Documente Academic
Documente Profesional
Documente Cultură
High-Voltage dc
Grid Protection
©istockphoto.com/iskrinka74
Fault Clearing
Strategies
and Protection
Algorithms
P
Protecting HigH-VoLtAge (HV) Dc griDs requires A Differ-
ent approach compared with that of ac power system protection and poses one
of the major challenges that must be resolved before the realization of large-
scale HVdc grids that use equipment from multiple vendors. HVdc grid pro-
tection, which is essential for safe and reliable HVdc grid operation, entails the
appropriate detection and fault clearing of dc-side short circuit faults (i.e., dc
faults). in this context, fault clearing refers to interrupting the dc fault current
and isolating the faulted component. fault current interruption is much more
0 0
–Udc/2 0 0
–Udc
–Udc –Udc
(a) (b) (c) (d) (e) (f)
figure 1. Three possible configurations for HVdc systems that indicate voltages during normal operation and prospec-
tive fault voltages and currents during pole-to-ground faults. (a) and (d) A symmetric monopole, (b) and (e) an asymmetric
monopole with metallic return, and (c) and (f) a bipole with metallic return.
complex in HVdc grids compared to ac systems because dc meshed connection of terminals, the power rating of ac–dc
fault currents have no naturally recurring zero crossings and, nodes, and the choice of grid configuration and grounding,
without countermeasures, quickly increase to values that are such as high-impedance grounded symmetric monopole or
unacceptable for power electronic components. conversely, low-impedance grounded asymmetric monopole or bipole.
the technologies used within HVdc grids offer options for for the selection of its components, we refer to the tech-
fault clearing beyond the well-known approach of using cir- nology used for transmission lines, converters, and fault-
cuit breakers in existing ac systems. clearing equipment. the combination of all of these aspects
determines the probability of faults in the system and their
Functional Requirements impact without HVdc grid protection.
for HVdc Grid Protection the impact of the fault on the system in terms of over-
to enable a cost-effective and reliable future power system current or overvoltage depends on the combination of fault
with HVdc grids, the design of HVdc grid protection must type and the grounding and configuration of the HVdc grid.
begin with determining the likelihood of faults occurring for pole-to-pole faults, irrespective of the grounding and
in the system, their impact on the system, and the type of configuration, dc fault currents quickly increase and reach
equipment available for clearing them. the HVdc grid- a high steady-state value in the absence of any protection.
protection design is, therefore, closely related to the overall the impact of pole-to-ground faults depends on the type of
design of the HVdc grid itself and with the selection of com- grounding: for a low-impedance grounded grid, prospec-
ponents within the HVdc grid. in this context, we refer to the tive fault currents are high, whereas for a high-impedance
overall design of the HVdc grid as the choices made in the grounded system, prospective overvoltages on the healthy
HVdc grid structure, i.e., the number of terminals, a radial or poles are high (figure 1).
the faults occurring in the system can be grouped into
several categories indicating the acceptability or unaccept-
ability of their probability and impact, which are combined
Fault Impact
Category 2: Unacceptable Impact to determine risk (figure 2). the resulting design of HVdc
grid protection will largely depend on the outcome of this risk
Category 1: Highly Unlikely
grid design has been determined, the overall objectives for they may be required to absorb a large amount of energy
every HVdc grid-protection scheme are the same: HVdc during fault current interruption.
grid protection should ensure continuity of secure power
system operation and avoid damage to system components Technology That Assists With
in case faults occur. for short circuit faults, this means that Clearing dc Faults
the HVdc grid protection should detect the faults, interrupt several means of interrupting or limiting dc fault currents
the short circuit currents, isolate the faulted component, and are available. Applied technologies include converters, ac
restore the system to a secure operation state. the protec- circuit breakers, dc circuit breakers, and combinations of
tion scheme should perform these functions without causing converter and circuit breakers.
unwanted ac or dc system instabilities. in addition, it should
avoid damage to equipment and property and guarantee AC Circuit Breakers
safety for personnel and the public. in current Vsc HVdc point-to-point schemes, ac circuit
A set of functional requirements for interacting with the breakers are installed in a converter station as the primary
connected ac system can be defined based on the constraints dc fault-interrupting device given that the ac–dc converter
for its secure operation and its components. each ac system itself, i.e., either a two-level or half-bridge modular multi-
grid code defines a maximum power imbalance that imposes level converter (MMc), has no dc fault-blocking capability.
a limit on the secure operation of the system. for instance, in for these types of converters, a fault current path from the ac
the entso-e (european) grid code, this maximum power to the dc side always exists via the antiparallel diodes within
imbalance is specified as 3 gW in continental europe for the converter’s submodules (figure 3). therefore, the ac cir-
an unspecified amount of time and in the united Kingdom cuit breakers eliminate the ac contribution to the dc fault
as 1.8 gW, to avoid a frequency deviation outside the range and typically interrupt the ac current associated with the dc
of 49.5–50.5 Hz for 60 s. HVdc grid protection should thus fault within a few cycles of the fundamental frequency. After
prevent loss of the HVDc line from causing a power imbal- eliminating the ac contribution, the dc fault current passively
ance in the connected ac system that exceeds that maximum decays to zero in a time interval that depends on converter
value. in addition to the maximum power imbalance, the topology and system parameters.
possible functional requirements for HVdc grid protection
relate to the transient stability of connected ac systems or to HVdc Circuit Breakers
the damage to its components. HVdc circuit breakers are the dc counterparts of ac circuit
Within the HVdc grid, functional requirements for HVdc breakers and can interrupt both nominal and short circuit
grid protection can be based on the continuity of the HVdc currents up to their short circuit rating. typically, HVdc cir-
grid operation itself (if required) or from the limits of its cuit breakers must interrupt currents in the 5–15-kA range
components. At present, there is no HVdc grid code that
defines the constraints within which secure operation is
achieved, and the following suggestions are given for illus-
tration purposes only. HVdc grid protection is required to SM SM SM
keep the voltage at converter terminals within certain limits Half Bridge
so they can remain connected. such a “converter dc fault SM SM SM +
ac Side dc Side –
ride through,” however, may not necessarily imply that every Full Bridge
converter remains in an active switching state or retains the SM +
capability of supporting the ac system during the entire fault –
duration. such grid protection should also avoid damage to
SM SM SM
the power electronic components and other equipment. At
present, for voltage source converter (Vsc)-based HVdc SM SM SM
point-to-point connections, the most critical components
are the converter power electronic switches, i.e., insulated-
gate bipolar transistors. in future HVdc grids, HVdc circuit figure 3. The schematic of an MMC comprising half- or
breakers (if any) could also become a limiting factor because full-bridge submodules. SM: submodule.
the fault current and limit it to a desired level instead of tics of this equipment, alternatives to the selective fault-clear-
reducing the dc fault current entirely to zero. certain types ing strategy exist. regarding these alternatives, the protection
of HVdc circuit breakers, e.g., the ones making use of con- zones used for fault current interruption do not necessarily
trollable power electronic modules, are capable of actively coincide with the components that should be isolated. these
limiting the current. superconducting fault-current limiters fault-clearing strategies can be classified in terms of “extent
use a component that is in superconducting mode during of the HVdc grid which is deenergized,” an approach followed
normal operation. therefore, it presents a low impedance to in the cigre technical brochure (tB) 739, or described in
the circuit. During faults, the superconducting component is terms of “action at the protection zone point-of-connection,”
driven out of superconducting mode, resulting in the loss of an approach followed by the european committee for elec-
superconducting capabilities and, thereby, presents a high trotechnical standardization (ceneLec).
impedance to the circuit. fault-current-limiting equipment in cigre tB 739, fault-clearing strategies are divided
can be installed in series with the transmission lines. in into three main philosophies. in the first philosophy, nonse-
this manner, they are able to limit both the transmission lective fault clearing, the entire HVdc grid is completely
line discharge currents as well as the contributions from de-energized prior to isolation of the faulted component
the ac–dc converters. fault current limiters that are located under near-zero voltage and current conditions. the faulted
in series with the ac/dc converters do not affect the line component should be identified during or after grid deenergi-
discharge currents. zation and may be automatically isolated using Hsss. After
the faulted component is isolated, the remaining part of the
High-Speed Switches HVdc grid is reenergized before power flow can resume. in
Dc high-speed switches (Hsss) can be used to quickly iso- the second philosophy, partially selective fault clearing, the
late a faulted line from the remaining dc network and oper- HVdc grid is subdivided into several protection zones. Here,
ate only under near-zero voltage and current conditions; the faulted zone is first quickly isolated from the healthy
therefore, these Hsss are not required to interrupt fault cur- zones of the grid. this requires that equipment capable of
rents. However, depending on the application, these switches interrupting dc fault currents is present at all boundaries of
may be required to interrupt small residual currents in the each protection zone. thereafter, the faulted element within
grid, which, e.g., result from passive discharge of capacitive the faulted zone is isolated, as in that of a nonselective phi-
or inductive grid components. in case residual currents have losophy. then the remaining portion of the initially faulted
zero crossings, these Hsss may make use of traditional ac zone is reenergized and reconnected to the healthy parts of
circuit breaker technology. Without current-zero crossings, the grid. the third philosophy, fully selective fault clearing,
the Hsss must provide a sufficiently high countervoltage or adopts an approach to dc fault clearing similar to the conven-
have an auxiliary circuit that creates a zero crossing, e.g., tional approach in ac systems.
a passive resonant circuit used in load transfer breakers in in the approach followed by ceneLec, three main con-
classic point-to-point HVdc connections. cepts applied within a certain protection zone are defined
based on the impact of dc faults within a protection zone on
Classification and Characterization of all ac and dc points of connection, i.e., 1) continuous opera-
Fault-Clearing Strategies for HVdc Grids tion, 2) temporary stop, and 3) permanent stop. for each of
HVdc grid protection does not necessarily implement the these concepts, a typical “fault separation time,” i.e., the
same conventional approach used for ac system protection. time at which recovery of the active power flow can start, is
in the conventional approach to ac system protection, circuit defined. these three main concepts are extended to a total
breakers are placed throughout the system and used to simul- of five when considering the availability of reactive power
taneously interrupt the fault current and isolate the faulted during dc fault separation. for a continuous operation, the
component. this has led to a fault-clearing strategy that exchange of active power with dc systems (connected at
divides the power system into zones containing grid elements a c point of connection) and active or reactive power with
such as transformers or transmission lines. in case of a fault, ac systems (connected at an ac point of connection) must
the protection scheme disconnects and de-energizes just the remain controllable during the entire fault separation pro-
zone containing the fault. given the different types of equip- cess, resulting in fault separation times of a few millisec-
ment available for HVdc grid protection and the characteris- onds. in the temporary stop concept, the disruption of active
grid as well as the faulted component isolated under voltages of the HVdc grid itself by keeping the dc voltage within an
and currents close to zero; however, it differs significantly acceptable range. these strategies require a higher invest-
from those strategies in that only a part of the HVdc grid ment cost in terms of fault-clearing equipment on the dc side
is deenergized. these strategies must rely on HVdc circuit (i.e., the HVdc circuit breakers at the end of each transmis-
breakers or dc–dc converters placed in between the protec- sion line) but may require less effort in restoring the power
tion zones to isolate the faulted zone from the healthy zones. flow, when compared with nonselective strategies. the par-
in the healthy zones, the dc voltage must be kept within the tially selective strategies face a tradeoff in limiting the extent
boundaries of the ac–dc converters to ensure power flow of the HVdc grid disconnected against the investment in dc-
continuity. in the faulted zones, any approach belonging side fault-clearing equipment. the final choice for a certain
to the nonselective protection philosophies can be used to strategy will depend on the investment costs associated with
interrupt the dc fault current and isolate the faulted com- the required fault-clearing equipment, the probability of each
ponent. After fault clearing, the faulted zone is reenergized type of fault, and the desired impact of fault clearing on the
and reconnected to the healthy zones. in figure 5(b), a par- HVdc grid itself and the connected ac systems. it is conceiv-
tially selective fault-clearing strategy is adopted to achieve able that the desired protection philosophy provides a higher
connection of systems dc1 and dc2 if an outage of the entire operation speed and fault-clearing selectivity as the grid
system, i.e., (dc1 + dc2), is, e.g., unacceptable to the con- grows in size. While each fault-clearing strategy has specific
nected ac grid, ac1. consequences for designing and operating HVdc grids, it is
plausible that systems using multiple strategies will arise,
Fully Selective With HVdc Circuit Breakers e.g., for backup and primary protection or for different sec-
for a selective fault-clearing strategy, HVdc circuit breakers tions of a single grid.
are located at the end of each line to interrupt the fault current
and simultaneously isolate the faulted line [(figure 5(c)]. this HVdc Grid-Protection Algorithms
strategy is similar to the conventional approach to ac system the functional requirements for protection algorithms used
protection, in which all of the converters adopt the continuous to detect faults and identify their location in HVdc grids are
operation concept (as defined by ceneLec), which implies largely the same as for their ac counterparts. requirements
that the fault is cleared sufficiently quickly to avoid collapse can be set for parameters such as speed, reliability, or sen-
of the dc voltage. if the symmetric monopole configuration sitivity. the main challenge is to achieve the desired reli-
is used, HVdc grid protection must also rebalance the pole ability, in terms of security and dependability, within a very
voltages when there are pole-to-ground faults. for pole rebal- small amount of time. in particular, protection algorithms
ancing, either special dc chopper circuits or converters that must make the correct decisions on whether to trip fault-
enable the injection of zero-sequence ac currents into the dc clearing equipment within the first milliseconds after fault
side can be used. detection. these decisions are based on the measured volt-
ages and currents. increased operating time of the protec-
Discussion tion algorithm may lead to a more reliable decision but
HVdc grid protection can be designed using a wide variety also to an increased overall fault-clearing time, which
of fault-clearing strategies, as described previously. choosing is unwanted given the quickly increasing dc fault cur-
a fault-clearing strategy is not straightforward and depends rent. When choosing and tuning protection algorithms,
on many factors, such as the desired overall reliability of the the HVdc grid topology, converter technology, system
power system, the relative power rating of the HVdc grid grounding, measurements, and operating points are impor-
compared to the connected ac system, the cost of fault-clear- tant considerations.
ing equipment, or adaptability of the adopted strategy to sys- this section focuses on algorithms for primary line pro-
tem expansion. the nonselective strategies only consider the tection in HVdc grids. fault detection for selective fault-
secure operation of connected ac systems and offer the lowest clearing strategies is more challenging than for nonselective
cost of all of the components at the dc side. these strategies strategies, so the focus is on algorithms for selective fault
require considerable effort to restore the HVdc grid, and grid detection. However, this does not prevent using the same
restoration times should be adapted to meet the ac system algorithms for nonselective fault-clearing strategies. the
constraints. the selective strategies consider the protection protection algorithms can be implemented using principles
based only on local measurements or on the communication refined using signal processing methods to improve their
of measurements from distinct locations in the grid. function in a noisy environment. communicationless protec-
Protection algorithms without communications rely only tion algorithms, based on undervoltage and overcurrent, are
on locally measured voltages and currents, as shown in fig- more suited to complement main or backup protection. the
ure 6(a). these algorithms can be classified as those detect- respective undervoltage or overcurrent criteria have a fixed
ing a fault during a transient and those monitoring a signal time requirement. in contrast with the fastest algorithms,
for a certain amount of time. these two criteria do not rely on the shape of the waveforms
Many of the proposed algorithms without communica- during the fault transient.
tions detect faults during the transient following the fault communication-based protection algorithms combine
event. Among these are voltage-derivative, current-deriva- information from both line ends to make a tripping deci-
tive, combinations of voltage- and current-derivative, sion and, therefore, require a communication channel to
and traveling-wave algorithms. the algorithms determine exchange logic signals or measured quantities from both line
whether the fault is inside the protection zone by using the ends, as shown in figure 6(b). the communication chan-
shape of the wavefront following a fault. Differentiating nel must allow for high-speed communication and most
wave shapes for internal and external faults requires know- likely would rely on fiber optic cables. the algorithms can
ing the electrical distance. this electrical distance is typi- be categorized as those communicating a status (directional
cally driven by the series inductors required for the HVdc comparison) and actual measurement data (differential). the
circuit breakers, which act as low-pass filters on the wave- protection zones are specific for communication-based pro-
fronts generated by external faults. remote faults on long tection algorithms and do not need dc line inductors to sepa-
cables are more difficult to detect than closer faults because rate the protection zones.
of wavefront distortion and attenuation during propagation A directional comparison can be implemented as either a
on the transmission line. the basic fault-detection meth- tripping or a blocking scheme. in both cases, a fault in the for-
ods based on transient voltages and currents can be further ward direction is detected at the local line end, which needs to
be confirmed by information from
the remote line end. in a tripping
Sharp Transient, Dampened Transient, scheme, the presence of the fault is
Easy Detection More Difficult Detection confirmed by a tripping signal from
the remote line end. A tripping
Protection Zone: Cable
signal is issued by the remote line
end if the measurements at that end
(Local) (Remote) indicate a fault in the forward direc-
dc Line dc Line
Protection Protection tion, i.e., in the direction of the pro-
tection zone. in a blocking scheme,
(a)
the presence of a fault is confirmed
Largest Smallest by the absence of a blocking signal
Communication Delay Communication Delay
from the remote line end. A block-
Protection Zone: Cable ing signal would indicate detection
of a fault in the reverse direction
at the remote end of the protection
(Local) (Remote)
dc Line dc Line zone. the tripping scheme intro-
Protection Protection duces the largest number of delays
Communication
in a directional comparison scheme;
(b) these delays occur at the local end
of the protection zone. While the
figure 6. A comparison of protection algorithms (a) without and (b) with communi- fault is perceived almost instanta-
cation. (Note that the comments refer to local dc line protection.) neously by the local measurements,
the algorithm must wait for signals communicated from the rely on an impedance between the protection zones, which,
remote line end to make a tripping decision. for HVdc grids, may be provided by an inductor in series
Differential line protection compares the currents or with the HVdc circuit breaker. for algorithms using commu-
traveling waves seen at both line ends. the basic principles nication, the algorithms may employ a traveling-wave differ-
of traveling-wave differential protection, originally devel- ential or directional-comparison protection scheme and must
oped for ac overhead line systems, may be applied to HVdc rely on a fast communication channel, such as a dedicated
systems. However, the algorithm may need an adaptation fiber optic cable.
for cable systems because of the larger influence of wave
distortion and attenuation in cable systems. for these algo- Acknowledgments
rithms, the delay caused by the wave propagation is sub- the authors acknowledge contributions from the members
tracted from the communication delay, which favors a high of Work Package 4 in the european Horizon 2020 project
speed of operation. Because these algorithms rely on the Progress on Meshed HVDc offshore transmission net-
exchange of measured quantities rather than logical signals, works (ProMotion). this work was funded by ProMo-
they impose a larger communication burden compared to tion under grant 691714.
directional algorithms.
communicationless algorithms have the advantage of For Further Reading
fast fault detection due to the absence of communication cigre, “Local control and protection of HVDc grids,”
delays but face difficulties with detecting remote faults. cigre, Paris, techn. Brochure 739, tech. rep. JWg B4/
By contrast, communication-based algorithms can detect B5.59, 2017.
remote faults while having an acceptable communication ProMotion consortium, “D4.2-Broad comparison of
delay. therefore, a combination of communication-based fault clearing strategies for Dc grids,” oct. 2017. [online].
and communicationless algorithms may be suitable for pro- Available: https://www.promotion-offshore.net/fileadmin/
tecting long lines. PDfs/D4.2_Broad_comparison_of_fault_clearing_strate-
gies_for_Dc_grids.pdf
Summary D. Van Hertem, o. gomis-Bellmunt, and J. Liang, eds.
the design of a reliable, effective HVdc grid-protection HVDC Grids for Offshore and Supergrid of the Future.
scheme depends on both system characteristics and the strat- Hoboken, nJ: Wiley, 2016.
egy used for fault clearing. system characteristics determine i. Jahn, n. Johannesson, and s. norrga, “survey of meth-
the requirements for protection by fixing the relationship ods for selective Dc fault detection in MtDc grids,” in
between the probability of faults and their impact and by Proc. 13th IET Int. Conf. AC and DC (ACDC) Power Trans-
setting constraints on secure system operation. the strat- mission, 2017.
egy used for fault clearing determines the technology to be
used (e.g., whether or not to use HVdc circuit breakers) and Biographies
determines the final impact of a fault on the system and its Willem Leterme is with energyVille, the university of Leu-
components. for HVdc grid protection, fault-clearing strat- ven (Katholieke universiteit Leuven), Belgium.
egies can be classified into three philosophies: nonselec- Ilka Jahn is with the royal institute of technology,
tive, partially selective, and fully selective. the impact of stockholm, sweden.
the fault on an ac or dc system can be determined from the Philipp Ruffing is with rheinisch-Westfälische tech-
actions taken by ac–dc converters during fault clearing. in nische Hochschule, Aachen, germany.
all cases, the fault-clearing strategies benefit from fast fault Kamran Sharifabadi is with equinor, stavanger,
detection and, in the case of a fully selective strategy, fast norway.
fault identification. the overview of protection algorithms Dirk Van Hertem is with energyVille, the university of
given here shows that these algorithms operate mainly on Leuven (Katholieke universiteit Leuven), Belgium.
traveling waves and may use a scheme without or with com-
p&e
munication. the algorithms not using communication must
Adopting
Circuit Breakers
for High-Voltage
dc Networks
S
Since the late 19th century, ac power tranSmiSSion
systems have been widely used for interconnecting multiple power-pro-
ducing plants with load centers. highly meshed ac transmission grids
with high redundancy and operating flexibility now operate worldwide.
these complex ac systems have proven reliable in securely providing
high levels of power, while also accommodating multiple voltage levels
to reduce loss.
two key components essential for transmission systems, besides
the lines themselves, are circuit breakers (cBs) and transformers. Such
units for ac transmission are relatively simple, reliable, and efficient.
cBs enable operators to open a circuit (line) under load and fault cur-
rents, which is essential for regular maintenance, system expansion, and
the physical integrity of large transmission systems. transformers make
it possible to change voltage levels, which is necessary for maintain-
ing safe and reliable systems, but also for reducing losses with long-
distance transmission.
however, ac transmission has many shortcomings, which have been
publicly debated since the war of the currents between tesla and west-
inghouse (who favored ac) and edison (who favored dc). with ac trans-
mission, reactive current transfers occur, which increase losses and
cause operating difficulties. also, for underwater cable transmission at
distances of more than 100 km, reactive power issues become severe
due to excessive line charging, making ac transmission in such applica-
tions impractical.
Digital Object Identifier 10.1109/MPE.2019.2897408
high-voltage dc (hVdc) transmission has been used since 1954. thanks
Date of publication: 17 April 2019 to important technological advances, its use has taken off in the last 20 years.
those advances include high-power electronic devices, such as thyristors and, more recently, transis-
tors, which have enabled the development of more compact voltage source converters (VScs). the vast
majority of hVdc systems consist of a single line or cable and use one ac–dc converter at each end. the
direct connection of multiple dc lines in networks has not been possible, primarily because suitable dc
cBs have not been available. nevertheless, in the last five years, two multiterminal VSc hVdc systems
have been built in china, and others are being designed and developed.
Dc transmission grids, a substantial technological advance over point-to-point hVdc connections,
are being considered for many applications worldwide. in europe, researchers involved in several major
projects have studied the use of a cable dc grid in the north Sea for integrating large amounts of offshore
wind energy and strengthening interconnections among european union countries. in china, plans have
been made for building a four-terminal dc grid with overhead lines.
For dc grids to work, the market has to offer dc cBs, preferably from multiple vendors. these cBs
must provide acceptable performance and reliability, ensure low loss, and be available in practical
sizes at a reasonable cost. much has been learned from long experience with ac cB technologies,
which are standardized at high voltage and very high current ratings. however, they are not suitable
for dc applications, and the technologies for dc cBs will be substantially different from those for ac
cBs. the performance requirements for dc cBs in dc grids are more stringent. also, opening a dc
circuit is technically much more challenging than opening an ac circuit.
over the last five to 10 years, some major advances in hVdc cB tech-
nologies have been introduced. multiple dc cB topologies have been
demonstrated in laboratories and brought to market. more recently,
these have been installed for the first time.
©istockphoto.com/smartboy10
Basic Performance
Requirements for dc CBs
1 2
1.6 GW 2 kA 2 kA 1.6 GW
CB12_1 CB12_2
CB15_1 CB25_2
ac System 1
CB14_1 ac System 2
CB23_2
5
±400 kV CB dc–ac
15_ 5 ±400 kV
5 25_ Converter
CB
_5 CB
45 35_
4 CB 5 3
1.6 GW dc CB
2 kA 400 kV
CB14_4 CB23_3 2 kA 1.6 GW
±400 kV ±400 kV
figure 1. A diagram showing a five-node dc grid with four ac–dc converters, eight dc cables, and 16 dc CBs per pole.
time) is within approximately 10 ms. this assumes that some studies of offshore environments show that the extra size and
converters may block by self-protection temporarily or per- weight of dc cBs could add significantly to platform costs.
manently, depending on the grid topology and the strategy
used for protecting the network. permanent blocking after Cost and Reliability
fault clearing occurs if the converter becomes isolated. this the widespread application of ac cBs to ac transmission sys-
results in grid capacity reduction. tems ensures a secure power supply and enables operational
flexibility. the simple dc system in Figure 1 may not provide
Ratings the same level of security and flexibility as in ac systems but,
in ac systems, ac cBs are rated for the largest available fault nevertheless, requires 32 dc cBs. the example shows that
level at their point of connection (the worst case steady-state future grids are likely to require a considerable number of dc
fault current). Dc cB prototypes recently brought to market cBs. these will cost more than ac cBs, and for some dc cB
by manufacturers are designed for only 15–20-ka peak inter- topologies the costs may be substantially higher.
rupting current. these state-of-the-art dc cBs have such low Because operators have so little experience with dc cBs,
ratings because of costs and technological limitations. the more study is needed about the internal complexity of dc cBs
ratings are, for the foreseeable future, lower than expected and their failure modes to fully understand their reliability.
fault levels at many dc buses. thus, dc cBs must operate Some dc cBs using semiconductor technologies have self-pro-
fast, before dc fault current exceeds their ratings and before tection as discussed later in this article. Such features need to be
it reaches destructive levels causing many converters to block considered by grid planners and protection system developers.
and leading to wider dc grid collapse.
Standardization of Inputs/Outputs
Bidirectional Operation in large dc grids, the protection system will consist of multiple
in many applications, dc cBs will be expected to interrupt relays (microcontroller based) and dc cBs that are intercon-
fault current in one direction only. Depending on how pro- nected and use adjusted settings controlled by the grid operator.
tection zones and protection systems are configured, some in the development of protection logic, grid topology changes
dc cBs may be expected to operate in both directions. also, and expandability must be considered as important factors.
bidirectional operation may be beneficial as a backup pro- achieving the desired operation of protection system with com-
tection function. application of a unidirectional dc cB may ponents made by different vendors requires that interconnec-
suffice in particular projects and result in substantial cost tions be standardized and that components be interoperable.
and size savings for some dc cB topologies.
Challenges With dc Circuit Opening
Fast, Multiple Open/Close Operations
Dc grids with overhead lines can be exposed to frequent DC Current Commutation
faults, many of which will be transient. as with overhead ac the first developers of dc systems learned that interrupting
transmission, reclosing with multiple cB operations within dc current is difficult. trying to separate cB contacts under
200–500 ms may reasonably be expected. with underground a current flow creates an arc, which for high-voltage systems
or underwater dc cable systems, however, almost all faults is self-sustaining and generates large amounts of heat caused
are permanent, and reclosing may not be included in the pro- by the arc resistance. with ac currents, there is a natural cur-
tection logic. the number of expected operations and timing rent-zero crossing twice every cycle (every 10 ms in 50-hz
of dc cB duty cycles may result in cost and size implications systems). this momentary current interruption—along with
for some dc cB topologies. engineering devices that ensure sufficient contact separation
and an arc-extinguishing chamber—enables modern ac cBs
Losses, Size, and Weight to reliably interrupt very large currents within 20–60 ms.
most of the time, dc cBs operate in a closed state and con- there are no natural current-zero crossings in dc systems.
duct load current. losses in closed-state dc cBs cost grid at low voltages of 10–30 V (automotive applications), the arc
operators revenue. also, dc cBs with high losses may require voltage is larger than the system voltage, and this reduces the
additional heat-removal equipment. Dc cBs will be notice- current to zero. at higher voltages, there are two principal
ably larger and heavier than ac cBs. in europe, dc grid methods to interrupt dc current.
Energy Topology
Absorber SA Figure 2 shows a typical topology
of a mechanical hVdc cB and
figure 2. A diagram showing a mechanical dc CB. illustrates the following.
18 18
16 Arcing Time 16
14 14
Idc
12 12
ILC
Current (kA)
Current (kA)
10 10
IVI1
8 8
VI2 Fully
6 6 Open
IS3
4 Trip 4 VI3 Begins
Signal VI1 Begins to Open VI3 Fully
to Close
2 VI1 Fully Open 2 Closed
0 0
0 5 10 15 20 25 30 0 5 10 15 20 25 30
Time (ms) Time (ms)
(a) (b)
100
600
VdcCB
400 80
Vdc
Energy (MJ)
Voltage (kV)
200 60
ESA
0 40
–400
0
0 5 10 15 20 25 30 0 5 10 15 20 25 30
Time (ms) Time (ms)
(c) (d)
figure 3. The four graphs show the interruption of a 15-kA peak dc fault current with a mechanical dc CB on a 400-kV
dc system, assuming a dc fault at t = 0 s. (a) Contacts require about 8 ms to fully separate. (b) The fault current is fully
extinguished after an additional 20 ms. (c) The graph indicates the arrester voltage level. (d) Energy dissipation by the ar-
resters (E SA) is about 83 MJ.
IT1
S1 T1
Residual
Breaker Auxiliary Branch
Idc Ldc IT2 dc Cable
T2A T2B dc
dc
Load
Source S2
+ Main Branch Fault +
Vdc VdcCB
– –
SA
Energy Absorber
16 16
S1 Opening
14 14 Time
12 12
Idc
10 10 IT2
Current (kA)
Current (kA)
8 8
6 6
IT1 Trip Signal
4 4
S1 Begins to Open
2 2
S1 Fully Open
0 0
0 2 4 6 8 10 0 2 4 6 8 10
Time (ms) Time (ms)
(a) (b)
800 25
VdcCB
600
20
400
Voltage (kV)
Energy (MJ)
Vdc 15
200
ESA
10
0
Fault Current
Suppression Time 5
–200
–400 0
0 2 4 6 8 10 0 2 4 6 8 10
Time (ms) Time (ms)
(c) (d)
figure 5. The four graphs show a dc fault on a 400-kV dc system interrupted by a hybrid dc CB that uses a 76-mH series induc-
tor (L dc). (a) The fault occurs at t = 0 s, and the current peaks at 15 kA. (b) S 1 begins to open when the current is transferred to
T2 . (c) The graph indicates the arrester voltage level. (d) The expected total energy dissipation (E SA) equals 21 MJ.
DC CBs Installed in China made the system more reliable and easier to control (Figure 6).
Figure 7 shows the topology and a photo of a prototype for 200-kV
Installed Hybrid dc CB in the Zhoushan hybrid hVdc cB. the three branches consist of the following:
Multiterminal System 1) the auxiliary branch carries nominal current and con-
among the islands of the Zhoushan archipelago, the largest tains a series that combines an ultrafast mechanical dis-
power-consuming islands include the main island of Zhoushan, fol- connector (uFD) with an auxiliary commutation switch,
lowed by the islands of Daishan, Qushan, yangshan, and Sijiao. which consists of a full-bridge submodule (FBSm) using
the annual load of the Zhoushan power grid reached 780 mw in high-power-rating iGBts. the FBSms appearing in the
2010, and is estimated to reach 2,000 mw in 2020 as a result auxiliary branch and main branch adopt the same full-
of higher demand stemming from economic development. bridge structure. this consists of four press-pack
a ±200-kV five-terminal VSc hVdc project, built by the iGBts and a snubber circuit. the auxiliary branch should
State Grid corporation of china, began commercial operation have as few FBSms as possible to reduce the on-state
in 2014. it transmits power from the mainland to the five islands. impedance. therefore, a 2 × 3 FBSm matrix design is
this project uses a modular multilevel converter and connects used, featuring low conduction losses and high reliabil-
by submarine cables. During normal operation, the Dinghai ity. to make maintenance easier, each FBSm uses an
converter station on Zhoushan island provides dc voltage con- integrated modular unit connected by an inductance-less
trol, and the other stations operate in power control modes. as busbar. a water-cooling system is needed because the
a result, the power flows from the Dinghai Station to the other auxiliary branch conducts the long-term load current.
stations. Due to the lack of hVdc cBs, clearing a dc fault was Because the uFD is opened with zero current, the con-
originally achieved by slow-acting operations of ac system tacts inside take up less space, and its driving mechanism
breakers. the lack of rapid fault isolation and the inability to is lightweight. the compact design is achieved by using a
switch circuits caused several technical problems, indicating a Vi with a voltage rating of 40.5 kV and current rating of
need for improved system security, greater operating flexibility, 2 ka rather than an SF6 cB. the maximum separation
higher reliability, and faster system restoration capabilities. time of the breaker must be within 2 ms to meet the fault-
in 2016, a hybrid dc cB rated 200 kV was installed at clearance time requirements of the Zhoushan project. as
the Dinghai Station on the Dinghai-to-Daishan line, which a result, a series connection of six Vis is adopted, and
each Vi is equipped with voltage-sharing devices.
2) the main branch interrupts fault currents and consists of
Yangshan Station Sijiao Station four series-connected modular units. each modular unit
100 MW 100 MW contains 36 FBSms in a series connection designed for
50-kV and 15-ka breaking capability. a cooling system
is not necessary for the main branch because it only ex-
periences the fault current for several milliseconds. the
32 km FBSm topology provides a bidirectional current path and
allows the hybrid cB to interrupt the fault current in either
39 km
direction. in addition, the capacitors in the FBSm enable
dc
Breaker soft turn-off of the iGBts, significantly decreasing the in-
46 km 17 km
duced voltage stress and balancing the voltage distribution
across the modular unit during fault interruption.
400 MW 3) the energy absorber branch is made up of surge arresters
Dinghai Station that limit transient interruption voltages (tiVs) and dis-
sipate the magnetic energy stored in the system.
300 MW 100 MW the installed hybrid hVdc cB offers the following ad-
Daishan Station Qushan Station vantages:
✔ a small footprint and low height, resulting from the
figure 6. A diagram showing the Zhoushan five-terminal integrated and compact design (installed at a 200-kV
HVdc transmission system with the installed hybrid dc CB. high-potential platform)
Auxiliary Branch
iT1
Ultrafast Auxiliary
Disconnector FBSM Branch
Energy Absorber
uDB
(a) (b)
figure 7. (a) The topology and (b) a prototype of a 200-kV hybrid HVdc CB.
table 1. Factors related to testing the insulation and operating characteristics of HVdc CBs.
Number Test Test Object Items Objective
1 Insulation test Phases to ground DC voltage withstand test To verify the voltage-withstanding
capacity and partial-discharge level of
2 Switching impulse withstand test support structure
3 Lightning impulse withstand test
4 Across open DC voltage withstand test To verify the voltage-withstanding
contacts capacity across open contacts
5 Switching impulse withstand test
6 Operating test Key components Peak withstand current test To verify the current-withstanding
capacitor of the CB
7 Overload withstand current test
8 Short-time withstand current test
9 Short-time withstand current test
10 Overall prototype Rated current-interruption test To verify the current-interruption
capacity and interruption time
11 Short circuit current-interruption test of the overall prototype and the
12 Rated current-making test program correctness of the control
and protection system
13 Short circuit-making test
Energy Absorber
MOV
Branches Rc Dc Absorber
C1
Tc SCR D
(a) (b)
figure 9. (a) The topology and (b) a prototype of a 160-kV mechanical HVdc CB.