LF_SMS SS#1_LCSS#8_SGPT Recommended Setting

L S I G
Board Panel No Panel Name Release Type and make Rating Curve
Pick Up(A) Curve Time(Sec) Pick Up(A) Curve Time(Sec) Pick Up Pick Up
Time(DT)
P02 IC-1 SACE PR122/P-LSIG 4000 0.69 6 1.6 0.5 3 0.1 0.5
P08 BC-1 SACE PR122/P-LSIG 4000 0.45 6 1.6 0.4 3 0.1 0.4
P11 IC-2 SACE PR122/P-LSIG 4000 0.69 6 1.6 0.5 3 0.1 0.5
LCSS#8 P03,P10 LF Process PDB SACE PR122/P-LSIG 1250 0.85 3 2.8 0.3 4 0.12 0.3
P04,P13 LF Main MCC SACE PR122/P-LSIG 800 0.85 3 3.5 0.3 5 0.15 0.3
P05 Welding PDB SACE PR122/P-LSIG 800 0.85 3 3.5 0.3 5 0.2 0.3
P07,P12 Auxiliary PDB SACE PR122/P-LSIG 800 0.85 3 3.5 0.3 5 0.15 0.3
LF Process PDB
IC-1 SACE PR122/P-LSIG 1250 0.8 3 2.8 0.3 4 0.12 0.3
LF Process PDB BC-1 SACE PR122/P-LSIG 1250 0.55 3 2.8 0.2 4 0.12 0.2
IC-2 SACE PR122/P-LSIG 1250 0.8 3 2.8 0.3 4 0.12 0.3
LF Main MCC
IC-1 SACE PR122/P-LSIG 800 0.8 3 3.5 0.3 5 0.15 0.3
LF Main MCC BC-1 SACE PR122/P-LSIG 800 0.55 3 3.5 0.2 5 0.15 0.2
IC-2 SACE PR122/P-LSIG 800 0.8 3 3.5 0.3 5 0.15 0.3
Welding PDB
IC-1 SACE PR122/P-LSIG 800 0.8 3 3.5 0.3 5 0.15 0.3
Welding PDB BC-1 SACE PR122/P-LSIG 800 0.55 3 3.5 0.2 5 0.15 0.2
IC-2 SACE PR122/P-LSIG 800 0.8 3 3.5 0.3 5 0.15 0.3
Auxiliary PDB
IC-1 SACE PR122/P-LSIG 800 0.8 3 3.5 0.3 5 0.15 0.3
Auxiliary PDB BC-1 SACE PR122/P-LSIG 800 0.55 3 3.5 0.2 5 0.15 0.2
IC-2 SACE PR122/P-LSIG 800 0.8 3 3.5 0.3 5 0.15 0.3

6.6kV_Upstream_2MVA Trafo Setting SEF Setting


Pick-Up 0.87 Current Setting 150 A
51> TMS 2.1 0.6 For NI Curve
TMS
Curve IEC VI 0.3 For EI Curve

Time Delay for


Pick Up 4.7 1 Sec
50> Upstream Tripping

DELAY(in milisec) 500 Settings are as per the


setting provided by TCE
50>>> Pick Up 14.8
for Auxiliary Trafo feed
DELAY(in milisec) 50 from T&D boards
Pick Up 0.25
50N> TMS 0.1
Curve DT
Pick Up 2
50N>>>
DELAY(in milisec) 50
CTR 200/1
NOTE: Care to be taken while uploading 50>> and 50N>> setting as same is used for
buszone blocking.This setting not to be changed.
LF HT Motor Setting
200kW Soft Water Pump Motor 500kW ID FAN Motor
SIEMENS_7SJ62 SIEMENS_7SJ62
CTR 40/1 CTR 100/1
THERMAL OVERLOAD ON THERMAL OVERLOAD ON
Termal Threshold K-Factor 0.59 Termal Threshold K-Factor 0.59
Time Constant Tth 60 Time Constant 75
Thermal Alarm 90 % Thermal Alarm 90 %
I. Alarm 0.59 I. Alarm 0.59
Kτ Factor 1.5 Kτ Factor 4
START PROTECTION ON START PROTECTION ON
I.motor start 3.3 × In I.motor start 3.36 × In
Start up Time 3 Sec Start up Time 42 Sec
Temp. Limit for cold motor (in %) 33 % Temp. Limit for cold motor (in %) 33 %
Startup time for warm motor (sec) 3 Sec Startup time for warm motor (sec) 42 Sec
Permissible locked rotor time(sec) 7.5 Sec Permissible locked rotor time(sec) 32 Sec
RESTART INHIBIT ON RESTART INHIBIT ON
Motor I.start / I.Norm 6 Motor I.start / I.Norm 6
Max. Permissible start time (T. Start Max) Max. Permissible start time (T. Start Max)
(Sec) 3 Sec (Sec) 42 Sec
Equilibrium Time (T equal) (Min) 1 Min Equilibrium Time (T equal) (Min) 1 Min
Min Inhibit Time Min Inhibit Time
(Min) 20 Min (Min) 20 Min
Max Permissible No of warm start 2 Max Permissible No of warm start 2
Difference between Cold & Warm start 1 Difference between Cold & Warm start 1
Extension K-Factor for cooling simulation of rotor Extension K-Factor for cooling simulation of rotor
at Zero speed (kτ at Stop) 5 at Zero speed (kτ at Stop) 5
Extension factor forcooling time constant with Extension factor forcooling time constant with
motor running (kτ at Run) 3 motor running (kτ at Run) 3
LOCKED ROTOR ON LOCKED ROTOR ON
Trip Current Threshold (I.stall) 1.5 × In Trip Current Threshold (I.stall) 1.57 × In
Trip Time Delay 7.5 Sec Trip Time Delay 32 Sec
Alarm Current Threshold (I.alarm) 1.3 Alarm Current Threshold (I.alarm) 1.4
Alarm Time Delay 0 Sec Alarm Time Delay 0 Sec
Blocking Duration After Motor Start (Tstart blk) 0 Sec Blocking Duration After Motor Start (Tstart blk) 42 Sec
UNBALANCE PROTECTION ON UNBALANCE PROTECTION ON
Neg. Seq. Current Threshold (I2>) 0.21 × In Neg. Seq. Current Threshold (I2>) 0.2 × In
Time Delay (T I2>) 5 Sec Time Delay (T I2>) 5 Sec
Curve Type DT Curve Type DT
Neg. Seq. Current Threshold (I2>>) 0.11 Neg. Seq. Current Threshold (I2>>) 0.11
Time Multiplier Setting (TMS I2>>) 2.1 Time Multiplier Setting (TMS I2>>) 2.1
Curve Type EI Curve Type EI
EARTH FAULT ON EARTH FAULT ON
CB CT Ratio 75/1 CB CT Ratio 75/1
Current Threshold (Io>) 0.04 × In Current Threshold (Io>) 0.07 × In
Time Delay (T Io>) 0.1 Sec Time Delay (T Io>) 0.1 Sec
Curve Type DT Curve Type DT
Rstab 85 OHM Rstab 85 OHM
SHORT CIRCUIT ON SHORT CIRCUIT ON
Current Threshold (I>) 3.95 Current Threshold (I>) 4.05
Time Delay (T I>) 50 ms Time Delay (T I>) 50 ms
Current Threshold (I>>) _ Current Threshold (I>>) _
Time Delay (T I>>) _ Time Delay (T I>>) _
Current Threshold (I>>>) Current Threshold (I>>>)
Blocking Blocking
Time Delay (T I>>>) Time Delay (T I>>>)

Not Applicable as CB CT is used for Earthfault Protection