Sunteți pe pagina 1din 21

Designing for

High-Voltage dc
Grid Protection

©istockphoto.com/iskrinka74
Fault Clearing
Strategies
and Protection
Algorithms

P
Protecting HigH-VoLtAge (HV) Dc griDs requires A Differ-
ent approach compared with that of ac power system protection and poses one
of the major challenges that must be resolved before the realization of large-
scale HVdc grids that use equipment from multiple vendors. HVdc grid pro-
tection, which is essential for safe and reliable HVdc grid operation, entails the
appropriate detection and fault clearing of dc-side short circuit faults (i.e., dc
faults). in this context, fault clearing refers to interrupting the dc fault current
and isolating the faulted component. fault current interruption is much more

By Willem Leterme, Ilka Jahn, Philipp Ruffing,


Kamran Sharifabadi, and Dirk Van Hertem
Digital Object Identifier 10.1109/MPE.2019.2897188
Date of publication: 17 April 2019

may/june 2019 1540-7977/19©2019IEEE ieee power & energy magazine 73


+Udc If,ss >> U≈0

Udc If,ss >> U≈0


+Udc/2 If,ss = 0 0

0 0

–Udc/2 0 0
–Udc

–Udc –Udc
(a) (b) (c) (d) (e) (f)

figure 1. Three possible configurations for HVdc systems that indicate voltages during normal operation and prospec-
tive fault voltages and currents during pole-to-ground faults. (a) and (d) A symmetric monopole, (b) and (e) an asymmetric
monopole with metallic return, and (c) and (f) a bipole with metallic return.

complex in HVdc grids compared to ac systems because dc meshed connection of terminals, the power rating of ac–dc
fault currents have no naturally recurring zero crossings and, nodes, and the choice of grid configuration and grounding,
without countermeasures, quickly increase to values that are such as high-impedance grounded symmetric monopole or
unacceptable for power electronic components. conversely, low-impedance grounded asymmetric monopole or bipole.
the technologies used within HVdc grids offer options for for the selection of its components, we refer to the tech-
fault clearing beyond the well-known approach of using cir- nology used for transmission lines, converters, and fault-
cuit breakers in existing ac systems. clearing equipment. the combination of all of these aspects
determines the probability of faults in the system and their
Functional Requirements impact without HVdc grid protection.
for HVdc Grid Protection the impact of the fault on the system in terms of over-
to enable a cost-effective and reliable future power system current or overvoltage depends on the combination of fault
with HVdc grids, the design of HVdc grid protection must type and the grounding and configuration of the HVdc grid.
begin with determining the likelihood of faults occurring for pole-to-pole faults, irrespective of the grounding and
in the system, their impact on the system, and the type of configuration, dc fault currents quickly increase and reach
equipment available for clearing them. the HVdc grid- a high steady-state value in the absence of any protection.
protection design is, therefore, closely related to the overall the impact of pole-to-ground faults depends on the type of
design of the HVdc grid itself and with the selection of com- grounding: for a low-impedance grounded grid, prospec-
ponents within the HVdc grid. in this context, we refer to the tive fault currents are high, whereas for a high-impedance
overall design of the HVdc grid as the choices made in the grounded system, prospective overvoltages on the healthy
HVdc grid structure, i.e., the number of terminals, a radial or poles are high (figure 1).
the faults occurring in the system can be grouped into
several categories indicating the acceptability or unaccept-
ability of their probability and impact, which are combined
Fault Impact

Category 2: Unacceptable Impact to determine risk (figure 2). the resulting design of HVdc
grid protection will largely depend on the outcome of this risk
Category 1: Highly Unlikely

Category 3: Unacceptable Risk


assessment and determine the final impact of faults on the
system. for instance, it is conceivable that the protection of
a symmetric monopolar cable grid differs considerably from
that of a bipolar grid that makes use of overhead lines. in the
first case, HVdc grid protection may use HVdc circuit break-
ers with low current interruption capability or may not use
HVdc circuit breakers at all to deal with rare fault occurrences
and the high likelihood of permanent faults. in the second
Category 4: Acceptable Risk
case, it may make sense to provide HVdc circuit breakers
Fault Probability at both ends of all the lines to quickly isolate the more fre-
quently recurring faults and provide for automatic reclosing of
figure 2. An example classification of power system faults the HVdc circuit breakers in the event of nonpermanent faults.
and impacts based on RTE’s “Mémento de la sûreté du Although a set of specific functional requirements for
système électrique.” HVdc grid protection can only be compiled once the HVdc

74 ieee power & energy magazine may/june 2019


It is conceivable that the desired protection philosophy
provides a higher operation speed and fault-clearing
selectivity as the grid grows in size.

grid design has been determined, the overall objectives for they may be required to absorb a large amount of energy
every HVdc grid-protection scheme are the same: HVdc during fault current interruption.
grid protection should ensure continuity of secure power
system operation and avoid damage to system components Technology That Assists With
in case faults occur. for short circuit faults, this means that Clearing dc Faults
the HVdc grid protection should detect the faults, interrupt several means of interrupting or limiting dc fault currents
the short circuit currents, isolate the faulted component, and are available. Applied technologies include converters, ac
restore the system to a secure operation state. the protec- circuit breakers, dc circuit breakers, and combinations of
tion scheme should perform these functions without causing converter and circuit breakers.
unwanted ac or dc system instabilities. in addition, it should
avoid damage to equipment and property and guarantee AC Circuit Breakers
safety for personnel and the public. in current Vsc HVdc point-to-point schemes, ac circuit
A set of functional requirements for interacting with the breakers are installed in a converter station as the primary
connected ac system can be defined based on the constraints dc fault-interrupting device given that the ac–dc converter
for its secure operation and its components. each ac system itself, i.e., either a two-level or half-bridge modular multi-
grid code defines a maximum power imbalance that imposes level converter (MMc), has no dc fault-blocking capability.
a limit on the secure operation of the system. for instance, in for these types of converters, a fault current path from the ac
the entso-e (european) grid code, this maximum power to the dc side always exists via the antiparallel diodes within
imbalance is specified as 3 gW in continental europe for the converter’s submodules (figure 3). therefore, the ac cir-
an unspecified amount of time and in the united Kingdom cuit breakers eliminate the ac contribution to the dc fault
as 1.8 gW, to avoid a frequency deviation outside the range and typically interrupt the ac current associated with the dc
of 49.5–50.5 Hz for 60 s. HVdc grid protection should thus fault within a few cycles of the fundamental frequency. After
prevent loss of the HVDc line from causing a power imbal- eliminating the ac contribution, the dc fault current passively
ance in the connected ac system that exceeds that maximum decays to zero in a time interval that depends on converter
value. in addition to the maximum power imbalance, the topology and system parameters.
possible functional requirements for HVdc grid protection
relate to the transient stability of connected ac systems or to HVdc Circuit Breakers
the damage to its components. HVdc circuit breakers are the dc counterparts of ac circuit
Within the HVdc grid, functional requirements for HVdc breakers and can interrupt both nominal and short circuit
grid protection can be based on the continuity of the HVdc currents up to their short circuit rating. typically, HVdc cir-
grid operation itself (if required) or from the limits of its cuit breakers must interrupt currents in the 5–15-kA range
components. At present, there is no HVdc grid code that
defines the constraints within which secure operation is
achieved, and the following suggestions are given for illus-
tration purposes only. HVdc grid protection is required to SM SM SM
keep the voltage at converter terminals within certain limits Half Bridge
so they can remain connected. such a “converter dc fault SM SM SM +
ac Side dc Side –
ride through,” however, may not necessarily imply that every Full Bridge
converter remains in an active switching state or retains the SM +
capability of supporting the ac system during the entire fault –
duration. such grid protection should also avoid damage to
SM SM SM
the power electronic components and other equipment. At
present, for voltage source converter (Vsc)-based HVdc SM SM SM
point-to-point connections, the most critical components
are the converter power electronic switches, i.e., insulated-
gate bipolar transistors. in future HVdc grids, HVdc circuit figure 3. The schematic of an MMC comprising half- or
breakers (if any) could also become a limiting factor because full-bridge submodules. SM: submodule.

may/june 2019 ieee power & energy magazine 75


within a time interval of several milliseconds. compared connects the ac to the dc system. this process enables them to
to ac circuit breakers, they are more complex because they block the fault current contribution from the ac to the dc side
must deal with dc currents, which have no naturally recur- without needing ac or dc circuit breakers. the most established
ring zero crossings. to interrupt these nonzero currents, converter with fault-blocking capability is the full-bridge
HVdc circuit breakers consist of several parallel paths that MMc (figure 3), which will see its first application in ger-
perform the functions of current interruption themselves many’s ultranet project. there are other promising converter
and absorb the energy present in the inductive elements configurations that allow for blocking and controlling dc fault
of the circuit. figure 4 illustrates these paths, where the currents while having reduced losses during normal opera-
upper path typically comprises a mechanical switch and tion, when compared with a full-bridge MMc. examples of
forms the path for normal conduction, the middle path is this are hybrid MMc configurations that use a combination of
an auxiliary path to aid in interrupting fault currents, and half- and full-bridge submodules or alternative topologies such
the lower path is an auxiliary path for energy absorption, as the alternate arm converter. fault-blocking capability may
typically consisting of metal–oxide varistors. the HVdc be achieved in a controlled or uncontrolled manner. A major
circuit breaker’s operation typically relies on a succession advantage of controlled blocking is the uninterrupted reactive
of actions, which depend on the technology used. reso- power controllability of the converter, which allows the con-
nant circuit breakers make use of mechanical breakers and verter to operate in a static synchronous compensator mode
resonant circuits that induce current-zero crossings [fig- during the entire fault-clearing process.
ure 4(a) and (b)]. Because of their slow clearing time, pas-
sive resonant breakers are not appropriate for interrupting DC–DC Converters
short circuit currents in Vsc-based HVdc systems. HVdc Proposed for transforming dc voltage from one level to
circuit breakers, based on a combination of power elec- another, dc–dc converters may also limit or even interrupt
tronics and mechanical breakers in the normal conduction fault current contribution from one side to the other. the
path, e.g., so-called hybrid HVdc circuit breakers, typi- dc–dc converter’s ability to block the transfer of fault currents
cally involve using power electronics to avoid arcs in the depends on its topology. All the topologies that use an inter-
mechanical breakers [figure 4(c)]. each of the technologies mediate ac stage, thereby providing galvanic isolation between
recommended by manufacturers has advantages and disad- both sides, can block the propagation of fault current from one
vantages in terms of speed, on-state losses, cost of compo- side to the other, irrespective of the fault-blocking capability
nents, physical dimensions, maximum current interruption of the ac–dc converters used. in direct dc–dc conversion, the
capability, or overall reliability and simplicity of the com- topologies are generally able to block fault-current propaga-
ponents used. Although HVdc circuit breakers are not yet tion in one direction, whereas only certain types of topologies
commercially available, prototypes have been tested and are able to block it in both directions. for instance, to achieve
found to perform in the range of expected requirements. bidirectional fault-blocking capability with an MMc-type
note that these prototypes all require fault-current-lim- dc–dc converter, submodules with fault-blocking capability
iting equipment. must be used.

Fault-Blocking Converters Fault Current Limiters


in contrast to converters without fault-blocking capability, con- At present, HVdc grid protection invariably requires equip-
verters with this capability are able to block the fault current ment that either limits the rate of rise or the magnitude of the
contribution from the ac system to the dc fault. these convert- dc fault current. fault-current-limiting equipment may take
ers rely on converter submodules that are able to insert volt- various forms, such as inductors in series with the circuit
ages of positive and negative polarity, unlike the half-bridge (typically air-core), active fault-current limiting through con-
submodule, which can only insert voltages of positive polar- verters with fault-blocking capability, HVdc circuit breakers
ity (see figure 3). As such, they can insert a voltage opposing with fault-current-limiting capability, or superconducting
the ac system voltage contribution in the fault current path that fault-current limiters. inductors in series with the circuit only
limit the rate of rise of the fault
current and act as a limiter only in
conjunction with equipment that
interrupts the dc fault current, such
as HVdc circuit breakers. these
inductors may be placed directly in
series with the dc circuit breakers
(a) (b) (c) or can also be found in the arms
of the ac–dc converters. the ac–dc
figure 4. Conceptual dc switchgear designs: (a) a passive resonant circuit breaker, converters with controlled fault-
(b) an active resonant circuit breaker, and (c) a hybrid circuit breaker. blocking capability can control

76 ieee power & energy magazine may/june 2019


HVdc grid protection does not necessarily
implement the same conventional approach used
for ac system protection.

the fault current and limit it to a desired level instead of tics of this equipment, alternatives to the selective fault-clear-
reducing the dc fault current entirely to zero. certain types ing strategy exist. regarding these alternatives, the protection
of HVdc circuit breakers, e.g., the ones making use of con- zones used for fault current interruption do not necessarily
trollable power electronic modules, are capable of actively coincide with the components that should be isolated. these
limiting the current. superconducting fault-current limiters fault-clearing strategies can be classified in terms of “extent
use a component that is in superconducting mode during of the HVdc grid which is deenergized,” an approach followed
normal operation. therefore, it presents a low impedance to in the cigre technical brochure (tB) 739, or described in
the circuit. During faults, the superconducting component is terms of “action at the protection zone point-of-connection,”
driven out of superconducting mode, resulting in the loss of an approach followed by the european committee for elec-
superconducting capabilities and, thereby, presents a high trotechnical standardization (ceneLec).
impedance to the circuit. fault-current-limiting equipment in cigre tB 739, fault-clearing strategies are divided
can be installed in series with the transmission lines. in into three main philosophies. in the first philosophy, nonse-
this manner, they are able to limit both the transmission lective fault clearing, the entire HVdc grid is completely
line discharge currents as well as the contributions from de-energized prior to isolation of the faulted component
the ac–dc converters. fault current limiters that are located under near-zero voltage and current conditions. the faulted
in series with the ac/dc converters do not affect the line component should be identified during or after grid deenergi-
discharge currents. zation and may be automatically isolated using Hsss. After
the faulted component is isolated, the remaining part of the
High-Speed Switches HVdc grid is reenergized before power flow can resume. in
Dc high-speed switches (Hsss) can be used to quickly iso- the second philosophy, partially selective fault clearing, the
late a faulted line from the remaining dc network and oper- HVdc grid is subdivided into several protection zones. Here,
ate only under near-zero voltage and current conditions; the faulted zone is first quickly isolated from the healthy
therefore, these Hsss are not required to interrupt fault cur- zones of the grid. this requires that equipment capable of
rents. However, depending on the application, these switches interrupting dc fault currents is present at all boundaries of
may be required to interrupt small residual currents in the each protection zone. thereafter, the faulted element within
grid, which, e.g., result from passive discharge of capacitive the faulted zone is isolated, as in that of a nonselective phi-
or inductive grid components. in case residual currents have losophy. then the remaining portion of the initially faulted
zero crossings, these Hsss may make use of traditional ac zone is reenergized and reconnected to the healthy parts of
circuit breaker technology. Without current-zero crossings, the grid. the third philosophy, fully selective fault clearing,
the Hsss must provide a sufficiently high countervoltage or adopts an approach to dc fault clearing similar to the conven-
have an auxiliary circuit that creates a zero crossing, e.g., tional approach in ac systems.
a passive resonant circuit used in load transfer breakers in in the approach followed by ceneLec, three main con-
classic point-to-point HVdc connections. cepts applied within a certain protection zone are defined
based on the impact of dc faults within a protection zone on
Classification and Characterization of all ac and dc points of connection, i.e., 1) continuous opera-
Fault-Clearing Strategies for HVdc Grids tion, 2) temporary stop, and 3) permanent stop. for each of
HVdc grid protection does not necessarily implement the these concepts, a typical “fault separation time,” i.e., the
same conventional approach used for ac system protection. time at which recovery of the active power flow can start, is
in the conventional approach to ac system protection, circuit defined. these three main concepts are extended to a total
breakers are placed throughout the system and used to simul- of five when considering the availability of reactive power
taneously interrupt the fault current and isolate the faulted during dc fault separation. for a continuous operation, the
component. this has led to a fault-clearing strategy that exchange of active power with dc systems (connected at
divides the power system into zones containing grid elements a c point of connection) and active or reactive power with
such as transformers or transmission lines. in case of a fault, ac systems (connected at an ac point of connection) must
the protection scheme disconnects and de-energizes just the remain controllable during the entire fault separation pro-
zone containing the fault. given the different types of equip- cess, resulting in fault separation times of a few millisec-
ment available for HVdc grid protection and the characteris- onds. in the temporary stop concept, the disruption of active

may/june 2019 ieee power & energy magazine 77


power exchange with dc systems (connected at a dc point of protection concepts, all of the converter stations adopt the
of connection) or active and reactive power exchange with “permanent stop” concept, as defined by ceneLec. As soon
ac systems (connected at an ac point of connection) must as a fault is detected using the sensors at the converter ter-
remain short such that the ac or dc system at a point of con- minals, a trip order is sent to the ac circuit breakers to inter-
nection does not enter into an abnormal operating mode. As rupt the fault current. When the ac circuit breakers of all ac/
such, the temporary stop concept is expected to have a fault dc converters in the grid have opened, the ac fault-current
separation time of a few hundred milliseconds. for a per- contribution to the dc fault current is eliminated, and the dc
manent stop, the disruption of active or active and reactive fault current and dc voltage passively decay to a value close
power may cause the transmission systems at the point of to zero. thereafter, the faulted component is isolated using
connection to enter an abnormal mode of operation, result- disconnect switches or Hsss connected at each end of the dc
ing in fault separation times of seconds. lines. reenergizing the ac–dc converters in the new postfault
each fault-clearing strategy results in different conse- situation can be achieved by reclosing the ac circuit break-
quences for the dc system and the connected ac systems, ers, restoring the dc voltage to within the normal operation
and, consequently, the functional requirements for HVdc grid range, and restoring the power flow to securely operate the
protection depend on adopted strategy. in the fully selective HVdc grid. this strategy is illustrated in the dc1 system in
philosophy, or in those zones making use of the “continuous- figure  5(a), where the ac circuit breakers of the half-bridge
operation” concept, HVdc grid protection should primarily MMcs are used to interrupt the fault current, and Hsss or
ensure that the dc voltage remains within acceptable limits, disconnect switches are used to isolate the faulted equipment.
which keeps the ac–dc converters connected. in nonselec-
tive strategies, the dc voltage inherently collapses, and HVdc Nonselective With Fault-Blocking Converters
grid protection is mainly required to clear the fault and allow in this strategy, converters with fault-blocking capability are
for later system restoration that does not endanger the secure used to quickly stop the fault current contribution from the
operation of the connected ac system. in this respect, options ac system to the HVdc grid through a joint action by all of
for the protection concepts are either a permanent or a tempo- the converters. consequently, the HVdc grid quickly deen-
rary stop. in partially selective strategies, HVdc grid protec- ergizes, and the fault currents decay to values close to zero.
tion must keep the dc voltage in the healthy zones of the sys- thereafter, the faulted line is isolated under near-zero volt-
tem and not endanger the secure operation of the ac system. age and current conditions with a dc Hss that has residual
therefore, the healthy zones of the system should adopt the dc interruption capability. once the faulted line is isolated,
continuous operation concept. the faulted zone takes either the converters restore the dc voltage and, subsequently, the
the permanent or temporary stop, depending on the constraints power flow. this concept is illustrated in application to the
imposed by the grid codes of the connected ac system(s). dc2 system shown in figure 5(a). Actively restoring the dc
voltage from zero requires using converters with controlled
Fault-Clearing Strategies for HVdc Grids fault-blocking capability. the active voltage restoration can
then occur faster compared with converters without con-
Nonselective With ac Circuit Breakers trolled fault-blocking capability or without fault-blocking
this strategy relies on the ac circuit breakers on the ac side of capability at all. Hence, with a nonselective strategy that
the ac–dc converters to interrupt the dc fault current. in terms uses converters with controlled fault-blocking capabil-
ity, dc voltage recovery can occur
faster compared with the nonse-
ac1 dc1 ac2 ac1 dc1 ac2 ac1 dc1∗ ac2 lective strategy that uses ac cir-
H H H H H H cuit breakers in conjunction with
converters without fault-blocking
H H H H H H capability. With this strategy, the
actions of the converters with con-
dc2 ac3 dc2 ac3 ac3
F F F
trolled fault-blocking capability
F F F
fall under the protection concept
F F F F F F known as temporary stop.
(a) (b) (c)
Partially Selective With
H F Half-/Full-Bridge Converter Circuit Breaker High-Speed Switch HVdc Circuit Breakers or
dc–dc Converters
figure 5. Example fault-clearing strategies in an extended HVdc grid: (a) a nonselec- this strategy is similar to the
tive fault clearing using ac circuit breakers (dc1) or fault-blocking converters (dc2), (b) nonselective fault-clearing strate-
a partially selective fault clearing using HVdc circuit breakers or a dc–dc converter, gies in that fault currents are inter-
and (c) a fully selective fault clearing using HVdc circuit breakers. rupted by deenergizing the HVdc

78 ieee power & energy magazine may/june 2019


In the faulted zones, any approach belonging to the nonselective
protection philosophies can be used to interrupt the dc
fault current and isolate the faulted component.

grid as well as the faulted component isolated under voltages of the HVdc grid itself by keeping the dc voltage within an
and currents close to zero; however, it differs significantly acceptable range. these strategies require a higher invest-
from those strategies in that only a part of the HVdc grid ment cost in terms of fault-clearing equipment on the dc side
is deenergized. these strategies must rely on HVdc circuit (i.e., the HVdc circuit breakers at the end of each transmis-
breakers or dc–dc converters placed in between the protec- sion line) but may require less effort in restoring the power
tion zones to isolate the faulted zone from the healthy zones. flow, when compared with nonselective strategies. the par-
in the healthy zones, the dc voltage must be kept within the tially selective strategies face a tradeoff in limiting the extent
boundaries of the ac–dc converters to ensure power flow of the HVdc grid disconnected against the investment in dc-
continuity. in the faulted zones, any approach belonging side fault-clearing equipment. the final choice for a certain
to the nonselective protection philosophies can be used to strategy will depend on the investment costs associated with
interrupt the dc fault current and isolate the faulted com- the required fault-clearing equipment, the probability of each
ponent. After fault clearing, the faulted zone is reenergized type of fault, and the desired impact of fault clearing on the
and reconnected to the healthy zones. in figure 5(b), a par- HVdc grid itself and the connected ac systems. it is conceiv-
tially selective fault-clearing strategy is adopted to achieve able that the desired protection philosophy provides a higher
connection of systems dc1 and dc2 if an outage of the entire operation speed and fault-clearing selectivity as the grid
system, i.e., (dc1 + dc2), is, e.g., unacceptable to the con- grows in size. While each fault-clearing strategy has specific
nected ac grid, ac1. consequences for designing and operating HVdc grids, it is
plausible that systems using multiple strategies will arise,
Fully Selective With HVdc Circuit Breakers e.g., for backup and primary protection or for different sec-
for a selective fault-clearing strategy, HVdc circuit breakers tions of a single grid.
are located at the end of each line to interrupt the fault current
and simultaneously isolate the faulted line [(figure 5(c)]. this HVdc Grid-Protection Algorithms
strategy is similar to the conventional approach to ac system the functional requirements for protection algorithms used
protection, in which all of the converters adopt the continuous to detect faults and identify their location in HVdc grids are
operation concept (as defined by ceneLec), which implies largely the same as for their ac counterparts. requirements
that the fault is cleared sufficiently quickly to avoid collapse can be set for parameters such as speed, reliability, or sen-
of the dc voltage. if the symmetric monopole configuration sitivity. the main challenge is to achieve the desired reli-
is used, HVdc grid protection must also rebalance the pole ability, in terms of security and dependability, within a very
voltages when there are pole-to-ground faults. for pole rebal- small amount of time. in particular, protection algorithms
ancing, either special dc chopper circuits or converters that must make the correct decisions on whether to trip fault-
enable the injection of zero-sequence ac currents into the dc clearing equipment within the first milliseconds after fault
side can be used. detection. these decisions are based on the measured volt-
ages and currents. increased operating time of the protec-
Discussion tion algorithm may lead to a more reliable decision but
HVdc grid protection can be designed using a wide variety also to an increased overall fault-clearing time, which
of fault-clearing strategies, as described previously. choosing is unwanted given the quickly increasing dc fault cur-
a fault-clearing strategy is not straightforward and depends rent. When choosing and tuning protection algorithms,
on many factors, such as the desired overall reliability of the the HVdc grid topology, converter technology, system
power system, the relative power rating of the HVdc grid grounding, measurements, and operating points are impor-
compared to the connected ac system, the cost of fault-clear- tant considerations.
ing equipment, or adaptability of the adopted strategy to sys- this section focuses on algorithms for primary line pro-
tem expansion. the nonselective strategies only consider the tection in HVdc grids. fault detection for selective fault-
secure operation of connected ac systems and offer the lowest clearing strategies is more challenging than for nonselective
cost of all of the components at the dc side. these strategies strategies, so the focus is on algorithms for selective fault
require considerable effort to restore the HVdc grid, and grid detection. However, this does not prevent using the same
restoration times should be adapted to meet the ac system algorithms for nonselective fault-clearing strategies. the
constraints. the selective strategies consider the protection protection algorithms can be implemented using principles

may/june 2019 ieee power & energy magazine 79


The main challenge is to achieve the desired reliability,
in terms of security and dependability, within a
very small amount of time.

based only on local measurements or on the communication refined using signal processing methods to improve their
of measurements from distinct locations in the grid. function in a noisy environment. communicationless protec-
Protection algorithms without communications rely only tion algorithms, based on undervoltage and overcurrent, are
on locally measured voltages and currents, as shown in fig- more suited to complement main or backup protection. the
ure 6(a). these algorithms can be classified as those detect- respective undervoltage or overcurrent criteria have a fixed
ing a fault during a transient and those monitoring a signal time requirement. in contrast with the fastest algorithms,
for a certain amount of time. these two criteria do not rely on the shape of the waveforms
Many of the proposed algorithms without communica- during the fault transient.
tions detect faults during the transient following the fault communication-based protection algorithms combine
event. Among these are voltage-derivative, current-deriva- information from both line ends to make a tripping deci-
tive, combinations of voltage- and current-derivative, sion and, therefore, require a communication channel to
and traveling-wave algorithms. the algorithms determine exchange logic signals or measured quantities from both line
whether the fault is inside the protection zone by using the ends, as shown in figure 6(b). the communication chan-
shape of the wavefront following a fault. Differentiating nel must allow for high-speed communication and most
wave shapes for internal and external faults requires know- likely would rely on fiber optic cables. the algorithms can
ing the electrical distance. this electrical distance is typi- be categorized as those communicating a status (directional
cally driven by the series inductors required for the HVdc comparison) and actual measurement data (differential). the
circuit breakers, which act as low-pass filters on the wave- protection zones are specific for communication-based pro-
fronts generated by external faults. remote faults on long tection algorithms and do not need dc line inductors to sepa-
cables are more difficult to detect than closer faults because rate the protection zones.
of wavefront distortion and attenuation during propagation A directional comparison can be implemented as either a
on the transmission line. the basic fault-detection meth- tripping or a blocking scheme. in both cases, a fault in the for-
ods based on transient voltages and currents can be further ward direction is detected at the local line end, which needs to
be confirmed by information from
the remote line end. in a tripping
Sharp Transient, Dampened Transient, scheme, the presence of the fault is
Easy Detection More Difficult Detection confirmed by a tripping signal from
the remote line end. A tripping
Protection Zone: Cable
signal is issued by the remote line
end if the measurements at that end
(Local) (Remote) indicate a fault in the forward direc-
dc Line dc Line
Protection Protection tion, i.e., in the direction of the pro-
tection zone. in a blocking scheme,
(a)
the presence of a fault is confirmed
Largest Smallest by the absence of a blocking signal
Communication Delay Communication Delay
from the remote line end. A block-
Protection Zone: Cable ing signal would indicate detection
of a fault in the reverse direction
at the remote end of the protection
(Local) (Remote)
dc Line dc Line zone. the tripping scheme intro-
Protection Protection duces the largest number of delays
Communication
in a directional comparison scheme;
(b) these delays occur at the local end
of the protection zone. While the
figure 6. A comparison of protection algorithms (a) without and (b) with communi- fault is perceived almost instanta-
cation. (Note that the comments refer to local dc line protection.) neously by the local measurements,

80 ieee power & energy magazine may/june 2019


The design of a reliable, effective HVdc grid-protection
scheme depends on both system characteristics and
the strategy used for fault clearing.

the algorithm must wait for signals communicated from the rely on an impedance between the protection zones, which,
remote line end to make a tripping decision. for HVdc grids, may be provided by an inductor in series
Differential line protection compares the currents or with the HVdc circuit breaker. for algorithms using commu-
traveling waves seen at both line ends. the basic principles nication, the algorithms may employ a traveling-wave differ-
of traveling-wave differential protection, originally devel- ential or directional-comparison protection scheme and must
oped for ac overhead line systems, may be applied to HVdc rely on a fast communication channel, such as a dedicated
systems. However, the algorithm may need an adaptation fiber optic cable.
for cable systems because of the larger influence of wave
distortion and attenuation in cable systems. for these algo- Acknowledgments
rithms, the delay caused by the wave propagation is sub- the authors acknowledge contributions from the members
tracted from the communication delay, which favors a high of Work Package 4 in the european Horizon 2020 project
speed of operation. Because these algorithms rely on the Progress on Meshed HVDc offshore transmission net-
exchange of measured quantities rather than logical signals, works (ProMotion). this work was funded by ProMo-
they impose a larger communication burden compared to tion under grant 691714.
directional algorithms.
communicationless algorithms have the advantage of For Further Reading
fast fault detection due to the absence of communication cigre, “Local control and protection of HVDc grids,”
delays but face difficulties with detecting remote faults. cigre, Paris, techn. Brochure 739, tech. rep. JWg B4/
By contrast, communication-based algorithms can detect B5.59, 2017.
remote faults while having an acceptable communication ProMotion consortium, “D4.2-Broad comparison of
delay. therefore, a combination of communication-based fault clearing strategies for Dc grids,” oct. 2017. [online].
and communicationless algorithms may be suitable for pro- Available: https://www.promotion-offshore.net/fileadmin/
tecting long lines. PDfs/D4.2_Broad_comparison_of_fault_clearing_strate-
gies_for_Dc_grids.pdf
Summary D. Van Hertem, o. gomis-Bellmunt, and J. Liang, eds.
the design of a reliable, effective HVdc grid-protection HVDC Grids for Offshore and Supergrid of the Future.
scheme depends on both system characteristics and the strat- Hoboken, nJ: Wiley, 2016.
egy used for fault clearing. system characteristics determine i. Jahn, n. Johannesson, and s. norrga, “survey of meth-
the requirements for protection by fixing the relationship ods for selective Dc fault detection in MtDc grids,” in
between the probability of faults and their impact and by Proc. 13th IET Int. Conf. AC and DC (ACDC) Power Trans-
setting constraints on secure system operation. the strat- mission, 2017.
egy used for fault clearing determines the technology to be
used (e.g., whether or not to use HVdc circuit breakers) and Biographies
determines the final impact of a fault on the system and its Willem Leterme is with energyVille, the university of Leu-
components. for HVdc grid protection, fault-clearing strat- ven (Katholieke universiteit Leuven), Belgium.
egies can be classified into three philosophies: nonselec- Ilka Jahn is with the royal institute of technology,
tive, partially selective, and fully selective. the impact of stockholm, sweden.
the fault on an ac or dc system can be determined from the Philipp Ruffing is with rheinisch-Westfälische tech-
actions taken by ac–dc converters during fault clearing. in nische Hochschule, Aachen, germany.
all cases, the fault-clearing strategies benefit from fast fault Kamran Sharifabadi is with equinor, stavanger,
detection and, in the case of a fully selective strategy, fast norway.
fault identification. the overview of protection algorithms Dirk Van Hertem is with energyVille, the university of
given here shows that these algorithms operate mainly on Leuven (Katholieke universiteit Leuven), Belgium.
traveling waves and may use a scheme without or with com-
p&e
munication. the algorithms not using communication must

may/june 2019 ieee power & energy magazine 81


By Dragan Jovcic, Guangfu Tang, and Hui Pang

Adopting
Circuit Breakers
for High-Voltage
dc Networks

S
Since the late 19th century, ac power tranSmiSSion
systems have been widely used for interconnecting multiple power-pro-
ducing plants with load centers. highly meshed ac transmission grids
with high redundancy and operating flexibility now operate worldwide.
these complex ac systems have proven reliable in securely providing
high levels of power, while also accommodating multiple voltage levels
to reduce loss.
two key components essential for transmission systems, besides
the lines themselves, are circuit breakers (cBs) and transformers. Such
units for ac transmission are relatively simple, reliable, and efficient.
cBs enable operators to open a circuit (line) under load and fault cur-
rents, which is essential for regular maintenance, system expansion, and
the physical integrity of large transmission systems. transformers make
it possible to change voltage levels, which is necessary for maintain-
ing safe and reliable systems, but also for reducing losses with long-
distance transmission.
however, ac transmission has many shortcomings, which have been
publicly debated since the war of the currents between tesla and west-
inghouse (who favored ac) and edison (who favored dc). with ac trans-
mission, reactive current transfers occur, which increase losses and
cause operating difficulties. also, for underwater cable transmission at
distances of more than 100 km, reactive power issues become severe
due to excessive line charging, making ac transmission in such applica-
tions impractical.
Digital Object Identifier 10.1109/MPE.2019.2897408
high-voltage dc (hVdc) transmission has been used since 1954. thanks
Date of publication: 17 April 2019 to important technological advances, its use has taken off in the last 20 years.

82 ieee power & energy magazine 1540-7977/19©2019IEEE may/june 2019


Appropriating the Vast Advantages
of dc Transmission Grids

those advances include high-power electronic devices, such as thyristors and, more recently, transis-
tors, which have enabled the development of more compact voltage source converters (VScs). the vast
majority of hVdc systems consist of a single line or cable and use one ac–dc converter at each end. the
direct connection of multiple dc lines in networks has not been possible, primarily because suitable dc
cBs have not been available. nevertheless, in the last five years, two multiterminal VSc hVdc systems
have been built in china, and others are being designed and developed.
Dc transmission grids, a substantial technological advance over point-to-point hVdc connections,
are being considered for many applications worldwide. in europe, researchers involved in several major
projects have studied the use of a cable dc grid in the north Sea for integrating large amounts of offshore
wind energy and strengthening interconnections among european union countries. in china, plans have
been made for building a four-terminal dc grid with overhead lines.
For dc grids to work, the market has to offer dc cBs, preferably from multiple vendors. these cBs
must provide acceptable performance and reliability, ensure low loss, and be available in practical
sizes at a reasonable cost. much has been learned from long experience with ac cB technologies,
which are standardized at high voltage and very high current ratings. however, they are not suitable
for dc applications, and the technologies for dc cBs will be substantially different from those for ac
cBs. the performance requirements for dc cBs in dc grids are more stringent. also, opening a dc
circuit is technically much more challenging than opening an ac circuit.
over the last five to 10 years, some major advances in hVdc cB tech-
nologies have been introduced. multiple dc cB topologies have been
demonstrated in laboratories and brought to market. more recently,
these have been installed for the first time.

©istockphoto.com/smartboy10
Basic Performance
Requirements for dc CBs

The Role of dc CBs


the critical functions of dc cBs include
controlled opening and closing of circuits
and, in case of faults, isolating faulted
dc lines. these functions are neces-
sary for the dc network to continue
operating while a line is under a
fault. if the faulted line were

may/june 2019 ieee power & energy magazine 83


not isolated, grid voltage would be low, and currents would dc voltage, which, for the system under consideration, implies
be high under the fault condition. high current would likely current of 4 ka and voltage of 320 kV.
lead to component damage, while low voltage would reduce in conventional ac transmission systems, generators have
power-transfer capability. Fast dc fault isolation is particu- many self-protection controls, but the thresholds are signifi-
larly significant for large dc grids, which may have numer- cantly higher relative to the nameplate-rated variables. the
ous converter stations and transmission lines. the converters line/cable impedances also have much higher values in ac than
being considered for the european north Sea dc grid are rated in dc systems, because the frequency, f, contributes to the reac-
at 1.5–2 Gw, while the total dc grid capacity may exceed tance (the imaginary part of the impedance, 2rfL, where L is
150 Gw in some scenarios. the inductance). these factors lead to the conclusion that, in a
Figure 1 shows a single-line diagram of a five- dc system, cBs (and protection systems) must respond much
node ±400-kV dc grid, consisting of four ac–dc bipole faster than in ac systems to prevent widespread loss in capacity
converters rated 800 mVa, 2 ka per pole interconnecting (converter blocking) and destructive fault current magnitudes.
the dc grid (buses 1–4) with corresponding ac systems, one
dc bus without a converter (node 5), eight dc cables, and Operating Speed
16 dc cBs per pole (32 dc cBs in total). the grid topology in a dc fault situation, current rises and voltage falls throughout
has been selected to illustrate how power can be transferred the dc grid during the delays associated with dc protection and
securely while limiting the number of dc cBs. in comparable dc cB operation. once the dc cBs open and isolate the dc fault,
ac systems, the number of ac cBs would be much higher, the dc voltage recovers, and dc power flows over the recon-
according to modern grid development practices. the indi- figured grid at a newly established balanced operating point,
cated power and voltage levels are in the highest range of which depends on the number of remaining operating convert-
demonstrated dc cB technology. ers and their control strategies. the faster the dc cBs operate,
For example, a short circuit fault occurring on the line the less likely it is that large parts of the dc grid will be lost.
linking buses 3 and 4 would insert a low impedance at the however, the blocking of nearby converters cannot be
point of fault and result in high currents flowing into the fault completely avoided, even with application of the fastest avail-
from all parts of the network (as indicated by red arrows). able dc cBs. this is because the converters closest to the fault
Depending on the impedances of the grid cables and on the point may experience high current and thus block before the
severity of the fault itself, the fault currents would have dif- dc cBs open. the most recent dc grid studies indicate that
ferent magnitudes, but they can easily reach 10–30 times temporary converter blocking for 10–30 ms is possible until
the rated current (say 20–60 ka) at some points. these are the dc fault is cleared. then the converters can be unblocked
destructive currents that grid components cannot withstand. to resume normal operation. the need for blocking convert-
all high-power ac–dc converters have self-protection ers will depend on the grid topology and the fault location.
control logic, which blocks and disconnects converters in the many studies indicate that dc grids of various sizes and
event of disturbances. typically, self-protection thresholds topologies can recover from any dc line fault if the total pro-
are set at approximately 2 per unit (p.u.) of current and 0.8 p.u. of tection time (dc cB opening time plus protection operation

1 2
1.6 GW 2 kA 2 kA 1.6 GW
CB12_1 CB12_2

CB15_1 CB25_2
ac System 1
CB14_1 ac System 2
CB23_2
5
±400 kV CB dc–ac
15_ 5 ±400 kV
5 25_ Converter
CB
_5 CB
45 35_
4 CB 5 3
1.6 GW dc CB
2 kA 400 kV
CB14_4 CB23_3 2 kA 1.6 GW

ac System 4 CB45_4 CB35_3

CB34_4 CB34_3 ac System 3


Fault

±400 kV ±400 kV

figure 1. A diagram showing a five-node dc grid with four ac–dc converters, eight dc cables, and 16 dc CBs per pole.

84 ieee power & energy magazine may/june 2019


Because operators have so little experience with dc CBs, more
study is needed about the internal complexity of dc CBs and
their failure modes to fully understand their reliability.

time) is within approximately 10 ms. this assumes that some studies of offshore environments show that the extra size and
converters may block by self-protection temporarily or per- weight of dc cBs could add significantly to platform costs.
manently, depending on the grid topology and the strategy
used for protecting the network. permanent blocking after Cost and Reliability
fault clearing occurs if the converter becomes isolated. this the widespread application of ac cBs to ac transmission sys-
results in grid capacity reduction. tems ensures a secure power supply and enables operational
flexibility. the simple dc system in Figure 1 may not provide
Ratings the same level of security and flexibility as in ac systems but,
in ac systems, ac cBs are rated for the largest available fault nevertheless, requires 32 dc cBs. the example shows that
level at their point of connection (the worst case steady-state future grids are likely to require a considerable number of dc
fault current). Dc cB prototypes recently brought to market cBs. these will cost more than ac cBs, and for some dc cB
by manufacturers are designed for only 15–20-ka peak inter- topologies the costs may be substantially higher.
rupting current. these state-of-the-art dc cBs have such low Because operators have so little experience with dc cBs,
ratings because of costs and technological limitations. the more study is needed about the internal complexity of dc cBs
ratings are, for the foreseeable future, lower than expected and their failure modes to fully understand their reliability.
fault levels at many dc buses. thus, dc cBs must operate Some dc cBs using semiconductor technologies have self-pro-
fast, before dc fault current exceeds their ratings and before tection as discussed later in this article. Such features need to be
it reaches destructive levels causing many converters to block considered by grid planners and protection system developers.
and leading to wider dc grid collapse.
Standardization of Inputs/Outputs
Bidirectional Operation in large dc grids, the protection system will consist of multiple
in many applications, dc cBs will be expected to interrupt relays (microcontroller based) and dc cBs that are intercon-
fault current in one direction only. Depending on how pro- nected and use adjusted settings controlled by the grid operator.
tection zones and protection systems are configured, some in the development of protection logic, grid topology changes
dc cBs may be expected to operate in both directions. also, and expandability must be considered as important factors.
bidirectional operation may be beneficial as a backup pro- achieving the desired operation of protection system with com-
tection function. application of a unidirectional dc cB may ponents made by different vendors requires that interconnec-
suffice in particular projects and result in substantial cost tions be standardized and that components be interoperable.
and size savings for some dc cB topologies.
Challenges With dc Circuit Opening
Fast, Multiple Open/Close Operations
Dc grids with overhead lines can be exposed to frequent DC Current Commutation
faults, many of which will be transient. as with overhead ac the first developers of dc systems learned that interrupting
transmission, reclosing with multiple cB operations within dc current is difficult. trying to separate cB contacts under
200–500 ms may reasonably be expected. with underground a current flow creates an arc, which for high-voltage systems
or underwater dc cable systems, however, almost all faults is self-sustaining and generates large amounts of heat caused
are permanent, and reclosing may not be included in the pro- by the arc resistance. with ac currents, there is a natural cur-
tection logic. the number of expected operations and timing rent-zero crossing twice every cycle (every 10 ms in 50-hz
of dc cB duty cycles may result in cost and size implications systems). this momentary current interruption—along with
for some dc cB topologies. engineering devices that ensure sufficient contact separation
and an arc-extinguishing chamber—enables modern ac cBs
Losses, Size, and Weight to reliably interrupt very large currents within 20–60 ms.
most of the time, dc cBs operate in a closed state and con- there are no natural current-zero crossings in dc systems.
duct load current. losses in closed-state dc cBs cost grid at low voltages of 10–30 V (automotive applications), the arc
operators revenue. also, dc cBs with high losses may require voltage is larger than the system voltage, and this reduces the
additional heat-removal equipment. Dc cBs will be notice- current to zero. at higher voltages, there are two principal
ably larger and heavier than ac cBs. in europe, dc grid methods to interrupt dc current.

may/june 2019 ieee power & energy magazine 85


1) the first uses power electronics to commutate current and dc cB operating times, this inductor limits the peak
into a parallel circuit. with this method, semiconductors fault current experienced by dc cBs and other components
provide solid insulation and can interrupt large currents in the dc grid. For example, a 400-kV dc bus with a desired
very quickly and without arcing. the principal challeng- interrupt time (dc cB opening and protection time) of 4 ms
es with this method are large component costs and high and a maximum peak interrupting current of 16 ka requires
losses during normal closed-state operation. an inductor of around 100 mh. Series inductors with dc cBs
2) the second uses additional circuits, such as commonly also enable the protection system to differentiate between
employed inductor–capacitor (lc) resonant systems, to faults in inner and outer protective zones. Because of these
create current-zero crossings in mechanical switches. multiple requirements for the series inductor, it is not clear
mechanical switches allow almost no closed-state losses whether the series inductor will be considered part of future
and are generally lightweight, compact, and inexpensive dc cB units or part of the dc protection system.
at high-voltage ratings. the main challenge is arcing, on the negative side, series inductors store energy and
which suggests the need for heavier and more complex make voltage control of dc grids less precise. in addition, in
contacts, leading in turn to slower opening speeds. the event of fault interruption, the energy stored in the induc-
Both methods are viable and have been demonstrated on hV tor must be dissipated by dc cBs.
and large-current dc cB units.
Main dc CB Topologies
DC Current Reduction and Dissipation of Energy Several manufacturers have invested substantially in further
the energy dissipation in a device is the product of the cur- developing dc cBs to voltage and current levels suitable for the
rent and voltage across the device, multiplied by time. with latest dc transmission technology. these manufacturers have
ac cBs, dissipation of energy is minimal because the con- reported results from laboratory tests of dc cB prototypes
tacts open when the load current crosses zero. any energy in the range of 40–80 kV with peak fault current interruption
in the system is conveniently dissipated in the arc chamber. capabilities of approximately 15–20 ka. plans call for these
units to become standard modules through series connections to
with dc cBs, nonlinear resistors (surge arresters) are gener-
ally used to provide counter dc voltage under the dc load/fault achieve higher dc voltage levels. reports from manufacturers
current at the moment of interruption. these resistors, an inte-and data from recent installations indicate that there are no
substantial obstacles to implementing 300–400-kV dc cBs.
gral part of all dc cBs, are also called energy absorbers because
they absorb the energy from the line inductances, which is a the european union has directed substantial resources
consequence of simultaneous high voltage and high current for a into research on dc cBs, including tests of several full-scale
(70–80 kV) dc cBs at an independent laboratory. there is a
short period until the dc current is brought to zero. the expected
joint effort by multiple manufacturers, grid operators, academ-
energy dissipation at a 400-kV dc voltage level is on the order of
10–100 mJ, which affects the thermal ratings and time constants ics, and consultants that is helping the industry better under-
of the absorbers. this is especially important if repeated dc cBstand dc cBs and how best to control and test them, know what
operations are required. this degree of energy dissipation also their operating limits and failure modes are, and determine
influences the cost, size, and weight of the dc cB. how they interact with dc grid components. considerable effort
is also being directed toward achieving interoperability among
Series Inductor With dc CBs various dc cB technologies and products from different manu-
each dc cB in hVdc grids requires a series inductor on the facturers and also toward initiating standardization.
order of 50–300 mh. although this inductor cannot reduce many different dc cB topologies have been pro-
the amplitude of the dc fault current, it can limit the fault posed, with some prototypes of varying ratings under-
current’s rate of rise. Sized for a given level of protection going field tests. many technologies related to dc cBs have
recently been patented, and inten-
sive research will continue in this
Residual Breaker Main Branch field. it is possible to group most
Idc Ldc VI2 IVI1 VI1 dc Cable
dc cB designs into two main
dc
dc
Load
families: 1) mechanical dc cBs
Source V IS3 VI3a
+ dcCB I LC Fault + and 2) hybrid dc cBs that use
Vdc C1a R
– 1a – semiconductor valves.
Current L VI3b
1
Injection C1b R1b Mechanical dc CBs
Branches

Energy Topology
Absorber SA Figure 2 shows a typical topology
of a mechanical hVdc cB and
figure 2. A diagram showing a mechanical dc CB. illustrates the following.

86 ieee power & energy magazine may/june 2019


1) the main branch consists of a breaker that is able to 3) the energy absorber consists of banks of surge arrest-
sustain arcing. this is usually an ac vacuum inter- ers. these arresters are based on standard surge arresters
rupter (Vi) with an enhanced driving mechanism to widely used in ac systems for overvoltage protection.
reduce opening time. 4) the residual breaker, Vi2, interrupts only a small current.
2) the current injection branches include precharged ca- this device does not need to have high opening speed.
pacitors. this topology shows two branches. this design 5) the current-limiting inductor L dc reduces the rate of
enables two operations in a short time, which may be the fault current rise.
essential considering the time it may take for capaci- the mechanical dc cB presented is also called a current
tors to charge. the second branch is not needed if the injection dc CB, because it employs precharged capacitors
required breaker duty cycle consists of only a single C 1a and C 1b, which substantially increase the speed of
opening. Switches Vi3a and Vi3b are similar to Vi1. each operation.
the natural resonant frequency of the lc circuit can
be increased to practical values in the range of 2–3 khz, Operating Principles
which would reduce the required sizes of L 1 and C 1 . Figure 3 illustrates an interruption of a 15-ka peak dc fault
the resistors R 1 are required for capacitor charging. current with a mechanical dc cB on a 400-kV dc system,

18 18
16 Arcing Time 16
14 14
Idc
12 12
ILC
Current (kA)
Current (kA)

10 10
IVI1
8 8
VI2 Fully
6 6 Open
IS3
4 Trip 4 VI3 Begins
Signal VI1 Begins to Open VI3 Fully
to Close
2 VI1 Fully Open 2 Closed
0 0
0 5 10 15 20 25 30 0 5 10 15 20 25 30
Time (ms) Time (ms)
(a) (b)
100
600
VdcCB
400 80
Vdc
Energy (MJ)
Voltage (kV)

200 60
ESA
0 40

Fault Current Suppression Time


–200 20

–400
0
0 5 10 15 20 25 30 0 5 10 15 20 25 30
Time (ms) Time (ms)
(c) (d)

figure 3. The four graphs show the interruption of a 15-kA peak dc fault current with a mechanical dc CB on a 400-kV
dc system, assuming a dc fault at t = 0 s. (a) Contacts require about 8 ms to fully separate. (b) The fault current is fully
extinguished after an additional 20 ms. (c) The graph indicates the arrester voltage level. (d) Energy dissipation by the ar-
resters (E SA) is about 83 MJ.

may/june 2019 ieee power & energy magazine 87


assuming a dc fault at t = 0 s. a 240-mh series inductor (L dc) 2) an auxiliary branch has low resistance and conducts full
is used. Figure 3(a) shows that it takes approximately 8 ms for load current in the closed state. this branch includes
the Vi1 contacts to fully separate. at that instant, Vi3 closes, ✔ a low-voltage (lV) semiconductor valve T1, also
injecting an oscillating current, I S3, which facilitates a zero called the load commutation switch, which should
crossing of I VI1 . when the arc is interrupted in Vi1, the dc have a voltage rating comparable to the closed-
current I dc is transferred to the energy absorber, and voltage state voltage drop of the valve T2 (i.e., on the order
VdcCB abruptly rises to the clipping voltage of the surge arrest- of 10 kV)
ers, which is commonly around 1.5 p.u. (600 kV). this high ✔ an ultrafast disconnect switch S 1, which cannot sup-
voltage brings a negative voltage across inductor L dc (400– port arcing (it can open only at zero current) but has
600 kV), enabling fault current suppression. the fault current an extremely fast opening speed (significant tech-
is fully extinguished after an additional 20 ms [Figure 3(b)]. nological advances have been made recently using
manufacturers commonly specify the time to voltage recov- thomson coil drivers, and the opening speed for
ery (8 ms in Figure 3) as the key indicator of dc cB performance. 320-kV units has been demonstrated as approxi-
the peak fault current is specified as the single indicator of inter- mately 2 ms)
rupting capability (15 ka at 8 ms), which is a key parameter for 3) energy absorber Sa, which consists of banks of surge
sizing the series inductor L dc . Sizing could vary for different dc arresters
cB technologies because of different opening speeds. 4) residual breaker S 2, which interrupts only the arrester
the expected energy dissipation by the arresters in this leakage current and whose opening speed is not critical.
case (E SA) is around 83 mJ, as seen in Figure 3(d). Figure 3 L dc is a current-limiting inductor.
illustrates fault current interruption in the positive direction, the lV valve t1 continuously conducts load current, and it
but this dc cB topology can similarly interrupt dc fault current must withstand fault current in the period before the protec-
in the negative direction. however, because the charge of capac- tion relay sends the trip signal. in practice, this valve consists
itor C 1 is unipolar, the responses in the negative direction will of several parallel branches, with each branch having a few
be slightly different, and component stresses might be higher. insulated gate bipolar transistors (iGBts) in series. Because
of the continuous conduction stress, this valve requires a
Hybrid dc CB forced-liquid cooling system. the main valve T2 conducts
the fault current for only around 2 ms. therefore, it does
Topology not need liquid cooling. however, the whole hybrid dc cB
Figure 4 shows a representative topology for a hybrid dc cB, should be located indoors (in a valve hall) similar to any
which consists of the following. large converter.
1) included is a main branch that has two 400-kV semi-
conductor valves, T2A and T2B (one for each direc- Operating Principles
tion). For protection in only one direction, just one Figure 5 illustrates a dc fault on a 400-kV dc system inter-
valve wou ld b e ne e de d. e a ch valve is similar to rupted by a hybrid dc cB that uses a 76-mh series inductor
one arm of a (six-arm) VSc hVdc converter. this (L dc). the fault occurs at t = 0 s , and the current peaks at
branch can conduct load current in a closed state, but 15 ka. Figure 5(b) shows that S 1 begins to open when the
losses would be high with prolonged operation. current is transferred to T2 and I T1 drops to zero. it takes

IT1

S1 T1
Residual
Breaker Auxiliary Branch
Idc Ldc IT2 dc Cable

T2A T2B dc
dc
Load
Source S2
+ Main Branch Fault +
Vdc VdcCB
– –
SA

Energy Absorber

figure 4. A diagram of a hybrid dc CB.

88 ieee power & energy magazine may/june 2019


2 ms for S 1 to fully open while T2 is conducting. once S 1 open the circuit at its self-protection threshold as the last line
is open, the current is commutated to the energy absorber by of defense.
opening T2 . as the current commutates to surge arresters,
their voltage rises to 1.5 p.u., which initiates current suppres- Fault Current Limiting
sion. it takes another 5 ms for the fault current to fall to zero, hybrid dc cBs can also act as dc fault current limiters. By
as seen in Figure 5(a). Figure 5(d) shows that the expected total employing the on/oFF control of the individual modules
energy dissipation (in this case, E SA) equals 21 mJ. in valve T2, the number of inserted arresters can be varied,
which can regulate current. this operating mode is limited
Self-Protection by the thermal capability of energy absorbers and can most
as with all high-power converters, the semiconductor valves likely be achieved for only short periods of time.
in hybrid dc cBs open in the event of excessive current. this this fault-limiting operating mode can be beneficial in
is a self-protective feature. although unlikely, a failure in some applications. it can help, for example, in
some grid protection components (relay, sensor, communica- 1) limiting fault currents, which allows additional response
tion, and others) could fail to send a trip signal to the dc cB time for fault clearing by other dc cBs installed on oth-
in a dc fault situation, which would result in a rising high er lines in a dc grid (in practical terms, the dc cBs or
dc cB current without a dc cB trip command. in practical protection systems on the other lines may have slower
terms, this means that the dc cB may open on its own to response times)
protect itself at some dc current threshold (which is much 2) limiting inrush currents when connecting dc lines,
higher than dc grid protection settings). if the dc grid protec- which eliminates the need for preinsertion resistors on
tion were to fail for whatever reason, the hybrid dc cB should the dc cBs.

16 16
S1 Opening
14 14 Time
12 12
Idc
10 10 IT2
Current (kA)
Current (kA)

8 8

6 6
IT1 Trip Signal
4 4
S1 Begins to Open
2 2
S1 Fully Open
0 0
0 2 4 6 8 10 0 2 4 6 8 10
Time (ms) Time (ms)
(a) (b)
800 25
VdcCB

600
20

400
Voltage (kV)

Energy (MJ)

Vdc 15
200
ESA
10
0
Fault Current
Suppression Time 5
–200

–400 0
0 2 4 6 8 10 0 2 4 6 8 10
Time (ms) Time (ms)
(c) (d)

figure 5. The four graphs show a dc fault on a 400-kV dc system interrupted by a hybrid dc CB that uses a 76-mH series induc-
tor (L dc). (a) The fault occurs at t = 0 s, and the current peaks at 15 kA. (b) S 1 begins to open when the current is transferred to
T2 . (c) The graph indicates the arrester voltage level. (d) The expected total energy dissipation (E SA) equals 21 MJ.

may/june 2019 ieee power & energy magazine 89


In 2016, a hybrid dc CB rated 200 kV was installed at the
Dinghai Station on the Dinghai-to-Daishan line, which made
the system more reliable and easier to control.

DC CBs Installed in China made the system more reliable and easier to control (Figure 6).
Figure 7 shows the topology and a photo of a prototype for 200-kV
Installed Hybrid dc CB in the Zhoushan hybrid hVdc cB. the three branches consist of the following:
Multiterminal System 1) the auxiliary branch carries nominal current and con-
among the islands of the Zhoushan archipelago, the largest tains a series that combines an ultrafast mechanical dis-
power-consuming islands include the main island of Zhoushan, fol- connector (uFD) with an auxiliary commutation switch,
lowed by the islands of Daishan, Qushan, yangshan, and Sijiao. which consists of a full-bridge submodule (FBSm) using
the annual load of the Zhoushan power grid reached 780 mw in high-power-rating iGBts. the FBSms appearing in the
2010, and is estimated to reach 2,000 mw in 2020 as a result auxiliary branch and main branch adopt the same full-
of higher demand stemming from economic development. bridge structure. this consists of four press-pack
a ±200-kV five-terminal VSc hVdc project, built by the iGBts and a snubber circuit. the auxiliary branch should
State Grid corporation of china, began commercial operation have as few FBSms as possible to reduce the on-state
in 2014. it transmits power from the mainland to the five islands. impedance. therefore, a 2 × 3 FBSm matrix design is
this project uses a modular multilevel converter and connects used, featuring low conduction losses and high reliabil-
by submarine cables. During normal operation, the Dinghai ity. to make maintenance easier, each FBSm uses an
converter station on Zhoushan island provides dc voltage con- integrated modular unit connected by an inductance-less
trol, and the other stations operate in power control modes. as busbar. a water-cooling system is needed because the
a result, the power flows from the Dinghai Station to the other auxiliary branch conducts the long-term load current.
stations. Due to the lack of hVdc cBs, clearing a dc fault was Because the uFD is opened with zero current, the con-
originally achieved by slow-acting operations of ac system tacts inside take up less space, and its driving mechanism
breakers. the lack of rapid fault isolation and the inability to is lightweight. the compact design is achieved by using a
switch circuits caused several technical problems, indicating a Vi with a voltage rating of 40.5 kV and current rating of
need for improved system security, greater operating flexibility, 2 ka rather than an SF6 cB. the maximum separation
higher reliability, and faster system restoration capabilities. time of the breaker must be within 2 ms to meet the fault-
in 2016, a hybrid dc cB rated 200 kV was installed at clearance time requirements of the Zhoushan project. as
the Dinghai Station on the Dinghai-to-Daishan line, which a result, a series connection of six Vis is adopted, and
each Vi is equipped with voltage-sharing devices.
2) the main branch interrupts fault currents and consists of
Yangshan Station Sijiao Station four series-connected modular units. each modular unit
100 MW 100 MW contains 36 FBSms in a series connection designed for
50-kV and 15-ka breaking capability. a cooling system
is not necessary for the main branch because it only ex-
periences the fault current for several milliseconds. the
32 km FBSm topology provides a bidirectional current path and
allows the hybrid cB to interrupt the fault current in either
39 km
direction. in addition, the capacitors in the FBSm enable
dc
Breaker soft turn-off of the iGBts, significantly decreasing the in-
46 km 17 km
duced voltage stress and balancing the voltage distribution
across the modular unit during fault interruption.
400 MW 3) the energy absorber branch is made up of surge arresters
Dinghai Station that limit transient interruption voltages (tiVs) and dis-
sipate the magnetic energy stored in the system.
300 MW 100 MW the installed hybrid hVdc cB offers the following ad-
Daishan Station Qushan Station vantages:
✔ a small footprint and low height, resulting from the
figure 6. A diagram showing the Zhoushan five-terminal integrated and compact design (installed at a 200-kV
HVdc transmission system with the installed hybrid dc CB. high-potential platform)

90 ieee power & energy magazine may/june 2019


✔ low power losses during normal operation, resulting had to be performed to verify the hVdc cB design. these
from use of fewer power semiconductor devices in the were developed based on the operating principles and condi-
main branch (six FBSms form a 2 × 3 matrix, cooling tions of the hVdc breaker as well as the present iec stan-
system, and power adapter) dard for testing VSc hVdc valves. the test was divided into
✔ use of a lightweight contact system (six Vis in series; two parts: the insulation test and the operating test.
40.5 kV because each uFD separates without experi- the insulation test verifies the voltage-withstanding capac-
encing current) ity and the voltage-sharing characteristic of an hVdc cB. the
✔ modular design (four modular units, 50 kV each; 36 operating test checks the capacity of each core component to
FBSms in each unit), which facilitates maintenance withstand serious stress and the operational properties under
and replacement of parts different circumstances. table 1 shows some of the main test-
✔ high reliability resulting from exposure to lower volt- ing considerations.
ages due to a series design that distributes voltages the 200-kV hybrid dc cB passed the test in which a
during switching. 15-ka short circuit current was cleared within 3 ms and the
Because no relevant international electrotechnical com- transient interruption voltage across the test object exceed-
mission (iec) standards currently exist, conformance tests ed 320 kV.

Auxiliary Branch
iT1

Ultrafast Auxiliary
Disconnector FBSM Branch

Main Branch Energy


iT2 Absorber
Main
Branch
FBSM FBSM FBSM FBSM FBSM FBSM FBSM FBSM
Modular Unit Modular Unit Modular Unit Modular Unit
iabsorb

Energy Absorber

uDB
(a) (b)

figure 7. (a) The topology and (b) a prototype of a 200-kV hybrid HVdc CB.

table 1. Factors related to testing the insulation and operating characteristics of HVdc CBs.
Number Test Test Object Items Objective
1 Insulation test Phases to ground DC voltage withstand test To verify the voltage-withstanding
capacity and partial-discharge level of
2 Switching impulse withstand test support structure
3 Lightning impulse withstand test
4 Across open DC voltage withstand test To verify the voltage-withstanding
contacts capacity across open contacts
5 Switching impulse withstand test
6 Operating test Key components Peak withstand current test To verify the current-withstanding
capacitor of the CB
7 Overload withstand current test
8 Short-time withstand current test
9 Short-time withstand current test
10 Overall prototype Rated current-interruption test To verify the current-interruption
capacity and interruption time
11 Short circuit current-interruption test of the overall prototype and the
12 Rated current-making test program correctness of the control
and protection system
13 Short circuit-making test

may/june 2019 ieee power & energy magazine 91


Installed Mechanical dc CB in Nan’ao 1) the main branch is made up of four 40-kV-rated dc
Multiterminal System voltage Vis connected in series, which satisfies re-
the nan’ao multiterminal hVdc project, with a ±160-kV- quirements for meeting system voltage levels and fast
rated dc voltage, was completed by the china Southern power response times. adequate voltage sharing during dy-
Grid and put into operation at the end of 2013. this proj- namic events and static state requirements are achieved
ect includes three converter stations: Sucheng, Jinniu, and by arming each Vi with a transient grading capacitor
Qing’ao. the project collects wind power supplied to Jinniu cj, damping resistor rj, and static voltage-sharing re-
and Qing’ao Stations and sends it to the mainland. the proj- sistor R X .
ect originally adopted the same method from the Zhoushan 2) the current injection branch is divided into a hV side
project of using ac breakers to interrupt dc faults. with this and a lV side. these are isolated electrically through
method, the lowest possible power losses were achieved, and the use of an air-core transformer with mutual induc-
capital expenses were kept low. however, the project suffered tance M, where the high coupling factor k allows for
from slow dc fault-clearing times. the project was upgraded high energy-transfer efficiencies. the air-core design
in 2017, with the installation of three mechanical dc cBs provides the most efficient method because it accom-
rated 160 kV (Figure 8). modates high power transfer at high frequency.
Figure 9 illustrates the topology and shows a photo of the 3) the energy absorber consists of banks of surge arrest-
installed prototype 160-kV mechanical hVdc cB. it consists ers directly connected to the series connection of the
of the following elements. four Vis.
Functioning under an operating
principle similar to that described
Sucheng Station Jinniu Station in the section “mechanical dc cB,”
200 MW 100 MW the nan’ao mechanical hVdc cBs
Cable
use a combination of inductors and
precharged capacitors to produce
dc the current zero through the Vis.
Breaker the difference is that the storage
capacitor in this scheme is charged
Overhead Line on the lV side of the cB rather
than at the hV side. this techni-
cal solution charges the storage
capacitor C 1 to the target voltage
by introducing an uninterruptible
50 MW
Qingao Station
power system (upS) boost circuit.
the upS voltage is boosted by the
figure 8. A diagram showing the Nan’ao three-terminal HVdc transmission system isolation transformer Tc and then
with installed mechanical dc CB. rectified into a dc voltage through

Energy Absorber
MOV

VI1 VI2 VI3 VI4


Main Branch Cj Rj Cj Rj Cj Rj Cj Rj
Rx Rx Rx Rx Main Current
Branch Injection
C2 L2 HV Side Branches
Current M
Injection L1 LV Side Energy
UPS

Branches Rc Dc Absorber
C1
Tc SCR D

(a) (b)

figure 9. (a) The topology and (b) a prototype of a 160-kV mechanical HVdc CB.

92 ieee power & energy magazine may/june 2019


converter station is the receiv-
ing terminal used to supply re-
Fengning
Kangbao dc dc newable power for Beijing.
1,500 MW 1,500 MW
Breaker Breaker the Zhangbei project adopts
ac a half-bridge modular multilevel
WF 227 km 500 kV
technology and uses overhead
dc dc
Breaker Breaker lines. as a result, dc breakers
must be installed at both ends
66 km 126 km of the line to clear potential dc
faults, such as those induced by
Zhangbei dc Beijing
dc lightning. a 500-kV dc breaker
3,000 MW Breaker 3,000 MW
Breaker
prototype was developed in 2018,
ac
219 km and the project is scheduled for
500 kV
dc dc operation in 2020.
Breaker Breaker
Acknowledgment
the work for this article was
ac ac funded in part by the national
500 kV 1,000 kV
Key r&D program of china
(2017yFB0902400).
figure 10. A diagram of the Zhangbei four-terminal HVdc grid with dc CBs.
WF: wind farm. For Further Reading
D. Jovcic and K. ahmed, High
Voltage Direct Current Trans-
the hV silicon rectifier D c, where the resistor R c is used to mission: Converters, Systems and DC Grids. hoboken, nJ:
limit the inrush current during the charging process. wiley, 2015.
compa red to convent iona l mechanical dc cBs, this J. häfner and B. Jacobson, “proactive hybrid hVDc
mechanical hVdc cB is less costly and more compact breakers—a key innovation for reliable hVDc grids,”
thanks to its air-core coupling reactor and smaller key presented at the cigré 2011 Bologna Symp., Bologna,
components in the injection branch. experimental results italy.
show that the mechanical hVdc cB successfully inter- K. tahata et al., “hVDc circuit breakers for hVDc grid
rupted a 9.2-ka fault current, with peak tiV reaching 272 kV applications,” in Proc. IET Int. Conf. on AC and DC Power
in 3.9 ms. Transmission, Birmingham, u.K.: Feb. 2015. doi: 10.1049/
cp.2015.0018.
DC CB Installed in the Zhangbei HVdc Grid G. tang, Z. he, h. pang, X. huang, and X. Zhang, “Basic
Due to its geographical advantage, the Zhangbei region of topology and key devices of the five-terminal Dc grid,” CSEE
northern china has seen considerable development of proj- J. Power Energy Syst., vol. 1, no. 2, pp. 22–35, June 2015.
ects for harnessing wind energy. the development of wind G. tang, X wei, and w Zhou, “research and develop-
projects is expected to continue at least into 2020. however, ment of a full-bridge cascaded hybrid hVDc breaker for
the task of successfully integrating these resources presents VSc-hVDc applications,” in Proc. Cigré 2016 Sess., paris,
challenges, because the wind farms are located some distance paper a3-117.
from where the power is consumed and because wind and, progress on meshed hVDc offshore transmission net-
thus, energy generation are intermittent and highly variable. works. accessed on: 2018. [online]. available: https://www
many of these concerns can be addressed with the implemen- .promotion-offshore.net/
tation of hVdc networks equipped with hVdc cBs. thus, a
±500-kV, 3,000-mw four-terminal hVdc grid project has Biographies
been proposed. Dragan Jovcic is with the aberdeen hVDc research cen-
the project adopts a four-terminal ring, and the operating tre at the university of aberdeen, united Kingdom.
configuration is a bipolar topology with a metallic return line Guangfu Tang is with the Global energy interconnec-
(Figure 10). the Zhangbei and Kangbao converter stations tion research institute of the State Grid corporation of
are the sending terminals collecting local wind power. the china.
Fengning converter station is a regulating terminal connected Hui Pang is with the Global energy interconnection re-
to a local pumped-storage hydroplant, which can even out search institute of the State Grid corporation of china.
p&e
the fluctuations in the production of wind power. the Beijing

may/june 2019 ieee power & energy magazine 93

S-ar putea să vă placă și