8
functions. Range - 40...+ 240 °C
The Pt100 sensors (‘Pt’ is the symbol for platinum) are the most Measuring current 1 mA
common devices used in industry have a nominal resistance of Refresh interval 0.25 s
100 ohms at 0 °C. Pt100 lead resistance (max per lead) 10 W
In order to compensate the additional resistance introduced by
the cables, three wires connection is recommended (example 1);

ON
with only two terminals, probes you must use a shielded cable
with three conductors carrying the schematic example 2 (Pt100

OFF
connected to RTD2 in the above figure).

8
However it is essential that the link between Terminal A and Ter-
minal B is made with cables of the same type (RL1 = RL2 = RL3).
Board address
For very short connections, two wires (Pt100 connected to RTD8
example 3) are permitted; the non-compensated resistance con-
nections resulting in an error proportional to the value of intro-
duced resistance.
The connection to the probes must be made with three conduc-
tors shielded cables and the screen should be earthed only at
one end, preferably on the relay; multiple connections may re-
sult in current circulation on the screen resulting noise on the
measure and are therefore to avoid.
It is recommended to position connections to the probe away
from power lines to avoid interference.

Optional board

In 5A 1A 5A UE 100V

RTD G I E 1A 1A 5A Un
UAUX 110-230 Vac/dc
100V
RTD G IN1C OC1E
NVA100-DX#MM00
PT1
G1
MPT1
G2
GND1 T1
G3
PT2
G4
MPT2
G5
GND2
PT100 INPUTS

G6 T2
PT3
G7
MPT3
G8
GND3 T3
G9
PT4
G10
MPT4
G11
GND4 T4
G12
PT5
G13
MPT5
G14
GND5 T5
G15
PT6
G16

G17
MPT6 A B
GND6 T6
PT1
G18
Example 1 MPT1 T1
PT100 INPUTS

PT7
G19
MPT7
G20 A B
GND7
G21 T7 PT2
G22
PT8
Example 2 MPT2 T2
MPT8
G23
GND8 T8
G24 T3...T7

PT8
Example 3 MPT8 T8

8 Modules-Pro-NX - Flyer - 02 - 2018


C L C u r r en t loop con ver t er
—— General OUTPUT CIRCUITS
In order to extend input capability the Pro_NX relays can be
customized through internal auxiliary CL module which include 6 —— Current converter
current loop converter outputs. Quantity 6
All the six converters are independently configurable in the fol- Output range (Loop1-Range...Loop6-Range):
lowing ranges: 0-5 mA, 0-20 mA
• 0-5 mA, 0-20 mA 4-20 mA
• 4-20 mA Max output current ± 22 mA
The following settings are user programmable: Type (Loop1-Type...Loop6-Type) Unipolar - Bipolar
• the coupling of the input measures Multiplier (Loop1-M... (Loop6-M) 0.01...100.00
• the type of the output signals (unipolar - bipolar) Polarity (Loop1-Polarity...Loop6-Polarity) Normal-Inverse
• the multiplier of the nominal (multiple of input, expressed as Resolution 2.5 μA
p.u. of nominal value whereby the converter output provides Accuracy 0.1% ± 5 μA
the full scale value set)
• the polarity of the output signals (Normal - Inverse)
Loop1-Type = Bipolar
LOAD NVA100X LOAD NVA100X
Terminals A1-A3-A5 Terminals A1-A3-A5
Loop1-Type = Unipolar I L1 I L1
I L2 I L1, I L2, I L3 I L2 I L1, I L2, I L3
I L3 I L3
LOAD NVA100X LOAD NVA100X Terminals B3-B5-B7 Terminals B3-B5-B7
Terminals A1-A3-A5 Terminals A1-A3-A5
I L1 U L1 U L1, U L2, U L3 U L1 U L1, U L2, U L3
I L1
I L2 I L2 I L1, I L2, I L3 U L2 U L2
I L1, I L2, I L3
I L3 I L3 U L3 U L3
Terminals B3-B5-B7 Terminals B3-B5-B7 mA
U L1 U L1, U L2, U L3 U L1 U L1, U L2, U L3 20
U L2 U L2
U L3 U L3

mA
10
20
4

10 -2 -1 0 1 2 P(Pn)
-4

4 -10

-2 -1 0 1 2 P(Pn)

-20

CL H OUTPUT MODULE Optional board


+ H1
MIS-1 # / ∩ -
H2
H3 In 5A 1A 5A UE 100V

H4 I E 1A 1A 5A Un
UAUX 110-230 Vac/dc
100V
CL H IN1C OC1E
H5 NVA100-DX#MM00
MIS-2 #/∩ -
H6
H7
H8
+ H9
MIS-3 #/∩ -
H10

+ H11
MIS-4 #/∩ -
H12
H13
H14
+ H15
MIS-5 #/∩ -
H16
H17
H18
+ H19
MIS-6 #/∩ -
H20

Modules-Pro-NX - Flyer - 02 - 2018 9


I R IG - B boar d I R B
—— General I/O CIRCUITS
In addition to time synchronization protocol using the SNTP pro-
tocol (Simple Network Time Protocol) over Ethernet network, Voltage levels:
the Pro_NX protection devices can be equipped with the IRIG-B • AM IRIG-B IN Max 12 Vpp
module (Inter-Range Instrumentation Group). • IRIG-B / 1PPS IN (Multiplexed) 5 V TTL
• IRIG-B OUT 5 V TTL
• 1PPS OUT 5 V TTL

Delays:
• 1PPS IN (X3) to 1PPS OUT (X5) <50 ns
• Unmodulated IRIG-B IN to 1PPS OUT <50 ns
• Modulated AM IRIG-B IN to 1PPS out <20 μs
• 1PPS OUT: Normally low
Active for 8 ms

Optional board

In 5A 1A 5A U En 100V

IRB I IN1C OC1E


I En 1A 1A 5A Un 100V
UAUX 110-230 Vac/dc

NVA100-DX#MM00 AM IRIG-B IN

IRIG-B/
1PPS IN

1PPS OUT

IRIG-B OUT

8
X1 IN AM IRIG-B IN
Modulated IRIG-B input (IRIG-B12#)
Board address
1 X3 IN IRIG-B IN / 1PPS IN
ON OFF Digital IRIG-B input (IRIG-B00#)
Digital input 1PPS (must be used with AM IRIG-B IN

X5 OUT 1PPS OUT


1PPS output

X7 OUT IRIG-B OUT


IRIG-B digital output

10 Modules-Pro-NX - Flyer - 02 - 2018


First optional module Second optional module CODE

None NVA100X # 0 0

OC2 NVA100X # 0 1

None RTD NVA100X # 0 2

IRB NVA100X # 0 3

CL NVA100X # 0 4

None NVA100X # 1 0

OC2 NVA100X # 1 1

IN2 RTD NVA100X # 1 2

IRB NVA100X # 1 3

CL NVA100X # 1 4

None NVA100X # 2 0

OC2 NVA100X # 2 1
RTD
IRB NVA100X # 2 3

CL NVA100X # 2 4

None NVA100X # 3 0

OC2 NVA100X # 3 1
IRB
RTD NVA100X # 3 2

CL NVA100X # 3 4

Note: the codes for optional modules are highlighted (red); for the complete coding please refer to the full encoding document

Headquarters: 20139 Milano - Piazza Mistral, 7 - Tel. +39 02 574 957 01 ra - Fax +39 02 574 037 63
Factory: 35127 Padova - Z.I. Sud - Via dell’Artigianato, 48 - Tel. +39 049 894 770 1 ra - Fax +39 049 870 139 0

www.thytronic.it www.thytronic.com thytronic@thytronic.it


OPTIONAL MODULES

NVA100X # 0 0

Versione / Type
Base / Basic B
Tensione-Frequenza / Voltage-Frequency V

Potenza / Power P
Motore-Generatore / Motor-Generator G

Banchi Condensatori / Bank Capacitor C

Mot.-Gen.-Trasf. con Differenziale / Mot.-Gen.-Transf. with Differential D


Differenziale Trasformatore / Transformer Differential T

Alimentazione / Auxiliary power supply


Alimentazione ausiliaria 24-48V / 24-48V auxiliary power supply 1

Alimentazione ausiliaria 110-230V / 110-230V auxiliary power supply 2

Tensione di riferimento / Secondary reference voltage


Versione ThySensor / ThySensor version (1) 0

100 V / 100 V J
400 V / 400 V U

Primo modulo opzionale / First option module


Nessuno / None 0

IN2 Modulo 16 ingressi digitali / IN2 16 binary inputs module 1

RTD Modulo 8 ingressi PT100 / RTD 8 PT100 inputs module 2

IRB Modulo sincronizzazione temporale IRIG-B / IRB IRIG-B time syncronization module 3

Secondo modulo opzionale / Second option module


Nessuno / None 0

OC2 Modulo 8 uscite relè comando / OC2 8 command relays ouputs module 1

RTD Modulo 8 ingressi PT100 / RTD 8 PT100 inputs module 2


IRB Modulo sincronizzazione temporale IRIG-B / IRB IRIG-B time syncronization module 3

CL Modulo 6 uscite corrente 4÷20mA / CL 6 current loop 4÷20mA outputs module 4

Optional modules

In 5A 1A 5A U En 100V
I En 1A 1A 5A Un 100V
UAUX 110-230 Vac/dc IN1C OC1E
NVA100X#JA2MM00

B
A

10

16 binary inputs 8 Output relays

Modules-Pro-NX - Flyer - 02 - 2018 12