Sunteți pe pagina 1din 12

MCBs or Miniature Circuit Breakers are electromechanical devices which protect an electrical circuit from an

overcurrent. The overcurrent, in an electrical circuit, may result from short circuit, overload or faulty design. An
MCB is a better alternative to a Fuse since it does not require replacement once an overload is detected. Unlike

fuse, an MCB can be easily reset and thus offers improved operational safety and greater convenience without

incurring large operating cost.

MCB or Miniature Circuit Breakers Fig.1: Image


of MCB

The principal of

operation is
simple. An MCB
functions by
interrupting the

continuity of
electrical flow
through the
circuit once a
fault is

detected. In
simple terms
MCB is a switch
which
automatically

turns off when


the current flowing through it passes the maximum allowable limit. Generally MCB are designed to protect
against over current and over temperature faults (over heating).

There are two contacts one is fixed and the other moveable. When the current exceeds the predefined limit a
solenoid forces the moveable contact to open (i.e., disconnect from the fixed contact) and the MCB turns off

thereby stopping the current to flow in the circuit. In order to restart the flow of current the MCB is manually
turned on. This mechanism is used to protect from the faults arising due to over current or over load.
To protect against fault arising due to over heating or increase in temperature a bi-metallic strip is used. MCBs
are generally designed to trip within 2.5 millisecond when an over current fault arises. In case of temperature
rise or over heating it may take 2 seconds to 2 minutes for the MCB to trip.
This article covers the insight of a single pole MCB commonly used in the house hold. The following image
shows the different internal parts of an MCB with top casing removed. The subsequent sections will examine
each part and its function.

Fig. 2: Internal Specifications of MCB

Tripping mechanism of MCB


The following image illustrates the tripping mechanism of the MCB. The circuit breaker contacts and the position
of the knob can easily be seen in both, ON and OFF, state. In the ON state the moveable contact touches the
fixed contact as shown in the image.

MCB or Miniature Circuit Breakers Fig. 3: ON State of MCB

The path of the current in the ON state is shown in the image below. The
live wire is screwed at the input terminal. From the input terminal the current flows to the fixed contact which is
touching the input terminal. The current then moves to the moving contact (since in the ON state it is touching
the fixed contact). The moving contact is connected to the electromagnetic coil of the solenoid by means of a
thick wire. The current from the moving contacts enters the electromagnetic coil. The current from the coil goes
to the bimetallic strip by means of another thick wire and finally to the output terminal where it is collected by
the neutral wire of the line.

MCB or Miniature Circuit Breakers Fig. 4: Coil Arrangement and Layout of Internal Parts

Connections of the coil


The following images clearly show the connection of the endpoints of the coil with the other parts of the circuit
and how the current enters and exits the coil.

Fig. 5: Image showing Connection Pattern of Coil

Switching Mechanism
The switching or the tripping mechanism can be closely observed in the following images. This mechanism is
used to automatically cut off the supply of the current when the current exceeds the permissible limits thereby
preventing any damage to the appliances.

Fig. 6: Switching Mechanism or Tripping Mechanism


Let
us

understand this system in further detail. The image below shows a closure look of the different parts of the
tripping mechanism. The moving part of the solenoid is called the plunger. It is like a solid semi cylinder
connected to a hammer at one end. The moveable contact is positioned slightly above the plunger and moves
axially along the plunger. It does not touch the plunger.

Fig.
7:

Plunger Mechanism

Role of Plunger
The heart of this mechanism is the solenoid which works on the principle of electro mechanism. As mentioned
earlier one end of the coil is connected to the moveable contact by means of a thick wire for current to pass
through it in the ON state. The coil of the solenoid is designed in such a way that when current passing through
it is within the permissible value, the magnetic force produced is not enough to pull the plunger. When the
current exceeds the permissible value, the magnetic force also increases and this magnetic force pulls the
plunger inside towards the center of the coil.

Fig. 8: Images showing Movement of Plunger

When the plunger moves it also pulls the moveable contact and forces it to separate from the fixed contact
thereby tripping the circuit. The moveable contact is connected to the knob by means of mechanical
arrangement and forces the MCB knob to fall down. The plunger is connected to a spring from inside the
electromagnetic coil and as the plunger moves towards the center of the coil, the spring gets loaded. After the
MCB trips (i.e., the moveable contact separates from the fixed contact and the current stops flowing) the spring
forces the plunger back to its normal state without disturbing the moveable contact.

Fig. 9: Moveable Contact--Plunger Arrangement


Mechanical Assembly
On further disassembling, different parts of this mechanical system can be seen. The images below shows all
the parts of the switching mechanism which are further detailed in the subsequent images.

Fig. 10: Dissambled view of Parts of Switching Mechanism


The following image shows the connection of the moveable contact with the coil. A thick wire carries the current
from the movable contact to the coil.

Fig. 11: Image showing Connection of Moveable Contact with Coil

Structure of Plunger
The image shows how the spring loaded mechanism works. The spring which is connected to the rod of the
plunger pushes the plunger back to its rest position once the tripping has taken place.

Fig. 12: Plunger and spring Arrangement

The image below shows the structure and arrangement of plunger, the moveable contact and the spring.

Fig. 13: Structure and Arrangement of Plunger, Moveable Contact, and Spring

Arrangement of mechanical parts


The dismantled mechanical parts used to pull the knob when the tripping takes place. When the MCB gets
tripped the moveable contact which is connected to the knob using these mechanical parts pulls the knob to the

off position.

Fig. 14: Dismantled parts of PCB

The following image shows the arrangement of the plunger, coil and the spring.

Fig. 15: Arrangement of Plunger, Coil, and Spring

Parts of MCB
The outgoing and incoming terminals have been shown in the following image.
Fig.
16:

Outgoing
and
Incoming
Terminals

All the parts


of this single

pole MCB
have been

shown
together in

the following
image.

Fig. 17:
Parts of
Single Pole
Assembly
Parts

Arc quenching
Arc quenching in MCB (Miniature Circuit Breakers)
Another important point to be considered in the design of circuit breakers is Arc quenching. To understand how

MCB carries out the arc quenching, it is important to know about the electric arc and how is it produced. When
an overcurrent is interrupted by the circuit breaker by opening its contacts, current tries to bridge the gap. In an

attempt to maintain the circuit, the air heats up and becomes a conductor. As a result an arc forms. In general,
when air and gases are heated, they become electric conductors. The hotter they get, the better they conduct.
The following image shows how an electric arc looks like.

Fig. 18: Image of Electric Arc

The heat from an uncontrolled arc in a circuit breaker can cause a rapid and violent expansion of the nearby air
and could severely damage the circuit breaker. Therefore, besides separating the electrical contacts, a circuit

breaker also has to quickly extinguish the arc. A number of factors can be employed for quenching the arc, such
as, speed, distance, dielectric strength, cooling etc.

a) Speed : When the contacts separate rapidly, there is less time for the arc to form and maintain itself.
b) Distance : When the distance between opened contacts is more, the arc has to stretch more to maintain

the current flow which requires more voltage.


c) Cooling : When the arc is forced against a cold material, it absorbs and dissipates the heat.

d) Dielectric Strength : When the arc is submerged in a medium with higher dielectric strength than air (sulfur
hexafluoride, SF6), the insulating nature of the medium helps in quenching the arc.

In an MCB, arc chutes or arc dividers are used for arc quenching. When the contacts of an MCB separate,

generating an electrical arc between them through air, the arc is moved into the arch chute where it is divided
into

small
segments. The overall energy level of the arc gets split up which is not sufficient to sustain the arc and

therefore it gets dissipated.

Fig. 19: Mechanism of Arc Production

Arc Chutes
The image below shows the arc chute used in the MCB for arc

quenching purposes.

Fig. 20: Arc


chute

Finally the next

images shows

how the arc chute

is positioned in

the MCB. The

fixed contact is

extended to the arc chute. This is done so as to transfer the arc to the interior of the breaker. The arc is broken

into smaller arc by the arc chute. These segmented smaller arc have a very small potential and hence get

naturally dissipated.

Fig. 21: Mechanical Arrangement of Arc Chute

On removing the holder which holds the arc chute, the mechanical structure and arrangement of the arc chute is

visible in the next image.

Fig. 22: Bimetallic Strips

Over heat protection


Over heat protection
The MCB’s also provide protection against overheating. It uses a bimetallic strip for the same. The arrangement

of the bimetallic strip is shown in the image below. The bimetallic strip is made up of two metals with different

temperature coefficients. When the current flows through the bimetallic strip, it gets heated. The heating results
in

bending of the bimetallic strip. The more is the heating, the more is the bending. The bimetallic strip is

mechanically connected to the tripping mechanism by means of a metal strip as shown in the image. When the

bimetallic strip bends it forces the metal strip to pull the plastic flap which in turn triggers the tripping mechanism
after certain allowed temperature limit for which the bimetallic strip is designed.

Fig.

23:

Mechanics of MCB Interiors

S-ar putea să vă placă și