C ATA LO G
—
The SACE Tmax PV range of
molded-case circuit-breakers and
switch-disconnectors for
photovoltaic applications offers an
increasingly comprehensive,
leading-edge solution that
anticipates the market trends.
C ATA LO G 3
—
Table of contents
01-07 Introduction
26-41 UL applications
—
CHAPTER 1
Introduction
02-03 Keeping ahead of the photovoltaic application trends
—
Keeping ahead of the photovoltaic
application trends
The SACE Tmax PV range of molded-case circuit- This trend is a known fact. By 2020, according to
breakers and switch-disconnectors for IEC and estimates, 93% of PV systems above one
UL applications on both the DC and AC sides of a megawatt will function with 1500V DC rated
photovoltaic plant, expands the widely voltage, especially in the area where UL
appreciated ability of the SACE Tmax T range to regulations are applicable. This will help to
provide the most adaptable and versatile solution increase the power density and significantly
for every type of application. The SACE Tmax PV reduce the number of combiners, inverters and
range was created with internationalization in conductors required compared to the currently
mind. It offers design engineers, panel builders used 1000V DC systems.
and inverter manufacturers the chance to rely on
a single provider and meet the specific
requirements of photovoltaic systems installed in
any part of the world.
A range that keeps pace with the times. But the
trend in photovoltaic systems is a growing use of
configurations based on string inverters and an
increase in operating voltages. The aim is to
enhance energy efficiency and limit the rated
currents involved, thereby reducing switchgear
size, installation time and costs.
INTRODUCTION 3
For use in such applications, the SACE Tmax PV This is especially the case in PV systems based on
range includes a series of molded-case circuit- configurations with string inverters, which
breakers and switch-disconnectors for PV typically require extremely long cables.
applications up to 1500V DC that conform Here again, the SACE Tmax PV range is one step
perfectly to UL and IEC standards. ahead of market requirements and proposes a line
Meanwhile, the AC equipment in photovoltaic of circuit-breakers for alternating current with
systems is also evolving at a continuous rate. The increased rated voltage values up to 800V AC.
inverters used at the present time are designed
to operate in coordination with 600 or 690V AC
distribution systems. Since they are connected to
the grid by transformers, new installations are
designed by increasing the voltage values and
reducing the losses, so as to create increasingly
efficient systems.
4 S AC E T M A X P V FO R P H OTOVO LTA I C A P P L I C AT I O N S A D A P TA B I L I T Y, V ER S AT I L I T Y A N D CO M P L E T E F R EED O M
—
Value proposition
Edge technologies to be a step ahead
— —
Energy efficiency Speed up your projects
SACE Tmax PV technology is ready to boost the Ensuring performances at 1500V for the DC side
overall trends toward higher voltages, either in PV and 800V for the AC side, SACE Tmax PV range
systems based on central inverters, where 1500V grants shorter installation times and lower wiring
on the DC side has become a market standard, costs for the most advanced photovoltaic plants
and in PV systems based on string inverters, architectures, with significant time savings for
where 800V on the AC side is the most up-to-date utilities, engineers and panel builders.
solution to cut down power losses. To be
highlighted that SACE Tmax PV range offers the
first 800V AC molded case circuit-breaker
according to UL 489 Standard available in the
market.
—
Space saving
Higher voltages running through a photovoltaic
plant means a reduced number of components
and easier logistics. Furthermore, SACE Tmax PV
range is one of the most compact in the market
and offers an integrated motorized version that
squeezes the sizes to unexpected limits.
INTRODUCTION 5
— —
Easy to install Global availability
SACE Tmax PV range offers a complete portfolio Inside the Tmax PV range you find products
of shared accessories, including connection meeting all the major worldwide Standards: IEC,
jumpers as mandatory for the UL versions. The UL, CCC and GB. This means that engineers, panel
jumper kits provide simplicity of installation and builders, inverter manufacturers and OEMs can
maximum safety. The SACE Tmax PV range is find the right solution for any solar plant,
derived from the widely known SACE Tmax T wherever it will be installed around the world.
range, ensuring edge technology, top-level
quality and no need to change installation
practices. Furthermore, SACE Tmax PV range is
perfectly integrated in the wide range of
electrical and mechanical accessories already
present in the SACE Tmax T range.
6 S AC E T M A X P V FO R P H OTOVO LTA I C A P P L I C AT I O N S A D A P TA B I L I T Y, V ER S AT I L I T Y A N D CO M P L E T E F R EED O M
—
Examples of photovoltaic plants
2 3 5
3 5 7 8
6
1
3
4 7
4 7
4 7
1. String Combiner
2. Molded Case Switch-Disconnector (e.g. T4D/PV-E)
3. Molded Case Circuit-Breakers Tmax PV (e.g. T4N/PV-E)
4. AC Combiner
5. Molded Case Circuit-Breakers for AC applications (e.g. T4V-HA)
6. Switchboard / AC Recombiner
7. Molded Case Circuit-Breakers for AC applications (e.g. T5V-HA)
8. Air Circuit-Breaker Emax 2
9. MV/LV Transformer - Compact Secondary Substation
INTRODUCTION 7
2 4
3
2 4 5 6 7 8
2 4
1. String Combiner
2. Molded Case Switch-Disconnector (e.g. T4D/PV-E)
3. Recombiner
4. Molded Case Circuit-Breakers (e.g. T4N/PV-E)
5. Molded Case Switch-Disconnector (e.g. T7D/PV-E)
6. Central inverter
7. Air Circuit-Breaker Emax 2
8. MV/LV Transformer - Compact Secondary Substation
8 S AC E T M A X P V FO R P H OTOVO LTA I C A P P L I C AT I O N S A D A P TA B I L I T Y, V ER S AT I L I T Y A N D CO M P L E T E F R EED O M
I E C A P P L I C AT I O N S 9
—
CHAPTER 2
IEC applications
10-10 Flexibility guaranteed for new IEC compliant
requirements
11-12 Ranges
22-25 Dimensions
10 S AC E T M A X P V FO R P H OTOVO LTA I C A P P L I C AT I O N S A D A P TA B I L I T Y, V ER S AT I L I T Y A N D CO M P L E T E F R EED O M
—
Flexibility guaranteed for new IEC
compliant requirements
In accordance with IEC 60947-3 and IEC 60947-2 specifications, the SACE Tmax
PV range proposes molded-case circuit-breakers and switch-disconnectors for
standard 1100V DC applications as well as a versatile choice of extended ratings
up to 1500V DC for today's increasingly demanding solar applications.
Connection jumpers are available for the SACE Tmax PV IEC range for
enhanced safety and ease of installation.
The SACE Tmax PV IEC range has been Thanks to dedicated jumper kits, all the poles
developed in order to protect the plant up to can be connected to a single polarity source
1500V DC. In addition, the T4N/PV-E series of with 4 poles in series or, alternatively, to a dual
extremely compact molded-case circuit- polarity source with 2 poles in series on the
breakers for applications up to 1500V DC with positive supply and two on the negative supply.
100 to 250A rated current is the best solution Similarly to all the other products in the range,
for protection and isolation, mainly in PV T4N/PV-E molded-case circuit-breakers can be
systems where centralized inverters are used. fitted with a vast assortment of electrical and
Available in the 4-pole version, T4N/PV-E mechanical accessories already available for
molded-case circuit-breakers are able to break the SACE Tmax T range.
short-circuit currents up to 25 kA in accordance
with standard IEC 60947-2 edition 5.0 Annex P,
and up to 10 kA in accordance with standard
IEC60947-2 edition 4.2 and GB14048.2.
I E C A P P L I C AT I O N S 11
—
Ranges
—
Ranges
Electrical charachteristics
Tmax PV circuit-breaker in compliance with IEC 60947-2 T4N-PV/E
Frame size (A) 250
Rated service current (A) 100-250
Number of poles (No.) 4
Rated sevice voltage, Ue (V) 1500
Rated impulse withstand voltage, Uimp (kV) 8
Rated insulation voltage, Ui (V) 1500
Rated ultimate short-circuit breaking capacity (kA) 25 according to IEC 60947-2 Edition 5.0 Annex P (τ = 1 ms)
@ 1500V DC, Icu (kA) 10 according to IEC 60947-2 Edition 4.2 and GB 14048.2 (τ = 5 ms)
Rated service short-circuit breaking capacity (kA) 20 according to IEC 60947-2 Edition 5.0 Annex P (τ = 1 ms)
@ 1500V DC, Ics (kA) 7.5 according to IEC 60947-2 Edition 4.2 and GB 14048.2 (τ = 5 ms)
Trip Unit TMF
Versions F
Standard terminals FCCu
Connections* Jumpers
Mechanical life (No. Operations) 7500
Electrical life (operations @ 1500V DC) (No. Operations) 1000**
Basic dimensions W (mm/in) 140/5.52
D (mm(in) 103.5/4.07
H (mm/in) 205/8.07
Weight (with standard teminals only) (kg/lbs) 3.05/6.72
* Selection of one of the jumper connection options is mandatory; ** Opening with SOR or UVR
I E C A P P L I C AT I O N S 13
—
Characteristic curves
Trip curves
T4N/PV-E TMF 250
In = 100 ... 250A
t [s]
104
103
102
10
10-1
I3 = 5 x In
10-2
10-1 1 10 102
x I1
14 S AC E T M A X P V FO R P H OTOVO LTA I C A P P L I C AT I O N S A D A P TA B I L I T Y, V ER S AT I L I T Y A N D CO M P L E T E F R EED O M
—
Characteristic curves
Limitation curves
T4N/PV-E T4N/PV-E
@ 1500V tau = 1ms @ 1500V tau = 5ms
Ip [kA] Ip [kA]
102 102
10 10
1 1
10-1 10-1
10-1 1 10 102 10-1 1 10 102
x I1 x I1
1 1
10-1 10-1
10-2 10-2
10-1 1 10 102 10-1 1 10 102
x I1 x I1
I E C A P P L I C AT I O N S 15
—
Quick reference tables
Size
LOAD T1D/PV LOAD
2+2 - lower
LOAD LOAD
LOAD LOAD
LOAD LOAD
LOAD LOAD
LOAD
LOAD 4PS - lower LOAD
LOAD LOAD
LOAD LOAD
LOAD LOAD
LOAD LOAD
LOAD
LOAD LOAD
4PS - upper
LOAD
LOAD
LOAD LOAD
LOAD LOAD
LOAD
LOAD LOAD LOAD LOAD LOAD
LOAD LOAD
LOAD LOAD
LOAD T3D/PV LOAD
2+2 - lower LOAD
LOAD
LOAD
LOAD
LOAD LOAD
LOAD LOAD LOAD LOAD
LOAD
LOAD LOAD LOAD LOAD
LOAD
LOAD
LOAD LOAD LOAD LOAD
LOAD LOAD
2+2 LOAD
- upper LOAD
LOAD
LOAD LOAD
LOAD LOAD
LOAD
LOAD
LOAD LOAD
LOAD
4PS - lower LOAD
LOAD LOAD
LOAD LOAD
LOAD LOAD
LOAD LOAD
LOAD
LOAD LOAD
LOAD LOAD
LOAD LOAD LOAD
LOAD LOAD
LOAD
LOAD
LOAD LOAD
LOAD
LOAD LOAD LOAD
LOAD LOAD
LOAD
LOAD LOAD
LOAD LOAD
LOAD
LOAD
LOAD
LOAD
I E C A P P L I C AT I O N S 17
LOAD LOAD
LOAD LOAD
LOAD LOAD
LOAD
Size LOAD
LOAD LOAD
T4D/PV 2+2 - lower LOAD LOAD
LOAD LOAD
LOAD LOAD
LOAD LOAD
LOAD LOAD
LOAD LOAD
2+2 - upper
LOAD LOAD LOAD LOAD
LOAD LOAD
LOAD LOAD
LOAD
LOAD LOAD
LOAD
LOAD LOAD
LOAD
LOAD LOAD LOAD
LOAD LOAD LOAD
LOAD 4PS -LOAD
upper LOAD
LOAD LOAD
LOAD LOAD LOAD LOAD
LOAD LOAD
LOAD
LOAD
LOAD LOAD
LOAD LOAD LOAD LOAD LOAD
LOAD LOAD
LOAD
LOAD
LOAD LOAD
LOAD
LOAD LOAD LOAD
LOAD
LOAD
LOAD 4PS - lower
LOAD LOAD
LOAD LOAD
LOAD
LOAD
LOAD
LOAD
LOAD LOAD
LOAD LOAD
LOAD
4PS - upper
LOAD
LOAD
LOAD LOAD
LOAD
LOAD
LOAD
LOAD
LOAD
LOAD LOAD
LOAD
18 S AC E T M A X P V FO R P H OTOVO LTA I C A P P L I C AT I O N S A D A P TA B I L I T Y, V ER S AT I L I T Y A N D CO M P L E T E F R EED O M
— LOAD LOAD
LOAD LOAD
LOAD LOAD
LOAD LOAD
LOAD LOAD
LOAD LOAD
LOAD LOAD
LOAD LOAD
LOAD LOAD
LOAD LOAD
LOAD LOAD
LOAD LOAD
LOAD LOAD
LOAD LOAD LOAD
LOAD LOAD
LOAD
LOAD LOAD
Size LOAD LOAD
LOAD LOAD
LOAD LOAD LOAD LOAD
LOAD
LOAD
LOAD LOAD
LOAD 2+2 - upper
LOAD
LOAD
LOAD LOAD
LOAD
LOAD
4PS - lower
LOAD
LOAD
LOAD
LOAD
LOAD
LOAD
LOAD
LOAD LOAD
LOAD
LOAD LOAD
LOAD LOAD
LOAD LOAD
LOAD
LOAD LOAD
LOAD
LOAD LOAD
LOAD LOAD
LOAD
LOAD LOAD
LOAD LOAD
LOAD
T7D/PV LOAD 2+2 - lower LOAD
1)
LOAD LOAD LOAD
LOAD LOAD
LOAD LOAD
LOAD 2+2 - upper
LOAD
LOAD
LOAD
LOAD
LOAD
LOAD
LOAD
4PS - lower LOAD
LOAD
LOAD LOAD
LOAD
LOAD
4PS - upper
LOAD LOAD
LOAD
LOAD
LOAD
I E C A P P L I C AT I O N S 19
LOAD LOAD
LOAD LOAD
LOAD Size LOAD
LOAD LOAD
LOAD LOAD
T4N/PV-E
LOAD LOAD
LOAD LOAD
LOAD LOAD
2) 2) 2)
LOAD
LOAD
LOAD LOAD
LOAD LOAD
LOAD
LOAD LOAD LOAD LOAD LOAD
LOAD LOAD 4PS - lower
LOAD LOAD
LOAD
LOAD
LOAD
LOAD
LOAD
LOAD LOAD
LOAD LOAD
LOAD LOAD
4PS LOAD
-LOAD
upper LOAD LOAD
LOAD
LOAD
LOAD LOAD LOAD LOAD
LOAD LOAD
LOAD LOAD
LOAD 2) LOAD 2) 2)
LOAD
LOAD
LOAD LOAD LOAD
LOAD LOAD LOAD
LOAD
LOAD
LOAD LOAD
LOAD LOAD LOAD
LOAD LOAD
LOAD LOAD
LOAD LOAD LOAD
LOAD
LOAD LOAD
LOAD
T7D/PV-E 2+2 - upper LOAD
LOAD
LOAD
LOAD LOAD
LOAD LOAD
LOAD
LOAD LOAD
LOAD
LOAD LOAD LOAD
2+2 - lower LOAD
LOAD LOAD
1) 1)
LOAD LOAD
LOAD
LOAD
LOAD
4PS - lower LOAD
1) 1)
LOAD
LOAD LOAD
1) Valid only when 1250 A jumpers are used; 2) Not valid for T4N/PV-E 250; 3) Not valid for T4N/PV-E
LOAD LOAD
20 S AC E T M A X P V FO R P H OTOVO LTA I C A P P L I C AT I O N S A D A P TA B I L I T Y, V ER S AT I L I T Y A N D CO M P L E T E F R EED O M
—
Temperature perfomances and Wiring
Temperature perfomances of Tmax PV at temperatures other than 40 °C and for different altitude are
reported in the following table.
Temperature [°C] / In [A] T1D/PV T3D/PV T4D/PV T5D/PV T6D/PV T7D/PV 1250 T7D/PV 1600
40 160 200 250 500 800 1250 1600
45 160 200 250 500 771 1225 1600
50 160 200 250 500 741 1199 1600
55 160 200 250 500 709 1171 1542
60 153 200 250 500 676 1141 1481
65 145 190 237 474 641 1109 1418
70 138 179 224 447 605 1074 1352
—
Power Losses and Insulation distances
METALLIC
FRAME IEC 60947-3 Insulation distances for installation in metallic cubicle
A [mm] B [mm] C [mm]
With jumpers No jumpers With jumpers No jumpers With jumpers No jumpers
B
Y
T1D/PV 55 20 100 50 100 20
A
A
T3D/PV 25 25 100 100 20 20
X X T4D/PV - T4D/PV-E 50 50 120 120 120 120
T4N/PV-E τ = 1ms 50 - 210 - 210 -
τ = 5ms 150 - 210 - 210 -
Y
C
Insulation distances in air between two Tmax PV with jumpers put side by side*
[mm]
T1 60
T3 50
T4 100
T4N/PV-E τ = 1ms 100
τ = 5ms 300
T5 100
T6 100
T7 200
* insulation distances can be reduced using suitable insulation barriers between breakers
UPPER UPPER
SUPPLY SUPPLY
22 S AC E T M A X P V FO R P H OTOVO LTA I C A P P L I C AT I O N S A D A P TA B I L I T Y, V ER S AT I L I T Y A N D CO M P L E T E F R EED O M
— HR HR
Dimensions 7Nm 7Nm
Ø 6.2
X
X Ø 6.2
X
X
EF Ø8,5
EF
7Nm Ø8.5
T1D/PV
X
X 7Nm X
X
7Nm
FC Cu FC Cu Y
24,5 12x12
Y
25 25 25 7Nm
X X X X X X X
1 1
Y Y
38,1 25 38,1
15 30 15 30
101,2 71 101,2 71
103 103
Y 2PS+2PS 20 5 4PS
FcCU EF HR FcCU EF HR
100
* Terminals configurations must be symmetrical with respect to x-x CB axis when CB is supplied from below.
58
12.5
X X X X
150
45
63
100
Y 3
35 35 35
70 1 69.2
175
COMPARTMENT DEPTH
PROFONDITA' QUADRO A
103
FCCu EF FC CuAl
I E C A P P L I C AT I O N S 23
2PS+2PS
FCCuAl
F FCCu EF
185mm
2
2PS+2PS
LOWER
UP TO Availability for
1100V Lower supply SUPPLY
T4D/PV-E UP TO Availability for
LOAD
only 1500V Lower supply
F
T4D/PV - T4D/PV-E 109
165 104.5
101
59 12
20
Y
1
100
60
59.5
X X X X
105
==
205
84.75
max 9,5
10.5
Ø 8.5
Y
17.5 1
21 5 (max)
35 35 35 113.5
140 140
T4N/PV-E X
20.8
19
τ = 1ms τ = 5ms
53.5
202.5
202.5
162.5
.5
21
18
Ø 18.9
64
28
35 35
35 35 35 35
35 35 35
UP TO Availability for
2PS+2PS
1100V Upper supply UPPER
SUPPLY
T4D/PV-E UP TO Availability for
only 1500V Upper supply
* Terminals configurations must be symmetrical with respect to x-x CB axis when CB is supplied from the top
—
Dimensions 2PS+2PS solution, Upper Supply
LOAD
F FCCu EF
2PS+2PS
UPPER SUPPLY
Availability for
Upper supply
T5D/PV
F EF
186 104.5
31
69.75 21 5÷10 max
Y
6
74
11
Ø
30
162.5
Ø 11
15.5
46.5
X X X X
205
6
X
X
74
Y 3
LOAD
FCCu F FCCu
2PS+2PS
38.5 UPPER SUPPLY
Availability for
Installation instructions
Upper supplycode
ONLY 25
1SDH000780R0002 for other configurations and supply ONLY
2x Ø 21.5
T5D/PV-E
25
28
162.5
186
2x Ø 21.5
F 104.5 46.5
56.5
FCCu
22.5
70
Y 5÷10 max
21
25Nm X
X
98,5
F FCCu EF
2PS+2PS
X X X X
205
LOWER SUPPLY
Availability for
Lower supply
LOAD
38.5
28
Y 3
22.5
77.75 2x Ø 21.5
COMPARTMENT DEPTH 46.5
PROFONDITA' QUADRO 25Nm
202
140 X
X
F FCCuAl EF
2PS+2PS
LOWER SUPPLY
Availability for
Lower supply
LOAD
F
T6D/PV 320 116
280
95
120 25 105
24 48
Y
84.5
85
150
408.5
X X X X
105
268
==
44
118.5
2PS+2PS 2PS+2PS
181
12
LOWER UPPER
SUPPLY SUPPLY
150
ø6 LOAD 9 Nm
Y 22.5 24 5
40 LOWER SUPPL Y
3 103
70 70 70 ES EF
108 2
X
18 N
X X
161
18 Nm
210
258
278
173
199.5
40.5
FCCuAl EF 15
T7D - T7D/PV-E X X
X
162.5
X
50
173
20
Ø19 4 ø13
= ø1
39
=
= 480
45
181
348
181
63.5
480 90
35
47 50 82 82
.5
44 70 8 .5 70
42
70 F70 70
70 FC Cu Al
(4 x 240 mm 2 )
480
X
LOAD
210
191
230
F FCCuAl
2PS+2PS
UPPER SUPPLY
Availability for
134
T7D/PV M 1250A
291.5
268
28
==
204
230
125 A
70 105 A
224.5 T7D/PV M 1600A
T7D/PV-E M 1600A
28
HR VR
26 S AC E T M A X P V FO R P H OTOVO LTA I C A P P L I C AT I O N S A D A P TA B I L I T Y, V ER S AT I L I T Y A N D CO M P L E T E F R EED O M
U L A P P L I C AT I O N S 27
—
CHAPTER 3
UL applications
28-28 Dedicated solutions compliant with UL Standards
29-29 Ranges
36-36 Wiring
39-41 Dimensions
28 S AC E T M A X P V FO R P H OTOVO LTA I C A P P L I C AT I O N S A D A P TA B I L I T Y, V ER S AT I L I T Y A N D CO M P L E T E F R EED O M
—
Dedicated solutions compliant with UL
Standards
The SACE Tmax PV UL range includes a full assortment of molded-case circuit-
breakers and switch-disconnectors to UL 489B standards. Multiple versions
that form a uniform product range and a complete portfolio of shared
accessories, including the connection jumpers that are mandatory for SACE
Tmax PV UL. The jumpers ensure ease of installation, safety and are fully
compliant with UL regulations.
The SACE Tmax PV range of molded-case Available in the 4-pole configuration, T7N-D/
circuit-breakers and switch-disconnectors for PV-E switch-disconnectors to UL standards
photovoltaic applications now includes a include versions with an integrated motor-
UL489B type-approved version designed for operator which do not require external
1500V DC installations with rated current up to components. This cuts down on overall size,
1200A. Compact and versatile, these UL circuit- reduces the amount of wiring and the
breakers and switch-disconnectors are the installation time, all to the benefit of the final
best DC solution for the switchgear and cost of the installation.
inverters in all PV systems and in all markets All products can be equipped with the most
where the North American regulations apply. common UL listed mechanical and electrical
A development of the switch-disconnector accessories already available for the SACE
platform with T7N-D/PV-E integrated motor, Tmax T UL molded-case circuit-breaker range.
the UL type-approved version provides
optimized isolating performance over the
entire current range.
U L A P P L I C AT I O N S 29
—
Ranges
Electrical charachteristics
Tmax PV circuit-breaker in compliance with UL 489B T4N/PV T5N/PV T6N/PV
Frame size (A) 200 400 600-800
Rated service current (A) 40-200 225-400 600-800
Number of poles (No.) 3 3 4
Rated service voltage (V) 1000V DC 1000V DC 1000V DC
Short-circuit interrupting rating @ 1000V DC (kA) 7.5 5 10
Trip Unit TMD/TMA TMF/TMA TMA
Versions F F F
Standard terminals F F F
Connections* Jumpers Jumpers Jumpers
Terminals provided with Jumper kit
FCCuAl FCCuAl-FCCu-ES FCCuAl-EF
(see ordering codes for details)
Mechanical life (No. Operations) 7500 7500 7500
Electrical life (operations @ 1000 VDC) (No. Operations) 1000** 500** 500**
Basic dimensions W (mm/in) 105/4.13 140/5.52 280/11.02
D (mm/in) 103.5/4.07 103.5/4.07 103.5/4.07
H (mm/in) 205/8.07 205/8.07 268/10.55
Weight (with standard terminals only) (kg/lbs) 2.35/5.18 3.25/7.17 12/26.46
* Selection of one of the jumper connection options is mandatory for Tmax PV UL ** openings with SOR or UVR
30 S AC E T M A X P V FO R P H OTOVO LTA I C A P P L I C AT I O N S A D A P TA B I L I T Y, V ER S AT I L I T Y A N D CO M P L E T E F R EED O M
—
Characteristic curves
103 103
102 102
10 10
1 1
10-1 10-1
I3 = 5,75…11,5 x In I3 = 5,75…11,5 x In
10-2 10-2
10-1 1 10 102 10-1 1 10 102
x I1 x I1
U L A P P L I C AT I O N S 31
103 103
102 102
10 10
1 1
10-1 10-1
I3 = 5,75...11,5 x In I3 = 5,75...11,5 x In
10-2 10-2
—
Quick reference tables
Size
T1N-D/PV 2+2 - lower LOAD LOAD LOAD
2+2 - upper
LOAD LOAD LOAD
LOAD
LOAD
LOAD LOAD
LOAD
LOAD LOAD LOAD
LOAD
LOAD
LOAD LOADLOAD LOAD LOAD
LOAD
1)
LOAD LOAD LOAD
LOAD
LOADLOAD LOAD LOAD
LOAD LOAD
LOAD
D LOAD
LOAD
LOAD
3PS - lower LOAD LOAD LOAD
1)
LOAD
LOAD LOAD LOAD LOAD LOAD
LOAD
LOAD LOAD LOAD LOAD
LOAD
3PS - upper
LOAD
LOAD LOAD
LOAD LOAD LOAD
1)
LOAD LOAD LOAD
D LOAD LOAD
1) Included with jumpers kit
LOAD
LOAD LOAD LOAD
LOAD LOAD
LOAD LOAD
LOAD
LOADLOAD LOAD LOAD
Size
LOAD LOAD LOAD
T5N-D/PV - 2+1 - lower LOAD LOAD LOAD
LOAD
T5N/PV
LOAD
1) 3) 2) 3) 4)
LOAD LOAD LOAD
LOAD LOAD LOAD
LOAD LOAD
LOAD
LOAD
LOAD LOAD LOAD
3PS - lower
LOAD
LOAD
LOAD
1) 3) 2) 3) 4)
LOAD LOAD LOAD
LOAD
LOAD LOAD
LOAD LOAD LOAD
LOAD
LOAD LOAD
3PS - upper
LOAD LOAD
LOAD
1) 3) 2) 3) 4)
LOAD LOAD LOAD
LOAD
LOAD LOAD LOAD
LOAD LOAD
LOAD LOAD
LOAD LOAD LOAD
LOAD LOAD LOAD
4PS - lower
LOAD LOAD LOAD
4) 3)
LOAD
LOAD LOAD
LOAD
LOAD
LOAD
—
Quick reference tables
Size
T7N-D/PV 2+2 - lower LOAD LOAD LOAD
3) 4)
2+2 - upper
LOAD LOAD LOAD
LOAD
3) 4)
LOAD
LOAD LOAD
4PS - lower
LOAD LOAD LOAD
LOAD
3) 4)
LOAD LOAD
LOAD
4PS - upper
LOAD LOAD LOAD
LOAD 3) 4)
LOAD
LOAD LOAD
LOAD
T7N-D/PV-E
LOAD 2+2 LOAD
- lower LOAD
LOAD
LOAD LOAD LOAD
LOAD 1) 5) 2) 3) 2) 4)
LOAD
LOAD LOAD
LOAD LOADLOAD
D LOAD
LOAD
LOAD LOAD LOAD
LOAD
1) 5) 2) 3) 2) 4)
LOAD LOAD LOAD
LOAD LOAD
LOAD LOAD
4PS - lower
LOAD LOAD LOAD LOAD LOAD LOAD
LOAD LOAD
LOAD
1) 5) 2) 3) 2) 4)
LOAD LOAD LOAD
LOAD
LOAD LOAD
LOAD LOADLOAD
LOAD LOAD
LOAD
4PS - upper
D LOAD LOAD LOAD LOAD LOAD
LOAD 1) 5) 2) 3) 2) 4)
LOAD LOAD LOAD
LOAD
LOAD
LOAD LOADLOAD LOAD
LOAD 1) Mandatory for T7 1200A; 2)LOAD
LOAD T7 1000A only; 3) Included with jumper kit "cable type"; 4) Included with jumper kit "busbar type"; 5) Included with jumper kit
LOAD
LOAD
LOAD LOAD
LOAD
D LOAD
LOAD
U L A P P L I C AT I O N S 35
—
Temperature perfomances
T4 PV UL range (MCCB)
With 40 °C Cables With 50 °C Cables
refer to page 38 for refer to page 38 for
cable dimensions cable dimensions
40 200 40 200
50 180 50 200
60 166 60 181
70 150 70 160
—
Wiring
Please note that for UL MCCBs two deratings are given, according to UL489B: one when 40°C cables
are used, and one when 50°C cables are used. Cables dimensions are given by UL489B.
Below, please find the relevant cabling info.
—
Power Losses
—
Insulation distances
METALLIC
FRAME UL489 Insulation distances for installation in metallic cubicle
A [mm] B [mm] C [mm]
T1N-D/PV 55 100 100
B
Y
C
Insulation distances in air between two Tmax PV with jumpers put side by side*
[mm]
T1 55
T3 -
T4 100
T5 100
T6 265
T7 330
* insulation distances can be reduced using suitable insulation barriers between breakers
— Jumper Kit T1N-D/PV-A for connection A Jumper Kit T1N-D/PV-B for connection B
Dimensions grounded system wiring 4PS, lower supply ungrounded system wiring 2PS+2PS, lower supply
36 14
36 14 25.7 4
25.7 4 1.42" 0.55" 1.01" 0.16"
1.42" 0.55"
36 1.01" 0.16" 36
1.42" 1.42"
2PS+2PS Y
4PS LOWER
LOWER SUPPLY
SUPPLY
X X
X X
7Nm
7Nm
62 lb·in
62 lb·in
1 1
0.04" 0.04"
25 11.2 25 11.2
25 25 25
0.98" 0.44" 0.98" 0.44"
0.98" 0.98"
25 25 25 71 0.98" 71
Y 38.1 2.8"
0.98" 0.98" 2.8" 1.5"
(see fig.H)
0.98" 38.1 (see fig.H) 101.2
1.5" 3.98" 103
101.2 103
3.98" 4.06" 4.06"
Jumper Kit T1N-D/PV-A for connection A Jumper Kit T1N-D/PV-B for connection B
grounded system wiring 4PS, upper supply ungrounded system wiring 2PS+2PS, upper supply
35 35
Y 1.38" Y
1.38"
3.93 "
3.93 "
100
100
* Terminals configurations must be symmetrical with respect to x-x CB axis when CB is supplied from the top. LOAD
8.07 "
8.07 "
X X X X X X X X
205
205
S S
50 mm 185 mm 50 mm 185 mm
2 2 2 2
ุ3
2.36 "
40÷100A 125÷200A
60
60
0.12" 31 35
R 31 35 R
1 1.22" 1.38" 1.22" 1.38"
Y Y
0.04" 1 10 18.85
35 35 10 18.85 35 35 S
S 0.75" 0.04" R 0.4" 0.75"
1.38" 1.38" R 0.4" 1.38" 1.38"
52.5 52.5
104.5 104.5
2.07" 2.07"
105 4.11" 4.11"
4.13" 109/4.29" 105
130 4.13" 109/4.29"
5.12" 140.5 130 140.5
5.53" 5.12" 5.53"
Jumper Kit T4N/PV-A for connection A Jumper Kit T4N/PV-B for connection B
Installation instructionsgrounded system wiring 3PS,
code 1SDH000779R0003 upper
for other supply
configurations and supply ungrounded system wiring 2PS+1, upper supply
Connection A 3PS
Availability for 2PS+1 UPPER SUPPLY
Upper supply NOT AVAILABLE
FCCuAl
3PS
40 S AC E T M A X P V FO R P H OTOVO LTA I C A P P L I C AT I O N S A D A P TA B I L I T Y, V ER S AT I L I T Y A N D CO M P L E T E F R EED O M
Jumper FCCuAl Kit T5N/PV UL-A for connection A Jumper FCCuAl Kit T5N/PV UL-B for connection B
grounded system wiring 3PS, lower supply 225A ungrounded system wiring 2PS+1PS, lower supply 225A
—
Dimensions
Availability for
3PS
Availability for
2PS+1PS
0.83"
0.83"
-
21
21
LOAD
3PS -
2PS+1PS
LOWER Ø 18.85 Ø 18.85
LOWER
SUPPLY 0.74" 0.74"
SUPPLY
+
+
LOAD
T5N-D/PV - T5V/PV
102
4.02" 165
21 46 6.5" 102
165 0.83" 1.81" = = 4.02"
6.5" 21 46
46.5 0.83" 1.81"
46.5 1.83"
Y 1.83"
Y
3.93"
100
3.93"
100
Jumper FCCuAl Kit T5N/PV UL-A for connection A Jumper FCCuAl Kit T5N/PV UL-B for connection B
grounded system wiringX3PS, lower supplyX 250A ungrounded system wiring 2PS+1PS, lower supply 250A
8.07"
X X
205
X X X
8.07"
X
0.12" 27
3 27 36 36
60
0.95"
1 1.52" -
24
24
46.5 LOAD 0.04"
1.83" 0.04" 102 46.5 46.5 38
140 4.02" 1.49"
3PS 5.51" - A
1.83" 1.83"
104.5
2PS+1PS
COMPARTMENT DEPTH
Y 69.75
PROFONDITA' QUADRO
LOWER 165
Ø 21.5 140.5 2.75" Ø 21.5
4.11"
COMPARTMENT DEPTH A
LOWER
PROFONDITA' QUADRO
6.5" 5.53" 140
SUPPLY 0.85"
5.51"
0.85"
SUPPLY 165
140.5
5.53"
+
Installation instructions code 1SDH000780R0003 for other configurations and supply 6.5"
+
LOAD
T6N-D/PV - T6N/PV
102
4.02" 165
+ 21 46 6.5" 102
165 0.83" 1.81" = = 4.02"
21 46
3PS 6.5"
46.5 0.83" 1.81"
UPPER
Y
46.5 UPPER SUPPLY
1.83"
1.83"
SUPPLY Y NOT AVAILABLE
3.93"
-
100
3.93"
100
LOAD
29.25
1.15"
3PS
Availability for X X
Upper supply
8.07"
X X
205
X X X
8.07"
FCCu X
205
3
2.91"
29.25
74
1.15"
2.36"
0.12"
3
60
0.12"
Y 38.5 1
46.5 1 1.52"
0.04"
1.83" 0.04" 102 46.5 46.5 38
140 4.02" 1.49"
1.83" 1.83"
5.51" COMPARTMENT DEPTH
A 104.5
Y 69.75
PROFONDITA' QUADRO
165 4.11"
140.5 2.75"
6.5"
PROFONDITA' QUADRO
A
5.53" 140 COMPARTMENT DEPTH
5.51" 140.5
165 5.53"
Installation instructions code 1SDH000781R0003 for other configurations and supply 6.5"
T7N-D/PV - T7N-D/PV-E
Kit T7N-D/PV-A for connection A grounded system wiring 4PS Kit T7N-D/PV-B for connection B ungrounded system wiring 2PS+2PS
FCCuAl - Example for Upper Supply FCCuAl - Example for Upper Supply
9.02 "
229
13.15 "
7.54 "
334
191.5
X
X
9.02 "
229
X
7.54 "
191.5
X 67.25 43 Nm
67.25 2.65 "
2.65 " 43 Nm 35.75 380 lb·in
1.41 "
35.75
380 lb·in
1.41"
7.87 "
200
5.28 "
134
268 5.28 "
18.03 "
134
X X X X
458
8.03 "
10.55 "
8.03 "
204
X X X
10.55 "
204
268
18.03 "
458
7.87 "
200
7.87 "
200
70 70 70 A
2.76 " 2.76 " 2.76 "
A 105
70 70 70 4.14 "
2.76 " 2.76 " 2.76 " CON MOSTRINA SENZA MOSTRINA CON MOSTRINA SENZA MOSTRINA
105 WITH FLANGE WITHOUT FLANGE WITH FLANGE WITHOUT FLANGE
4.13 " mm 165 170 mm 165 170
A in 6.50" 6.69" A in 6.50" 6.69"
F - Example
Installation for Upper
instructions codeSupply F -supply
1SDH000789R0003 for other configurations and Example for Upper Supply
9.02 "
13.15 "
229
334
X
5.28 "
134
X
9.02 "
229
X
5.28 "
134
10
24 10
7.87 "
10
200
10
24
14.5
5.28 "
134
268 5.28 "
18.03 "
14.5
134
X X X X
458
8.03 "
10.55 "
8.03 "
204
X X X
10.55 "
204
268
18.03 "
458
7.87 "
200
7.87 "
200
70 70 70 A
2.76 " 2.76 " 2.76 "
A 105
70 70 70 4.14 "
2.76 " 2.76 " 2.76 " CON MOSTRINA SENZA MOSTRINA CON MOSTRINA SENZA MOSTRINA
105 WITH FLANGE WITHOUT FLANGE WITH FLANGE WITHOUT FLANGE
4.13 " mm 125...164 170 mm 125...164 170
A in 4.9"...6.5" 6.69" A in 4.9"...6.5" 6.69"
42 S AC E T M A X P V FO R P H OTOVO LTA I C A P P L I C AT I O N S A D A P TA B I L I T Y, V ER S AT I L I T Y A N D CO M P L E T E F R EED O M
8 0 0 V A C A P P L I C AT I O N S 43
—
CHAPTER 4
800V AC applications
44-44 Full protection for string inverters with 800V AC
output
45-45 Ranges
49-49 Wiring
52-55 Dimensions
44 S AC E T M A X P V FO R P H OTOVO LTA I C A P P L I C AT I O N S A D A P TA B I L I T Y, V ER S AT I L I T Y A N D CO M P L E T E F R EED O M
—
Full protection for string inverters with
800V AC output
Once again, ABB meets market demands by proposing a series of AC products
for this type of application, designed to address two distinct trends in state-of-
the-art plant design: the growing number of PV systems using string inverters
and the increase in rated voltages.
SACE Tmax PV T4V-HA and T5V-HA circuit- To be highlighted that T4V-HA UL up to 150A
breakers for AC applications are now available and T5V-HA UL are 100% rated.
in UL type-approved versions and versions that Ideal for protecting AC switchgear and string
conform to Standards IEC 60947-2 and inverters, these circuit-breakers can be
GB14048.2. The T4V-HA version bearing the integrated with the entire range of electrical
three UL, IEC and CCC marks and T5V-HA and mechanical accessories already available
bearing both the IEC and UL marks can be for the SACE Tmax T molded-case circuit-
supplied. breaker range.
Size T4 controls currents up to 250A and can
break short-circuit current up to 25kA, while
size T5 controls currents up to 630A and breaks
short-circuit current up to 32kA.
8 0 0 V A C A P P L I C AT I O N S 45
—
Ranges
IEC
T4V-HA T5V-HA
Rated uninterrupted current [A] 80, 100, 125, 160, 200, 250 320 400 500 630
Rated service voltage [V] 800 800
Rated impulse withstand voltage, Uimp [kV] 8 8
Rated insulation voltage, Ui [V] 1000 1000
Distribution System IT, TN IT, TN
Rated breaking capacity, Icu [kA] 25 32
Rated service breaking capacity, Ics [kA] 12 16
Category of use (IEC 60947-2) A A
Isolation behaviour Yes Yes
Reference Standards IEC60947-2/GB14048.2 IEC60947-2/GB14048.2
Product Certification IEC - CCC IEC - CCC
Trip unit type TMA TMA PR221
Poles 3P/4P 3P/4P
Class of pollution III III
Derating on uninterrupted current @ 4000m 93% 93%
Working Temperature [°C] -25 + 70 -25 + 70
Electrical life [No. Operations] 2000 1000
Mechanical life [No. Operations] 20000 20000
Version F F
Terminals (cables, busbars) Front, FcCuAl (1x185), FcCu (1x185) Front, FcCuAl (1x240), FcCu (1x240) Front
UL
T4V-HA T5V-HA
Rated uninterrupted current [A] 80, 100,125,150, 200 300
Rated 100% up to 150A, 80% at 200A 100%
Rated service voltage [V] 800 800
Rated impulse withstand voltage, Uimp [kV] 8 8
Rated insulation voltage, Ui [V] 1000 1000
Distribution System Δ Δ
Short circuit interrupting rating [kA] 25 25
Isolation behaviour Yes Yes
Reference Standards UL489 UL489
Product Certification UL - IEC - CCC UL - IEC
Trip unit type TMA TMA, PR221
Poles 3P/4P 3P/4P
Class of pollution III III
Derating on uninterrupted current @ 4000m 93% 93%
Working Temperature [°C] -25 + 70 -25 + 70
Electrical life [No. Operations] 4000 1000
Mechanical life [No. Operations] 20000 20000
Version F F
Terminals FcCuAl (1x350kcmil) FcCuAl (1x500kcmil)
46 S AC E T M A X P V FO R P H OTOVO LTA I C A P P L I C AT I O N S A D A P TA B I L I T Y, V ER S AT I L I T Y A N D CO M P L E T E F R EED O M
—
Characteristic curves
t [s] t [s]
10 4 10 4
10 3 10 3
10 2 10 2
10 10
1 1
10 -1 10 -1
I3 = 5…10 x In I3 = 5…10 x In
10 -2 10 -2
10 -1 1 10 10 2 10 -1 1 10 10 2
x I1 x I1
t [s] t [s]
10 4 10 4
0.4...1 0.4...1
0.4 1 0.4 1
1 1
10 3 10 3
1...10 1...10
10 2 10 2
10
10
10 10
10 2 10 2
1 1
10 -1 10 -1
T4 T4
T5 400 T5 400
T5 630 T5 630
10 -2 T6 630 10 -2 T6 630
T6 800 T6 800
T6 1000 T6 1000
10 -3 10 -3
10 -1 1 10 1 10 10 -1 1 10 1 10
x In I [kA] x In I [kA]
8 0 0 V A C A P P L I C AT I O N S 47
t [s] t [s]
10 4 10 4
10 3 10 3
10 2 10 2
10 10
1 1
10 -1 10 -1
I3=5…10 x In I3=5…10 x In
10 -2 10 -2
10 -1 1 10 10 2 10 -1 1 10 10 2
x I1 x I1
—
Temperature performances
IEC
Circuit-breaker with electronic trip unit
up to 40°C 50°C 60°C 70°C
Imax [A] I1 Imax [A] I1 Imax [A] I1 Imax [A] I1
Tmax T5 630
630 1 580 0.92 529 0.84 479 0.76
UL
Circuit-breaker with electronic trip unit
up to 140°F/40°C 122°F/50°C 140°F/60°C 158°F/70°C
Imax [A] I1 Imax [A] I1 Imax [A] I1 Imax [A] I1
Tmax T5 300
300 1 264 0.88 228 0.76 189* 0.63
* In order to grant 288A it is necessary to use a cable size of 500kmcil with lug 1x240mm2
—
Wiring
IEC
Wire options Tmax T4V-HA IEC and T5V-HA
Ambient temp. 40°C
Cable type Copper Aluminum
In (A) required wires (number x section)
T4V-HA
80 1 x 25mm2 1 x 35mm2*
100 1 x 35mm 2
1 x 50mm2*
125 1 x 50mm 2
1 x 70mm2*
160 1 x 70mm2 1 x 120mm2*
200 1 x 95mm 2
1 x 150mm2*
250 1 x 150mm 2
1 x 185mm2*
T5V-HA
320 1 x 185mm2 2 x 120mm2*
400 1 x 240mm2 2 x 150mm2*
500 2 x 150mm2* 2 x 240mm2*
630 2 x 185mm2* Lug not available
*with FcCuAL
UL
Wire options Tmax T4V-HA UL and T5V-HA
Ambient temp. 40°C
Cable type Copper Aluminum
In (A) required wires (number x section)
T4V-HA
80 1 x 4 AWG 1 x 2 AWG
100 1 x 3 AWG 1 x 1 AWG
125 1 x 1 AWG 1 x 2/0 AWG
150 1 x 1/0 AWG 1 x 3/0 AWG
200 1 x 3/0 AWG 1 x 250kcmil
T5V-HA
300 1 x 350kcmil 1 x 500kcmil
50 S AC E T M A X P V FO R P H OTOVO LTA I C A P P L I C AT I O N S A D A P TA B I L I T Y, V ER S AT I L I T Y A N D CO M P L E T E F R EED O M
—
Power losses
IEC
Type Trip Unit In [A] P [w/pole]
T4 TMA 80 4,6
100 5,2
125 6,2
160 7,4
200 9,9
250 13,7
T5 TMA 320 13,6
400 19,5
500 28,8
ELT 630 41,0
UL
Type Trip Unit In [A] P [w/pole]
T4 TMA 80 4,6
100 5,2
125 5,7
150 6,9
200 9,9
T5 TMA 300 12,3
ELT 300 9,3
8 0 0 V A C A P P L I C AT I O N S 51
Tmax
Tmax T4V-HA T4V-HA IEC-UL
IEC-UL
DOC.- N.°B1583
DOC. N.° 1SDH001607R0001 1SDH001607R0001 - B1583
—
1 1
Insulation distances
OFF 断开 OFFON
断开闭合 ON 闭合 跳扣 TRIPPED 跳扣
TRIPPED
T4V-HA
AC Un<=800V AC
2 ≤ 800V ACUn<=800V
Un 2 3 3
METALLIC FRAMEMETALLIC⾦属配电柜
FRAME ⾦属配电柜
LINE
LINE
进线 LINE 进线
M E TA L L I C F R A M E
MINIMUM MINIMUM
DIMENSIONS DIMENSIONS 最⼩尺⼨
最⼩尺⼨
Y Y
C
C
B
B
D D
D D
E E
G
G
F
F
X X X X X X XX XX X X
A
A
Tmax T5V-HA
TmaxIEC-UL
T5V-HA IEC-UL
DOC. N.° 1SDH001608R0001 - B1583
DOC. N.° 1SDH001608R0001 - B1583
1108.5 1
B
B
C
C
_
>3 <2 _
_ >3
_ >3 108.5
130 _<2_
_ >3
<2 130 _
<2
Y Y
LO A D 负载 LOAD 负载
LOAD E F G E F G
A CB D A B C D
IEC 100 300 420IEC 100 300 420
IEC 325 A 160
150 IEC 50 325
B 150 160 50
C D E F G
UL 109 181 301UL 109 181 301
IEC UL 325 325 100 54.5
90.5UL 15090.5 100
325 54.5
160 50 100 300 420
UL 90.5UL15
UL (R50) 325 325 (R50)54.590.590.5 15
325 54.5
100 54.5 109 181 301
ON 闭合 ONTRIPPED
OFF 断开 OFF 断开 闭合 TRIPPED
跳扣 跳扣
T5V-HA
Un<=800V AC
2 ≤ 800V AC
Un Un<=800V AC
2 3 3
METALLIC FRAME ⾦属配电柜 ⾦属配电柜
LINE
L I N E 进线LINE 进线
M E TA L L I C FMETALLIC
R AME FRAME
MINIMUM DIMENSIONS
MINIMUM 最⼩尺⼨
DIMENSIONS 最⼩尺⼨
Y Y
C
C
B
D DD D
X XX X X XX X X XX X
G
G
F
F
A
E E
B
_3
> 108.5 _>
<2 _ 108.5155<2
_ 3 >3 _ >3
_<2
_ 155 _
<2
Y Y
LOAD
LO A D
LOAD 负载
负载
A ABC AD BB C D C D E EF G E FF G G
IEC IEC 325 150 50 150
IEC 160 325
325 150 160 50 160 50 IEC 100 100
300 IEC
420 100 300
300 420 420
UL UL 90.5
325 325 121 90.5
UL 100 325 90.5 100 121 100 121 UL 242 242 301 242 181
181 UL 181 301 301
52 S AC E T M A X P V FO R P H OTOVO LTA I C A P P L I C AT I O N S A D A P TA B I L I T Y, V ER S AT I L I T Y A N D CO M P L E T E F R EED O M
—
Dimensions
T4V-HA IEC/UL
F
7 F
3p 4p
3P 4P
140
52,5 105 112,5
Y Y
35 35 35 35 35 103,5 Y
70
17,5 17,5 20 max 8 35
ø5 ø 5, 17,5
,5 ,5 ,5 - = = 5-M
ø8 ø8 M5
max 9,5 5
max 9,5
102,5
102.,5
105
84,75
88
148,2 113,2
88
59,5
2,7 5,5 2,7 5,5
X X X X
105
X X X
205
176
176
7
169,5
F
205
3p 4p
140
52,5 105 112,5
Y Y
35 35 35 35 35 103,5 Y
Y35 70 Y
Y 17,5 max 25 17,5 20 max 8
ø5 ø 5, 17,5
,5 ,5 139 ,5 - = = 5-M
ø8 ø8 M5
5
max 9,5
max 9,5
102,5
102.,5
8
105
FC Cu
84,75
88
148,2 113,2
88
59,5
X X
205
176
176
169,5
205
T4V-HA IEC/UL
Y
102,5
Y
105 Y max 25
88
84,75
FC Cu X
176
X X X X
205
X X X
105
176
205
169,5
8 FC Cu
3p
3P 4P 4p
140 105 112,5
Y Y
Y 52,5 35 35 103,5 70
35 35Y 35 20 18x18 ø5 Y35 ø5
,5 - 17,5Y
,5 - = =
M5 M5
139
19
102,5
102,5
105
88
84,75
148,2 113,2
88
59,5
5,5
9
2,7 2,7 5,5
X FC CuAl
176
X X X X
205
X X X
105
3p 4p
176
205
169,5
112,5
140 105 Y Y
103,5
Y 52,5 35 35 70
35 35 35 Y 25,9 ø 18 ø5 35 ø5
,5 - = = ,5 - 17,5
M5 M5
20,8
Y Y Y
102,5
102,5
139
105
84,75
88
148,2 113,2
88
59,5
105
X X X X X X X X
176
169,5
205
9 3p 4p
FC CuAl
112,5
140 105 Y Y
Installation instructions code 1SDH001607R0001 for other configurations
103,5 and supply
15,5
Y35 52,5 35 70
35 35Y 35 YY 25,9 ø 18 ø5 Y35 ø5
26 ø 10 ,5 -
M5 = = ,5 - 17,5Y
M5
139
20,8
102,5
102,5
105
84,75
88
148,2 113,2
88
59,5
105
X X X X X X X X
76
Y Y
Y max 25
8 0 0 V A C A P P L I C AT I O N S 139 53
8 FC Cu
3p 4p
140 105 112,5
Y Y
Y 52,5 35 35 103,5 70
35 35 35 20 18x18 ø5 35 ø5
,5 - = = ,5 - 17,5
M5 M5
19
102,5
102,5
105
88
84,75
148,2 113,2
88
59,5
2,7 5,5 2,7 5,5
X
176
X X X X
205
X X X
105
176
205
169,5
Y Y Y
FC Cu Al
9 3p 4p
FC CuAl
3P 4P
112,5
140 105 Y Y
103,5
Y 52,5 35 35 70
35 35 35 Y 25,9 ø 18 ø5 35 ø5
,5 - = = ,5 - 17,5
M5 M5
20,8
102,5
102,5
105
84,75
88
148,2 113,2
88
59,5
2,7 5,5 2,7 5,5
176
205
105
X X X X X X X X
176
169,5
205
15,5
Y 26 ø 10 Y Y
Y
139
T4V-HA IEC/UL
HIGH TERMINAL COVERS
28
30
—
Dimensions
T5V-HA IEC/UL
7F F
186 139,5 112,5
3p
3P 4P 4p
Y 69,75
46,5 46,5 103,5 Y
46,5 46,5 46,5 20 5÷10 max
ø5 46,5 ø5 93
5 ,5 - = = ,5 -
ø 10,
5
ø 10, M5 M5 Y
102,5
23,25
max 11
max 11
102,5
86,25
105 105
88
59,5
88
194,2 147,7
2,7 5,5 2,7 5,5
105
X X X X
205
X X X
176
205
172,5
176
7 F
186 139,5 112,5
3p 4p
Y 69,75
46,5 46,5 103,5 Y
46,5 46,5 46,5 20 5÷10 max
ø5 46,5
Y ø5 93 Y
Y max 35 max 35 5 ,5 - = = ,5 -
ø 10,
5
ø 10, 139 M5 M5 Y
102,5
23,25
max 11
max 11
102,5
86,25
105 105
88
59,5
88
194,2 147,7
2,7 5,5 2,7 5,5
8 FC Cu
105
X X X X
205
X X X
176
205
172,5
176
112,5
3p 4p
186 139,5
103,5
Y 69,75
20 18x18 46,5 46,5
Installation
46,5 instructions
46,5 46,5 code 1SDH001607R0001 for other configurations and supply ø5 46,5 ø5 93
,5 - = = ,5 -
M5 M5 Y
Y
Y Y
Y max 35 max 35
139
102,5
23,25
T5V-HA IEC/UL
102,5
86,25
105 105
59,5
88
88
194,2 147,7
2,7 5,5 2,7 5,5
X
105
X X X X X X X X
FC Cu
8
176
FC Cu
172,5
205
205
176
112,5
3P 3p 4P 4p
186
24
139,5
103,5
Y 69,75
46,5 46,5 20 18x18
46,5 46,5 46,5 ø5 46,5 ø5 93
,5 - =Y = ,5 - Y
Y M5 Y
Y M5
139
102,5
23,25
102,5
86,25
105 105
59,5
88
88
194,2 147,7
2,7 5,5 2,7 5,5
9
X
105
X X X X X X X
FC CuAl
X
176
172,5
205
205
176
105 105
59,5
86,25
194,2 147,7
88
88
9
176
176
105
FC CuAl
172,5
205
3p 4p
23,5
23,25
102,5
102,5
105 105
59,5
86,25
194,2 147,7
88
88
176
176
05
,5
5
Y max 35 max 35
139
8 0 0 V A C A P P L I C AT I O N S 55
8 FC Cu
112,5
3p 4p
186 139,5
103,5
Y 69,75
46,5 46,5 20 18x18
46,5 46,5 46,5 ø5 46,5 ø5 93
,5 - = = ,5 -
M5 M5 Y
Y
102,5
23,25
102,5
86,25
105 105
59,5
88
88
194,2 147,7
2,7 5,5 2,7 5,5
X
105
X X X X X X X X
176
172,5
205
205
176
24
Y Y Y
139
T5V-HA IEC/UL
FC Cu Al
9 3P 4P
FC CuAl
186 139,5 112,5
3p 4p
Y 69,75 Y
46,5 46,5 103,5
46,5 46,5 46,5 ø5 46,5 ø5
26,5 ø24,5 ,5 - ,5 93
= = -M
M5 5 Y
23,25
102,5
102,5
105 105
59,5
86,25
194,2 147,7
88
88
2,7 5,5 2,7 5,5
X X X X X X X X X
205
176
176
105
172,5
205
23,5
Y Y Y Y
139
T5V-HA IEC/UL
HIGH TERMINAL COVERS
26
54
—
CHAPTER 5
Ordering codes
58-59 IEC range ordering codes
—
IEC range ordering codes
Switch-disconnector
Code Description
1SDA069816R1 T1D/PV 160 4p F FC Cu 1100V DC
1SDA082693R1 T3D/PV 200 4p F F 1100V DC
1SDA069823R1 T4D/PV 250 4p F F 1100V DC
1SDA069824R1 T5D/PV 500 4p F F 1100V DC
1SDA069825R1 T6D/PV 800 4p F F 1100V DC
1SDA069826R1 T7D/PV 1250 4p F F 1100V DC
1SDA069827R1 T7D/PV 1250 4p F F M 1100V DC
1SDA069828R1 T7D/PV 1600 4p F F 1100V DC
1SDA069829R1 T7D/PV 1600 4p F F M 1100V DC
1SDA073559R1 T4D/PV-E 250 4p F F 1500V DC
1SDA076898R1 T5D/PV-E 500 4p FF 1500V DC
1SDA073560R1 T7D/PV-E 1250 4p F F M 1500V DC
1SDA073561R1 T7D/PV-E 1600 4p F F M 1500V DC
Circuit-breakers
Code Description
1SDA082910R1 T4N/PV-E 250 TMF 100 4p F F 1500V DC
1SDA082911R1 T4N/PV-E 250 TMF 125 4p F F 1500V DC
1SDA082912R1 T4N/PV-E 250 TMF 160 4p F F 1500V DC
1SDA082913R1 T4N/PV-E 250 TMF 200 4p F F 1500V DC
1SDA082914R1 T4N/PV-E 250 TMF 250 4p F F 1500V DC
For circuit-breakers at 1000V DC, see catalog Tmax T code 1SDC210015D0208.
Jumper kit
Code Description
1SDA069876R1 KIT 2 JUMPER 2+2PS T1D/PV 160 4p
1SDA069877R1 KIT 3 JUMPER 4PS T1D/PV 160 4p
1SDA076162R1 KIT 2JUMPER U 2+2PS T3D/PV 200
1SDA076163R1 KIT 3JUMPER U 4PS T3D/PV 200
1SDA070454R1 KIT 2JUMPER U 2+2PS T4D/PV 250
1SDA070455R1 KIT 3JUMPER U 4PS T4D/PV 250
1SDA085254R1 KIT 2JUMPER U 2+2PS T4N/PV-E 200 1500V DC
1SDA085255R1 KIT 3JUMPER U 4PS T4N/PV-E 200 1500V DC
1SDA085253R1 KIT 3JUMPER U 4PS T4N/PV-E 250 1500V DC
1SDA085251R1 KIT 2 JUMPER U 2+2PS T4N/PV-E 250 1500V DC
1SDA070456R1 KIT 2JUMPER U 2+2PS T5D/PV 500
1SDA070457R1 KIT 3JUMPER U 4PS T5D/PV 500
1SDA076899R1 KIT 2JUMPER U 2+2PS T5D/PV-E 500 1500V DC
1SDA070491R1 KIT 2JUMPER U 2+2PS T6D/PV 800
1SDA070492R1 KIT 3JUMPER U 4PS T6D/PV 800
1SDA070429R1 KIT JUMPER U 2+2PS T7D/PV 1250
1SDA070431R1 KIT JUMPER U 2+2PS T7D/PV 1600
1SDA070430R1 KIT JUMPER U 4PS T7D/PV 1250
1SDA070432R1 KIT JUMPER U 4PS T7D/PV 1600
ORDERING CODES 59
Tmax PV can be accessoried with Tmax T series accessories, except for the following exceptions.
—
UL range ordering codes
Switch-Disconnector
Code Description
1SDA070004R1 T1N-D/PV 100 MCS UL 4p F FC Cu 1000V DC
1SDA070460R1 T4N-D/PV 200 MCS UL 3p F F 1000V DC
1SDA070471R1 T5N-D/PV 400 MCS UL 3p F 1000V DC
1SDA070493R1 T6N-D/PV 600 MCS UL 4p F F 1000V DC
1SDA070494R1 T6N-D/PV 800 MCS UL 4p F F 1000V DC
1SDA070448R1 T7N-D/PV 1000 MCS UL 4p F F M 1000V DC
1SDA082657R1 T7N-D/PV-E 1000 MCS UL 4p F F M 1500V DC
1SDA082915R1 T7N-D/PV-E 1200 MCS UL 4p F F M 1500V DC
Circuit-breaker
Code Description
1SDA070461R1 T4N/PV 200 UL TMD 40 3p F F 1000V DC
1SDA070462R1 T4N/PV 200 UL TMD 50 3p F F 1000V DC
1SDA070463R1 T4N/PV 200 UL TMA 80-800 3p F F 1000V DC
1SDA070467R1 T4N/PV 200 UL TMA 100-1000 3p FF 1000V DC
1SDA070468R1 T4N/PV 200 UL TMA 125-1250 3p FF 1000V DC
1SDA070469R1 T4N/PV 200 UL TMA 150-1500 3p FF 1000V DC
1SDA070470R1 T4N/PV 200 UL TMA 200-2000 3p FF 1000V DC
1SDA079819R1 T5N/PV 250 UL TMD 1500-3000 3p FF 1000V DC
1SDA079820R1 T5N/PV 225 UL TMD 1500-3000 3p FF 1000V DC
1SDA079818R1 T5N/PV 300 UL TMD 1500-3000 3p FF 1000V DC
1SDA070472R1 T5N/PV 400 UL TMA 400-4000 3p FF 1000V DC
1SDA070495R1 T6N/PV 800 UL TMA 600-6000 4p FF 1000V DC
1SDA070496R1 T6N/PV 800 UL TMA 800-8000 4p FF 1000V DC
Kit Jumpers
Code Description
1SDA070424R1 KIT 2 JUMPER 2+2PS T1N-D/PV-B 100 UL 4p
1SDA070425R1 KIT 3 JUMPER 4PS T1N-D/PV-A 100 UL 4p
1SDA070483R1 KIT 1 JUMPER 2+1PS T4N/PV-B 100A UL 3p
1SDA070484R1 KIT 1 JUMPER 2+1PS T4 PV-B 200A UL 3p
1SDA070485R1 KIT 2 JUMPER 3PS T4N/PV-A 100A UL 3p
1SDA070486R1 KIT 2 JUMPER 3PS T4 PV-A 200A UL 3p
1SDA070487R1 KIT 1 JUMPER 2+1PS T5 PV-B 400 UL 3p cables
1SDA070488R1 KIT 2 JUMPER 3PS T5 PV-A 400 UL 3p cables
1SDA074504R1 KIT 1 JUMPER 2+1PS T5 PV-B 400 UL 3p busbars
1SDA074505R1 KIT 2 JUMPER 3PS T5 PV-A 400 UL 3p busbars
1SDA079821R1 KIT 1 JUMPER 2+1PS T5 PV-B 225 UL 3p
1SDA079823R1 KIT 1 JUMPER 2+1PS T5 PV-B 250 UL 3p
1SDA079824R1 KIT 2 JUMPER 3PS T5 PV-A 225 UL 3p
1SDA079825R1 KIT 2 JUMPER 3PS T5 PV-A 250 UL 3p
1SDA070499R1 KIT 2 JUMPER 2+2PS T6 PV-B 600 UL 4p
1SDA070500R1 KIT 3 JUMPER 4PS T6 PV-A 600 UL 4p
1SDA070501R1 KIT 2 JUMPER 2+2PS T6 PV-B 800 UL 4p
1SDA070502R1 KIT 3 JUMPER 4PS T6 PV-A 800 UL 4p
1SDA070451R1 KIT 2 JUMPER 2+2PS T7N-D/PV-B 1000 UL 4p cables
1SDA070452R1 KIT 3 JUMPER U 4PS T7N-D/PV-A 1000 UL 4p cables
1SDA081762R1 KIT 2 JUMPER 2+2PS T7N-D/PV-B 1000 UL 4p busbars
1SDA081763R1 KIT 3 JUMPER U 4PS T7N-D/PV-A 1000 UL 4p busbars
1SDA083038R1 KIT 2JUMPER 2+2PS T7N-D/PV1200 UL Term.F
1SDA083039R1 KIT 3JUMPER U 4PS T7N-D/PV1200 UL Term.F
ORDERING CODES 61
Tmax PV can be accessoried with Tmax T series accessories, except for the following exceptions.
Frame size Incompatibilities
T1D PV Interlocks, KLC, PLL
T3D PV Interlocks, KLC, PLL
T4D PV Interlocks
T5D PV Interlocks
T6D PV Interlocks
T7D PV Interlocks
T7D PV M Interlocks
Accessories part number, wirings and data can be found in the Tmax T UL489 1SDC210023D0201 technical catalog.
62 S AC E T M A X P V FO R P H OTOVO LTA I C A P P L I C AT I O N S A D A P TA B I L I T Y, V ER S AT I L I T Y A N D CO M P L E T E F R EED O M
—
800V AC IEC and UL ranges ordering codes
www.abb.com